1 TECHNICAL & SERVICE MANUAL SAP KM97AHA ( 2) + SAP CM1827AHA FILE NO. Destination: Australia MULTI-SPLIT SYSTEM AIR CDITIER Indoor Model No Product Code No. Outdoor Model No. Product Code No. SAP KM97AHA S SAP CM1821AHA S Indoor Unit Outdoor Unit SAP CM1821AHA SAP KM97AHA ( 2) REFERENCE NO. SM700505

2 IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard WARNING or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can CAUTI result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIS WARNING When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSAL INJURY OR DEATH. LY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the unit s weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leakfree connection. Check carefully for leaks before starting the test run. When Servicing Turn the power at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTI Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. i

3 Table of Contents Page Unit Combination... iii 1. OPERATING RANGE SPECIFICATIS 2-1. Unit Specifications Major Component Specifications Other Component Specifications DIMENSIAL DATA COOLING CAPACITY HEATING CAPACITY AIR THROW DISTANCE CHART REFRIGERANT FLOW DIAGRAM ELECTRICAL DATA 8-1. Electrical Characteristics Electric Wiring Diagrams INSTALLATI INSTRUCTIS 9-1. Installation Site Selection Remote Control Unit Installation Position Recommended Wire Length and Diameter FUNCTI Room Temperature Control Dry Operation Freeze Prevention Overload Prevention Cold draft Prevention Defrosting Operation TROUBLESHOOTING Check before and after troubleshooting Air conditioner does not operate Some part of air conditioner does not operate Air conditioner operates, but abnormalities are observed If a sensor is defective ARRANGEMENT OF ELECTRICAL COMPENT CHECKING ELECTRICAL COMPENTS Measurement of Insulation Resistance Checking Continuity of Fuse on PCB Ass'y Checking Motor Capacitor MAINTENANCE Changing Address of Remote Control Unit in Indoor Unit APPENDIX ii

4 Unit Combination Combine indoor and outdoor units only as listed below. Outdoor Unit Indoor Unit Symbol of Indoor Unit Refer to SAP CM1827AHA KM97 KM97 A B Fig.1 Indoor Unit Outdoor Unit A B Fig.1 iii

5 1. OPERATING RANGE Cooling Heating Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 C D.B. / 23 C W.B. 43 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. Maximum 27 C D.B. 24 C D.B. / 18 C W.B. Minimum 16 C D.B. 8 C D.B. / 9 C W.B. 1

6 2. SPECIFICATIS 2-1. Unit Specifications Indoor Unit Outdoor Unit SAP KM97AHA SAP CM1827AHA No. of indoor units. 1-unit 2-unit Power Source 240 V 1-phase 50 Hz 240 V 1-phase 50 Hz Cooling Heating Cooling Heating Capacity kw BTU/h 9,000 11,300 17,400 21,700 Air circulation (High) m 3 /h x 2 Moisture removal (High) Liters/h x 2 Voltage rating V Available voltage range V 216 to to 264 Running amperes A Power input W 1,040 1,090 2,120 2,000 Power factor % C.O.P. W/W Compressor locked rotor amperes A Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour / 12-hour or Fan speeds Indoor / Outdoor 3 and Auto / 1 Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,200 Refrigerant control Capillary tube Dimensions & Weight Features Electrical Rating Performance Operation sound Indoor Hi / Me / Lo db-a 40 / 34 / 31 Outdoor Hi db-a 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant tube Narrow tube mm (in.) 6.35 (1/4) diameter Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling: Indoor air temperature 27 C DB/19 C WB Outdoor air temperature 35 C DB/24 C WB Heating: Indoor air temperature 20 C DB Outdoor air temperature 7 C DB/6 C WB 2 DATA SUBJECT TO CHANGE WITHOUT NOTICE.

7 2-2. Major Component Specifications Indoor Unit SAP KM97AHA Part No. POW KM97GHS Controls Microprocessor Control circuit fuse 250 V 3.15 A Remote Control Unit RCS 2MHS4E G Type Cross flow Number... Dia. and length mm 1... ø70 / L598 Fan motor model... Q ty KFV2Q 11B5P... 1 No. of poles... rpm (240 V, High) ,960 Nominal output W 10 Coil resistance (Ambient temp. 20 C) Ω WHT BRN : WHT VLT : VLT ORG : 37.4 ORG YEL : 87.8 YEL PNK : 95.8 Type Internal thermal fuse Safety Open C 145 ± 2 devices Operating temp. Close Run capacitor µf 1.0 VAC 440 Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25 C) Ω WHT BLU (respectively 4 wires) : 380 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m Controller PCB Flap Motor Fan & Fan Motor Heat Exch. Coil DATA SUBJECT TO CHANGE WITHOUT NOTICE. 3

8 Outdoor Unit SAP CM1827AHA Controller PCB POW C186CMH Control circuit fuse 250 V 3 A Type Rotary (Hermetic) Compressor model... Q ty C R95H5K... 2 / S... 2 Nominal output W 950 x 2 Compressor oil... Amount cc SUNISO 4GSD T x 2 Coil resistance (Ambient temp. 25 C) Ω C R : 2.88 C S : 6.87 Type External (OLR 1, 3) External (OLR 2, 4) Overload relay... Number MRA CS 7C Safety Operating Open C 145 ± ± 3 devices temp. Close C 69 ± ± 5 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 16.5 A Run capacitor µf Q ty VAC Type Propeller Number... Dia. mm 1... ø400 Fan motor model... Q ty SG6 51B5P... 1 No. of poles... rpm (240 V,High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT BRN : 92.1 WHT PNK: Safety Type Internal protector devices Operating Open C 130 ± 8 temp. Close Automatic reclosing Run capacitor µf 2.0 VAC 480 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.6 Face area m External Finish Acrylic baked-on enamel finish Compressor Fan & Fan Motor Heat Exch. Coil DATA SUBJECT TO CHANGE WITHOUT NOTICE. 4

9 2-3. Other Component Specifications Indoor Unit SAP KM97AHA Transformer (TR) ATR-J125 Rating Primary AC 230V, 50Hz Secondary 19V, 0.631A Capacity 12VA Coil resistance Ω (at 21 C) Primary (WHT WHT): 205 ± 10% Secondary (BRN BRN): 1.5 ± 10% Thermal cut-off temp. 150 C Thermistor (Coil sensor TH1) PBC-41E-S4 Resistance kω 20 C 40.1 ± 5% 20 C 6.5 ± 5% 10 C 24.4 ± 5% 30 C 4.4 ± 5% 0 C 15.3 ± 5% 40 C 3.0 ± 5% 10 C 9.9 ± 5% 50 C 2.1 ± 5% Thermistor (Room sensor TH2) DTN-TKS106E Resistance kω 25 C 5.0 ± 3% Outdoor Unit SAP CM1827AHA Power Relay (PRA, PRB) DFU24D1-F (M) Coil rating DC 24V Coil resistance Ω (at 20 C) 650 ± 10% Contact rating AC 250V, 20A Termistor (Coil sensor) PBC-41E-S15 Resistance kω 10 C 23.7 ± 5% 25 C 5.3 ± 5% 0 C 15.0 ± 5% 30 C 4.4 ± 5% 10 C 9.7 ± 5% 40 C 3.1 ± 5% 20 C 6.5 ± 5% Solenoid Coil (4-way Valve SCA, SCB) CHV-01Ai038A1 (Coil), CHV-0101 (Valve) Coil rating AC 230V, 50Hz, 5W Coil resistance Ω (at 20 C) 1,408 ± 7% 5

10 3. DIMENSIAL DATA Indoor Unit SAP KM97AHA Rear panel (center point of gravity) Remote control unit Center of tubing hole (3 places) 124 Drain hose ø18 Narrow tube ø6.35 (1/4") Wide tube ø9.52 (3/8") Unit : mm 6

11 Outdoor Unit SAP CM1827AHA Air intake Air discharge 4 ø12 holes Magnified illustration 3 1 To Indoor Unit A To Indoor Unit B 1 2 Narrow tube service valve ø6.35(1/4") Wide tube service valve ø9.52(3/8") 3 Check Port Unit : mm 7

12 4. COOLING CAPACITY 1 - indoor unit in operation A(or B) Indoor Unit SAP K97AHA ( 1) Outdoor Unit SAP CM1827AHA 240 V Single phase 50 Hz NOTE A : SAP K97AHA B : SAP K97AHA RATING CAPACITY 2.65 kw EVAPORATOR CDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 8

13 2 - indoor units in operation Indoor Unit SAP K97AHA ( 2) Outdoor Unit SAP CM1827AHA 240 V Single phase 50 Hz A + B NOTE A : SAP K97AHA B : SAP K97AHA RATING CAPACITY 5.10 kw EVAPORATOR CDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 9

14 5. HEATING CAPACITY Indoor Unit Outdoor Unit SAP K97AHA SAP CM1827AHA Heating capacity ratio (%) Outdoor temperature ( C DB) NOTE 1) Point of Rating condition Black dot in the chart indicate the following rating condition. Indoor : 20 C DB Outdoor : 7 C DB / 6 C WB 2) Above characteristics indicate instantaneous operation, which does not take into consideration defrost operation. 3) Fan speed : High 10

15 6. AIR THROW DISTANCE CHART Indoor Unit SAP KM97AHA Cooling Room air temp. Fan speed : : 27 C High Horizontal distance (m) Axis air velocity (m/s) Vertical distance (m) Axis air velocity Flap angle 0 30 Heating Room air temp. Fan speed : : 20 C High Horizontal distance (m) Axis air velocity (m/s) Vertical distance (m) Axis air velocity Flap angle

16 7. REFRIGERANT FLOW DIAGRAM Indoor Unit SAP K97AHA ( 2) Outdoor Unit SAP CM1827AHA Heat exchanger Indoor Unit A Wide tube O.D. 9.52mm (3/8") Narrow tube O. D. 6.35mm (1/4") Check port Muffler Strainer Accumulator Compressor A Check valve Drier ( ) 4 Way valve Heat exchanger Indoor Unit B Wide tube O.D. 9.52mm (3/8") Narrow tube O.D. 6.35mm (1/4") Check port Muffler Strainer Accumulator Compressor B Check valve Drier ( ) 4 Way valve Heat exchanger Capillary tube Wide Tube Service valve Narrow Tube Service valve 12

17 Heat exchanger Indoor Unit A Wide tube O.D. 9.52mm (3/8") Narrow tube O.D. 6.35mm (1/4") Check port Muffler Strainer Accumulator Compressor A Check valve Drier ( ) 4 Way valve Heat exchanger Indoor Unit B Wide tube O.D. 9.52mm (3/8") Narrow tube O.D. 6.35mm (1/4") Check port Muffler Strainer Capillary tube Accumulator Compressor B Check valve Drier ( ) 4 Way valve Heat exchanger Capillary tube Wide Tube Service valve Narrow Tube Service valve Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. Thickness: Min. 8 mm Wide tube Insulation Narrow tube Thickness: Min. 8 mm CAUTI After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 13

18 8. ELECTRICAL DATA 8-1. Electrical Characteristics 1 - indoor unit in operation A(or B) Indoor Unit SAP K97AHA ( 1) Outdoor Unit SAP CM1827AHA NOTE A : SAP K97AHA B : SAP K97AHA COOLING Performance at Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor 240V Single phase 50Hz Rating Conditions Running Amps. A Power Input kw Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. HEATING Performance at Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor 240V Single phase 50Hz Rating Conditions Running Amps. A Power Input kw Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 20 C D.B. Outdoor Air Temperature 7 C D.B. / 6 C W.B. Full Load Conditions : Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24 C D.B. / 18 C W.B. 14

19 2 - indoor units in operation Indoor Unit SAP K97AHA ( 2) Outdoor Unit SAP CM1827AHA A + B NOTE A : SAP K97AHA B : SAP K97AHA COOLING Performance at Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor 240V Single phase 50Hz Rating Conditions Running Amps. A Power Input kw Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. HEATING Performance at Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor 240V Single phase 50Hz Rating Conditions Running Amps. A Power Input kw Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 20 C D.B. Outdoor Air Temperature 7 C D.B. / 6 C W.B. Full Load Conditions : Indoor Air Temperature 27 C D.B. Outdoor Air Temperature 24 C D.B. / 18 C W.B. 15

20 8-2. Electric Wiring Diagram Indoor Unit SAP KM97AHA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 16

21 Outdoor Unit SAP CM1827AHA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 17

22 9. INSTALLATI INSTRUCTIS 9-1. Installation Site Selection Maximum Allowable Tubing Length(L) and Elevation Difference(H). INDOOR UNIT Tubing length (L) The Multi-Split System outdoor unit should be installed as close to the indoor units as possible. Maximum allowable length of the refrigerant tubing and elevation difference between outdoor and indoor units are shown in Table 1. Table 1 Indoor Unit AVOID: direct sunlight., Combination Max allowable Limit of Limit of elevation Required amount tubing length tubing length(l). difference(h). of additional Outdoor unit Indoor unit at shipment.(m) (m) (m) refrigerant*(g/m) CM1827 WARNING KM97 KM97 To prevent abnormal heat generation and the possibility of fire, don t place obstacles, 5 cm min. enclosures and grills in front of or surrounding the air conditioner in a way that may block air flow. Less than elevation difference (H) between the 2 units * If total tubing length becomes 7.5 to 15 m (max.),charge additional refrigerant (R22) by 15 g/ m. No additional charge of compressor oil is necessary. Fig. 1 Wall-Mounted Wall-mounted Type Type 5 cm min. INDOOR UNIT Front View Fig.2a OUTDOOR UNIT 5 cm min. nearby heat sources that may affect performance of the unit. areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. DO: select an appropriate position from which every corner of the room can be uniformly air-conditioned. (High on a wall is best) select a location that will hold the weight of the unit. select a location where tubing and drain pipe have the shortest run to the outside. allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2a) CAUTI For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 1.5m from floor level. Indoor Unit Minimum height from floor level 1.5m Floor level Fig. 2b Wall 18

23 Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 3) damp, humid or uneven locations. DO: choose a place as cool as possible. choose a place that is well ventilated. Outdoor unit Hot air Exhaust fan Heat source allow enough room around the unit for air intake/exhaust and possible maintenance. (Figs. 4a and 4b) provide a solid base (concrete block, cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5) use lug bolts or equal to bolt down unit, reducing vibration and noise. Fig. 3 Fig 3 Required space around the unit. Air intake Min. 5 cm Air discharge Min. 10 cm Top View Fig. 4a Top View Min. 40 cm Valve side Min. 25 cm Obstacle above Air discharge 2 m 2 m Ground Obstacle Side View Fig. 44b- C Anchor bolts (4 pcs.) Air intake Min. 10 cm Concrete or equal About 40 cm About 10 cm Fig. 5 Fig. 5 - A 19

24 9-2. Remote Control Unit Installation Position The remote control unit can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: In direct sunlight Behind a curtain or other place where it is covered More than 8 m away from the air conditioner In the path of the air conditioner's airstream Where it may become extremely hot or cold Where it may be subject to electrical or magnetic interference 6-1. When attaching to wall (Fig.6a) 1) Confirm the indoor unit beeps when the / button is pressed at the wall location where the remote control unit is to be attached, then attach the holder to the wall. 2) When taking out the remote control unit, pull it from the holder. When using the remote control unit Point the transmission portion of the remote control unit at the receiver area of the indoor unit when operating the remote control unit, and during operation of the air conditioner. Do not place objects which may block the transmitted signals between the receiver and the remote control unit. Truss-head tapping screw 4 16mm (supplied) Remote control unit holder Fig.6a When mounting the remote control unit to prevent theft (Fig.6b) 1) Attach the holder to the wall with one of the screws (using only the hole in the top of the holder). 2) Remove the cover of the remote control unit and take out the batteries. Next, place the remote control unit in the holder. 3) Fasten both the remote control unit and holder to the wall with the remaining screw (using the hole in the bottom of the holder). 4) Install the batteries in the remote control unit and close the cover. Truss-head tapping screw 4 16mm (supplied) Holder Fig.6b Holder 20

25 9-3. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. Table 2 lists recommended wire lengths and size for power supply systems. NOTE Refer to the WIRING SYSTEM DIAGRAM for the meaning of "A", "B" and "C" in Table 2. Table 2 Model Cross Sectional Area (mm 2 ) (A) Power Supply Wiring Length (m) (B) Power Line Length (m) (C) Cont rol Line 2 (#14) 3.5 (#12) 2 (#14) 0.75 (#18) Fuse or Circuit Capacity CM A # AWG (American Wire Gauge) WARNING WARNING CAUTI Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.). Each wire must be firmly connected. No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part. To avoid the risk of electric shock, each air conditioner unit must be grounded. Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit. Indoor unit A Terminal Indoor unit B Terminal WIRING SYSTEM DIAGRAM B C B C Grounding line 240 V 240 V Grounding line 240 V 240 V Power supply Single-phase, 50Hz, 240V Grounding line A Outdoor unit Terminal 8PA Power line Low voltage control line Terminal 8PB Power line Low voltage control line Terminal 3P 21

26 10. FUNCTI Room Temperature Control Cooling Room temperature control is obtained by cycling the compressor and under control of the room temperature sensor in the remote control unit. The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit. Signal from remote control unit 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes Thermo. Thermo. Thermo. Thermo. Thermo. Thermo. Thermo. set temp. T+1 C T C More than 5 minutes 5 minutes 3 minutes Room temp. Compressor Outdoor fan Indoor fan Set speed The control circuit will not attempt to turn the compressor until the compressor has been for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize. As a protective measure, the control circuit switches the compressor after 5 minutes or more of compressor operation. Thermo. : When the room temperature is above T + 1 C (T C is set temperature). Compressor Thermo. : When the room temperature is equal to or below set temperature T C. Compressor 22

27 Heating Room temperature control is obtained by cycling the compressor and under control of the room temperature sensor in the remote control unit. The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit. Signal from remote control unit More than 5 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes Thermo. Thermo. Thermo. Thermo. Set temp. T C T 1 C T 2 C 5 minutes 5 minutes Room temp. Compressor Outdoor fan 30 seconds 30 seconds Indoor fan LL Set speed LL LL Set speed LL Standby lamp * 1 * 1 Indoor heat exch. coil temp. 35 C * 1 25 C 20 C Solenoid coil (4-way valve) (Reversing cycle) Operation button The control circuit will not attempt to turn the compressor until the compressor has been for at least 5 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize. As a protective measure, the control circuit switches the compressor after 5 minutes or more of compressor operation. Thermo. : When the room temperature is below T 1 C (T C is set temperature). Compressor Thermo. : When the room temperature is equal to or above set temperature T C. Compressor NOTE *1: Refer to "10-5 Cold Draft Prevention". 23

28 10-2. Dry Operation (Dehumidification) Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning and automatically as shown in the chart below according to the room temperature. Room temp. T+2 C Set temp. T C T 1 C Room temp. 15 C Cooling operation *Dry A1 zone Compressor : Continuous operation FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation only while the compressor is. *Dry B zone Compressor : Intermittent operation ( for 3 minutes and for 9 minutes) FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation only while the compressor is. Monitor zone Both the indoor and outdoor units stop. NOTE Intermittent ventilation occurs by switching the indoor fan speed between L LL. Dry operation does not occur when the room temperature is under 15 C, which is the monitor zone. When the compressor stops, the indoor fan stops as well. 24

29 10-3. Freeze Prevention (Cooling) This function prevents freezing of the indoor heat exchange coil. When the compressor has been running for 10 minutes or more and the temperature of the indoor heat exchange coil falls below 1 C, the control circuit stops the compressor for at least 6 minutes. The compressor does not start again until the temperature rises above 8 C or 6 minutes has elapsed. Room temp. Thermo. Thermo. T+1 C Set temp. T C Indoor heat exch. coil temp. 6 minutes More than 6 minutes 1 C More than 10 minutes More than 10 minutes Compressor Indoor fan Set speed Set speed Overload Prevention (Heating) This function prevents overheating of the indoor heat exchange coil. When the temperature of the indoor heat exchange coil rises above 54 C, and if the indoor fan is L (low speed), then the fan speed changes from L (low speed) to M (medium speed). When the temperature of the indoor heat exchange coil rises above 57 C, the outdoor fan stops. Indoor heat exch. coil temp. C Outdoor fan Indoor fan H or M or L H H, M M, L M Compressor 25

30 10-5. Cold Draft Prevention (Heating) This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coil have sufficiently warmed up. STANDBY lamp on front of the indoor unit lights up when the indoor fan speed is either LL or. Indoor heat exch. coil temp. C 35 C 25 C 20 C Compressor Indoor fan LL Set speed LL Standby lamp Initial start LL = Very low speed 26

31 10-6. Defrosting Operation (Heating) Defrosting Flowchart * Split System A (or B) * Heating operation Split System B (or A) Heating operation * Split System A: Indoor unit A Compressor A Solenoid coil A * Split System B: Indoor unit B Compressor B Solenoid coil B 20 minutes masking Temperature in outdoor heat exchanger coil drops 1 deg/6 min. or more and repeats 3 times continuously. 6 minutes masking Temperature in outdoor heat exchanger coil falls to 14 C or lower. Preparation for defrosting Defrosting starts. Defrosting starts. Defrosting Defrosting (= Cooling cycle) Cold draft prevention Cold draft prevention Temperature in outdoor heat exchanger coil is 26 C or higher. Defrosting time is over 13.5 minutes. Defrosting stops. Defrosting stops. 27

32 Defrosting Mode Timing Chart Start of defrosting Defrosting 13.5 min. or outdoor coil temp. 26 C Release of defrosting 65 sec. 65 sec. Compressor A 5 sec. 5 sec. 5 sec. Compressor B 1 min. 4-way valve A and B Outdoor fan Indoor fan A Set speed 30 sec. * 1 Set speed Standby lamp A Light Indoor fan B Set speed * 1 Set speed Standby lamp B Light Indoor heat exch. coil temp. 35 C Unit A Unit B Release of cold draft prevention NOTE *1. No LL fan operation during this period. 28

33 11.TROUBLESHOOTING Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing Check power supply wiring. Check that power supply wires are correctly connected to terminals No.1 and No.2 on the 3p terminal plate in the outdoor unit Check inter-unit wiring. Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit Check power supply. Check that voltage is in specified range (±10% of the rating). Check that power is being supplied. Outdoor unit 1 2 Terminal plate B Terminal plate A Power supply Single-phase, 50Hz, 240V Ground Inter-unit power wiring Inter-unit control wiring Inter-unit power wiring Inter-unit control wiring Indoor unit B Indoor unit A Check lead wires and connectors in indoor and outdoor units. Check that coating of lead wires is not damaged. Check that lead wires and connectors are firmly connected. Check that wiring is correct. 29

34 11-2. Air conditioner does not operate Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to, it is tripped soon. (Resetting is not possible.) There is a possibility of ground fault. Check insulation resistance. If resistance value is 2MΩ or less, insulation is defective ( NO ). WARNING * Set circuit breaker to. 1 Remove both power supply wires and inter-unit wires from terminal plate in outdoor unit. Measure insulation resistance of outdoor unit. NO Insulation of outdoor unit is defective. Measure insulation resistance of electrical parts in outdoor unit. 2 Remove inter-unit wires from terminal plate in indoor unit. Measure insulation resistance of indoor unit. NO Insulation of indoor unit is defective. Measure insulation resistance of electrical parts in indoor unit. B. Circuit breaker trips in several minutes after turning the air conditioner on. There is a possibility of short circuit. Check capacity of circuit breaker. Capacity of circuit breaker is suitable. NO Replace with suitable one (larger capacity). Measure resistance of compressor motor winding. (CMA and CMB) 30

35 Neither indoor nor outdoor unit runs. A. Power is not supplied. Check power supply. Power is being supplied to the outdoor unit. NO Circuit breaker is tripped. Power failure Reset breaker. Wait for recovery or contact power company. B. Check "OPERATI selector" switch in the indoor unit. OPERATI selector switch is set in position. YES Switch Ass'y or indoor PCB Ass'y is defective. NO Set OPERATI selector switch to. C. Check remote control unit. Try to run with another remote control unit. OK First remote control unit is defective. Check for residue buildup on transmitter of remote control unit. Clean transmitter. Check for residue buildup on remote control receiver on front of indoor unit. Clean receiver. 31

36 D. Check fuse on the indoor PCB Ass'y. Check fuse on indoor PCB Ass'y for continuity. (F) OK If fuse has been blown, Measure resistance of indoor fan motor winding. (FMI) OK Check operation lamp to see if light is. Light is Measure resistance of flap motor winding. (FLP) OK Measure resistance of primary and secondary winding of transformer. (TR) OK Replace the fuse. Indoor PCB Ass'y or switch Ass'y is defective. E. Check TIMER SELECT button on the remote control unit. Timer is turned. Check to see if is displayed on remote control. YES Cancel the timer mode. 32

37 Only outdoor unit does not run. A. Check setting temperature. COOL Is room temperature too low? NO HEAT Is room temperature too high? NO Try to lower setting temperature by temperature setting button cooler. Outdoor unit still does not run. Try to raise setting temperature by temperature setting button warmer. Outdoor unit still does not run. Try to run using another remote control unit. OK Try to run using another remote control unit. OK Remote control unit is defective. Remote control unit is defective. B. Check PCB Ass'y in either indoor or outdoor unit. Check voltage between terminals No. 3(+) and No. 4 at terminal plate. (DC 24V) No voltage appears. OK Outdoor PCB Ass'y is defective. Indoor PCB Ass'y is defective Only indoor unit does not run. Indoor PCB Ass'y is defective. 33

38 11-3. Some part of air conditioner does not operate Only indoor fan does not run. Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. Check fan casing foreign matter on inside. Fan motor burnout or foreign matter in bearings. Remove foreign matter or repair. Repair or replace. Measure resistance of indoor fan motor winding. OK Check fan motor capacitor Only flap motor does not run. Measure resistance of flap motor winding Only outdoor fan does not run. Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. Check fan casing for foreign matter on inside. Fan motor burnout or foreign matter in bearings. Remove foreign matter or repair. Repair or replace. Measure resistance of outdoor fan motor winding. OK Check fan motor capacitor. (CF) 34

39 Only compressor does not run. Check compressor motor capacitor. (CA,CB) Overload relay is working. (OLR 1 to 4) YES Measure coil resistance of power relay. (PRA,PRB) Measure resistance of compressor motor winding. Temperature of compressor is abnormally high. YES Refrigerant gas shortage. NO YES Charge refrigerant gas (R22). Rotor may be locked up. 35

40 11-4. Air conditioner operates, but abnormalities are observed Operation does not switch from HEAT to COOL (or COOL to HEAT). Remote control unit may be defective. Receiver in switch Ass'y may be defective. Measure resistance of 4 way valve's winding. COOL HEAT Check voltage between terminals No. 3(+) and No. 5 at terminal plate. (DC 24V) No voltage appears. OK Outdoor PCB Ass'y is defective. Indoor PCB Ass'y is defective. HEAT COOL Check voltage between terminals No. 3(+) and No. 5 at terminal plate. (0V) CAUTI Units A and B cannot be operated in different modes simultaneously (for example, unit A operating in the heating mode while unit B is operating in the cooling or drying mode). When operating two units at the same time, set them both to the same mode. Note however that though technically different modes, unit A can operate in the cooling mode while B is operating in the drying mode. If the units are operated in different modes (for example, unit A in the heating mode and unit B in the cooling or drying mode), the results are as follows. (Example) Unit A in heating mode Unit B in cooling or drying mode Unit A in heating mode (Heating operation takes precedence.) Unit B fan operating If unit A is stopped, unit B will switch to cooling or drying operation. 36

41 Poor cooling or heating. Check position of remote control unit. Cool or warm air from air conditioner reaches position directly. YES Change position of remote control unit. Wide and narrow tubes between indoor unit and outdoor unit are insulated. YES NO Insulate both wide and narrow tubes separately and then tape together. Measure temperature of suction and discharge air of air conditioner. Temperature difference is small. Possibility of gas shortage. Charge refrigerant gas (R22). Temperature difference between suction and discharge air is large enough (approx. 10 deg. or more). Check for clogging of air filter. Air filter is clogged. Clean filter. Fan speed is set to LOW. YES Set fan speed to either HIGH or MEDIUM. Review cooling load estimate, if performance of air conditioner is normal. Reduce cooling or heating load or replace the air conditioner with larger capacity Excessive cooling or heating. Set temperature is suitable. NO Set temperature to higher or lower value using temperature setting buttons of the remote control unit. Remote control unit is placed where it can detect room temperature properly. NO Change position of remote control unit. 37

42 11-5. If a sensor is defective Indoor coil temp. thermistor (TH1) is defective. Operation lamp on front side of indoor unit is flashing on and off. (*) YES Thermistor (TH1 ) is defective. (That is, sensor is SHORT.) No Replace thermistor. Function of freeze prevention continues to work in cooling mode. Refer to 5-4 "Freeze Prevention" YES Thermistor (TH1 ) is not connected to indoor PCB Ass'y, or its temperature sensor is defective. (That is, sensor is OPEN.) Replace thermistor. No NOTE Alarm Signal (*) Operation lamp on the front side of the indoor unit will flash on and off when the indoor coil thermistor is defective. (That is, sensor is SHORT). At the same time the outdoor unit will stop. Indoor unit will operate only for ventilation Room temp. thermistor (TH2) is defective. A. Open When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low room temperature. a) In Cooling mode: The air conditioner soon stops and will not start again. (Thermo.) Neither outdoor fan nor compressor runs. b) In Heating mode: The air conditioner continues to operate. (Thermo.) Both the outdoor fan and compressor do not stop. As a result, the room becomes too warm. B. Short When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high room temperature. a) In Cooling mode: The air conditioner continues to operate. (Thermo.) Both the outdoor fan and compressor do not stop. As a result, the room becomes too cold. b) In Heating mode: The air conditioner soon stops and will not start again. (Thermo.) Neither outdoor fan nor compressor runs. Temperature sensor Lead wires Thermistor Structure NOTE Definition of Open or Short Circuit of Sensor (Thermistor) Open... A lead wire is broken or disconnected or the circuit inside the temperature sensor is open. Short... The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit inside the temperature sensor is closed. 38

43 12. ARRANGEMENT OF ELECTRICAL COMPENT Indoor Unit SAP KM97AHA Electric Parts Room temp. thermistor (TH2) Fan motor capacitor (C) Transformer (TR) Coil temp. thermistor (TH1) Terminal plate PCB Ass'y Switch Ass'y Flap motor (FLP) 39

44 ELEC BOX Outdoor Unit SAP CM1827AHA PCB Ass'y (Controller) Parts Layout in Unit Heat exchenger coil Thermistor Compressor A (CMA) Compressor B (CMB) PCB Ass'y Fan motor Solenoid coil B (SCB) Solenoid coil A (SCA) Electric Parts Compressor motor capacitor (CA) Compressor motor capacitor (CB) Varistor (SA1) Fan motor capacitor (CF) Varistor (SA2) Power relay B (PRB) Overload relay (OLR1) Overload relay (OLR3) Power relay A (PRA) Terminal Plate (To Indoor Unit A) Terminal Plate (To Indoor Unit B) Terminal Plate (To Power supply) 40

45 13. CHECKING ELECTRICAL COMPENTS Measurement of Insulation Resistance The insulation is in good condition if the resistance exceeds 2MΩ. Clip Ground wire Power Supply Wires Probe Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 1) Insulation tester Terminal plate Fig. 1 Then measure the resistance between the ground wire and the other power wire. (Fig. 1) Probe Indoor Unit Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate. (Fig. 2) Note that the ground line terminal should be skipped for the check. (Fig. 2) Outdoor Unit Copper tube or metallic part Clip Insulation tester Fig. 2 Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. 2) Probe Measurement of Insulation Resistance for Electrical Parts Clip Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 3 and 4) Refer to Electric Wiring Diagram. Copper tube or metallic part Insulation tester Fig. 3 NOTE If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin. Metallic part Probe From fan motor, compressor and other parts Clip Insulation tester Fig. 4 41

46 13-2. Checking Continuity of Fuse on PCB Ass'y Fuse Remove the PCB Ass'y from the electrical component box. Then pull out the fuse from the PCB Ass'y. Check for continuity using a multimeter as shown in Fig. 6. PCB Ass y Checking Motor Capacitor Fig. 5 Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. Fuse The capacitor is good if the pointer bounces to a great extent and then gradually returns to its original position. Fig. 6 The range of deflection and deflection time differ according to the capacity of the capacitor. Multimeter Compressor motor capacitor Fan motor capacitor Fig. 7 42

47 11. MAINTENANCE Changing Address of Remote Control Unit in Indoor Unit If you are installing more than 1 indoor unit (up to 2) in the same room, it is necessary for you to assign each unit its own address, so each can be operated by its own separate remote control unit. You assign the addresses by matching the switch positions of each indoor unit with the switch positions of its remote control unit. Following table shows the position you can use up to 2 indoor units installed in the same room. Unit No. Indoor Unit Address (Control PCB) Remote Control Address 1 A 2 B To Change Address on PCB Ass y (1) Locate the address switch S10 on the control PCB Ass y of indoor unit. (2) Change the switch to position. NOTE Address switche S10 on the control PCB Ass y is in the position at time of shipment. To Change Address on Remote Control Unit (1) Remove the batteries before changing the address. (2) Remove tab marked A to change the address of the remote control unit. (3) When it is removed, the address is automatically set to B. (4) After inserting the batteries, press ACL button. ACL button NOTE Address switch on the remote control unit is in A position at time of shipment. 43

48 APPENDIX Remote Control Unit Sensor Transmitter Display / operation button (Cover closed) 1 HR. TIMER button Temperature setting buttons (TEMP.) MODE selector button FLAP button TIMER button ADDRESS switch NIGHT SETBACK button FAN SPEED selector button TIMER SET button (which advances the time displayed) TIMER button ACL button A/C SENSOR button Battery compartment (Pull off the cover to expose the batteries.) NOTE The illustration above pictures the remote control unit after the coverhas been lowered and removed. Unit Display and Operation Selector INDOOR UNIT TIMER lamp STANDBY lamp OPERATI lamp OPERATI STANDBY TIMER TEST REMOTE CTROL receiver Operation selector 44

49

50 SANYO Electric Co.,Ltd. Osaka, Japan SM /2002

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: ASR609CL ASR612CL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. ASR609CL 387006970 ASR612CL 387006971 0.8180.250.0 05/2002 IMPORTANT! Please read

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL Outdoor Unit GR54M2C Indoor Unit MCA27MC (X2) MULTI-SPLIT SYSTEM AIR CONDITIONER Indoor Unit Outdoor Unit MCA27MC GR54M2C 0.8180.195.0 04/2001 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K303A + SAP C303A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K303A A 1 852 098 83 Outdoor Model No.

More information

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A TECHNICAL & SERVICE MANUAL SAP K181A SAP K241A + SAP C181A + SAP C241A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K181A S 1 852 068 06 SAP K241A

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: GRF188R5TAA GRF228R5TAA GRF228R7TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GRF188R5TAA 38.7107.083 GRF228R5TAA 38.7107.084 GRF228R7TAA 38.7107.085

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO. TECHNICAL & SERVICE MANUAL SAP K301AH + SAP C301AH FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K301AH S 1 852 071 34 Outdoor Model No. Product Code

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510 TECHNICAL & SERVICE MANUAL SA 93AH FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-93AH 1 851 006 97 Australia SA 93AH REFERENCE NO. SM700510 IMPORTANT! Please Read Before

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE726SCL AE752SCL AE71SCL3 AE735SCL AE752SCL3 AE100SCL3 AE764SCL3 AE125SCL3 SPLIT SYSTEM AIR CONDITIONER Model No. AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AE22AH 387031006 AE28AH 387031007 AE38AH 387031008

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL AWR222CLE - AER222SC AWR222CLE - AER222SC3 SPLIT SYSTEM AIR CONDITIONER 0.8180.076.0 03/00 Important! Please Read Before Starting This air conditioning system meets strict safety

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW22AL 387030005 AW28AL 387030006 AW38AL 387030007 AW42AL 387030094 0.8180.467.0

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: DUAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.098 38.7107.103 38.7107.106 0.8180.597.03 09/2012 IMPORTANT! Please read before installation

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL HEAT PUMP MODELS INDOOR UNIT: MPAF188R5TAA MPAF228R5TAA COOLING MODELS MPAF188C5TAA MPAF228C5TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAF188R5TAA 38.7104.033

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA-

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MCAF72R5TA- 387104015 MCAF92R5TA- 387104016 MCAF122R5TA- 387104017

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MRAF99R5IAA 38.7104.065 MRAF129R5IAA 38.7104.062 MPAF99R5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS - Wall-mount indoor unit - OPERATING LIMITS Cooling Maximum conditions Heating Maximum conditions Outdoor temperature : 122 F (50 C) D.B. Outdoor temperature : 75 F (24 C) D.B.

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF94R5IAA + GRF97R5I MCAF124R5IAA + GRF127R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF94R5IAA

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL XH7R / CH7R, C7R XH7R / CH7R, C7R XH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R THH7R / CH7R THH7R / CH7R FILE NO. KH7R / CH7R, C7R KH07R / CH07R,

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS0971 + C0971 + CL0971 KS1271 + C1271 + CL1271 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS0971 KS1271 Product

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XS171 & PNRXS187 + C171 XS171 & PNRXS187 + CL171 XS187 & PNRXS187 + CH187 XS187 & PNRXS187 + CL187 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KE30NKU CS-KE36NKU Product Code No. 1 852 360 88

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL TECHNICAL & SERVICE MANUAL INDOOR UNIT: MCAF94MR5IAA MCAF124MR5IAA MCAF184MR5IAA MCAF244MR5IAA NOV.2003 Destination: General area (50Hz) Europe (50Hz) Australia (50Hz) General area (60Hz) DC INVERTER MULTI-SYSTEM

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL KHS308 + CH308 KHS368 + CH368 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KHS308 KHS368 Product Code No. 85 354 8 85 354 9 Outdoor

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : KMS0772 FILE NO. KMS0972 KMS1272 KMS1872 KMS2472 Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF88R5I + GRF86R5I MCAF48R5I + GRF46R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF88R5I MCAF88R5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS7 & PNRXS87 + CH7 XHS87 & PNRXS87 + CH87 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS7 (PNRXS87) XHS87 (PNRXS87)

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MPAFIA0R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAFIA0R5IAA 38.7104.074 0.8180.590.01 10/2012 IMPORTANT! Please read before installation

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL Indoor Unit MCA201R MCA271R MCA351R Outdoor Unit GR201R GR271R GR351R SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT 0.8180.263.1 06/2002 Important! Please Read Before

More information

Using the Remote Control Unit

Using the Remote Control Unit Remote Control Unit (continued) SENSOR button Temperature Display Selector button Time Display Selector button ACL button (ALL CLEAR) When you press this button (use a small-tipped object such as a ballpoint

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKS7NKU CS-MKS9NKU CS-MKS12NKU CS-MKS18NKU CS-MKS24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MCAF78MR5I MCAF98MR5I MCAF128MR5I MCAF188R5I MCAF248R5I FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity

More information

INVERTER SPLIT SYSTEM AIR CONDITIONER

INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV91EH + SAP-CRV91EH FILE NO. INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. Outdoor Model No. Product Code No. Destination SAP-KRV91EH 1 852 065

More information

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA TECHNICAL & SERVICE MANUAL STK-RCS-7TWSUA FILE NO. Destination: North America WIRED REMOTE CONTROLLER Model No. STK-RCS-7TWSUA Product Code No. 1 852 353 85 REFERENCE NO. SM700799 Important! Please Read

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Solenoid Valve Kit For 3WAY VRF System CZ-PXXXHR3 () IMPORTANT! Please Read Before Starting This solenoid Valve kit must be installed by the sales dealer or installer. This information

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 05-355 KMS0772_indoor 3/16/06 5:27 PM Page a INSTALLATION INSTRUCTIONS Inverter Split System Air Conditioner COOL/ DRY Model This air conditioner uses the new refrigerant R410A. For Indoor Unit Contents

More information

TEST RUN SERVICE MANUAL

TEST RUN SERVICE MANUAL TEST RUN SERVICE MANUAL Model No. Outdoor Unit ME Class Model Name HP U-MEE 0HP U-0MEE HP U-MEE HP U-MEE HP U-MEE HP U-MEE 0HP U-0MEE U-MEEE U-0MEEE U-MEEE U-MEEE U-MEEE U-MEEE U-0MEEE Indoor Unit Class

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245SCH2O( I ) Cooling only model ARGO 235HPH2O( I ) Heat pump model 0.8180.519.1 11 / 2007 Table of contents Page A SPECIFICATIONS 1) Unit specifications

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Inverter Split System Air Conditioner COOL/ DRY Model This air conditioner uses the new refrigerant R410A. Contents Page Model Combinations IMPORTANT! Please Read Before Starting...

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MPAF90MRI MPAF0MRI MPAF80RI MPAF0RI DC INVERTER MULTISYSTEM AIR CONDITIONER Capacity Indoor Model No..6 kw.0 kw. kw 7.0 kw MPAF90MRI MPAF0MRI MPAF80RI MPAF0RI Wall

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK20ZD-S - 1 - INDOOR UNIT Model SRK20ZD-S OUTDOOR UNIT Model SRC20ZD-S REMOTE

More information

XHS1271 XHS1872. This air conditioner uses the new refrigerant R410A. COOL/DRY/HEAT Model

XHS1271 XHS1872. This air conditioner uses the new refrigerant R410A. COOL/DRY/HEAT Model XHS1271 XHS1872 COOL/DRY/HEAT Model INSTRUCTION MANUAL Inverter-Controlled Split System Air Conditioner MODE D EMPLOI Climatiseur de type séparé contrôlé par inverseur This air conditioner uses the new

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL REVE DCI HPL/SCL 0.8180.615.01 06/2012 Pagina 1 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3 2) Major Component specifications 4 B OPERATING RANGE 6

More information

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET AUTO COOL DRY MODE TIMER ON OFF TIMER OFF/ON TEMP ON TIMER FAN SPEED AIR SWING SET 1 2 3 FAN SPEED AIR SWING OFF CANCEL AC RC SET CHECK CLOCK RESET Order No: PAPAMY1611008CE Indoor Unit CS-MPS9SKH CS-MPS12SKH

More information

7-5. Remove the Grille to Install the Indoor Unit

7-5. Remove the Grille to Install the Indoor Unit 7-5. Remove the Grille to Install the Indoor Unit Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps as given below.

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

NO. F ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-100A KM-125A MODEL SERVICE MANUAL

NO. F ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-100A KM-125A MODEL SERVICE MANUAL NO. F003-756 ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CTAINED CRESCENT CUBER MODEL KM-100A KM-125A SERVICE MANUAL IMPORTANT This manual should be read carefully before the icemaker is

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR ASU9RL2 ASU12RL2 OUTDOOR AOU9RL2 AOU12RL2 1.INDOOR UNIT : ASU9RL2 ASU12RL2 DTR_AS072E_01 2012.11.02 1. INDOOR UNIT CONTENTS 1. FEATURE...

More information

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit RCW-54CB RO-50CA RC-54CA RO-50CA RC-54HA RO-50HA CONTENTS SPECIFICATIONS OUTLINE AND DIMENTIONS CIRCUIT DIAGRAM REFRIGERANT SYSTEM

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER TECHNICAL MANUAL & PARTS LIST DRAFT WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK50HE-S, SRK56HE-S (Split system, air cooled cooling only type) SRK50CE-S, SRK56CE-S

More information

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS OWNER S MANUAL High-Wall Fan Coil Unit Page GENERAL 2,3 OPERATING MODES 2 REMOTE CONTROL 2 OPERATION 3-9 REMOTE CONTROL OPERATION 3 INDOOR UNIT DISPLAY 5 EMERGENCY OPERATION 5 PRESSING THE ON/OFF BUTTON

More information

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SPECIFICATION... 1 FUNCTIONS... 5 SERVICE FUNCTION EXPLANATION... 7 OPERATION DETAILS... 8 TROUBLESHOOTING GUIDE... 13 PERFORMANCE

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

Кондиционеры Mitsubishi Heavy

Кондиционеры Mitsubishi Heavy Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK28HD, SRK40HD INDOOR UNIT Models SRK28HD, SRK40HD OUTDOOR UNIT Model SRC28HD REMOTE CONTROLLER Model SRC40HD GENERAL

More information

SERVICE Manual AIR CONDITIONER AW0719 AW Precautions. 2. Product Specifications. 3. Operating Instructions and Installation

SERVICE Manual AIR CONDITIONER AW0719 AW Precautions. 2. Product Specifications. 3. Operating Instructions and Installation ROOM AIR CONDITIONER AW079 AW089 SERVICE Manual AIR CONDITIONER CONTENTS. Precautions 2. Product Specifications 3. Operating Instructions and Installation 4. Disassembly and Reassembly 5. Troubleshooting

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LLCC AS G09LLCC AS G12LLCC OUTDOOR AO G07LLCC AO G09LLCC AO G12LLCC 1.INDOOR UNIT : AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02

More information

AIR-CONDITIONER SERVICE MANUAL

AIR-CONDITIONER SERVICE MANUAL FILE NO. A90-9608 SERVICE MANUAL AIR-CONDITIONER S SPLIT BUILT-IN DUCT TYPE RAV-362B-PE/ RAV-462B-PE/ SPLIT CEILING TYPE RAV-362C-PE/ RAV-462C-PE/ SPLIT CASSETTE TYPE RAV-362U-PE/ RAV-462U-PE/ PRINTED

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK T AVAILABLE C AMPM AMPM SPLIT-TYPE, HEAT PUM PAIR CDITIERS No. OC REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PLH Indoor unit [Model names] PLH-3AK PLH-3AKH PLH-AKS PLH-AKHS PLH-5AKS PLH-5AKHS PLH-6AKS

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER Owner s Manual Model: 3554190/3554191/3554192/3554193 3554194/3554195/3554196/3554197 IMPORTANT NOTE: Read this manual carefully

More information

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2

Room Air Conditioner CONTENTS CS-E9BKP CU-E9BKP5 CS-E12BKP CU-E12BKP5. Order No: MAC C2 Order No: MAC008C Room Air Conditioner CS-E9BKP CU-E9BKP5 CS-EBKP CU-EBKP5 CONTENTS Page Page Features Functions Product Specifications 6 Dimensions 0 5 Refrigeration Cycle Diagram 6 Block Diagram 7 Wiring

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump R-10A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFF(A/H)H, DFC(A/H) Please read the operating instructions and safety precautions carefully and thoroughly before installing and

More information

Features. Simple One-touch Wireless Remote Control The remote control unit has several features to facilitate automatic operation.

Features. Simple One-touch Wireless Remote Control The remote control unit has several features to facilitate automatic operation. 01_KMS1872_En.fm Page 2 Monday, November 14, 2005 1:28 PM Features This air conditioner is an inverter type unit that automatically adjusts capacity as appropriate. Details on these functions are provided

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

DUCT type. Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

DUCT type. Большая библиотека технической документации   каталоги, инструкции, сервисные мануалы, схемы. SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-25CA RD-25HA RD-30CA RD-30HA RO-25CA RO-25HA RO-30CA RO-30HA C O N T E N T S SPECIFICATIONS.............................................

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER FREE JOINT MULTI AIR CONDITIONER INDOOR UNIT MH020FPEA MH023FPEA MH026FPEA MH035FPEA MH052FPEA MH8VP2-09 MH9VP2-07 MH9VP2-2 MH026FKEA MH035FKEA MH052FDEA OUTDOOR UNIT MH8VP2X MH9VP2X MH052FXEA2 MH068FXEA4

More information

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1 SPLIT-TYPE AIR CONDITIONERS Revision D: Changing defrost finish temperature has been corrected (10-1.). Please void OBH516 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED

More information