Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator

Size: px
Start display at page:

Download "Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator"

Transcription

1 Installation Instructions Model MDACT MXL/FireFinder-XLS Multi-Point Digital Alarm Communicator INTRODUCTION The Model MDACT from Siemens Industry, Inc. is a multipoint serial dialer for use in MXL and FireFinder- XLS systems where point identification of alarm, supervisory, status or trouble indication is required at central stations. The MDACT has the following features: Multiple Data Protocols: Contact ID and SIA 00 Event History Buffer Dual Phone Line Interface Option Bus Interface for Built-in Programming using DCT-P LCD Remote Keypad LEDs for Heartbeat, System Trouble and Phone Line Trouble (one per line) Real Time Clock NOTE: The NIM-2D Upgrade Kit, P/N , must be used. The MDACT is compatible with the following: MMB ROM version 0.4 and higher SMB ROM version 6.4 and higher CSG-M version.05 and higher PMI version 4.0 and higher Zeus version 4.0 and higher For MXL programming, refer to MXL Operation, Installation, and Maintenance Manual, P/N , MXL-IQ Operation, Installation, and Maintenance Manual, P/N , CSG-M Manual, P/N , and CSG-M Version.05 Update, P/N , as applicable. For FireFinder-XLS programming, refer to the FireFinder-XLS Installation, Operation and Maintenance Manual, P/N , and the Zeus Quick Start Manual, P/N OPERATION The MDACT delays the AC Fail trouble signal in accordance with NFPA and UL requirements. Refer to the MDACT Programming Manual, P/N for further information. INSTALLATION Remove all system power before installation, first battery and then AC. (To power up, connect the AC first, then the battery.) The MDACT installs into the MXL optional MOM-4/-2 card cage where it occupies one half width slot. The CABLE P/N TO MMB-2/-3, SMB-2/-3 OR PSR- DO NOT USE DO NOT USE TB TB3 P5 P TB P MOM-4 INSTALLED IN MXL PANEL P3 P2 MDACT P8 TB7 P0 TB2 MDACT P TB4 NOTE: MDACT can only be installed in MOM-4/-2 slots P2 or P4. TO MMB-2/-3, SMB-2/-3, PSR- OR PSC-2 24V Figure MDACT Installation In MXL Panel Siemens Industry, Inc. Building Technologies Division Florham Park, NJ P/N Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada

2 TO PSC-2 24V P5 TB6 P7 MOM-2* INSTALLED IN FIREFINDER-XLS PANEL DO NOT USE WITH FIREFINDER-XLS, SEE XMI INSTALLATION INSTRUCTIONS, P/N TB2 P2 XMI P8 TB7 P0 MDACT P TB4 FOR FIREFINDER-XLS, ONLY * MODEL MOM-2 IS AVAILABLE. REQUIRES MOUNTING PLATE MOM2-XMP. DO NOT USE WITH FIREFINDER-XLS, SEE XMI INSTALLATION INSTRUCTIONS, P/N Figure 2 MDACT Installation In FireFinder-XLS Panel SW NIM-2D P6 M W 3 JP SW3 W X NOTE: Switch SW3 is factory set. All switches must remain in the ON position. INSTALL JUMPER PLUGS IN ORIENTATION AS SHOWN. POSITION M SHOWN SELECTED. M W JP4 W X P6 INSTALL JUMPER PLUGS IN ORIENTATION AS SHOWN. Figure 3 NIM-2D Module Board 2

3 MDACT can be installed in either slot P2 or slot P4 of the MOM-4/-2. (See Figure.) For FireFinder-XLS, only the MOM-2 can be used. (See Figure 2.) Setting the Switches Set all switches, configuration jumpers, and connection cables before installing them into the MOM-4/-2. See Figure 3 for switch locations.. Use switch SW to set the MXL MNET or FireFinder-XLS HNET network address. Set this switch according to the address where the MDACT is installed in the MXL or FireFinder-XLS network map. Refer to the CSG-M or Zeus configuration printout for the address of the module. See Table for MXL (MNET) and XLS (HNET) settings. 2. Switch SW3 is factory set. All switches must remain in the ON position. 3. Set jumper plugs on JP4 to the "M" position. 4. Set jumper plugs on P6 to the positions shown in Figure 3. Telephone Connectons Telephone Cord Installation Connect the primary phone line to the MDACT modular jack "Line" using a phone cord. Connect the secondary phone line to the MDACT jack "LINE2" using another phone cord. See Figure 4 for phone line connection. NOTE: You must connect separate primary and secondary phone lines to the MDACT for all applications. Location To prevent jamming of alarm and other reports, wire and locate the RJ3X or RJ38X jack so that normal phone use is temporarily interrupted while the MDACT transmits data (See Figure 5). After installation, confirm that the MDACT seizes the line, acquires dial tone and reports correctly to the receiver. Phone Line LINE Phone Line LED Phone Line 2 LINE 2 SYS TROUBLE HEARTBEAT Phone Line 2 LED System Trouble LED Heartbeat LED A B KEYPAD Dialer To NIM-2D Factory Connection Keypad Molex Connector Pins No Connection No Connection Figure 4 Dialer PCB Layout 3

4 Full Modular Phone Jack To Dialer R T RJ3X Module R T NOTE: Use the supplied telco cable assemblies to connect to an RJ3 jack. Make sure the RJ3 jacks are mounted in a secure location to prevent false disconnections and/or tampering. Figure 5 RJ3X Wiring Notification Do not connect registered equipment to party lines or coin-operated telephones. If the local telephone company requests notification before you connect the MDACT to the telephone network, supply the following information: the particular line to which you are connecting the MDACT the make, model and serial number of the device the FCC registration number (ESVMUL-4654-AL-E) and ringer equivalence (0.0B). If the telephone company makes changes in its communications facilities, equipment, operations or procedures that may affect the performance of the MDACT, the telephone company is obligated to notify the user in writing. The MDACT meets the requirements of UL 950. Connecting the Keypad to the MDACT NOTE: The DCT-P LCD Remote Keypad is used strictly for programming and debugging purposes only. A DCT-P LCD Remote Keypad can be used to operate the MDACT Communicator. Plug the molex connector from the DCT-P onto the connector pins on the MDACT board as shown in Figure 6. Use the following steps when programming the MDACT from the DCT-P.. Set the DCT-P address between and Use the wire connector supplied with the DCT-P to connect the DCT-P to the MDACT. See Figure Program the MDACT as explained in the programming section of the MDACT Programming Manual, P/N NOTE: If there is no keypad activity for three minutes, the keypad is disabled. The keypad's buzzer sounds and a "SYSTEM FAULT" message will appear on the keypad. Disconnect the keypad from the MDACT by removing the wire harness plug from the MDACT's keypad pins, then reconnect the wire plug harness to re-enable the keypad. 4

5 MDACT Fire Communicator LINE LINE 2 SYS TROUBLE HEARTBEAT DCT-P Terminal Strip ++- -AB KEYPAD NC C NO KEYPAD +2 VDC RED Com BLACK Data In GREEN Data Out YELLOW Figure 6 Keypad Connection to MDACT Fire Communicator ELECTRICAL RATINGS Active Active Standby 5VDC Module Current 24VDC Module Current 24VDC Module Current Compatibilities 0mA 380mA 320mA The following receivers and panels have been proven to be compatible with the MDACT under the method required by Underwriters Laboratories. Receivers that are not listed as compatible should not be used with the MDACT. Available Reporting Formats Contact ID (CID): Is the preferred reporting format. It provides a four digit account code followed by a three digit event code, a two digit group number, and a three digit contact number, all of which are used to provide specific point identification. SIA: Security Industry Association (SIA) Digital Communication Standard. The DACT provides level compatibility which includes tonal acknowledge, basic reports only, and fixed reporting codes. 5

6 Compatible Receivers (q = Available) Report Format Radionics D6500 Radionics D6600 Sur-gard SG-SLR Osborne/Hoffman Quick Alert Model II Ademco 685 Silent Knight SK9000 Contact ID q q q q q SIA 300 q q q SIA 0 q q q Figure 7 MDACT UL Listed Compatibility 6

7 TABLE NETWORK ADDRESS PROGRAMMING (SW) NETWORK ADDRESS PROGRAMMING ADDR ADDR ADDR ADDR ILLEGAL 064 OXOOOOOO 28 XOOOOOOO 92 XXOOOOOO 00 ILLEGAL 065 OXOOOOOX 29 XOOOOOOX 93 XXOOOOOX 002 ILLEGAL 066 OXOOOOXO 30 XOOOOOXO 94 XXOOOOXO OOOOOOXX OOOOOXOO OOOOOXOX OOOOOXXO OOOOOXXX OOOOXOOO OOOOXOOX OOOOXOXO OOOOXOXX OOOOXXOO OOOOXXOX OOOOXXXO OOOOXXXX OOOXOOOO OOOXOOOX OOOXOOXO OOOXOOXX OOOXOXOO OOOXOXOX OOOXOXXO OOOXOXXX OOOXXOOO OOOXXOOX OOOXXOXO OOOXXOXX OOOXXXOO OOOXXXOX OOOXXXXO OOOXXXXX OOXOOOOO OOXOOOOX OOXOOOXO OOXOOOXX OOXOOXOO OOXOOXOX OOXOOXXO OOXOOXXX OOXOXOOO OOXOXOOX OOXOXOXO OOXOXOXX OOXOXXOO OOXOXXOX OOXOXXXO OOXOXXXX OOXXOOOO OOXXOOOX OOXXOOXO OOXXOOXX OOXXOXOO OOXXOXOX OOXXOXXO OOXXOXXX OXOOOOXX OXOOOXOO OXOOOXOX OXOOOXXO OXOOOXXX OXOOXOOO OXOOXOOX OXOOXOXO OXOOXOXX OXOOXXOO OXOOXXOX OXOOXXXO OXOOXXXX OXOXOOOO OXOXOOOX OXOXOOXO OXOXOOXX OXOXOXOO OXOXOXOX OXOXOXXO OXOXOXXX OXOXXOOO OXOXXOOX OXOXXOXO OXOXXOXX OXOXXXOO OXOXXXOX OXOXXXXO OXOXXXXX OXXOOOOO OXXOOOOX OXXOOOXO OXXOOOXX OXXOOXOO OXXOOXOX OXXOOXXO OXXOOXXX OXXOXOOO OXXOXOOX OXXOXOXO OXXOXOXX OXXOXXOO OXXOXXOX OXXOXXXO OXXOXXXX OXXXOOOO OXXXOOOX OXXXOOXO OXXXOOXX OXXXOXOO OXXXOXOX OXXXOXXO OXXXOXXX XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO XOOXOXXX XOOXXOOO XOOXXOOX XOOXXOXO XOOXXOXX XOOXXXOO XOOXXXOX XOOXXXXO XOOXXXXX XOXOOOOO XOXOOOOX XOXOOOXO XOXOOOXX XOXOOXOO XOXOOXOX XOXOOXXO XOXOOXXX XOXOXOOO XOXOXOOX XOXOXOXO XOXOXOXX XOXOXXOO XOXOXXOX XOXOXXXO XOXOXXXX XOXXOOOO XOXXOOOX XOXXOOXO XOXXOOXX XOXXOXOO XOXXOXOX XOXXOXXO XOXXOXXX XXOOOOXX XXOOOXOO XXOOOXOX XXOOOXXO XXOOOXXX XXOOXOOO XXOOXOOX XXOOXOXO XXOOXOXX XXOOXXOO XXOOXXOX XXOOXXXO XXOOXXXX XXOXOOOO XXOXOOOX XXOXOOXO XXOXOOXX XXOXOXOO XXOXOXOX XXOXOXXO XXOXOXXX XXOXXOOO XXOXXOOX XXOXXOXO XXOXXOXX XXOXXXOO XXOXXXOX XXOXXXXO XXOXXXXX XXXOOOOO XXXOOOOX XXXOOOXO XXXOOOXX XXXOOXOO XXXOOXOX XXXOOXXO XXXOOXXX XXXOXOOO XXXOXOOX XXXOXOXO XXXOXOXX XXXOXXOO XXXOXXOX XXXOXXXO XXXOXXXX XXXXOOOO XXXXOOOX XXXXOOXO XXXXOOXX XXXXOXOO XXXXOXOX XXXXOXXO XXXXOXXX 056 OOXXXOOO 20 OXXXXOOO 84 XOXXXOOO 248 ILLEGAL 057 OOXXXOOX 2 OXXXXOOX 85 XOXXXOOX 249 ILLEGAL 058 OOXXXOXO 22 OXXXXOXO 86 XOXXXOXO 250 ILLEGAL 059 OOXXXOXX 23 OXXXXOXX 87 XOXXXOXX 25 ILLEGAL 060 OOXXXXOO 24 OXXXXXOO 88 XOXXXXOO 252 ILLEGAL 06 OOXXXXOX 25 OXXXXXOX 89 XOXXXXOX 253 ILLEGAL 062 OOXXXXXO 26 OXXXXXXO 90 XOXXXXXO 254 ILLEGAL 063 OOXXXXXX 27 OXXXXXXX 9 XOXXXXXX 255 ILLEGAL O = OPEN (or OFF) X = CLOSED ( or ON) 7

8 Siemens Industry, Inc. Building Technologies Division Florham Park, NJ P/N Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W Fire Safety Installation Instructions Model NIM-W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION The SIEMENS Model NIM-W provides a new communication path for the following uses:

More information

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply Fire Safety Installation Instructions Model PSR- Remote Power Supply Figure PSR- Remote Power Supply INTRODUCTION The SIEMENS Model PSR- (See Figure ) is a microprocessor controlled remote power supply

More information

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION Fire Safety Installation Instructions Model SM- ontrollable Signal Module OPERATIO The Model SM- ontrollable Signal Module has two fully supervised, programmable circuits. The outputs supply two lass B

More information

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet Description The F-DACT(F) is a digital alarm communicator transmitter for F-series fire alarm control

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION Fire Safety Installation Instructions Model RCC-/R and RSE- Remote Control Centers INTRODUCTI The SIEMENS Model RCC-/R Remote Command Center (See Figure ) provides the option to remotely annunciate and

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Fire Control/Communicator

Fire Control/Communicator Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS MODEL XR5FC/XR5SL COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed

More information

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Operating Instructions MXL Multi-Line Keyboard/Display Panel Operating Instructions MXL Multi-Line Keyboard/Display Panel Local Mode Operation TRODUCTION When the MXL Keyboard/Display Panel is installed in a control panel, the components are behind a locked door.

More information

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation. Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and

More information

1.1 Features Accessory Devices About This Manual How to Use This Manual

1.1 Features Accessory Devices About This Manual How to Use This Manual Content Section 1 Introduction... 1-1 1.1 Features... 1-1 1.2 Accessory Devices... 1-1 1.3 About This Manual... 1-2 1.3.1 How to Use This Manual... 1-2 Section 2 Agency Requirements... 2-1 2.1 Telephone

More information

1. Introduction. 1.1 Features

1. Introduction. 1.1 Features 1. Introduction The Silent Knight Model 5128/29 is a low-cost slave communicator that meets the requirements for UL 864, NFPA 72 Central Station Fire Protective Signaling System and Remote Signaling. NOTE:

More information

Installation Instructions Model CDC-4

Installation Instructions Model CDC-4 Installation Instructions CDC-4 Conventional Card INTRODUCTION The SIEMENS CDC is a card that allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class or Class B conventional

More information

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04 MODEL 5104B Fire Communicator Installation and Operation Manual Part Number 151053 E, 09/04 Content Section 1 Introduction... 1-1 1.1 Feature... 1-1 1.2 Accessory Devices... 1-2 1.3 About This Manual...

More information

D2071A. Operation & Installation Guide Fire Alarm Control Panel

D2071A. Operation & Installation Guide Fire Alarm Control Panel D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4

More information

Installation Instructions Model ABHW-4S

Installation Instructions Model ABHW-4S Installation Instructions Model ABHW-4S Intelligent Audible Base for Sleeping Area with 520Hz Low Frequency Sounder Introduction Application note The Model ABHW-4S audible base from Siemens Industry, Inc.

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

Installation Guide. Control/Communicator

Installation Guide. Control/Communicator Installation Guide Control/Communicator 33120G Page 2 Copyright 2001 Radionics Contents 1.0 Introduction... 5 1.1 Listings and Approvals... 5 1.1.1 Fire... 5 1.1.2 Burglary... 5 1.2 FCC Notice... 5 1.2.1

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

D2412 Control / Communicator Installation Manual

D2412 Control / Communicator Installation Manual D2412 Control / Communicator Installation Manual C Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable. However, Radionics,

More information

MODEL 5128/29. Installation Manual. Fire Slave Communicator. Trim Line. Part Number D, 06/02

MODEL 5128/29. Installation Manual. Fire Slave Communicator. Trim Line. Part Number D, 06/02 MODEL 5128/29 Fire Slave Communicator Installation Manual Part Number 150805D, 06/02 Trim Line Content Section 1 Introduction...1 1.1 Features...1 1.2 Optional Devices...2 1.3 UL Fire Listed Receivers

More information

D2071A Fire Control/Communicator Digital Alarm Communicator Transmitter (DACT)

D2071A Fire Control/Communicator Digital Alarm Communicator Transmitter (DACT) D2071A Fire Control/Communicator Digital Alarm Communicator Transmitter (DACT) Installation and Programming Manual 74-06200-000-C 12/98 1998 Radionics, Inc. FCC Notice This equipment generates, uses and

More information

INSTALLATION INSTRUCTIONS TALKBACK MODULE

INSTALLATION INSTRUCTIONS TALKBACK MODULE 273 Branchport Avenue Long Branch, N.J. 07740 (732) 222-6880 MODEL NUMBER: TBM-101 FCC REGULATIONS: INSTALLATION INSTRUCTIONS TALKBACK MODULE This equipment complies with Part 68 of the FCC Rules. On the

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

R E G E N C Y Model 2615 Control/Communicator. Installation Manual. Part Number , Rev. A Initial Release Date: March 1995 Revised August 1998

R E G E N C Y Model 2615 Control/Communicator. Installation Manual. Part Number , Rev. A Initial Release Date: March 1995 Revised August 1998 R E G E N C Y Model 2615 Control/Communicator Installation Manual Part Number 150863, Rev. A Initial Release Date: March 1995 Revised August 1998 Interactive Technologies, Inc. TE CHNO LO G IES Security

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS AES IntelliTAP Satellite / Remote Dialer Data Receiver Page 1 AES IntelliTAP Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device Version 1.10 Installation Guide CONTENTS How it Works

More information

Supervised Security System Owner's Guide

Supervised Security System Owner's Guide Owner's Guide PSC06 READ THIS FIRST This equipment generates and uses radio frequency energy, and if not installed and used properly, that is, in strict accordance with the manufacturers instructions,

More information

All-In-One Wireless Security System V1.0. Model #: MG-6060

All-In-One Wireless Security System V1.0. Model #: MG-6060 All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual DRAFT Table of Contents Introduction... 5 About Magellan and this Manual... 5 Conventions... 5 Specifications...

More information

FireSeeker Model FS-250C Addressable Fire Alarm Control Panel

FireSeeker Model FS-250C Addressable Fire Alarm Control Panel FireSeeker Model FS-250C Addressable Fire Alarm Control Panel One intelligent signaling line circuit (DCLB + DCLA) SureWire Polarity insensitive loop wiring Utilizes S-Series detectors and devices Supports

More information

FireFinder XLSV Digital Emergency Voice Alarm / Communication System

FireFinder XLSV Digital Emergency Voice Alarm / Communication System s Data Sheet Fire Safety Products FireFinder XLSV Digital Emergency Voice Alarm / Communication System ARCHITECT AND ENGINEER SPECIFICATIONS Eight (8) digital audio channels Compatible with Model PMI-3

More information

Digital Alarm Communicator/Transmitters 411/411UD. Manual. Document LS GE-E 1/29/2014 Rev: A P/N LS GE-E:A ECN

Digital Alarm Communicator/Transmitters 411/411UD. Manual. Document LS GE-E 1/29/2014 Rev: A P/N LS GE-E:A ECN Digital Alarm Communicator/Transmitters 411/411UD Manual Document LS10105-000GE-E 1/29/2014 Rev: A P/N LS10105-000GE-E:A ECN 13-875 Fire Alarm & Emergency Communication System Limitations While a life

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

R A D I O N I C S. D7212 Control/Communicator Operation and Installation Manual B 2/ Radionics

R A D I O N I C S. D7212 Control/Communicator Operation and Installation Manual B 2/ Radionics R A D I O N I C S D7212 Control/Communicator Operation and Installation Manual Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be

More information

XR10/XR20 Command Processor Panels Installation Guide

XR10/XR20 Command Processor Panels Installation Guide XR10/XR20 Command Processor Panels Installation Guide 10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator LT-0229 (5/97) MODEL XR10/XR20 COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

System Overview (continued) System Components. The FireFinder XLS system has been seismic qualified in accordance with:

System Overview (continued) System Components. The FireFinder XLS system has been seismic qualified in accordance with: s FireFinder XLS Advanced Fire Alarm Control Panel Standard / 2500-point-capacity addressable fire-alarm control panel (FACP) Ability to network with other FireFinder XLS systems Powerful, easy-to-use

More information

Fire Alarm Control/Communicator

Fire Alarm Control/Communicator Fire Alarm Control/Communicator Operation and Installation Guide Power Alarm Trouble Silenced Radionics FIRE CONTROL/COMMUNICATOR R 31499F Page 2 2000 Radionics. Contents Contents 1.0 Notices... 9 1.1

More information

Digital Alarm Communicator/Transmitter. Document # /07/00 Rev. P/N 50921:C ECN

Digital Alarm Communicator/Transmitter. Document # /07/00 Rev. P/N 50921:C ECN Digital Alarm Communicator/Transmitter 411 C Document #50921 3/07/00 Rev. P/N 50921:C ECN 00-106 2000 Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors,

More information

Model SK Installation and Operations Manual. Fire Control / Communicator. Document Rev: P P/N :P ECN:

Model SK Installation and Operations Manual. Fire Control / Communicator. Document Rev: P P/N :P ECN: Model SK-5208 Fire Control / Communicator Installation and Operations Manual Document 151204 Rev: P P/N 151204:P ECN: 17-0298 Installation Procedure Adherence to the following will aid in problem-free

More information

INSTALLATION MANUAL PC25OO

INSTALLATION MANUAL PC25OO INSTALLATION MANUAL PC25OO NOTES ON UL INSTALLATION This equipment is UL listed in accordance with UL standard 1023 (Household Burglar Alarm System Units), UL standard 985 (Household Fire Warning Units)

More information

Digital Alarm Communicator/Transmitter 411UD. Document # /07/00 Rev. P/N 50759:C ECN

Digital Alarm Communicator/Transmitter 411UD. Document # /07/00 Rev. P/N 50759:C ECN Digital Alarm Communicator/Transmitter 411UD C Document #50759 3/07/00 Rev. P/N 50759:C ECN 00-106 2000 Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors,

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

Installation Guide. XRSuper6 / XR20 / XR40

Installation Guide. XRSuper6 / XR20 / XR40 Installation Guide XRSuper6 / XR20 / XR40 Command Processor Panels MODEL XRSuper6/XR20/XR40 COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and,

More information

All-In-One Wireless Security System V1.0. Model # MG Programming Guide

All-In-One Wireless Security System V1.0. Model # MG Programming Guide All-In-One Wireless Security System V1.0 Model # MG-6060 Programming Guide Things You Should Know... 4 About This Programming Guide... 4 Conventions... 4 Installer Code (Default: 0000 / 000000)... 4 Maintenance

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3

More information

D7212 Control/Communicator Operation and Installation Manual

D7212 Control/Communicator Operation and Installation Manual D7212 Control/Communicator Operation and Installation Manual Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable. However,

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Operation and Installation Guide. Radio Communicator

Operation and Installation Guide. Radio Communicator Operation and Installation Guide Radio Communicator Operation and Installation Guide 90026-201D Page 2 2004 Bosch Security Systems Contents 1.0 SAFECOM Telemetry Communications System... 5 1.1 SAFECOM

More information

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories

More information

Rev C May GE Interlogix. Part No: R. CareGard. User Guide

Rev C May GE Interlogix.   Part No: R. CareGard. User Guide g 466-1936 Rev C May 2003 GE Interlogix www.ge-interlogix.com Part No: 60-883-95R CareGard User Guide FCC Notices FCC Part 15 Information to the User Changes or modifications not expressly approved by

More information

Table of Contents. All-In-One Wireless Security System V1.3. Programming Guide. Model # MG-6060 / MG-6030

Table of Contents. All-In-One Wireless Security System V1.3. Programming Guide. Model # MG-6060 / MG-6030 All-In-One Wireless Security System V1.3 Programming Guide Model # MG-6060 / MG-6030 Table of Contents Things You Should Know... 2 About This Programming Guide... 2 Conventions... 2 Installer Code (Default:

More information

FIREFINDER-XLS CONTROL PANEL

FIREFINDER-XLS CONTROL PANEL FIREFINDER-XLS CONTROL PANEL Installation, Operation and Maintenance Manual P/N 315-033744-4 Siemens Building Technologies Fire Safety CAUTION ALL WIRING MUST BE DONE AS DESCRIBED BELOW TO OBTAIN SAFE

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

Personal Assistance System Owner s Manual

Personal Assistance System Owner s Manual Personal Assistance System Owner s anual 3 3 O UNT A C K G HOUS RCORD nstall Run AC Power Battery Low 4 2 8 3 6 PROG 0 RCORD Personal Assistance System PA800 RAD THS FRST This equipment generates and uses

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS CSM-4 Controllable Signal/Releasing Module ENGINEER AND ARCHITECT SPECIFICATIONS Supervised Alarm Notification Appliance Circuits Operates Audible or Visual Devices Class A (Style Z) or Class B (StyleY)

More information

D169 2-Way Voice Verification Module. Installation and Operating Manual Radionics 34105B 3/97

D169 2-Way Voice Verification Module. Installation and Operating Manual Radionics 34105B 3/97 D169 2-Way Voice Verification Module Installation and Operating Manual Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable.

More information

INSTALLATION MANUAL & PROGRAM RECORD SHEET

INSTALLATION MANUAL & PROGRAM RECORD SHEET INSTALLATION MANUAL & PROGRAM RECORD SHEET TABLE OF DESCRIPTION CONTENTS PAGE WIRING MANUAL 2-6 MENU CHART 7 INSTALLER FUNCTIONS 8 MENU 1 SYSTEM TIMES 9 MENU 2 ZONE CONFIGURATION 10-14 MENU 3 SYSTEM OPTIONS

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

Installation Instructions

Installation Instructions Model S5832SG Control Panel 8 to 32 Zones Installation Instructions Table of Contents Table of Contents Compliance and Regulatory Information...i Installing and Connecting the Control Panel... 1-5 Sierra

More information

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E...

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E... 5$1*(5( DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS General Description... 2 Standard and Optional Parts List... 2 Feature Definitions... 3 Comments about the 8600E... 4 Terminal

More information

OUT TO WALLJACK. Input

OUT TO WALLJACK. Input Innovative Technologies in Custom Electronic Design & Manufacturing Thank you for purchasing our Intermediate FreezeAlarm, model FA-I. The FreezeAlarm Intermediate model will automatically call up to three

More information

SIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL.

SIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL. Page 1 / 15 Installation and user manual Page 2 / 15 Sira s.r.l. reserves the right to make modifications to this manual and the product described herein without prior notice. Sira s.r.l. shall not be

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

UDACT-300A. Digital Alarm Communicator Transmitter. Installation and Operation Manual. LT-888 Rev 3 June DEF 2 ABC ENTER MENU 6 GHI JKL MNO

UDACT-300A. Digital Alarm Communicator Transmitter. Installation and Operation Manual. LT-888 Rev 3 June DEF 2 ABC ENTER MENU 6 GHI JKL MNO UDACT-300A Digital Alarm Communicator Transmitter RS-485 COMMON TROUBLE CPU FAIL LINE 1 LINE 2 POWER ON 1 2 ABC 3 DEF ENTER 4 5 6 GHI JKL MNO MENU 7 PRS 8 TUV 9 WXY CANCEL * 0 # QZ INFO Installation and

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

Air Duct Housings. Description

Air Duct Housings. Description Air Duct Housings Series IL, and Series 3 Ionization or Photoelectric Detectors Optional Relays for Supplementary Equipment Operation Optional Control Module for Self-contained Operation (Series 3 Detectors

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Voice Dialer. Manual E-921CPQ E-921KPQ

Voice Dialer. Manual E-921CPQ E-921KPQ Voice Dialer Manual Models Available E-921CPQ E-921KPQ Certification When triggered by an alarm system, the ENFORCER Voice Dialer can call up to 5 numbers and deliver a user-recorded 20-second voice message,

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

INSTALLATION GUIDE XR100 SERIES COMMAND PROCESSOR PANEL

INSTALLATION GUIDE XR100 SERIES COMMAND PROCESSOR PANEL INSTALLATION GUIDE XR100 SERIES COMMAND PROCESSOR PANEL MODEL XR100 SERIES ACCESS CONTROL COMMAND PROCESSOR PANEL INSTALLATION GUIDE Contains installation instructions for use with the Model XR100 and

More information

Radionics D4112 Program Sheet

Radionics D4112 Program Sheet Programming only by downloading, 5200 Programmer or 5100 "Wand" Programmer Plug programmer in and momentarily short Reset Pin to Terminal 25 to enable program mode 1. Account Account # I I I I I (0 to

More information

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION...2 STANDARD AND OPTIONAL PARTS LIST...2 FEATURE DEFINITIONS...3 TERMINAL DRAWING AND SPECIAL NOTES...4

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module

Fire Safety. Installation Instructions Model D2300CPS Fiber Optic Interface INTRODUCTION MOUNTING ELECTRICAL CONNECTIONS. Figure 1 D2300CPS Module Fire Safety Installation Instructions Model Fiber Optic Interface INTRODUCTION The Model from Siemens uilding Technologies, Inc. (See Figure 1) is a Fiber Optic interface for the MXL s RS-485 network (MNET

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher IMPORTANT WARNING:This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be

More information

StarLink SLE Commercial Series Dual-Path Alarm Communicators INSTALLATION INSTRUCTIONS

StarLink SLE Commercial Series Dual-Path Alarm Communicators INSTALLATION INSTRUCTIONS 333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440 or visit us at http://tech.napcosecurity.com/ (Note: Technical Service is for security

More information

Section 9 System Operation

Section 9 System Operation Section 9 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this

More information