Installation Instructions Model SSD-C-REM

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Installation Instructions Model SSD-C-REM"

Transcription

1 Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder module that displays the event status of a system and has the capability to control the system remotely from the PMI It has four character alphanumeric LCD character lines, backlit upon status change or display toggling This module is supervised by the main panel and also has LEDs and an optional sounder to indicate the status of the system The SSD-C-REM has the capability to store up to event messages and has pushbuttons to scroll through these events Its display is independent from the display on the PMI During the SSD-C-REM initial power up, the SSD-C-REM is configured in Display-only mode ACKNOWLEDGE SILENCE UNSILENCE RESET Figure SSD-C-REM System Status Display The following items are supplied with the SSD-C-REM: nuts to mount the housing to the CAB// or REMBOX/ Cable P/N - for connection to an RNI (requires RNI Rev or higher) OPERATION The SSD-C-REM has six LEDs and a sounder to indicate the status of the fire alarm panel The LCD indicates the state of a specific event The SSD-C-REM also has push buttons that allow the user to scroll through the events list, and/or take control of the system The SSD-C-REM can be used in two different vectoring applications: No Vectoring and Queue Vectoring Refer to the Programming section on page for information on configuring the system When the SSD-C-REM is used in a No Vectoring application, all events that occur in the system are displayed on the SSD-C-REM If the SSD-C-REM is configured with System Control, it can take full control of the system (Acknowledge events, Silence/ Unsilence Audibles and Reset the system) P/N -- Siemens Building Tec echnologies

2 Queue Vectoring displays only the specific event type (such as Alarm only, Trouble only, etc) and is set by deselecting any Display type in the Zeus Programming Tool An SSD-C-REM with System Control has control of the system as long as the system events are the same event type for which it is configured Otherwise, it responds as Display Only For example, if the SSD-C-REM is configured as an ALARM-only display and there are only alarms present in the system then the SSD-C-REM will have full system control However, if for the same SSD-C-REM, there are alarms and troubles in the system, then pressing a control push-button (Acknowledge, Silence, Unsilence or Reset) on the SSD-C-REM will have no effect on the system The corresponding LED of the queue type not vectored will activate momentarily to indicate to the user that an event of a different queue is present in the system Controls and Indicators The front panel of the SSD-C-REM contains LEDs, LCD display, up and down navigational buttons, and Acknowledge, Silence, Unsilence, and Reset buttons, as shown in Figure The LEDs and their functions are defined as follows: ALARM (Red) Normally OFF Indicates that there is no alarm event in the system ON (flashing) Indicates that at least ONE alarm event is unacknowledged ON (steady) Indicates that ALL alarm events have been acknowledged SUPERVISORY (Yellow) Normally OFF Indicates that there is no supervisory event in the system ON (flashing) Indicates that at least ONE supervisory event is unacknowledged ON (steady) Indicates that ALL supervisory events have been acknowledged SECURITY (Yellow) Normally OFF Indicates that there is no security event in the system ON (flashing) Indicates that at least ONE security event is unacknowledged ON (steady) Indicates that ALL security events have been acknowledged TROUBLE (Yellow) Normally OFF Indicates that there is no trouble event in the system ON (flashing) Indicates that at least ONE trouble event is unacknowledged ON (steady) Indicates that ALL trouble events have been acknowledged P/N --

3 AUDIBLES ON (Yellow) Normally OFF Indicates that NACs are in supervisory mode or that ALL silenceable NACs have been silenced ON (steady) Indicates that at least ONE NAC has been activated AUDIBLES SILENCED (Yellow) Normally OFF Indicates that NACs are in supervisory mode or that there is at least ONE activated NAC in the system ON (steady) Indicates that previously activated NACs have been silenced When both AUDIBLES ON and AUDIBLES SILENCED LEDs are in the OFF state, it indicates that all NACs in the system are in supervisory mode The Sounder operates as follows: SOUNDER Normally OFF Indicates that the system is in supervisory mode or all events in the system have been acknowledged or that a push button has been pressed ON-STEADY Indicates that at least one unacknowledged alarm is present in the system ON-PULSING Indicates that at least one unacknowledged non-alarm (supervisory, security, or trouble) event is present in the system (and that there are no alarm events present or all alarm events have been acknowledged) When the SOUNDER DISABLE option is selected in the Zeus Programming Tool, the sounder remains OFF, regardless of the status of the system In systems where the country selected is Canada, the sounder disable option is not available The pushbuttons and their functions are defined as follows: UP ARROW During Supervisory Mode: Activates the LCD backlight for minutes When Event Is Displayed: Displays the event with the next higher priority (See Figure for more information about the differences between US and Canada) DOWN ARROW During Supervisory Mode: Activates the LCD backlight for minutes When Event Is Displayed: Displays the event with the next lower priority (See Figure for more information about the differences between US and Canada) P/N --

4 The events are displayed one at a time and cycle through a circular list once the first or last event message is reached See Figure UNITED STATES CANADA MOST RECENT ALARM ALARM MOST RECENT SUPERVISORY SUPERVISORY MOST RECENT SECURITY SECURITY MOST RECENT TROUBLE TROUBLE ALARM MOST RECENT ALARM SUPERVISORY SECURITY TROUBLE MOST RECENT MOST RECENT MOST RECENT SUPERVISORY SECURITY TROUBLE Figure Event Priority - United States and Canada ACKNOWLEDGE During Supervisory Mode: Activates LCD backlight for minutes When Event Is Displayed: Acknowledges the unacknowledged queue and/or events with the highest priority If no events are present, it is ignored SILENCE During Supervisory Mode: Activates LCD backlight for minutes When Event Is Displayed: Silences all activated silenceable NACs when all alarm events are acknowledged If NACs are already silenced, it is ignored UNSILENCE During Supervisory Mode: Activates LCD backlight for minutes When Event Is Displayed: Reactivates all silenceable NACs that were previously silenced If NACs are already active, it is ignored RESET During Supervisory Mode: Activates LCD backlight for minutes When Event Is Displayed: Resets the system provided that all events are acknowledged and all silenceable NACs are silenced If system is already reset, it is ignored P/N --

5 LCD (See Figure ) The LCD backlight activates for minutes when an event occurs or when a push button is pressed Supervisory Mode: Line - Current date and time Line - Custom message and system ID Line - Custom message and system ID Line - Blank Active Event Mode: Line - Event Status, module/device address, date and time of the event Line - Custom message for the module/device, acknowledged/non-acknowledged Line - Event category or trouble type, sequence number of the event Line - Total number of Alarms, Supervisory, Security, and Trouble events in the system or vectored to the SSD-C-REM may,, ::pm custom message - system id # system custom message - system id # normal alarm - may,, ::pm custom message for this alarm ack d smoke of alm= supv= sec= trbl= Figure SSD-C-REM LCD - Supervisory Mode (Top) and Active Event Mode (Bottom) P/N --

6 PRE-INSTALLATION The following components must be set prior to installing the SSD-C-REM housing enclosure to the SSD-C-REM mounting plate Refer to Figure S Option Select DIP Switch: S-SW: Set to ON if the SSD-C-REM is the end of the PAIR A wiring S-SW: Set to ON if the SSD-C-REM is the end of the PAIR B wiring S-SW: Set to OFF: Not Used S-SW: Set to OFF: Not Used S S S P R P P S S ON Figure SSD-C-REM Switch Location If the SSD-C-REM is located at the end of the wire, add the terminating resistance to the communication wire by setting SW and SW to the ON position This allows the NIC-C to properly supervise the communication wires S, S, S Network Address Switches: Set the three-digit HNET network address for the SSD-C-REM using the three ten-position rotary switches located on the board (See Figure ) Each of these addresses must be the same as the addresses assigned in the Zeus Programming Tool The range of allowable addresses is from to (leading zeros must be used) S, Reset Switch: Momentarily Closed switch that when pressed will re-initialize the SSD-C-REM operation R LCD Trimmer Adjustment (factory set): Turn to adjust the LCD contrast as required If the SSD-C-REM fails, the TROUBLE LED will flash at a fast rate, the sounder will pulse and no push buttons will respond The PMI detects this failure as a nonresponding module trouble condition P/N --

7 PROGRAMMING In order to perform its desired operation, the SSD-C-REM must be programmed using the Zeus Programming Tool The SSD-C-REM properties must be set before normal operation In the Zeus Programming Tool, highlight the selected SSD-C-REM module in the Physical View and open the Detail View - Properties to modify and/or define the following SSD-C-REM properties: HNET Address: This address must match the address set in the SSD-C-REM hardware Base Language Custom Message: This message is associated with the SSD-C-REM module Alternate Language Custom Message: This message associated with the SSD-C-REM module is in an alternate language Display Alarms: If selected, alarm events are displayed on the SSD-C-REM; otherwise, alarm events are filtered Display Supervisory Events: If selected, supervisory events are displayed on the SSD-C-REM; otherwise, supervisory events are filtered Display Security Events: If selected, security events are displayed on the SSD-C-REM; otherwise, security events are filtered Display Troubles: If selected, trouble events are displayed on the SSD-C-REM; otherwise, trouble events are filtered WIRING Disconnect BATTERY and AC prior to working on equipment Refer to Figure for a typical wiring connection of SIEMENS Model SSD-C-REM to the FireFinder-XLS System NOTES: Compatible wire size: - AWG No EOLR required S-, S- must be in the ON position if the SSD-C-REM is at the end of the Style or Style network Use twisted pair or twisted shielded pair Terminate shield at one end only Power Limited to NFPA per NEC All wiring is power limited and supervised PAIR B (STYLE ONLY) PAIR A (STYLE, STYLE ) SSD-C-REM NIC-C PMI/CPC PSC- VDC (POWER LIMITED) FireFInder XLS ENCLOSURE Figure Typical SSD-C-REM Connection To The FireFinder-XLS P/N --

8 ON The wiring diagram in Figure shows the connections from the SSD-C-REM to the NIC-C and PSC- Refer to the NIC-C Installation Instructions, P/N - and the PSC- Installation Instructions, P/N - for additional wiring information DO NOT USE DO NOT USE DO NOT USE NIC-C ONE SLOT OF CC- PAIR B PAIR A DO NOT USE + TB TB EARTH GROUND TB PSC- A A+ B B+ + E SSD-C-REM P S S S P S Figure Wiring The SSD-C-REM In A CAB// P/N --

9 The wiring diagram in Figure shows the SSD-C-REM connected to an RNI in a REMBOX/ Refer to the RNI Installation Instructions, P/N -, for additional wiring SSD-C-REM TB A A+ B B+ TB + E P P S ON A A+ B B+ TB S TO PSC- TB OR ANY UL/ULC REGULATED, POWER LIMITED POWER SUPPLY LISTED FOR FIRE PROTECTIVE SIGNALING USE V RET +V + V RNI TB Figure Wiring An SSD-C-REM In A REMBOX/ With A Pre-Rev RNI Newer versions of the RNI (Rev or higher) have an additional connector (P) for direct connection to the SSD-C-REM A cable (P/N -) provides HNET and V signals to the SSD-C-REM No further wiring is required at the SSD-C-REM For wiring information regarding HNET and V connection to the RNI, refer to the RNI Installation Instructions, P/N - SSD-C-REM TB TB TB S P DO NOT USE DO NOT USE S S S P P P CABLE P/N - TB V P RNI S ON Figure Wiring An SSD-C-REM In A REMBOX/ With A Rev Or Higher RNI P/N --

10 INSTALLATION The SSD-C-REM mounts directly into a CAB// or REMBOX/ Refer to Figure INNER DOOR SSD-C-REM Figure Mounting The SSD-C-REM Mount the SSD-C-REM to the inner door of the CAB// or REMBOX/ using the four supplied nuts Up to four LCM- or SCM- modules may be mounted below the SSD-C-REM Optionally, up to two FCM- modules may be mounted below the SSD-C-REM ELECTRICAL RATINGS T ypical ma at VDC Max I nput Voltage VDC (Nominal ) An auxiliary regulated power-limited power supply may be used to provide power to the SSD-C-REM The power supply must be UL/ULC approved for Fire Protection Signaling Application Be sure to include the SSD-C-REM in the battery calculations, Inc Fernwood Road Florham Park, New Jersey, Ltd Kenview Boulevard Brampton, Ontario LT E CN P/N --

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION Fire Safety Installation Instructions Model RCC-/R and RSE- Remote Control Centers INTRODUCTI The SIEMENS Model RCC-/R Remote Command Center (See Figure ) provides the option to remotely annunciate and

More information

FIREFINDER-XLS CONTROL PANEL

FIREFINDER-XLS CONTROL PANEL FIREFINDER-XLS CONTROL PANEL Installation, Operation and Maintenance Manual P/N 315-033744-4 Siemens Building Technologies Fire Safety CAUTION ALL WIRING MUST BE DONE AS DESCRIBED BELOW TO OBTAIN SAFE

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

FireSeeker Model FS-250C Addressable Fire Alarm Control Panel

FireSeeker Model FS-250C Addressable Fire Alarm Control Panel FireSeeker Model FS-250C Addressable Fire Alarm Control Panel One intelligent signaling line circuit (DCLB + DCLA) SureWire Polarity insensitive loop wiring Utilizes S-Series detectors and devices Supports

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

R Series Remote Annunciators and Expander Installation and Operation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P/N 3100969 REV 1.0 ISS 15JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may

More information

FireFinder XLSV Digital Emergency Voice Alarm / Communication System

FireFinder XLSV Digital Emergency Voice Alarm / Communication System s Data Sheet Fire Safety Products FireFinder XLSV Digital Emergency Voice Alarm / Communication System ARCHITECT AND ENGINEER SPECIFICATIONS Eight (8) digital audio channels Compatible with Model PMI-3

More information

Desigo TM Fire Safety System A comprehensive fire-protection system

Desigo TM Fire Safety System A comprehensive fire-protection system s Desigo TM Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2)

More information

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the

More information

System Overview (continued) System Components. The FireFinder XLS system has been seismic qualified in accordance with:

System Overview (continued) System Components. The FireFinder XLS system has been seismic qualified in accordance with: s FireFinder XLS Advanced Fire Alarm Control Panel Standard / 2500-point-capacity addressable fire-alarm control panel (FACP) Ability to network with other FireFinder XLS systems Powerful, easy-to-use

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

R-Series Remote Annunciators and Expanders Installation and Operation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide R-Series Remote Annunciators and Expanders Installation and Operation Guide P/N 3100969-EN REV 05 ISS 06MAY13 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2013

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

MPC-6000 / MPC-7000 / RND-2

MPC-6000 / MPC-7000 / RND-2 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

More information

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W Fire Safety Installation Instructions Model NIM-W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION The SIEMENS Model NIM-W provides a new communication path for the following uses:

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

PN:51264:A2 ECN Remote Fire Annunciator FDU-80. Document /14/00 Rev: A.

PN:51264:A2 ECN Remote Fire Annunciator FDU-80. Document /14/00 Rev: A. PN:51264:A2 ECN 00-245 Remote Fire Annunciator FDU-80 Document 51264 6/14/00 Rev: A Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors, heat detectors, manual

More information

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 574-052 Rev. F This page intentionally blank Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights

More information

ARCHITECT AND ENGINEER SPECIFICATIONS

ARCHITECT AND ENGINEER SPECIFICATIONS s Desigo Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2) two-heightunit

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

D1255RB/D1256RB/D1257RB

D1255RB/D1256RB/D1257RB D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609

More information

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. The following products have not received UL

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION & OPERATION MANUAL GAMEWELL P/N 71810 60 PLEASANT STREET ISSUE 3, 10/04/2000 ASHLAND, MA 01721 FIRMWARE VER. 7 THIS PAGE INTENTIONALLY

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

Inside a typical. Intelligent Voice Communication System. Mounting Diagram. 2 Cerberus PRO. 252 / 504-point Cerberus PRO fire / voice system

Inside a typical. Intelligent Voice Communication System. Mounting Diagram. 2 Cerberus PRO. 252 / 504-point Cerberus PRO fire / voice system Data Sheet Cerberus PRO Intelligent Voice Communication Advanced fire-protection system with integrated voice evacuation ARCHITECT AND ENGINEER SPECIFICATIONS Powerful, intelligent and user-friendly fire

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

XT30/XT50 PROGRAMMING PART 2. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 2. Bell Options

XT30/XT50 PROGRAMMING PART 2. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 2. Bell Options Slide 1 XT30/XT50 Basic Training Programming- Part 2 Slide 2 Objectives After completing this course you will: 1) Understand how to prepare the panel for programming and how to access the built-in programmer.

More information

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98 USER'S GUIDE FA1220CV 2-Partition Security System N7003-1V2 7/98 SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Fire Protection... 4 Alarms... 5 Emergency

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL Advanced Gen-set Controller OPERATOR S MANUAL Display readings Push-button functions Alarm handling Log list Document no.: 4189340607A SW version 3.5X.X or later Table of contents 1. ABOUT THIS DOCUMENT...3

More information

D A R A - 4. Data Aire Relay Auto-Changeover

D A R A - 4. Data Aire Relay Auto-Changeover D A R A - 4 Data Aire Relay Auto-Changeover WARNING: If adding the DARA-4 panel to existing units that did not include a DARA-4 panel when originally purchased it will be necessary to add a relay or relays.

More information

FieldServer Driver - Serial FS SBT-FSI (Siemens Building Technologies Foreign Systems Interface)

FieldServer Driver - Serial FS SBT-FSI (Siemens Building Technologies Foreign Systems Interface) Driver Version: 1.06 Document Revision: 4 Description FieldServer Driver - Serial FS-8700-40 SBT-FSI (Siemens Building Technologies Foreign Systems Interface) This FieldServer driver can be used to poll

More information

Voice Board. Installation and Programming Guide. Runner 4/8,PowerWave 4/8/16 &, Elite64. Add-on Board For Storing Recorded Voice Messages

Voice Board. Installation and Programming Guide. Runner 4/8,PowerWave 4/8/16 &, Elite64. Add-on Board For Storing Recorded Voice Messages ELECTRONIC ENGINEERING LTD. Voice Board Runner 4/8,PowerWave 4/8/16 &, Elite64 Add-on Board For Storing Recorded Voice Messages And listen-in. Installation and Programming Guide. P/N 7101372 Rev. C V.K

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

Beacon 110 Gas Monitor Operator s Manual

Beacon 110 Gas Monitor Operator s Manual Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual 24 Viceroy Road Unit #6 & 7 Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX: (905) 660-7204 MS-2410BC Conventional Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

s Notification Appliances

s Notification Appliances s Notification Appliances Data Sheet Fire Safety Products AS & AH Audible Horn Strobe / Audible Horn Appliances Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-R AH-W Product Overview Fast installation

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

NetworX NX-8V2. LED Keypad User Manual

NetworX NX-8V2. LED Keypad User Manual NetworX NX-8V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous

More information

System Introduction. 1.1 Specifications

System Introduction. 1.1 Specifications System Introduction S E C T I O N 1 1.1 Specifications Downloading Software Support PC585 uses DLS-1 v6.5 and up. Flexible Zone Configuration Four fully programmable zones; system expandable to eight zones

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

NetworX Series NX-1500E LED Keypad

NetworX Series NX-1500E LED Keypad NetworX Series NX-1500E LED Keypad User Manual SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system

More information

Lamp Driver Module LDM-32F

Lamp Driver Module LDM-32F PN 50055:C0 ECN 01-155 Lamp Driver Module LDM-32F Instruction Manual Document 50055 03/20/2001 Rev: C Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors,

More information

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual RAM-5-LCD Remote Annunciator Installation and Operation Manual LT-9 Rev. July Table of Contents. Introduction 6. Contact Us... 6. Mechanical Installation 8. Mounting Dimensions... 8. Configuring the Main

More information

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B VISTA-32FBPT Commercial Fire and Burglary Partitioned Security Systems with Scheduling User Guide 800-11045 2/12 Rev. B 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...6

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

Fire Alarm Control Panel Installation, Commissioning & Operation MAN

Fire Alarm Control Panel Installation, Commissioning & Operation MAN DH4 ZoneSense Fire Alarm Control Panel Installation, Commissioning & Operation MAN 1531-5 Access Level 1 (Normal Operation) Responding To An Alarm Zone FIRE Alarm Indicator - flashing Common FIRE Alarm

More information

FX-350/351/353 SERIES

FX-350/351/353 SERIES FX-350/351/353 SERIES Analog/Addressable Fire Alarm Panel Programming Manual LT- 1040 Rev 3.1 January 2017 FX-350/351/353 Series Programming Manual Table of Contents System Configuration... 1 Panel Configuration...

More information

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E Instruction Manual Document 51512 8/6/2014 Rev: G3 P/N 51512:G3 ECN 14-523 Fire Alarm & Emergency Communication System Limitations While a life safety

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

NetworX NX-548E Receiver Installation Instructions

NetworX NX-548E Receiver Installation Instructions NetworX NX-548E Receiver Installation Instructions Content Introduction... 1 Internal mounting... 1 External mounting... 2 Wiring... 3 DIP switch settings... 3 Power up... 3 Programming... 4 Testing and

More information

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A $'(0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHP 8VHU*XLGH N7003V3 5/04 Rev A 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...5 Fire Protection...6 Burglary Protection...6 Alarms...6

More information

VS1 Intelligent Life Safety System

VS1 Intelligent Life Safety System Vigilant Catalog Small Building Fire Alarm Solutions VS1 Intelligent Life Safety System Overview The Vigilant VS1 intelligent life safety system offers the speed of high-end intelligent processing in a

More information

Planning Elevator Relay Groups Programming Millenium for Windows Software

Planning Elevator Relay Groups Programming Millenium for Windows Software Installation Booklet: Elevator Control Unit (ECU) Introduction The Elevator Control Unit (ECU) is an option in the Millenium for Windows systems. Once you add an elevator in the software, each elevator

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2003-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2003-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

Table of Contents. Appendix A Special Characters 31

Table of Contents. Appendix A Special Characters 31 Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...

More information

Operating Instructions MEW01091 Revision 3

Operating Instructions MEW01091 Revision 3 Operating Instructions MEW01091 Revision 3 Fire Alarm System EBL128 V1.1.x Author: Jan Pettersson Date of issue: 2008-07-11 Date of rev: 2010-05-28 This page has deliberately been left blank. Table of

More information

TrueAlert Notification Appliances

TrueAlert Notification Appliances TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

Fire Alarm Control/Communicator

Fire Alarm Control/Communicator Fire Alarm Control/Communicator Operation and Installation Guide Power Alarm Trouble Silenced Radionics FIRE CONTROL/COMMUNICATOR R 31499F Page 2 2000 Radionics. Contents Contents 1.0 Notices... 9 1.1

More information

Alarms and Events. Defining Alarm Conditions. Database-Generated Alarms

Alarms and Events. Defining Alarm Conditions. Database-Generated Alarms 9 Defining Alarm Conditions Database-Generated Alarms The LookoutDirect alarm service keeps track of error messages and any process elements you have defined alarm conditions for. You can define alarm

More information

NETWORX TM. User manual NX-4

NETWORX TM. User manual NX-4 NETWORX TM User manual NX-4 POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous alarm.

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network.

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network. 28 31 00 PART 1 - GENERAL 1.01 SCOPE A. Background: Washington State University has agreements with Simplex- Grinnell and Siemens Industry, Inc. to provide Fire Detection and Alarm (FDA) systems for the

More information

SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP.

SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP. SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP. 3 1 PANEL SWITCHES. 3 FIRE ZONE LAMP 4 OTHER LAMPS 4 MULTIPLEX OUTPUT.

More information

ZP2 Series Operation Manual

ZP2 Series Operation Manual ZP2 Series Operation Manual P/N 501-405203-2-31 REV 03.10 ISS 07NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire & Security.

More information

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA90621-2268

More information

MIR2. System Operations Manual. P/N Rev 1.5 OCT98

MIR2. System Operations Manual. P/N Rev 1.5 OCT98 MIR2 System Operations Manual P/N 270676 Rev 1.5 OCT98 DEVELOPED BY COPYRIGHT NOTICE Mirtone, Inc. 90 Fieldstone Court Cheshire, CT USA 06410-1212 Tel: 1-(888) 649-9827 Fax: 203-250-1931 Copyright 1998

More information

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111 NETWORK FIRE ALARM CONTROL PANEL FX-2009-12NDS Description FX-2009-12NDS in a BB-5008R enclosure. Mircom s FleX-Net Series is a powerful intelligent networkable fire alarm solution designed with many levels

More information

Class A and Expansion NAC Modules Installation Instructions

Class A and Expansion NAC Modules Installation Instructions Class A and Expansion NAC Modules Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1245 Flex Amplifier Expansion NAC (XNAC) 4100-1246

More information

9822 Marine Fire and Detection Equipment. Cerberus PRO. Cerberus PRO. Marine Fire and Detection Equipment. Models FH-2071-UM, BP-62 and USCG-HPLATE

9822 Marine Fire and Detection Equipment. Cerberus PRO. Cerberus PRO. Marine Fire and Detection Equipment. Models FH-2071-UM, BP-62 and USCG-HPLATE Cerberus PRO Marine Fire and Detection Equipment s FH-2071-UM, BP-62 and USCG-HPLATE Cerberus PRO Fire Safety Products ARCHITECT AND ENGINEER SPECIFICATIONS Marine equipment is used with Cerberus PRO 252-point

More information

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information