22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

Size: px
Start display at page:

Download "22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review"

Transcription

1 Parry Sound District Social Services Administration Board Housing and Community Services October 10, 2018 c/o Andrew Ball, Properties and Capital Projects Coordinator 22A Belvedere Avenue, No. of Pgs.: 1 of 5 / attached (1) Parry Sound, ON P2A 1J2 22A BELVEDERE AVENUE - SPRINKLER SYSTEM EXPANSION FEASIBILITY REVIEW Type of building: Residential Conducted on: September 18, 2018 Dear Andrew Ball, FCS attended site to conduct a Review of existing site conditions at on Tuesday, September 18 th, 2018 to provide options regarding potential sprinkler system expansion. FCS Fire Consulting services was retained at the request of Parry Sound District Social Services Administration Board Housing and Community Services to provide consulting services to determine the feasibility of expanding the current sprinkler system coverage to provide protection to the entire building. It has been recognized that due to the aging population of occupants within the building, evacuation in a fire emergency presents a greater risk to the safety of occupants based on the time to safely exit the building via exit stairwells during the evacuation process. Therefore, the intent to voluntarily expand the sprinkler system coverage would provide a higher level of safety to the building by providing early detection and local containment of fire until fire services are available on site. This would also provide longer evacuation times or reduce the requirement to fully or partially evacuate occupants within the building. FCS conducted a visual assessment of the building which included the review of the existing sprinkler system design configuration, major fire protection / life safety equipment installed within the building, select residential suite configuration and layout, and all mechanical / electrical / service rooms. The review commenced with a visual review of major equipment rooms (fire alarm panel, elevator shaft, sprinkler room, and generator room), then proceeded to the top of the building and continued down to the bottom floor of the building. A fire safety assessment was also conducted to identify any possible deficiencies that may impact the proposed sprinkler system expansion. Site findings are also provided See Appendix A of this report. This report outlines the initial review process. We look forward to coordinating a conference call to review our findings upon provision of our formal budget as outlined in our report. Thank you. Yours truly, President 1

2 22 A Belvedere, Parry Sound OBJECTIVE To conduct a sprinkler feasibility review as it pertains to the existing occupancy at 22A Belvedere Ave., Parry Sound. Our evaluation also includes a general review of existing fire systems and fire code compliance. The following report will summarize sprinkler feasibility, options and our recommendations, as applicable and provide an outline of general fire safety deficiencies noted at the time of our inspection. BUILDING INFORMATION The building is a five (5) storey low-rise residential building, with one (1) below grade level. There is no parking available within the below-grade level of the building. Parking is provided at the exterior of the building, located on the north-east portion of the property. The basement level consists of residential suites, common storage, a common room with washrooms, janitor s room, and a storage accessible from the exterior of the building. The ground floor is comprised of residential suites, moving room, garbage room, mechanical room, electrical room, laundry room, generator room, superintendent s suite, and corridor pathway to the Belvedere Heights building. The building is classified as a Group C occupancy under the Ontario Building Code. FCS understands that the building was constructed in An addition to the building was constructed in 1996, which also included the construction of a sub-basement level. The building is equipped with a Mircom Series 1000 single stage multi-zone fire alarm system. This building is equipped with manual pull stations and automatic detection devices throughout. The Fire Alarm System has alarm zoning and trouble indicators. The Fire Alarm System is monitored by 3 rd party monitoring station. A wet sprinkler system provides partial protection to the building. The building is equipped with two (2) elevators; one provides access to each floor within the building, the second elevator serves the ground 5 th floor level. Residential suites are equipped with at least one (1) battery operated combination smoke/ carbon monoxide alarm and audible speaker, which is connected to the Fire Alarm System. The building is confirmed to contain asbestos within the stucco in the ceilings within the building. Page 2

3 METHODOLOGY 22 A Belvedere, Parry Sound The FCS team, comprised of (FCS President / Senior Code Consultant), Tom Marchese, PMP, P.Eng. (FCS Project Manager), Julia Signorini, FPET (Fire Protection Engineering Technologist) and Bob Disano (Sprinkler Designer) attended site on September 18, 2018 to conduct a visual review of the main sprinkler components and review of building site conditions. An invasive review of the in-service piping was not conducted at this time. No operational tests of the equipment were conducted. During the site visit, the team completed the following: Conducted a visual review of the main sprinkler room, two (2) residential units, and all common areas, service rooms, vertical risers and common closets within the building Met with the Properties and Capital Projects Coordinator, Andrew Ball, to obtain information on the service history and to escort out team throughout the evaluation. DOCUMENT REVIEW FCS conducted a review of documents provided by management including: annual test and inspection reports, site drawings and pictures as provided by management. A review of the fire safety plan including building configuration was completed off-site. ON SITE OBSERVATIONS Sprinkler System The building is provided with partial sprinkler protection. Additionally, the building is equipped with a wet standpipe system throughout. The main sprinkler shutoff valves and fire pump is located in the basement level mechanical room. The main valves located in the mechanical room are labeled as follows: Zone #17 - Garbage Chute Zone #10-1 st Floor Zone #16 - Outdoor Storage Zone #24 - Main Shutoff Zone #25 - Main Service Shutoff Zone #22 - Fire Pump Inlet Zone #23 - Fire Pump Outlet The fire pump has a rated capacity of 155 U.S. 55 PSI. The Fire Department Connection for the sprinkler and standpipe system is located within 3m from the main entrance. Page 3

4 22 A Belvedere, Parry Sound There is one (1) municipal fire hydrant that serves this building, located along Belvedere Avenue, North-East of the building. The municipal hydrant is located within 90m of the main residential entrance. The Mircom multi-zone fire alarm control panel was clear of trouble, appeared in good condition, with no visible components by-passed. ANALYSIS The building is concrete with typical life safety system coverage for the age and retrofit improvements previously undertaken. The addition of complete building sprinkler coverage is voluntary only and not required by the Ontario Fire Code. The addition of a sprinkler system expansion to provide coverage throughout the building is feasible. The system, if determined to be warranted by management, will be required to be installed throughout the building, including corridors, suites, all rooms, balconies due to enclosure design and to accommodate bulkheads in limited areas. There are multiple available areas such as the garbage chute, existing service raceways, stairwells and spaces to conceal the main larger pipe runs, while corridor, suite pipe and sprinkler heads will be exposed in some areas. A mockup of the potential design would be considered as part of the tender process. The complete sprinkler coverage NFPA-13 design would facilitate potential consideration of increased use of the building for elderly seniors and vulnerable occupants. Existing Sprinkler System expansion feasibility summary: 1. The existing sprinkler system appears in reasonable condition and expansion is feasible. 2. Partial sprinkler of the building in common areas only is not recommended as compliance with NFPA-13 is required and potential fire risk is higher within suites then common corridors. 3. The majority of the head end sprinkler equipment can be repurposed for this expansion. 4. The incoming water main appears to be 4 and is anticipated to be sufficient for the design. 5. It appears that the sprinkler expansion may be feasible without the addition of a fire pump. 6. There is no existing back flow preventer that will be required for sprinkler modification. 7. We anticipate approximately 600 sprinkler heads throughout common areas and suites. 8. The majority of the system would be a wet system, with limited dry heads for balconies and potentially exterior cold storage area. To be determined during design. 9. Low capacity fire pump may be required, however not anticipated to require DC back up. 10. Generator has sufficient power should DC back up be required. 11. Due to the age of the existing heads (approx years); replacement is recommended. 12. The integrity of the existing piping would be reviewed and flushes as part of the project. 13. No sprinkler flow data or date of last sprinkler flow was available at site at time of assessment. 14. Multiple sprinkler zones are required to be added for individual floor and valve annunciation. 15. Anticipate minor piping visible within suites. 16. Project would include all required design, installation, inspection and certification requirements 17. A permit will be required for the proposed sprinkler retrofit and fire panel modifications Page 4

5 Additional measures: 22 A Belvedere, Parry Sound 1. The existing fire alarm system has been retrofitted in past and will require upgrading to accommodate new sprinkler zones. We recommend the budget carry potential contractor pricing for upgrading the existing fire alarm system versus panel expansion only for your consideration. 2. The project would take into consideration and be aligned with asbestos remediation. 3. A revision of the fire safety plan will be required to effectively reflect building conditions. 4. The areas identified in the fire safety assessment are required to be addressed. 5. Affected areas will require fire stopping and refinishing with typical standard beige paint. NOTE: drawings available on site are dated between 1974 and BUDGET The budget is being refined to determine the material and labour costs of project with extras, such as refinishing and complete fire alarm replacement being considered as additional price points for consideration. The general initial sprinkler budget currently under review is approximately $250,000. RECOMMENDATIONS / CONCLUSION Upon review of provided documentation and onsite findings, it is determined that the existing sprinkler system does have the capability to be expanded to provide further coverage or full building coverage. Further to the review of existing sprinkler conditions, it is identified that the existing fire alarm panel does have the capability to expand and accommodate the sprinkler system expansion. REPORT BY: Julia Signorini, Fire Protection Engineering Technologist &, President, Senior Fire Code Consultant REVIEWED BY: Tom Marchese, PMP, P. Eng. Project Manager End Report The repairs required within the fire safety assessment appendix are to be undertaken as soon as possible as they constitute non-compliance of the Fire Code and in limited areas non-compliance with the Building Code. The recommended upgrades are an attempt to achieve a higher level of compliance then required by the Ontario Fire Code. assumes no liability for the completion of any recommended work and the Owner is responsible for carrying out all work at his/her sole expense. Page 5

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

CFAA Technical Seminar Ontario Building Code Updates to 2015

CFAA Technical Seminar Ontario Building Code Updates to 2015 CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT ABA FASHIONS LTD. SENA KALYAN COMMERCIAL COMPLEX (2ND FLOOR), PLOT # 9, BLOCK # F, TONGI, GAZIPUR March 16, 2014 Accord - Bangladesh RMG Fire Safety Inspection ABA Fashions

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012 SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015423

More information

Module 9: Ontario Building Code Fire Fighting Provisions

Module 9: Ontario Building Code Fire Fighting Provisions Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances 1. Sprinklers i) Sprinkler Systems

More information

A GUIDE FOR CONDUCTING FACILITY PRE-FIRE PLANS

A GUIDE FOR CONDUCTING FACILITY PRE-FIRE PLANS A GUIDE FOR CONDUCTING FACILITY PRE-FIRE PLANS 1. Sketch Each Floor 2. Show Roof access of venting devices 3. Show approaches to the facility 4. Indicate the size of the facility (Length and Width) 5.

More information

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:. 2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT AMAZON TEX KNIT FASHION LTD JOBEDA PLAZA, 85 AC DHAR ROAD KALIRBAZAR May 21, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/21/2014 by Hughes Associates, Inc. This

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level

More information

4 August Islington Fire Protection Transpower NZ Limited

4 August Islington Fire Protection Transpower NZ Limited 4 August 2011 Islington Fire Protection Contents 1. Introduction...1 General Approach...2 2. General Notes...3 3. Description of Building Areas...4 Use, Layout, Fire Load, Criticality and Division...4

More information

SAMPLE FIRE SAFETY PLAN. ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba. Prepared by: John Smith Last reviewed: Bill Jones 2014

SAMPLE FIRE SAFETY PLAN. ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba. Prepared by: John Smith Last reviewed: Bill Jones 2014 SAMPLE FIRE SAFETY PLAN ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba Prepared by: John Smith 2011 Last reviewed: Bill Jones 2014 Page 1 of 19 Table of Contents 1. Building Information 2.

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT ALAUDDIN GARMENTS LTD. 88, KAZI NAZRUL ISLAM AVENUE, TAJGAON, DHAKA- 1215 OTHER FACTORIES: CAMBRIDGE GARMENTS, PRIMODIAL April 27, 2014 Page 2 SUMMARY was surveyed for fire

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT KAROONI KNIT COMPOSITE RATANPUR, SHAFIPUR KALIAKOIR OTHER FACTORIES: NONE April 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/5/2014 by Hughes Associates, Inc.

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Woodvale Pentecostal Church

Woodvale Pentecostal Church FIRE SAFETY PLAN For Woodvale Pentecostal Church Nepean, Ontario Revised May 2016 INDEX This index is to facilitate and organize easy reference for the Fire Safety Plan CHAPTER A CHAPTER B CHAPTER C CHAPTER

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Philip Rizcallah, P. Eng. NRC-IRC Canadian Codes Centre Presented by Stan Dueck CRBO Overview Where are the major

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PADMA SWEATERS LTD. 1/B DARUS SALAM ROAD, SECTION 1. MIRPUR OTHER FACTORIES: NONE. July 9, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/9/2014 by Hughes Associates,

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC

More information

Single Room Occupancy Hotel Safety & Stabilization Task Force

Single Room Occupancy Hotel Safety & Stabilization Task Force Page 1 of 6 Graphics Version Skip to Content Single Room Occupancy Hotel Safety & Stabilization Task Force sfgov residents business government visitors online serviceshelp Single Room Occupancy (SRO) Hotel

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Residential Care Facilities Requirements

Residential Care Facilities Requirements Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

Center for Life Safety Education

Center for Life Safety Education Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT Page 1 FIRE SAFETY INSPECTION REPORT Impress Fashion Ltd. ACCORD ID: 12245 Dag No. 2224, Matuial, Konapara, Katherpool, Jatrabari, Dhaka-1362 Other Factories: None Date: August 27, 2015 Sl No. Category

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

Building Self-Inspection Program

Building Self-Inspection Program Building Self-Inspection Program www.tridentinsurance.net Lines of Business: Property, General Liability, Worker s Compensation, Public Official Liability Risk Control Strategy/Key Issues: Reduce physical

More information

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS 1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

BC Building Code Checklist Part 3 Planning and Development Department

BC Building Code Checklist Part 3 Planning and Development Department BC Building Code Checklist Part 3 Planning and Development Department Project: Civic address: Permit No.: CRP: Certified Professional: Date: 1 Value of Construction: $ Developed Site Area: m2 2 BUILDING

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

150 Elgin - Office Tower and Grant House Renovations

150 Elgin - Office Tower and Grant House Renovations APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT YOUNG INTERNATIONAL PLOT NO. 32-36, SECTOR 5-CEPZ, CHITTAGONG OTHER FACTORIES: NONE July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by Hughes Associates,

More information

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose INVITATION TO QUOTE Title: Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, 2018 Purpose The District of Sparwood (Sparwood) invites interested parties (Respondents) to submit

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS 1) Purpose: In an effort to provide for consistency in administering the Existing Building Code and Property Maintenance Code for existing buildings as they pertain to Certificates of Use and Occupancy,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing

More information

McMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION

McMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION 4/5/017 1:58:50 PM C. 1445 DRIVE NEENAH, WI 54956 EXISTING JUSTICE CENTER IS FULLY SPRINKLED C. EXISTING FIRE PUMP BASEMENT LEVEL EXISTING FDC FOR DRY STANDPIPE IN STAIRWELL SHALL BE DEMOLISHED, SEE FP

More information

Town of Cochrane Policy

Town of Cochrane Policy Town of Cochrane Policy Policy No.: Policy Title: Approval Date: Revision Date: Department: 1401-01 Fire Department Lock Box Program January 22, 1996 September 24, 2007 Community and Protective Services

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

FACILITY PROFILE CALIFORNIA ASSOCIATION OF HEALTH FACILITIES DISASTER PLANNING GUIDE

FACILITY PROFILE CALIFORNIA ASSOCIATION OF HEALTH FACILITIES DISASTER PLANNING GUIDE This facility profile is a document that provides a general overview and listing of relevant information pertaining to operational and property characteristics. This information should be shared with local

More information

Building and Grounds Self-Inspection Program

Building and Grounds Self-Inspection Program www.alterisus.com Building and Grounds Self-Inspection Program Each building and its accompanying grounds should be inspected at regular intervals, ideally on a monthly or quarterly basis. In this way,

More information

LAND USE ASSESSMENT REPORT (LUAR) PROPOSED AFFORDABLE HOUSING COMPLEX MAIN ROAD PDE FILE NUMBER: REZ

LAND USE ASSESSMENT REPORT (LUAR) PROPOSED AFFORDABLE HOUSING COMPLEX MAIN ROAD PDE FILE NUMBER: REZ LAND USE ASSESSMENT REPORT (LUAR) PROPOSED AFFORDABLE HOUSING COMPLEX 560-564 MAIN ROAD PDE FILE NUMBER: REZ13-00008 PREPARED FOR P.O. BOX 908 ST. JOHN'S, NL CANADA A1B 4C4 PROPONENT BROOKSIDE DEVELOPMENTS

More information

Checklist For Life Safety

Checklist For Life Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 11550 Stone Ave N, #205, Seattle, WA 98133 Thank you for your interest in this Faira Certified

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information