Electrical Inspection Special Electrical

Size: px
Start display at page:

Download "Electrical Inspection Special Electrical"

Transcription

1 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes a control panel in the main office and a remote annunciator on the exterior near the Marie Drake entrance. Notification devices (horns & strobes) are located in the corridors, in the stairwells, and in the Multipurpose room. Manual pull stations are located at the exits and near the entrances to the stairways. The alarm and trouble signals are transmitted to the Central Alarm Agency by telephone dialer. Condition of the building system: The system appears to be in fair condition, providing the service originally intended. The control panel is no longer manufactured rendering spare parts difficult if not impossible to find. The system is no longer in compliance with NFPA 72 and was installed prior to the establishment of ADA guidelines. There are no notification devices in the classrooms or restrooms presenting increased safety hazards if a fire occurs. Remaining life expectancy: 0 years May 2005 Harborview Elementary School Condition Survey Report Page 194 of 210

2 Deficiency Replace Fire Alarm System Fire alarm panel is at least 23 years old and is at the end of its service life. The alarm panel is no longer manufactured and spare parts are difficult to purchase. The fire alarm system does not comply with current NFPA or ADA codes. Deficiency category: RR, C, & F Remedy Replace the entire system. Bring the system into compliance with current NFPA 72 and ADA guidelines including the provision of notification devices in the restrooms and classrooms. Estimated Construction Cost: $102,100 May 2005 Harborview Elementary School Condition Survey Report Page 195 of 210

3 0942 Communication Systems Telephone, data, intercom, TV, sound, cable trays, etc. Telephone: The telephone system appears to have been installed in the past 10+ years based on the generation of equipment installed. The system includes a switch in the basement with circuits to telephones in each classroom and office. The circuiting utilizes Category 3 cables. The system appears to be programmed for intercom as well as dialing to outside lines and internal telephones. The system includes voice mail capability. There is little or no raceway system for the circuiting. Network: A network system resides throughout the building, developed in its current configuration in recent years with Category 5 cables. The central server room for the district resides in the basement within the administrative offices. The terminals in the classrooms and offices in this building are configured from this room. There is little or no raceway system for the circuiting. Intercom: A new system was installed with the 1982 renovation. It has been subsequently partially dismantled, leaving only the speakers in the classrooms. The telephone is utilized for intercom functions. TV: A TV cable is installed to the administrative offices in the basement facilitating the network system. There is none to the classroom portion of the building. Sound: A sound system resides in the Multipurpose Room with large speakers mounted to the walls in the corners. Cable Trays: There are none. Condition of the building system: Telephone: The system is in fair condition. The equipment is still supported with parts, although they are becoming more difficult to find. The equipment has a low failure rate and numerous technicians remain available in the community for services. The circuiting is in poor condition with little protection from physical damage. It was reported that it is desired that the system be replaced in the near future with a network IP based system. Network: The system is in poor to fair condition. Much of the system is installed with cables routed across ceilings and walls. The cables are susceptible to physical damage. The Category 5 cables are sensitive to pinching and sharp radius turns, all resulting in reduced data volume transmission. The classrooms appear to be configured with few terminals for computers for the teachers and the students. The server facility in the basement appears temporary without a dedicated room within which to reside for physical security. The circuiting is draped from the ceiling allowing cable pinching and sharp radius turns. The racks are inadequate with limited cable management structure. The cooling and UPS systems appear inadequate. May 2005 Harborview Elementary School Condition Survey Report Page 196 of 210

4 TV: There are TVs with VCR or DVD players in the classrooms. There is no TV cable to allow connection to the utility provided programming. Sound: The sound system appears to be in fair condition. Remaining life expectancy: Telephone: 5 years Network: 0 to 5 years Sound: 5 years May 2005 Harborview Elementary School Condition Survey Report Page 197 of 210

5 Deficiency Upgrade the Telephone/Intercom System Telephone system is outdated and while still serviceable, the school district desires to upgrade the system for standardization throughout the district s facilities. The intercom system is no longer functioning. Deficiency category: RR, F Remedy Replace phone system with a network based IP system with an integrated intercom. Replace the circuiting utilizing concealed raceways and cable tray with new cables and terminals. Integrate with the network circuiting where possible. Estimated Construction Cost: $211,200 May 2005 Harborview Elementary School Condition Survey Report Page 198 of 210

6 Deficiency Upgrade the Network System Circuiting.The classrooms are configured with few terminals for computers for the teachers and the students. The circuiting is draped from the ceiling allowing cable pinching and sharp radius turns. Deficiency category: RR, F Remedy Replace the circuiting utilizing concealed raceways and cable tray with new cables and terminals. Integrate with the telephone circuiting where possible. Provide an intermediate rack with patch panels and switches dedicated to the elementary school. Provide a backbone connection to the district server room. Estimated Construction Cost: $192,000 May 2005 Harborview Elementary School Condition Survey Report Page 199 of 210

7 Deficiency Upgrade the Network Server Facility The server facility in the basement appears temporary without a dedicated room within which to reside for physical security. The circuiting is draped from the ceiling allowing cable pinching and sharp radius turns. The racks are inadequate with limited cable management structure. The cooling and UPS systems appear inadequate. Deficiency category: RR, F Remedy Provide a new server room with isolation from the offices in the administrative wing for better system security. Provide an appropriate amount of cooling and UPS capacity. Provide circuit support with raceways and cable trays, and cable management structure. Provide better dust control for the equipment. Estimated Construction Cost: $86,500 May 2005 Harborview Elementary School Condition Survey Report Page 200 of 210

8 Deficiency Cable TV System for the Classrooms A TV cable is installed to the administrative offices in the basement facilitating the network system. There isn t a cable TV network to the classroom portion of the building. Deficiency category: F Remedy Provide new circuiting utilizing new cable tray and raceways, all concealed in the walls and ceilings. Integrate with the circuiting for the Network and Telephone Systems. Provide terminals for each classroom as well as the Multipurpose Room. Estimated Construction Cost: $49,500 May 2005 Harborview Elementary School Condition Survey Report Page 201 of 210

9 0943 Security System Sensors, CCTV, accessories control, etc. Intrusion Detection & Access Control: An intrusion detection system with Access arming and disarming control at the main entrance was provided with the installation of a Building Management System in The system continues to function with motion sensors monitoring the corridors and keypads allowing staff to disarm and arm the system. The Building Management System has been upgraded (refer to the Mechanical portion of this study). Surveillance Cameras: None Condition of the building system: The equipment is in fair condition. The function of the system is good with continued optimal coverage of normally traveled routes. Additional features may be considered to integrate lighting control and full access control. Remaining life expectancy: 5 years May 2005 Harborview Elementary School Condition Survey Report Page 202 of 210

10 Deficiency Upgrade the security system. The security system is 20 years old and nearing the end of its service life. Deficiency category: RR, F Remedy Provide new motion sensors and access controls. Update to yield improved coverage. Integrate control of the lights allowing operation only with successful access. Estimated Construction Cost: $99,000 May 2005 Harborview Elementary School Condition Survey Report Page 203 of 210

11 0945 Other Special Electrical Clocks, low voltage, heating, etc. The clock system utilizes a digital control panel located in the school offices to operate clocks located in the classrooms and the Multipurpose Room. Condition of the building system: The controls and clocks are currently produced. The control panel appears to have been installed in the recent 10+ years. It is known to be of good quality with little or no maintenance requirement and a long service life. Remaining life expectancy: 10+ years No deficiencies noted for this building system. May 2005 Harborview Elementary School Condition Survey Report Page 204 of 210

12 May 2005 Harborview Elementary School Condition Survey Report Page 205 of 210

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 131 - QUEENS, 170-45 84TH AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-18

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 184 - QUEENS, 163-15 21 ROAD, New York, 11357 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-05 11:46

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 16 - BROOKLYN, 157 WILSON STREET, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-30

More information

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report Facility Attachment F Campus Capital Needs Sales Surtax Funded Detail Report Facilities Services 2700 Judge Fran Jamieson Way Viera, Florida 32940-6601 Condition Code Estimate Longleaf Elementary 1.78

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 152 - MANHATTAN, 93 NAGLE AVENUE, New York, 10040 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-05

More information

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes MEMORANDUM To: From: Attendees/Absentees Derek Gallagher DG Date: June 14, 2016 Comm. No: 152235 Subject: Independent School District #879 Delano Secondary School Additions and Renovations June 6, 2016

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-20 11:37 AM 2018-01-09

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20

More information

PROPOSED SCOPE OF WORK

PROPOSED SCOPE OF WORK WATERTOWN CITY SCHOOL DISTRICT SCHOOL AND COMMUNITY WORKING TOGETHER SMART SCHOOLS PROJECT PROPOSED SCOPE OF WORK BCA PROJECT NO. 2017-100 NOVEMBER 2, 2017 Prepared By: & 327 Mullin Street 2136 Five Mile

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Changes to this Division since the last issuance are indicated with yellow highlighted text. Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS OF AMERICAN STUDIES - BRONX, 2925 GOULDEN AVENUE, New York, 10468 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 260 - MANHATTAN, 425 WEST 33RD STREET, New York, 10001 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-16

More information

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review Parry Sound District Social Services Administration Board Housing and Community Services October 10, 2018 c/o Andrew Ball, Properties and Capital Projects Coordinator Email:aball@psdssab.org 22A Belvedere

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 47 - QUEENS, 9 POWER ROAD, New York, 11693 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-20 12:40

More information

Sagebrush Elementary School East Temple Place Aurora, Colorado 80015

Sagebrush Elementary School East Temple Place Aurora, Colorado 80015 Sagebrush Elementary School 14700 East Temple Place Aurora, Colorado 80015 Year Opened 1977 Current Square Footage 57,100 Site Acreage 7.66 sagebrush.cherrycreekschools.org Asphalt and concrete work; electrical

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FRANCIS LEWIS HS TRANSPORTABLE - Q, 58-20 UTOPIA PARKWAY, New York, 11365 Inspection Id Inspection Type Time In Last Edited EE :

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 80 AX(PETR COMPL-BLDG E)-S.I., 715 OCEAN TERRACE, New York, 10301 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Master Facility Planning Update School Board Meeting May 26, 2016

Master Facility Planning Update School Board Meeting May 26, 2016 Master Facility Planning Update School Board Meeting May 26, 2016 Master Facilities Committee Overview Reflection of Committee Work Review of District Wide Facility Issues Identified District Wide Facility

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Project Scenario Summary Report http://fusion.deltacollege.edu/code/planning/project/editfpu/scenariorpt.asp?id=2629&ce... Page 1 of 1 11/7/2017 California Community Colleges Project Scenario Summary 2019

More information

DIVISION 13 - SPECIAL CONSTRUCTION

DIVISION 13 - SPECIAL CONSTRUCTION DIVISION 13 - SPECIAL CONSTRUCTION I. GENERAL A. This division contains the following elements: 1. Relocatable Buildings. 2. Telephone and Data Systems. 3. Intercom and Clock/Bell System. 4. Wiring and

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

2014 Bond Project Guide

2014 Bond Project Guide 2014 Bond Project Guide Bush Elementary School Page 1 Instructional Technology Computers, Projectors, Mobile Carts, Document Cameras and Printers Wireless Connectivity New Construction New Tech Center

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:... 2 2. EMERGENCY POWER... 3 B. LIGHTING...4 1. GENERAL... 4 2. AVERAGE MAINTAINED

More information

BSD Technical Standard. Division 28: Electronic Safety & Security

BSD Technical Standard. Division 28: Electronic Safety & Security Division 28: Electronic Safety & Security I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for electronic safety and security in BSD facilities.

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 138 AX (CROWN HGTS ECC 1)-K, 960 PROSPECT PLACE, New York, 11216 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111

Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Year Opened 1958 Current Square Footage 50,504 Site Acreage 8.53 greenwood.cherrycreekschools.org $220,720 Electrical

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Charleston excellence is our standard County SCHOOL DISTRICT

Charleston excellence is our standard County SCHOOL DISTRICT Charleston excellence is our standard County SCHOOL DISTRICT FACILITY SECURITY ACCESS CONTROL, INTRUSION DETECTION, AND SURVEILLANCE DESIGN SPECIFICATIONS FOR NEW CONSTRUCTION, ADDITIONS, AND MAJOR RENOVATIONS

More information

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16 1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated

More information

Master Project List Report

Master Project List Report Blue Hills Elementary School 01-8215 Site Utilities Replacement $52,835 01-8502 Modernization $3,135,933 01-8525 Exterior Painting $181,478 01-8552 Kindergarden Fencing $13,180 Install new backflow preventer.

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 69 PORTABLE - QUEENS, 77-02 37TH AVENUE, New York, 11372 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-24 8:36 AM 2018-05-16

More information

MEDIA CENTER September 30, 2010

MEDIA CENTER September 30, 2010 MEDIA CENTER September 30, 2010 I. PROGRAM REQUIREMENTS Refer to the project-specific Schedule of Spaces for student stations, square footage, and for any requirements that may differ from the prototype

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: TERS PREP HS(OL REDIRECTION)-K, 226 BRISTOL STREET, New York, 11212 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Crime Central Station Burglary Alarm Systems

Crime Central Station Burglary Alarm Systems Page 1 of 10 Scope This criteria is intended to provide Loss Control Representatives with specific guidelines and information for evaluating central station burglar alarm systems for risks carrying crime

More information

Facilities Master Planning

Facilities Master Planning Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction CITY HALL ADA ENHANCEMENT/REMODEL 2016 ACTION PLAN 1978 Construction 1 HISTORY At the February 2, 2016 Council Workshop Council Motions included: The direction to staff to move forward with the City Hall

More information

ELECTRICAL DESIGN GUIDELINES SECTION GUIDELINE SPECIFICATIONS-DUVAL COUNTY PUBLIC SCHOOL

ELECTRICAL DESIGN GUIDELINES SECTION GUIDELINE SPECIFICATIONS-DUVAL COUNTY PUBLIC SCHOOL The design guidelines, which follow, are intended to supplement the Educational Specifications and State Requirements for Educational Facilities (SREF). All electrical service (temporary, new, disconnection

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

REPORT CARD TO THE COMMUNITY MAY 15, 2018

REPORT CARD TO THE COMMUNITY MAY 15, 2018 REPORT CARD TO THE COMMUNITY MAY 15, 2018 O On May 10, 2014 voters in Greenville ISD approved a $72,275,000 bond election. BOND PROPOSAL PROJECT BOND AMOUNT CONSTRUCT A NEW BOWIE ELEMENTARY SCHOOL $17,600,000

More information

MADISON ELEMENTARY SCHOOL

MADISON ELEMENTARY SCHOOL TWIN RIVERS UNIFIED SCHOOL DISTRICT MADISON ELEMENTARY SCHOOL 54 HARRISON STREET NORTH HIGHLANDS, CALIFORNIA 95660 ORIGINAL BUILDING COMPLETED: 96, 67 BUILDING AREA: 45,69 SITE ACREAGE: 0 BUILDING CAPACITY:

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

Forest Hills Facilities Plan

Forest Hills Facilities Plan Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Business Owner s Security Buyers Guide

Business Owner s Security Buyers Guide Business Owner s Security Buyers Guide You re a business owner. That means you wear a lot of hats including that of the security manager. One of your many jobs is to protect your customers, employees,

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: DIV. COMPUTER INFO-DATA CENTER-K, 2 METROTECH CENTER, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,

More information

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction 1 Widen Elementary School Site Summary Address 5605 Nuckols Crossing Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 1986 Total Campus Building Area (combined) 74,523

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 90 MINISCHOOL - BRONX, 1116 SHERIDAN AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

ELECTRONIC SAFETY AND SECURITY SYSTEMS

ELECTRONIC SAFETY AND SECURITY SYSTEMS 281316 ELECTRONIC SAFETY AND SECURITY SYSTEMS PART 1: GENERAL 1.01 RELATED DOCUMENTS A. Policy 8.1 Responsible Use of Video Surveillance Systems B. Policy 8.4 Management of Keys and Other Access Control

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN 04.13.2017 1 MONTICELLO INTERIOR FINISHES PAINT MOULDING WALLS ACCENT DOORS DOOR TRIM/STAIRS

More information

SHOREWOOD SCHOOL DISTRICT FACILITY ASSESSMENT. October 25, 2016 EUA Project:

SHOREWOOD SCHOOL DISTRICT FACILITY ASSESSMENT. October 25, 2016 EUA Project: October 25, 2016 EUA Project: 316125-01 Page 1 Eppstein Uhen Architects October 25, 2016 TABLE OF CONTENTS SECTION 1 EXECUTIVE SUMMARY TEAM CONTACTS PROJECT INTENT DATA GATHERING PROCESS UNDERSTANDING

More information

PASS Security Plan Checklist

PASS Security Plan Checklist [School District Name] PASS Security Plan Checklist SCHOOL DISTRICT INFORMATION Address: Telephone Number: Fax Number: Number of Employees: Number of Students: School Resource Officer: TIER CONTINUUM:

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: PRE-K CENTER @ 107-17 NORTHERN BOULEVARD - QUEENS, 107-17 NORTHERN BOULEVARD, New York, 11368 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3

More information

Meadow Point Elementary School East Grand Avenue Aurora, Colorado 80015

Meadow Point Elementary School East Grand Avenue Aurora, Colorado 80015 Meadow Point Elementary School 17901 East Grand Avenue Aurora, Colorado 80015 Year Opened 1982 Current Square Footage 53,100 Site Acreage 7.48 meadowpoint.cherrycreekschools.org $2,081,600 Electrical system,

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

Allisonville Elementary School Facilities Highlights Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767

Allisonville Elementary School Facilities Highlights Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767 Allisonville Elementary School Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767 ADA improvements are Fire alarms need to be updated Playground equipment needs to be

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information