AMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR
|
|
- Peregrine Warner
- 5 years ago
- Views:
Transcription
1 January 26, 2018 AMENDMENT NO.: III TO INVITATION FOR BID NO.: GPA FOR PHYSICAL SECURITY AND ACCESS CONTROL SYSTEM (ACS) REPAIR AND UPGRADE AT VARIOUS GPA LOCATIONS Prospective Bidders are hereby notified of the following inclusions and response to inquiries received from G4S Security Systems (Guam) Inc. dated January 05, 2018: INCLUSIONS: ATTACHMENT D: ADDITIONAL REQUIREMENTS Camera View Specifications Public Announcement (PA) Specifications Door Replacement Specifications G4S Security Systems (Guam) Inc. inquiry dated 01/05/18: 1. Is this a Multi-Step Sealed Bidding as stated in the page 28, paragraph 13, a. & b.? It does not indicate it on page 1 under description, which is normally done by GPA bids. This is not a multi-step bid. 2. Can GPA provide a floor plan with dimensions for the Gloria Nelson Building, GPA s Transmission and Distribution (T&D) in Dededo, GPA Combustion Turbine (CT) in Dededo and GPA s Transportation Compound in Tamuning? Refer to Attachment B for the Fadian floor plan. For T&D, Dededo CT and the Transportation facility only the view of the perimeter is being asked for camera coverage. GPA Physical Security and Access Control System (ACS) Repair and Upgrade at Various GPA Locations D.Fejeran Page 1 of 4
2 3. What is the payment term for this bid? Net 30 days upon delivery/invoice or Net 15 days upon delivery/invoice? Is progress billing with schedule of values acceptable on this bid? Payment Terms is Net 30 Days. 4. On page 3, under Scope of Work on Phases I-IV, please define GPA s Field of view form Camera(s) location and Scope of view from Camera(s) location? We would to establish the difference between the two. Refer to Attachment D Additional Information. 5. How many cameras does the existing Geo Vision system have? What is the maximum number of IP cameras or licenses can the existing Geo Vision system has? Please provide Geo Vision system model/part number or license? What is the make/model number of the current IP cameras? The current Geo Vision system has 16 connected cameras. To clarify Geo Vision license will NOT be required for any IP Cam. Please see attachment A Minimum camera specifications (Internal/External). Make and model is NDT 85-TMVSYA Under scope of work for installing an alarm cover on the emergency release pull station for all locations where the emergency pull station exists. Are these release pull station only for the existing access control system? Can GPA provide quantity as the layout does not specify the locations? Since the release of this IFB, the Emergency Pull Station coves have already been installed and thus will no longer be part of Scope. No bid on this is required. 7. What is the current Access Control System at Gloria B. Nelson Public Service Building? Model/make and who was the provider? The current Access Control System is Odyssey Encrypted Dual Host. The provider is Solutions Guam. 8. What is the existing telephone system at Gloria B. Nelson Building? Who was the provider? Current phone system at the Gloria B. Nelson Building is ShoreTel VoIP systems. Provider is Pacific Data Systems (PDS). 9. What is the existing local sound system at Gloria B. Nelson Building? Who was the provider? No existing local sound system is in place. GPA Physical Security and Access Control System (ACS) Repair and Upgrade at Various GPA Locations D.Fejeran Page 2 of 4
3 10. Is there an existing PA system in place at Gloria B. Nelson Building? Who was the provider? There are no existing PA system in place. Please see Attachment D Additional Info. 11. What is the existing fire alarm system at Gloria B. Nelson Building? Who as the provider? The existing fire alarm system is Minimax MS-320. Phoenix Pacific Guam provides support for the system. 12. Will GPA be responsible for providing remote access connectivity to include infrastructure (copper/fiber) for CCTV remote sites at Dededo s Transmission and Distribution (T&D), Combustion turbine (CT) and Transportation Compound in Tamuning? Dededo T&D, Dededo CT and the Transportation Compound all have existing network connectivity back to GPA Fadian Data Center. All vendors will provide network and communication wiring from IP Camera to primary switch(es) at IDF Cabinet for each location. Required conduit and other installation to include equipment, hardware and services should be part of the proposed cost. Please see Attachment D Additional Information. 13. All new equipment and installation required shall conform to Guam building codes and standards. If applicable, are contractors allowed to utilize existing conduits/cable trays/idf boxes, or termination boxes for wire/cable installation? Is the Gloria B. Nelson Building Plenum rated ceiling? Contractors will be able to utilize existing conduits/cable trays/idf boxes or termination boxes where applicable or allowable. All communications cables installed in the Gloria B. Nelson Building must be Plenum rated. Please see Attachment D Additional Information. 14. Can G4S arrange another site visit at Gloria B. Nelson Building as well as the three other GPA sites in Dededo and Tamuning to conduct a more thorough assessment of the premises? A Non-Mandatory Site Visit is scheduled for Tuesday, January 30, 2018 at 9:00 A.M. for the following locations: GPWA Fadian Main Facility Dededo CT T&D Compound Transportation Interested parties are to meet at our GPWA Fadian Main Facility, 1 st. Floor, Procurement Office. GPA Physical Security and Access Control System (ACS) Repair and Upgrade at Various GPA Locations D.Fejeran Page 3 of 4
4
5 ATTACHMENT D ADDITIONAL REQUIREMENTS Please note the following additional requirements: a) Contractor will maintain replacement equipment sufficient to provide general replacement of any equipment failure under warranty of the system within one working day of a notification of failure. b) All drawings, manuals etc. become the possession of the client at hand over with no paper or digital materials relative to the design and installation of the system retained by the contractor. These materials will be archived on site and made available as necessary to facilitate the repair or service of the system. c) Design Calculations: Please provide your lens calculations to support your camera locations. These calculations will confirm the fields of view and detail requirements as defined previously. d) Band Width Calculations: Please include the band width calculations for each of the cameras to be installed. Your logic in generating these calculations should include maximum FPS expectations. e) Lightening Protection: In the event cameras are mounted on standalone poles sufficient efforts will be made to provide lightening protection for the equipment. f) Cabling: All cables will be home run and individually marked with the IP address they are programmed to. Acceptable marking will be in the form of printed labels standard to the IP industry. The cable will be grey to comply with the current site standards and plenum jacketed where cable is running in an open environment. g) Electrical Requirements: Where connection to an existing electrical service is utilized, this connection will be clearly identified to the breaker it is associated with it. Additionally, confirmation from the client relative to acceptable circuit loading will be provided. Where there is no existing power available the contractor will have the appropriate drop installed in a method that is compliant with all local permitting and design standards. h) Outside Connections: All outside connections will be installed in NEMA rated boxes consistent with the environment they are located in. i) Tamper Protection: All exterior boxes installed in support of this system will be tampered against un authorized access. This tampering will take the form of NC or NO switches monitored through the alarm inputs on the cameras. j) Drawings: A complete set of as Built drawings will be included in the turn over package. These drawings will include: device type, address, location and wire mapping, port demarcation, electrical demarcation etc. This drawing does not require and engineers stamp and can be accurately represented in a riser diagram.
6 FADIAN MAIN OFFICE 1. FADIAN HALL WAYS: The primary purpose of these cameras: CAMERA VIEW SPECIFICATIONS a) Give a clear view over the entire distance of the hallway. b) At points of Entry and Exit ensure a view which will provide detail significant enough for recognition of the individual(s), while maintaining the best overall definition viewing possible. c) Provide illumination standards sufficient to retain viewing consistent with the day time viewing area. Low Light Color capabilities is preferred but the minimum of IR support for the area is required. 2. ELEVATOR LOBBIES: The primary purpose of these cameras: a) Ensure a view which will provide detail significant enough for recognition of the individual(s) entering the elevators and adjacent stairwells. b) Provide illumination standards sufficient to retain viewing consistent with the day time viewing area. Low Light Color capabilities is preferred but the minimum of IR support for the area is required. 3. EMPLOYEE ENTRANCE GATE: The primary purpose of this coverage is to: a) Provide the identity all vehicles accessing or leaving the employee parking area. This identification to include the license plate of the vehicle in all environments 24 hours per day. A solution which would also identify the driver would be a plus. b) The location of this camera will be such so that it can be monitored by another existing or new camera to protect it against vandalism and damage. c) Installation of vehicle impact protection if the camera is installed in a location where that impact may occur. d) An option to include the LPR Software should be added as an option and priced separately. 4. CASHIERS AREA: The primary purpose of this camera is to: a) Provide coverage of activities occurring in the Cashier area. b) Coverage should be focused on identifying individuals conducting business with the cashiers.
7 5. MAIN ENTRANCE REVISION: a) No camera is required at the front gate. b) Signage indicated that a CCTV System is in place and monitored 24 Hours Per Day is to be installed in an area readily viewable from incoming vehicle. c) Signage will be of a reflective material designed for illumination by vehicular headlights. 6. PARKING LOT CAMERAS: The primary purpose of these cameras: a) To provide accurate viewing of incidents occurring in any of the parking areas. The incident information should be sufficient to clearly identify the vehicles involved. b) IR illumination sufficient to maintain the area of coverage for the day time viewing should be included with the coverage. c) The cameras were originally defined to be mounted on the roof. A more reasonable location for these cameras would be above the first floor on the exterior of the building. REMOTE SITES (T&D COMPOUND DEDEDO/COMBUSTION TURBINE COMPOUND DEDEDO/TRANSPORTATION COMPOUND TAMUNING) 1. PERIMETER: The perimeter areas to be protected should provide activity identification along the perimeter. This protection will produce the same level of view 24 hours per day with the daylight in color and the darkness in monochrome supported by Infrared illumination. Activity field of view is defined for this application as the ability to determine intrusion throughout the cameras view. Optional mapping of Pan, Tilt and Zoom cameras to produced enhanced object identification should be offered and an option. 2. ASSET PROTECTION: Where assets have been identified either in the bid documents, addendums, responses and/or at the site visits, they will require site access monitoring sufficient to provide individual or vehicular identity. This identity is required where immediate access to a protected asset may be affected. Where the monitoring of the intruder in general is monitored throughout the general coverage, and that coverage is uninterrupted, it is sufficient to demonstrate that identification, at any point in the coverage.
8 To paraphrase: If an individual or vehicle is picked up in the general coverage, as long as that coverage is non- interrupted, a video capture sufficient to provide an identifiable image acquired at any time through the process will be sufficient. 3. GATE VIDEO The same standard of video viewing and recording will be required as defined in the specifications applied to the gate system at Fadian.
9 PUBLIC ANNOUNCEMENT (PA) SPECIFICATIONS Additional clarification for the specifications for the PA system as follows: a) System will be compliant with the latest version of NFPA 72 Standards as defined in Chapter 24. Additional standards may be in place relative to the AHJ (Authority Having Jurisdiction) and are mandatory as well. b) The contractor is responsible for coordinating with the current service providers for the existing Fire Alarm System, Access Control System and Elevator Company where an interface is required. The contractor is responsible for all charges resulting from these interfaces to include permit fees, drawing etc. c) Contractor is responsible for all fees necessary for the recertification and testing of those systems. d) Special consideration will be given for system compliance with the facility Active Shooter protocols. e) Minimum UPS will be providing to maintain the system for up to 2 hours. f) Protection against power strikes/surges will be included.
10 DOOR REPLACEMENT SPECIFICATIONS Following doors at Fadian main office which listed for repair/replacement: 1) Double Door on 2 nd Floor to Employee parking lot. Repair or replace door closures. 2) Double Door on 1 ST Floor smoking area 3) 2 nd Floor Exterior Pedestrian Door Engineering Dept. Specifications to repair/replace doors as follows: a) Currently the doors fail to close completely OR are intermittent resulting in a failure of the ACS protection. b) Restoration, Repair or Replacement of the hardware on all doors which should include: Interface with the existing ACS system. This will require coordination with the ACS Service Provider and all costs associated with this will be the responsibility of the contractor Meet or exceed ANSI Grade 1, ADA, NFPA 72 Standards or Requirements and be UL listed. Work with the existing Doors. Restoration of surfaces abandoned as a result of the removal of the existing hardware, to include fill plugs or materials consistent with existing surfaces and be weatherproofed. Where painting may be involved the paint will be consistent with the existing surface.
GARCIA GALUSKA DESOUSA Consulting Engineers
L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as
More informationRFP Addendum 2 March 31, 2016
RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)
More informationAre You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems Siemens AG 2015 All rights reserved. usa.siemens.com/infrastructure-cities
More informationBSD Technical Standard. Division 28: Electronic Safety & Security
Division 28: Electronic Safety & Security I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for electronic safety and security in BSD facilities.
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationElectronic Safety and Security
28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationAddendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017
Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor
More informationChapter 1 Introduction
Chapter 1 Introduction Chapter 1 provides an overview of the fundamental aspects of the industries that influence electronic safety and security (ESS) design. Table of Contents Introduction to Safety
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationPhysical and Environmental Security. CISSP Guide to Security Essentials Chapter 8
Physical and Environmental Security CISSP Guide to Security Essentials Chapter 8 Objectives Site access controls including key card access systems, biometrics, video surveillance, fences and walls, notices,
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationPROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS
SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationWIRELESS CCTV. Oil, Gas and Renewables Site Security.
WIRELESS CCTV Oil, Gas and Renewables Site Security Wireless CCTV Wireless CCTV (WCCTV) is a market leading, customer focused provider of portable, redeployable surveillance solutions. WCCTV manufactures
More informationPhysical Security Standards WARREN J. BUJOL, IBERIABANK MATTHEW RONIGER, IBERIABANK
Physical Security Standards WARREN J. BUJOL, IBERIABANK MATTHEW RONIGER, IBERIABANK Physical Security Standards Agenda Making a Case for Physical Security Why have Standards? Risk Assessments - Justifications
More informationInnovating security where you need it most. Transportation: License Plate Capture.
Innovating security where you need it most. Transportation: License Plate Capture. License Plate Capture 2 License Plate Capture: Manage the usage of roads and parking lots more effectively by knowing
More informationCity of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1
City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1 BID TITLE: Facility Access Control and Security System REQUESTING DEPARTMENT: Development Services RELEASE DATE: July 12, 2016 DUE DATE: August 4,
More informationDatasheet Face Recognition [Genetec VMS]
Datasheet Face Recognition [Genetec VMS] Version 3.6 This Specification Sheet gives the details of system requirements, features and other salient points of AllGoVision Face Recognition application for
More informationAppendix 1 LACCD Districtwide Security Performance Requirements
Appendix 1 LACCD Districtwide Security Performance Requirements SECTION LISTING 28 01 10 Overview 28 13 00 Access Control System 28 13 01 Access Control System Installation 28 13 26 Access Control Remote
More informationACTIVE INFRARED BARRIER
Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology
More informationPanel XTO210/610/710 GPRS
P r o d u c t S p e c i f i c a t i o n s S h e e t Doc. - Ref. 220-XTO Version : Juin 2013 Description Supervised Wireless Technology The XTO control panel is a Videofied weatherproof, wireless, battery
More informationIntroducing the innovative ipids Indoor Outdoor Detection System MANUFACTURING SECURITY SOLUTIONS
Introducing the innovative ipids Indoor Outdoor Detection System 1 SENSITIVE Electronic Sensors installed on the perimeter fence, and communicating to a central computer. Can adapt to any type of fence.
More informationBUILDING SECURITY and EVACUATION RELATED POLICIES: REVIEWED: AS NEEDED
POLICY 120 BUILDING SECURITY and EVACUATION REVISED: 1/93, 01/02, 09/08, 08/10, 04/11, 07/11, 12/13, 10/15, 07/16, 08/18 CFA STANDARDS: RELATED POLICIES: REVIEWED: AS NEEDED A. PURPOSE The purpose of this
More informationComprehensive Security for Banks and Credit Unions
Comprehensive Security for Banks and Credit Unions Trust a Turnkey Solutions Provider As a leading security provider, STANLEY Security understands the needs of financial institutions like yours and has
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationYou are required to READ ALL PAGES. of this application
Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationUSD 380 Centralia, Frankfort & Vermillion
PROJECT MANUAL District Wide Security Upgrade Project Software and Hardware Specifications Covering Locking Hardware Access Control Software & Hardware Video Software & Hardware January 30, 2018 USD 380
More informationDATA CENTER SECURITY. March 2017 Anton Panaitescu
DATA CENTER SECURITY March 2017 Anton Panaitescu a-panaitescu@optex.com.pl +40 742 02 02 09 Activities Company Overview Business Domain Creation of a safer, more secure and more comfortable society. Security
More informationNOTICE TO ALL FIRMS. Bid RFI Questions and Answers
Purchasing Department 227 West 27 th Street New York, NY 10001 Purchasing Dept. Tel. 212-217-3630 Purchasing Dept. Fax 212-217-3631 Purchasing@fitnyc.edu NOTICE TO ALL FIRMS Date: March 8, 2018 To: From:
More informationNEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015
NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized
More informationA.C.E. Security Consultants House of Worship Checklist
A.C.E. Security Consultants House of Worship Checklist (Revised November 4, 2016. Jim McGuffey) House of Worship Check List Location Location Location Location Comments Employee/Parishioner Awareness List
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More information205 CMR: MASSACHUSETTS GAMING COMMISSION
205 CMR 141.00: SURVEILLANCE OF THE GAMING ESTABLISHMENT Section 141.01: Approval of Surveillance System 141.02: Commission Access to the Surveillance System 141.03: CCTV Equipment 141.04: Areas to Be
More informationProperty Name & Address [ Property Name ] - [ Property Address ]
Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire
More informationTotally Wireless Video Security
Totally Wireless Video Security Traditional Video Surveillance ($50,000+) vs. Event-Based Videofied Solution ($2,500) Executive Summary: Totally Wireless Video Security has been effective but cost and
More informationUBC Technical Guidelines Section Edition Access Control Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 28 05 00 Access Services: General Standards.2 Section 08 71 00 Door Hardware 1.2 Coordination Requirements.1 UBC Access Services 1.3 Description.1
More informationMNEC NFPA 72 WHITE PAPER
MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating
More informationSTATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY)
STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC-213-100797 RACCOON CREEK STATE PARK (BEAVER COUNTY) I. SCOPE OF WORK: The Commonwealth of Pennsylvania, Department of Conservation
More informationCHAPTER Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 973
CHAPTER 2013-203 Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 973 An act relating to low-voltage systems; amending s. 489.503, F.S.; revising an exemption from
More informationTECHNICAL BULLETIN No: 0040
National Security Inspectorate Sentinel House, 5 Reform Road, Maidenhead, SL6 8BY E: nsi@nsi.org.uk W: nsi.org.uk Dated: 12 October 2017 To: 1. All NSI NACOSS Gold and System Silver Companies 2. Applicant
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationSafety & Security Checklist by Layers of Building and Grounds The Church Safety and Security Guidebook (Brotherhood Mutual Insurance)
Appendix D Safety & Security Checklist by Layers of Building and Grounds The Church Safety and Security Guidebook (Brotherhood Mutual Insurance) Assessing Specific Areas Look at each Layer of Security
More informationG-MAX IVS R123 Vibration Sensors Perimeter Intrusion Detection System
PS-4001-48461-A G-MAX IVS R123 Sensors Perimeter Intrusion Detection System Product Specifications G-Max Security Tech Ltd a l d o r e c o t e c L td. I n t e g r a t e d S e c u r i t y s y s t e m s
More informationADPRO. Integrated Security and Surveillance Solutions. Intelligent - Flexible - Reliable
ADPRO Integrated Security and Surveillance Solutions Intelligent - Flexible - Reliable 01/02 09:33 10/08 18:25 09/05 14:20 11/12 16:15 07/10 17:55 THE NEW PARADIGM FOR SECURITY Innovative, integrated security
More informationPASS Security Plan Checklist
[School District Name] PASS Security Plan Checklist SCHOOL DISTRICT INFORMATION Address: Telephone Number: Fax Number: Number of Employees: Number of Students: School Resource Officer: TIER CONTINUUM:
More informationArchitectural and Engineering Specification for a Real-Time Locating System Flare
Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is
More informationMarch 11, 2013 ADDENDUM #1. RFP-DEM-12/ FDEM Facility Security System Replacement
STATE OF FLORIDA DIVISION OF EMERGENCY MANAGEMENT RICK SCOTT Governor BRYAN W. KOON Director March 11, 2013 ADDENDUM #1 RFP-DEM-12/13-015 FDEM Facility Security System Replacement The Division is issuing
More informationA basic guide to BS 8418:2015 CCTV Systems for Installers
A basic guide to BS 8418:2015 CCTV Systems for Installers April 2017 For other information please contact: British Security Industry Association t: 0845 389 3889 e: info@bsia.co.uk www.bsia.co.uk Form
More informationCOMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal October 2013 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...
More informationCorporate Presentation
Corporate Presentation Ontech s Controlled Magnetic Field technology, marks the next generation in the world's security systems, satisfying market demands with innovative new functionality not available
More informationRE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan
ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or
More informationInnovative Security Solutions That Increase Force Protection Effectiveness
Innovative Security Solutions That Increase Force Protection Effectiveness Security Management Solutions for the New Millennium JTS-LLC, Copyright 2005 1 Components of the Force Protection Discussion Statement
More informationPreliminary Site Security Plan Operations Cassadaga Wind Farm
Preliminary Site Security Plan Operations Cassadaga Wind Farm January 2016 Table of Contents 1. Introduction... 3 2. Access roads... 3 3. Wind Turbines... 3 4. Substations... 3 5. Operations and Maintenance
More informationHMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3
HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationCentered on future family lifestyles, Lechange provides a newer, better quality of life and experience for consumers. Through providing a complete series of new products and services for numerous scenarios
More informationWIRELESS CCTV. Utility Site Security & Surveillance.
WIRELESS CCTV Utility Site Security & Surveillance Wireless CCTV WCCTV is the UK s leading provider of site security systems for utilities and critical national infrastructure sites, including power stations,
More informationApartment Fire & Safety Inspection. City of Guadalupe
Apartment Fire & Safety Inspection City of Guadalupe Intent Provide information and the most common violation. It is NOT the intent to Identify all hazards a building may experience. It is NOT intended
More informationSecurity Considerations for Secure Workplaces
Security Considerations for Secure Workplaces Mitchell Factor HMA Consulting, Inc. USA Canada UK UAE Overview Security Risk Assessment The Process Security Design Process Technology Updates & Design Considerations
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:
More informationMulch fires, trash can fires, or other fire outside a building should be reported by the following methods:
University of Maryland FIRE EVACUATION PLAN HEALTH SCIENCE FACILITY I (HSF I) POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will
More informationArchitectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone
Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone April 15, 2014 Page 1 of 14 G6DA0115-001 This document is intended to provide performance specifications
More informationMass Transit Use Cases. Indoor and Outdoor Signage Options from Adaptive Micro Systems
Mass Transit Use Cases Indoor and Outdoor Signage Options from Adaptive Micro Systems History of Adaptive Micro Systems - Adaptive was established in 1978 in Milwaukee, Wisconsin - We own a 75,000 square
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationSECTION SECURITY TESTING AND COMMISSIONING
SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,
More information"VOICE OF SECURITY: Trends In Intercom, Public Address, and Mass Notification Emergency Communications
"VOICE OF SECURITY: Trends In Intercom, Public Address, and Mass Notification Emergency Communications ASIS Houston Chapter Luncheon May 21, 2014 Paul Rux Director of Sales Mexico / South Central Region
More informationCCDC EXPANSION PROJECT
CCDC EXPANSION PROJECT TEMPORARY MOBILE KITCHEN RFP NO. 12-0132-3 Addendum #1 ADDENDUM #1 IS BASED ON THE INFORMATION DISCUSSED AT THE MANDATORY PRE-BID MEETING THAT WAS HELD ON THURSDAY, JANUARY 10, 2013
More informationNFPA 72 Code Changes vs 2013
NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996
More informationArchived Content. This content was archived on August 24, 2016.
This content was archived on August 24, 2016. Archived Content The Marihuana for Medical Purposes Regulations (MMPR) are no longer in effect and have been archived. They were replaced by the new Access
More informationADDENDUM NO. 1 FDVA-ITB B ITB TITLE: Bennett SVNH Nurse Call System ISSUE DATE: March 27, 2014
Mike Prendergast Executive Director State of Florida DEPARTMENT OF VETERANS AFFAIRS Division of Administration and Public Information 11351 Ulmerton Road, #311-K Largo, FL 33778-1630 Phone: (727) 518-3202
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationTen-Point Checklist for Emergency Preparedness
Ten-Point Checklist for Emergency Preparedness This checklist was developed by Dr. Susan M. Smith, and graduate students participating in a UT Safety Workshop graduate class. NOTE: Evaluators should indicate
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationStandards and Safety Update
Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical
More informationBrochure. Security Designed, Installed by Experts
Brochure Security Designed, Installed by Experts 02 03 Introduction Working in Partnership with our Customers. At b2b Secure IT our commitment to our customer is simple; we will provide an unrivalled end
More informationTIME: ~ : L.\9 ClAM.laPM BY: /t-_a. BEFORE THE OFFICE OF PUBLIC ACCOUNTABILITY. has yet to seriously evaluate the original procurement concerns
PACIFIC DATA SYSTEMS 5 ILIPOG DRIVE HBC BLDG SUITE 4A TAMUNING, GUAM 969 TELEPHONE: ( 6) 300-00 3 FACSIMILE: (6) 300-065 RECElVEL OFFJCE OF PUBLIC ACCOUNTA LUU PROCUREMENT APPEALS DATE: =rf_._.._..._/c_lf...
More informationA guide to the changes between BS 8418:2010 and BS 8418:2015
A guide to the changes between BS 8418:2010 and BS 8418:2015 March 2016 For other information please contact: British Security Industry Association t: 0845 389 3889 e: info@bsia.co.uk www.bsia.co.uk Form
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationTW-8000 TAUT WIRE FENCE
TW-8000 TAUT WIRE FENCE www. rbtec. com Email: info@rbtecom GENERAL TW-8000 Product information INTRUDALERT is a powerful electronic system specifically designed for total perimeter protection of critical
More informationVictor Shapilsky and Adison Ang
Victor Shapilsky and Adison Ang Incident Detection Systems in Motorway Tunnels Overview Incidents Delayed incident detection Performance criteria for incident detection systems Available incident detection
More informationThe last date of submission of responses has been extended up to 14: 00 hrs on 20/07/2018.
TCIL/S&TC/2017-18/AIPS Dated: 17.07.2018 Corrigendum No. 11 Sub: Amendment for Pre-bid Tie-Up for selection of OEM / Master Integrator for the design, supply, installation, commissioning & CAMC of perimeter
More informationDOCUMENT ADVERTISEMENT FOR BIDS
IFB 15-014 - 2015 Fire Alarm Upgrades for 4-15078 DOCUMENT 00 11 13 ADVERTISEMENT FOR BIDS 1.1 PROJECT INFORMATION A. Notice to Bidders: Qualified bidders may submit bids for project as described in this
More informationFIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY
UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the
More informationFlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a
Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and
More informationMULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning
CAMPUS FIRE SAFETY CODE TALK Campus Fire Safety e-newzone MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning By Ernesto Vega Janica,
More informationStandard Operating Procedure CCTV Guidelines
Purpose To establish clear guidelines that pertain to the use of CCTV Video Surveillance Technology used in the Annapolis Valley Regional School Board. Introduction With the increased use of CCTV systems
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationWIRELESS CCTV. Site Security & Surveillance.
WIRELESS CCTV Site Security & Surveillance Wireless CCTV WCCTV is the UK s leading provider of rapid-deployment CCTV Towers, specifically designed to provide all-in-one site security for temporary sites
More informationIF IT S NOT LIT, IT S NOT SECURE ADVANCED PERIMETER SECURITY OUR LIGHTS ARE YOUR MOST ACTIVE DETERRENT. STOP INTRUDERS BEFORE THEY ACT FLASH GLARE
ADVANCED PERIMETER SECURITY IF IT S NOT LIT, IT S NOT SECURE FLASH GLARE Force Intruders into Retreat. OUR LIGHTS ARE YOUR MOST ACTIVE DETERRENT. STOP INTRUDERS BEFORE THEY ACT An extremely effective and
More informationPanel XT210/610/ Description. Supervised Wireless Technology
P r o d u c t S p e c i f i c a t i o n s S h e e t Doc. - Ref. 220-XT Version : June 2013 Description The XT control panel is a Videofied wireless, battery operated, hybrid alarm system that is designed
More informationDS-2TD Thermal & Optical Network Bullet Camera
DS-2TD2836-50 Thermal & Optical Network Bullet Camera Introduction Hikvision DS-2TD2836-50 Thermal Bi-spectrum Network Bullet Camera is applied to perimeter defense and fire-prevention purposes in critical
More information