1 Mail To: Service At: Account # Plano Molding Co Plano Molding Company 431 E South St 431 E. South Street Plano, IL Plano, IL Tested in accordance with NFPA 72. IL License Test Summary Test Type Total Count Pass Count Fail Count Not Tested Count Audio - s AV Control Valve CONTROL VALVE Fire Pump - Loss of Power FIRE PUMP - LOSS POW Fire Pump - Running FIRE PUMP - RUNNING Pull Station PULL STATION Smoke/Heat Combo COMBO SMOKE/HEAT Supv H/L Air SUPV H/L AIR Temperature Sensor TEMP SENSOR W-F Pressure WF-PRESSURE WF-Vane WF-VANE Totals Inspection Tasks Area - Location - Zone - ID - Monitoring station? ADS Time Out? 0816 By Who? 1095 Owner (or rep) name and number? na Was the onsite person notified of test results? na Time In? 1042 By Whom? 1095 Panel Section Area FCI Location - Hallway by lunch room Zone - ID - Make & Model 7200 FCI Battery Size & Date 2-12v18ah 9/11 Local trouble sounder, lights, displays, buttons, and switches functional? Ground fault test Battery and charging circuit test: Panel-NAC Area - Location - Type - ID - N/A LED's functional Buttons and switches functional N/A Ground fault test Charging circuit normal? Battery load test? 2-12v8ah 12/15 Battery and charging circuit test: Panel-NAC Area - Location - Radio Type - ID - N/A LED's functional Buttons and switches functional N/A Ground fault test Charging circuit normal? Battery load test? 2-12v8ah 11/12 Battery and charging circuit test: Page 1 of 6

2 Smoke/Heat Combo File room Z Smoke/Heat Combo By conference room B Z Smoke/Heat Combo Lower level Z Pull Station at panel Z Pull Station at panel Z Pull Station area 7 Z Pull Station Plano store Z Pull Station engineering office exit dr Z Pull Station at shipping dock area dr 4 Z Pull Station at main entrance Z Pull Station at employee entrance Z Pull Station area 1 Z Pull Station area 1 West exit Z Pull Station area 2 Z Pull Station area 1 South exit Z Pull Station at engineering exit Z Audio - s 27 AVS/11 strobes Temperature Sensor Pump Room Z Temperature Sensor Area 7 East Wall Z Temperature Sensor Finishing Room Z Temperature Sensor Plano store storage Z Temperature Sensor Area 6 Warehouse Z Temperature Sensor Tool Room Z Temperature Sensor Area 4 Materials Office Z Temperature Sensor Front Office Z Temperature Sensor Area 2 East Z Temperature Sensor Area 2 by Riser Z Temperature Sensor area 1 Z Control Valve pump room Z Control Valve pump room Z Control Valve E riser area 7 Z Control Valve riser 5 area 4 in closet Z Control Valve area 2 riser 3/Outside Z Control Valve area 3 outside/main parking lo Z Control Valve riser 6/ Outisde PIV Z Control Valve riser 8/ Outside PIV Z Control Valve area 4 riser 5 Outside PIV Z Control Valve Bldg 5 Riser Z Control Valve Area 2 Riser 2/Outside Z Control Valve Area 2 Riser 1 Lube/Outside Z Page 2 of 6

3 Fire Pump - Running Fire Pump - Loss of Power Pump room Z57 Supv H/L Air Riser 2 Area 7 Z W-F Pressure area 7 Z WF-Vane building area 4 Z WF-Vane area 2 riser 2 Z WF-Vane building 4 area 3 Z WF-Vane building 5 Z WF-Vane building 6 Z WF-Vane building 7 Z WF-Vane area 2 riser 3 Z WF-Vane area 2 riser 1 Z WF Trip Delay Area - Location - building 6 Zone - Z64 ID - ** Time to alarm? WF Trip Delay Area - Location - building area 4 Zone - Z66 ID - * Time to alarm? 18 seconds WF Trip Delay Area - Location - area 2 riser 2 Zone - Z68 ID - * Time to alarm? 80 seconds WF Trip Delay Area - Location - building 4 area 3 Zone - Z67 ID - * Time to alarm? 90 seconds WF Trip Delay Area - Location - building 5 Zone - Z65 ID - * Time to alarm? 20 seconds WF Trip Delay Area - Location - building 7 Zone - Z61 ID - * Time to alarm? 90 seconds WF Trip Delay Area - Location - area 2 riser 3 Zone - Z69 ID - * Time to alarm? 53 seconds WF Trip Delay Area - Location - area 2 riser 1 Zone - Z60 ID - * Time to alarm? 43 seconds Smoke/Heat Combo 2nd Floor Upper level Z Smoke/Heat Combo 2nd Floor At sales Z Smoke/Heat Combo 2nd Floor At sales Z Smoke/Heat Combo 2nd Floor Marketing Z Smoke/Heat Combo 2nd Floor Marketing room Z Pull Station 2nd Floor at sales 2nd fl Z Smoke/Heat Combo Annual Bldg 4 Z Smoke/Heat Combo Annual Bldg 8 Z Smoke/Heat Combo Annual Bldg 6 Z Control Valve city pressure Pump room Z FAIL Temperature Sensor Office area Area 3 Eng Closet Z Page 3 of 6

4 Transmitter Section Area - Radio Location - Outside lunch rm west wall Transmitter Type? Radio Battery Size & Date 12v8ah 3/15 Fire Signal Received? Trouble Signal Received Supervisory Signal Received N/A Zone - ID - N/A Page 4 of 6

5 Inspection Discrepancies Mail To: Service At: Account # Plano Molding Co Plano Molding Company 431 E South St 431 E. South Street Plano, IL Plano, IL Audio - s Area - Location - 27 AVS/11 strobes Zone - ID - WF-Vane Area - Location - building area 4 Zone - Z66 ID blocked by product Smoke/Heat Combo Area - Annual Location - Bldg 4 Zone - Z4 ID Smoke/Heat Combo Area - Annual Location - Bldg 8 Zone - Z6 ID Smoke/Heat Combo Area - Annual Location - Bldg 6 Zone - Z5 ID Control Valve Area - city pressure Location - Pump room Zone - Z58 ID FAIL Page 5 of 6

6 Inspection Discrepancies FAIL No supervisor signal Summary of all Devices on Inspection Reference - FT Tested in accordance with NFPA 72. IL License Device Summary Test Type Total Count Pass Count Fail Count Not Tested Count Audio - s AV Control Valve CONTROL VALVE Fire Pump - Loss of Power FIRE PUMP - LOSS POW Fire Pump - Running FIRE PUMP - RUNNING Pull Station PULL STATION Smoke/Heat Combo COMBO SMOKE/HEAT Supv H/L Air SUPV H/L AIR Temperature Sensor TEMP SENSOR W-F Pressure WF-PRESSURE WF-Vane WF-VANE Totals Page 6 of 6

Alarm Detection Systems, Inc.

Alarm Detection Systems, Inc. Mail to: Service at Account: 25980 Little Rock-fox Fire Dept Plano Molding Company 5 EAST NORTH STREET 431 E. South Street PLANO, Illinois 60545 Plano, IL 60545 Test Type Summary Total Pass Fail Not Tested

More information

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604

More information

VSC Fire & Security, Inc.

VSC Fire & Security, Inc. JOB#: 12775876 VSC Fire & Security, Inc. 10640 Iron Bridge Road, Suite G Jessup MD 20794 (301) 575-1500 www.vscfs.com Important: Deficiencies, Comments and Explanations any FAIL or NEGATIVE responses are

More information

Final EC Inspection Report 03/2010

Final EC Inspection Report 03/2010 2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

USAutomatic Sprinkler Corporation

USAutomatic Sprinkler Corporation Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)

More information

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

Silent Knight Software Suite Intelliknight Training

Silent Knight Software Suite Intelliknight Training Silent Knight Software Suite Intelliknight Training Module 2 Summary of all the SBUS Modules and addressable points in your program System Add SBUS Module Left click, right click on Module Select Add 1

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION Underwriters Laboratories Inc. FIRE ALARM SYSTEM PRE-INSPECTION DATA SHEETS PLEASE RETURN COMPLETED FORMS TO UL PRIOR TO INSPECTION PROTECTED PROPERTY City: State: Zip Code: ALARM SERVICE COMPANY File

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

Class A and Expansion NAC Modules Installation Instructions

Class A and Expansion NAC Modules Installation Instructions Class A and Expansion NAC Modules Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1245 Flex Amplifier Expansion NAC (XNAC) 4100-1246

More information

TrueAlert Addressable Notification Appliances

TrueAlert Addressable Notification Appliances Fire Control ** IS NORMAL ** :0:pm Mon 9-Feb-9 SY S TE M AC SUPERVISORY TROUB LE SILENCED SUPV TROUBLE SILENCE RESET CONTROL DISC ON NEC T POW ER + V ZONE P WR + 0V ZONE P WR - +IDNE T IDC + - IDNE T IDC

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For

Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance For CarDon & Associates Fall Creek Health & Living Prepared by: L.Thompson/T.Roe 7/31/2014 Report Length:

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information

First Alert 1200C Installer Notes M. Leuck

First Alert 1200C Installer Notes M. Leuck First Alert 2C Installer Notes M. Leuck. Programming can done by standard keypads 2. Enter programming with Installer Code + 8 + + 3. Another method of entering programming: Power system down, then back

More information

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A $'(0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHP 8VHU*XLGH N7003V3 5/04 Rev A 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...5 Fire Protection...6 Burglary Protection...6 Alarms...6

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

Technical Manuals Online! - K4855V1 3/00 FA560 3 STAY B 1 OFF 2 AWAY 6 C D 5 TEST 9 CHIME # 8 CODE I I I I I I READY ARMED MAX

Technical Manuals Online! -   K4855V1 3/00 FA560 3 STAY B 1 OFF 2 AWAY 6 C D 5 TEST 9 CHIME # 8 CODE I I I I I I READY ARMED MAX ARMED MAX INSTANT READY READY R BYPASS R R )$& )$&&1 6HFXULW\6\VWHP A 1 OFF 2 AWAY 3 STAY B 4 5 TEST 6 C D 7 * FA560 8 CODE 0 9 CHIME # I I I I I I HEAT COOL BYPASS ACTIVE 8VHU*XLGH K4855V1 3/00 TABLE

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

SECTION 7 EVACUATION PROCEDURES

SECTION 7 EVACUATION PROCEDURES SECTION 7 EVACUATION PROCEDURES 7.1 Refinery Evacuation Procedure 2 7.1.1 Procedures for Operating Critical Equipment Prior to Evacuation 3 7.2 Sulfur Recovery Unit Evacuation Procedure 4 7.3 HF Alkylation

More information

Doc. No Part No Rev. U * T*

Doc. No Part No Rev. U * T* Doc. No. 430545 Part No. 579-357 Rev. U *0579357T* Blank Page- Back of Front Cover Copyrights and Trademarks 2005-2018 Johnson Controls. All rights reserved. Specifications and other information shown

More information

Wander Management Solutions

Wander Management Solutions Wander Management Solutions Products, LLC Universal Product Features: No on-board antenna in door panel, detection zones created by external receivers Individually tune each receiver directly from the

More information

QA16 Addressable Panel Programming Manual V3.07.3

QA16 Addressable Panel Programming Manual V3.07.3 QA6 Addressable Panel Programming Manual V.07.. User Reference Instruction Click HL Fire Tool v.07. to start the initial screen HL Fire Tool v.07. Type Address Location Name Module 4 Project Options At

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

User's Manual 5120XM N8031 6/96

User's Manual 5120XM N8031 6/96 Fire and Burglary System User's Manual 5120XM N8031 6/96 SYSTEM OVERVIEW...3 General...3 Zones...3 Fire & Emergency Protection...3 Burglary Protection...4 Alarms...4 Memory of Alarm...4 ABOUT THE KEYPADS...5

More information

Sprinkler Inspection Certificate

Sprinkler Inspection Certificate Sprinkler Inspection Certificate For New Dimensions High School 4900 Old Pleasant Hilll Road Kissimmee, FL 34746 Tested to NFPA 25 Standards This Inspection was performed in accordance with applicable

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

User's Manual. Safewatch Pro. N7229 6V1 Rev B 4/99

User's Manual. Safewatch Pro. N7229 6V1 Rev B 4/99 Security System User's Manual Safewatch Pro N7229 6V1 Rev B 4/99 IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every possible point of entry to a home

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Technical Manuals Online! - USER'S MANUAL

Technical Manuals Online! -   USER'S MANUAL USER'S MANUAL FA162C Security System N7527-1V2 Rev B 4/99 2 SYSTEM OVERVIEW... 4 General... 4 A Partitioned System... 4 Zones... 4 Burglary Protection... 5 Security Codes... 5 Fire Protection... 6 Alarms...

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800) The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B VISTA-32FBPT Commercial Fire and Burglary Partitioned Security Systems with Scheduling User Guide 800-11045 2/12 Rev. B 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...6

More information

VISTA-20SE/VISTA-20HWSE

VISTA-20SE/VISTA-20HWSE Security System User's Manual VISTA-20SE/VISTA-20HWSE N7527V2 6/97 2 SYSTEM OVERVIEW... 4 General... 4 A Partitioned System... 4 Zones... 4 Burglary Protection... 5 Security Codes... 5 Fire Protection...

More information

Opal TM AV Devices. Data Sheet. Benefits

Opal TM AV Devices. Data Sheet. Benefits Opal TM AV Devices Data Sheet Notifier s Opal AV (Audio Visual) range is designed to alert building occupants of an emergency. The Opal AV range of analogue addressable, loop powered, audible and visual

More information

Residential Fire Sprinkler Inspection

Residential Fire Sprinkler Inspection Residential Fire Sprinkler Inspection Hickory, NC 88.38.6363 Charleston, SC 843.78.08 Greensboro, NC 336.373.3973 Columbia, SC 803.99.00 Raleigh, NC 99.834.9644 Greenville, SC 864.458.7070 Charlotte, NC

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review Parry Sound District Social Services Administration Board Housing and Community Services October 10, 2018 c/o Andrew Ball, Properties and Capital Projects Coordinator Email:aball@psdssab.org 22A Belvedere

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98 USER'S GUIDE FA1220CV 2-Partition Security System N7003-1V2 7/98 SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Fire Protection... 4 Alarms... 5 Emergency

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805) Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including

More information

DUNCAN STUDENT CENTER. Emergency Action Plan

DUNCAN STUDENT CENTER. Emergency Action Plan DUNCAN STUDENT CENTER Emergency Action Plan August 21, 2017 DUNCAN STUDENT CENTER - EMERGENCY ACTION PLAN An emergency action plan describes the actions employees should take in case of fire or other emergency

More information

FIRE ALARM SYSTEM INSPECTION

FIRE ALARM SYSTEM INSPECTION 13555 Wellington Center Circle Suite 123 Gainesville, VA 20155 T: 1-888-883-2867 F: 703-468-6070 www.vectorsecurity.com FIRE ALARM SYSTEM INSPECTION Upon arrival, contact Vector Security Service Dept.

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Lehi High School Emergency Plan

Lehi High School Emergency Plan Lehi High School Emergency Plan POWER OUTAGE In the event of an extended power outage, please have the students in your classroom remain with you during the entire outage. We will not change classes on

More information

Property Name & Address [ Property Name ] - [ Property Address ]

Property Name & Address [ Property Name ] - [ Property Address ] Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Patrick County Horizons Jeb Stuart Hwy. Stuart, Va

Patrick County Horizons Jeb Stuart Hwy. Stuart, Va Patrick County Horizons 24141 Jeb Stuart Hwy. Stuart, Va. 24171 Emergency Preparedness Plan Severe Weather/Earthquake/Building Damage/Fire/Missing Person Policy: Per page 22 of the PCS licensure manual:

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only) 2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R-3.1

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

L-Series, Emergency Communication Devices

L-Series, Emergency Communication Devices Notification Appliances L-Series, Emergency Communication Devices Description The L-Series Emergency Communications devices and accessories combine application versatility with all of the same time-saving

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant

More information

ABOUT THE CONSOLES A CONSOLES STYLE CONSOLES (SHOWN WITH KEYPAD COVER REMOVED) 5137AD ALPHA CONSOLE 6139 ALPHA CONSOLE 4127 4137AD 612716120 6137 FIXED-WORD CONSOLES FIXED-WORD CONSOLES FUNCTIONS OF THE

More information

Facilities Management

Facilities Management Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction

More information

Technical Bulletin Bulletin Number: 2012_02 Released: 1 st May 2012

Technical Bulletin Bulletin Number: 2012_02 Released: 1 st May 2012 RX / QX V4.51 and PX V5.00 UTC Climate, Controls and Security Systems is pleased to announce the release of Version 4.51 for the RX / QX (Grade 2) control panels, and Version 5.00 for the PX (Grade 3)

More information

Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification

Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification In order to successfully pass the inspection, your property will need to meet all regulations mandated by the state and municipality.

More information

ELECTRONIC SOUNDER STROBE Model : AVD-C407

ELECTRONIC SOUNDER STROBE Model : AVD-C407 ELECTRONIC SOUNDER STROBE Model : AVD-C407 MULTRON range of combination Electronic Sounders with Strobe Lights are designed to complement our Fire Alarm products both technically and aesthetically as an

More information

RE6100 Series Helix Security and Automation Platform

RE6100 Series Helix Security and Automation Platform CONFIGURATION Resolution Compatibles RE6100 Series Helix Security and Automation Platform C G UI D E Configuration Settings Table 1 - Panel Settings Table 2 - Zone Settings Table 3 - Device Settings Table

More information

Fire Command Center. XR2400F User s Guide

Fire Command Center. XR2400F User s Guide Fire Command Center XR2400F User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm. 1. Turn the keyswitch to enable

More information

Opal TM AV Devices. Data Sheet. Benefits

Opal TM AV Devices. Data Sheet. Benefits Opal TM AV Devices Data Sheet Notifier s Opal AV (Audio Visual) range is designed to alert building occupants of an emergency. The Opal AV range of analogue addressable, loop powered, audible and visual

More information

TULANE UNIVERSITY EMERGENCY ACTION PLAN

TULANE UNIVERSITY EMERGENCY ACTION PLAN TULANE UNIVERSITY EMERGENCY ACTION PLAN This is the Emergency Action Plan developed by Tulane University applicable for the prescribed building and department. It has been designed to assist personnel

More information

Emergency Evacuation Plan

Emergency Evacuation Plan Emergency Evacuation Plan Scope and Applicability This procedure applies to a wide variety of emergencies both man-made and natural which may require a workplace to be evacuated. These emergencies include

More information

Emergency Evacuation Routes and Meeting Locations

Emergency Evacuation Routes and Meeting Locations Emergency Evacuation Routes and Meeting Locations Alarms In the event of an fire alarm, all occupants shall evacuate the immediate area. EVACUATE if the fire audible alarms are activated Unless informed

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

The complete conventional fire warning system

The complete conventional fire warning system The complete conventional fire warning system www.espuk.com MAG2P 2 Zone Fire Panel 2 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call

More information

EMERGENCY RESPONSE PLAN MANUAL. Nursing

EMERGENCY RESPONSE PLAN MANUAL. Nursing EMERGENCY RESPONSE PLAN MANUAL INDIANA STATE UNIVERSITY Nursing PAGE 2 TABLE OF CONTENTS BUILDING COORDINATOR 3 RESPONSE TEAM MEMBERS 3 NOTIFICATION 3 EVACUATION 4 ASSEMBLY POINTS 5 DISABLED SAFE AREAS

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

2012 SunTrust Center ERT Annual Review. 919 East Main St. Richmond, VA

2012 SunTrust Center ERT Annual Review. 919 East Main St. Richmond, VA 2012 SunTrust Center ERT Annual Review 919 East Main St. Richmond, VA 1 & 2 Purpose of Emergency Response Program Emergency Response Team, Members and Responsibilities Evacuation Procedures Other Emergency

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

MMX TM. Intelligent Fire Alarm Network. User Guide

MMX TM. Intelligent Fire Alarm Network. User Guide MMX TM Intelligent Fire Alarm Network User Guide LT-893SEC Rev 1 May 2017 MMX TM User Guide Table of Contents Introduction... 1 About this Manual... 1 Front Panel Indicators, Controls, and Operation...

More information