1 Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Inspection Date Oct 10, 2016 Contact: Steve Walters Title: Site Manager Company: Fire & Life Safety America, Inc. - Charlotte Contact: Devon R. Haggerty Title: Inspector
2 Executive Summary Building Information Contact: Steve Walters Address: 757 S. Anderson Rd Phone: Address: City/State/Zip: Rock Hill, AC Country: United States of America Inspection Performed By Company: Fire & Life Safety America, Inc. - Charlotte Fax: Mobile: steve.walters@cityofrockhill.com Inspector: Devon R. Haggerty Address: 812 Biscayne Drive Phone: Address: City/State/Zip: Concord, NC Fax: Mobile: Country: United States of America System Control Unit drhaggerty@flsamerica.com Manufacturer: Siemens Inspection Date: 10/07/2016 IDC Style: Model Number: fire finder Install Date: 07/08/2014 SLC Style: Software Version: Version Date: 10/07/2014 NAC Style: Location: 1st Siemens panel Monitoring Current Protection: Company: Phone: Account #: Central Station Signal Verification Type: Mfg: Model #: Test Time/Date: Restore Time Fire & Life Safety America, Inc. - Charlotte 1 06/06/2017
3 Inspection Summary Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty % Sound Test % % 0 0% % Initiating % % % % Control % % % 0 0% Totals % % % % Certification Company: Fire & Life Safety America, Inc. - Charlotte Inspector: Devon R. Haggerty Contact: Steve Walters Signed: Devon R. Haggerty Certification Type Signed: Number NICET Inspection and Testing of Water-Based Systems Level II North Carolina Certified Backflow Assembly Tester 1172-cm-1077 North Carolina Fire Sprinkler Inspection Technician Fire & Life Safety America, Inc. - Charlotte 2 06/06/2017
4 Discrepancy Report Control Panel: 1 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer Product Safety Commission's website and is subject to a recall by the manufacturer is included. Device Type Manufacturer ModelNumber Date Qty Items listed for Recall by Manufacturer No recalled items found during this inspection. ScanID Location Problem Address Reference Pull Station Initiating car wash Failed to Report 1 NFPA (B) and gas station 105 Failed to Report 1 NFPA (B) and gas station 105 Failed to Report 1 NFPA (B) NFPA (B) and Code References System defects and malfunctions shall be corrected. and Inspection, testing, and maintenance programs shall satisfy the requirements of this Code, shall conform to the equipment manufacturer's recommendations, and shall verify correct operation of the fire alarm system. Fire & Life Safety America, Inc. - Charlotte 3 06/06/2017
5 Control Panel: n/a The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer Product Safety Commission's website and is subject to a recall by the manufacturer is included. Device Type Manufacturer ModelNumber Date Qty Items listed for Recall by Manufacturer No recalled items found during this inspection. Sound Test Location Problem Device Reference Sound Testing Sound Test Location Problem Device Reference Sound Test Points 0001 car wash and gas pumps see note Sound Test Fire & Life Safety America, Inc. - Charlotte 4 06/06/2017
6 Proposed Solutions Report Control Panel: 1 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis. ScanID Location Solution Model # Cost Fix Pull Station Initiating car wash Investigate T/M gas station 105 Investigate T/M gas station 105 Investigate T/M Fire & Life Safety America, Inc. - Charlotte 5 06/06/2017
7 Control Panel: n/a The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis. ScanID Location Solution Description Cost Fix Sound Test Sound Testing 0001 car wash and gas pumps T/M Fire & Life Safety America, Inc. - Charlotte 6 06/06/2017
8 Notes & Recommendations Control Panel: n/a The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category. ScanID Note Device Type Location Comment Sound Test car wash and gas pumps see note Car wash and gas station did not function correctly Fire & Life Safety America, Inc. - Charlotte 7 06/06/2017
9 Inspection & Testing Control Panel: 1 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date Control Passed Battery 1st Fire finder panel Tested 11:39:47 AM 10/07/2016 Battery 1st Fire finder panel Tested 11:39:50 AM 10/07/2016 Battery 1st Siemens panel Tested 11:39:39 AM 10/07/2016 Battery 1st Siemens panel Tested 11:39:42 AM 10/07/2016 Battery 1st Upper Cornell panel Tested 11:40:31 AM 10/07/2016 Battery 1st Upper Cornell panel Tested 11:40:33 AM 10/07/2016 Battery 1st 102 room 523 Tested 11:41:17 AM 10/07/2016 Battery 1st 102 room 523 Tested 11:41:26 AM 10/07/2016 Battery 1st 102 switch gear room Tested 11:42:27 AM 10/07/2016 Battery 1st 102 switch gear room Siemens panel Tested 11:42:34 AM 10/07/2016 Initiating Duct Detector 1st Shops 330 Tested 8:34:24 AM 10/07/2016 Duct Detector 1st Shops 330 Tested 8:34:33 AM 10/07/2016 Duct Detector 1st warehouse mezzanine Shops 330 Tested 9:49:54 AM 10/07/2016 Duct Detector 2nd mechanical 244 Tested 9:22:50 AM 10/07/2016 Duct Detector 2nd mechanical 244 Tested 9:23:19 AM 10/07/2016 Duct Detector 2nd mechanical 244 Tested 9:23:35 AM 10/07/2016 Heat Detector 2nd Computer room Tested 9:18:10 AM 10/07/2016 Heat Detector 2nd Computer room Tested 9:18:14 AM 10/07/2016 Pull Station 1st Exit door Tested 8:52:58 AM 10/07/2016 Pull Station 1st Exit door front lobby Tested 9:02:56 AM 10/07/2016 Pull Station 1st Exit door front lobby Tested 9:03:57 AM 10/07/2016 Pull Station 1st Exit door meeting room Tested 9:09:18 AM 10/07/2016 Pull Station 1st Exit door rear lobby Tested 9:12:01 AM 10/07/2016 Pull Station 1st Lower stair well Tested 8:54:11 AM 10/07/2016 Pull Station 1st Shops 330 Tested 8:35:31 AM 10/07/2016 Pull Station 1st Shops 331 Tested 8:43:46 AM 10/07/2016 Pull Station 1st Shops 341 Tested 8:42:46 AM 10/07/2016 Pull Station 1st Shops 342 Tested 8:41:10 AM 10/07/2016 Pull Station 1st Shops 342 Tested 8:41:15 AM 10/07/2016 Pull Station 1st Shops 357 Tested 8:38:58 AM 10/07/2016 Pull Station 1st Shops 361 Tested 8:48:09 AM 10/07/2016 Pull Station 1st 102 garage Tested 11:43:13 AM 10/07/2016 Pull Station 1st 102 garage Exit door Tested 9:54:11 AM 10/07/2016 Pull Station 1st 102 garage Exit door Tested 11:43:11 AM 10/07/2016 Pull Station 1st 102 garage office Exit door Tested 11:42:22 AM 10/07/2016 Pull Station 1st 102 public works fab shop Exit door front lobby Tested 11:43:00 AM 10/07/2016 Fire & Life Safety America, Inc. - Charlotte 8 06/06/2017
10 Device Type Location Service Time Date Passed Pull Station 1st 102 public works fab shop Exit door front Tested 11:43:03 AM 10/07/2016 lobby Pull Station 1st 102 storage Tested 9:44:30 AM 10/07/2016 Pull Station 1st 102 warehouse Tested 9:45:40 AM 10/07/2016 Pull Station 1st 102 warehouse Tested 9:46:50 AM 10/07/2016 Pull Station 1st 102 warehouse Tested 9:47:21 AM 10/07/2016 Pull Station 1st purchase area Tested 11:41:32 AM 10/07/2016 Pull Station 1st shops building near 326 Exit door Tested 8:21:43 AM 10/07/2016 Pull Station 1st shops building near facp Exit door Tested 8:19:11 AM 10/07/2016 Pull Station 1st warehouse Tested 9:40:38 AM 10/07/2016 Pull Station 1st warehouse Tested 9:41:42 AM 10/07/2016 Pull Station 1st warehouse Tested 9:42:23 AM 10/07/2016 Pull Station 1st warehouse Tested 9:43:16 AM 10/07/2016 Pull Station 2nd Top of stairwell 1 Tested 9:16:23 AM 10/07/2016 Pull Station 2nd Top of stairwell 2 Tested 9:29:05 AM 10/07/2016 Smoke Detector 1st 1 st floor evelator Tested 9:00:35 AM 10/07/2016 Smoke Detector 1st Panel smoke Tested 9:02:25 AM 10/07/2016 Smoke Detector 1st 102 room 523 Tested 11:41:23 AM 10/07/2016 Smoke Detector 1st 102 switch gear room 1 st floor evelator Tested 11:42:49 AM 10/07/2016 Smoke Detector 2nd 2nd floor evelator Tested 9:14:38 AM 10/07/2016 Device Type Location Service Time Date Failed/Other Initiating Pull Station car wash Tested 11:43:29 AM 10/07/2016 Pull Station gas station 105 Tested 11:44:06 AM 10/07/2016 Pull Station gas station 105 Tested 11:44:22 AM 10/07/2016 Fire & Life Safety America, Inc. - Charlotte 9 06/06/2017
11 Control Panel: 2 - Siemens fire finder The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date Device Type Location Service Time Date Passed Control Control Panel 1st Siemens panel Tested 11:40:28 AM 10/07/2016 Fire & Life Safety America, Inc. - Charlotte 10 06/06/2017
12 Control Panel: 3 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date Device Type Location Service Time Date Passed Control Annunciator 1st main entrance Tested 8:19:13 AM 10/10/2016 Battery 1st electrical 361 Tested 8:17:46 AM 10/10/2016 Battery 1st electrical 361 Tested 8:18:32 AM 10/10/2016 Battery car wash Tested 8:18:42 AM 10/10/2016 Battery car wash Tested 8:19:02 AM 10/10/2016 Power Supply 1st electrical 361 Tested 8:17:18 AM 10/10/2016 Power Supply 1st Siemens panel Tested 11:40:25 AM 10/07/2016 Power Supply 1st 102 em 523 Tested 11:41:20 AM 10/07/2016 Power Supply 1st 102 switch gear room Tested 11:42:54 AM 10/07/2016 Power Supply car wash Tested 8:16:38 AM 10/10/2016 Initiating Heat Detector 1st elevator room Tested 8:20:29 AM 10/10/2016 Pull Station 1st meeting room Tested 8:20:45 AM 10/10/2016 Smoke Detector 1st elevator room Tested 8:20:02 AM 10/10/2016 Smoke Detector 1st main entrance Tested 8:19:47 AM 10/10/2016 Fire & Life Safety America, Inc. - Charlotte 11 06/06/2017
13 Service Summary The Service Summary section provides an overview of the services performed in this report. Device Type Service Quantity Failed/Other Pull Station Tested 3 Total 3 Passed Annunciator Tested 1 Battery Tested 14 Control Panel Tested 1 Duct Detector Tested 6 Heat Detector Tested 3 Power Supply Tested 5 Pull Station Tested 33 Smoke Detector Tested 7 Total 70 Fire & Life Safety America, Inc. - Charlotte 12 06/06/2017
14 Auxiliary Functions Testing Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated. Type Location Comment ScanID Simulated Duct Detector Passed Air Duct 2nd mechanical 244 Passed Heat Detector Pre-Action System 2nd Computer room Passed Pre-Action System 2nd Computer room Passed Fire & Life Safety America, Inc. - Charlotte 13 06/06/2017
15 Sound and Visual Testing The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report. Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded. Location Sound Test Points Comment Failed/Other Ambient db Alarm db Intelligibility Voice STI Sound car wash and gas pumps see note 0001 Test Fire & Life Safety America, Inc. - Charlotte 14 06/06/2017
16 Battery & Power Supply Testing Control Panel: 3 The Control & Power Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Battery Sealed Lead Acid 1st electrical Sealed Lead Acid 1st electrical Sealed Lead Acid car wash 7 12 Sealed Lead Acid car wash 7 12 Fire & Life Safety America, Inc. - Charlotte 15 06/06/2017
17 Inventory & Warranty Report Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Device or Item Category % of Inventory Quantity Pull Station Initiating 48.65% 36 Duct Detector Initiating 8.11% 6 Smoke Detector Initiating 9.46% 7 Heat Detector Initiating 4.05% 3 Battery Control 18.92% 14 Power Supply Control 6.76% 5 Control Panel Control 1.35% 1 Annunciator Control 1.35% 1 Type Qty Model # Description Install Date In Service - 2 Years to 3 Years Battery 2 Sealed Lead Acid 10/07/2014 Heat Detector 2 Fixed Temperature 10/07/2014 Pull Station 7 10/07/2014 Power-Sonic Battery 2 Sealed Lead Acid 10/07/2014 Siemens Duct Detector 4 AD2-P 10/07/2014 Duct Detector 2 AD2-P Photoelectric 10/07/2014 Pull Station 28 HMS-D Single Action 10/07/2014 Smoke Detector 5 HMS-D 10/07/2014 Battery 6 Sealed Lead Acid 07/08/2014 Fire & Life Safety America, Inc. - Charlotte 16 06/06/2017
18 Control Panel: 2 - Siemens fire finder The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Type Qty Model # Description Install Date Siemens In Service - 2 Years to 3 Years Control Panel 1 fire finder 07/08/2014 Fire & Life Safety America, Inc. - Charlotte 17 06/06/2017
19 Control Panel: 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Type Qty Model # Description Install Date Siemens In Service - 2 Years to 3 Years Annunciator 1 07/08/2014 Battery 4 pad-3 Sealed Lead Acid 07/08/2014 Heat Detector 1 07/08/2014 Power Supply 5 pad-3 07/08/2014 Pull Station 1 Dual Action 07/08/2014 Smoke Detector 2 07/08/2014 Fire & Life Safety America, Inc. - Charlotte 18 06/06/2017
Fire Alarm and Life Safety System Inspection Certificate
www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance
More informationSprinkler Inspection Certificate
Sprinkler Inspection Certificate For New Dimensions High School 4900 Old Pleasant Hilll Road Kissimmee, FL 34746 Tested to NFPA 25 Standards This Inspection was performed in accordance with applicable
More informationPURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE
PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE 100 West Washington Street, Room 320 Hagerstown, MD 21740-4748 P: 240.313.2330 F: 240.313.2331 www.washco-md.net PUR-1331 ADDENDUM NO. 3 NOTICE TO PROSPECTIVE
More informationSecurityScan Inspection Certificate
SecurityScan Inspection Certificate For Sample Inspection Report 123 Main Street Kalamazoo, MI 49007 Tested to applicable Standards This Inspection was performed in accordance with applicable Standards.
More information109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:
109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationFire Alarm System Inspection and Testing Report
Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationSkilled Healthcare Documentation Requirements Life Safety and Fire Protection
DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationBuilding Name: Our Lady of Sorrows Date: July 10, 2013
1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationData Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
More informationInspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY
FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:
More informationFire Alarm Testing and Inspection Report
Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationLifeAlarm Fire Alarm Control Panels
LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationConventional Releasing Control Panel
s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationUnified Fire Authority - Fire Prevention Bureau
Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationINSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital
More information2018 NICET Code Transition Changes
2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationNFPA Changes
Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function
More informationIntelligent Detection Devices
Intelligent Detection Devices Multi-Criteria Fire Detector [with ASAtechnology TM ] Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena
More informationDIVISION 28 ELECTRONIC SAFETY AND SECURITY
281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationFinal EC Inspection Report 03/2010
2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationResidential Fire Sprinkler Inspection
Residential Fire Sprinkler Inspection Hickory, NC 88.38.6363 Charleston, SC 843.78.08 Greensboro, NC 336.373.3973 Columbia, SC 803.99.00 Raleigh, NC 99.834.9644 Greenville, SC 864.458.7070 Charlotte, NC
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationStandard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment
NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document
More informationCOMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.
4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationNFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities
Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing
More informationFIRE ALARM SYSTEM INSPECTION
13555 Wellington Center Circle Suite 123 Gainesville, VA 20155 T: 1-888-883-2867 F: 703-468-6070 www.vectorsecurity.com FIRE ALARM SYSTEM INSPECTION Upon arrival, contact Vector Security Service Dept.
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationMichigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE
PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationFireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
More informationTechnician Tools CAN/ULC-S CAN/ULC-S537-13
September 21 2016 Edmonton, AB Technician Tools CAN/ULC-S536-13 CAN/ULC-S537-13 Presented By: Mark Wilson Disclaimer The following presentation is in no way affiliated with, or presented on behalf of any
More informationSilent Knight Software Suite Intelliknight Training
Silent Knight Software Suite Intelliknight Training Module 2 Summary of all the SBUS Modules and addressable points in your program System Add SBUS Module Left click, right click on Module Select Add 1
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationFire alarm system specification for multiple tenant retail buildings
Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:
More informationIntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide
IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationThe 2013 National Fire Alarm and Signaling Code
ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to
More information1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.
PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and
More informationModel OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors
Intelligent Detection Devices Multi-Criteria Fire / CO Detector [with ASAtechnology TM ] ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors
More informationFire - Rescue. November 2016
Fire - Rescue Fire Alarm and Central Station Monitoring Plan Submittal Guidelines November 2016 Plan Submittal Guidelines are provided based on the 2015 International Fire Code, Policies, and Local Amendments.
More informationVentura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department
Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA 93010 Purchasing Department TO: All Jobwalk Attendees July 19, 2018 FROM: Janice Kisch, Purchasing
More informationCase Study Media Contact Beth Welch, or
Case Study Media Contact Beth Welch, 203-484-6202 or beth.welch@honeywell.com LEXUS DEALER PURSUES FIRE PROTECTION PERFECTION Lexus of North Miami is a Florida-based, high-end auto retailer offering an
More informationSTATE OF NORTH CAROLINA
STATE OF NORTH CAROLINA DEPARTMENT OF ADMINISTRATION STATE CONSTRUCTION OFFICE Fire Alarm GUIDELINES AND POLICIES 2011 Instruction to Designers: 1. Designers for State projects involving fire alarm systems
More informationAUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS
AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS Building stairwell and vestibule pressurization systems must be retested and recertified
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationADDENDUM No. 3 BID NO TRANSMISSION WAREHOUSE OFFICE REMODEL
205 E. 28 th St. P.O. Box 1000 Bryan, TX 77805 Phone: 979-821-5860 FAX: 979-821-5747 http://www.btutilities.com September 15, 2015 ADDENDUM No. 3 BID NO. 150-11-15 TRANSMISSION WAREHOUSE OFFICE
More informationAlarm Detection Systems, Inc.
Mail to: Service at Account: 25980 Little Rock-fox Fire Dept Plano Molding Company 5 EAST NORTH STREET 431 E. South Street PLANO, Illinois 60545 Plano, IL 60545 Test Type Summary Total Pass Fail Not Tested
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report
More informationNYC Department of Education
Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More information2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014
2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles
More informationElevator Emergency Equipment Instructor s Guide
Table of Contents Overview.......4 Sensory Inspection 11 Emergency Equipment in Elevator Systems..14 Fire Service Phase I & II 24 Summary..35 1 Icons Used In This Guide Agenda Topic # Topic Title Duration
More informationICC CODE CORNER 2015 International Fire Code
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS PART THREE 907.2.12 Special Amusement Buildings 907.2.12 Special amusement buildings. An automatic smoke detection system shall be provided in special amusement
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical
More informationAND ARCHITECT SPECIFICATIONS
PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification
More informationMS Rev. 2/DACT-UD: Intelligent Addressable FACP with Optional 2nd Loop
MS-9600 Rev. 2/DACT-UD: Intelligent Addressable FACP with Optional 2nd Loop DF-52395:A A1-90 Addressable General The Fire Lite MS-9600 is a compact, cost-effective, intelligent addressable fire alarm control
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationVSC Fire & Security, Inc.
JOB#: 12775876 VSC Fire & Security, Inc. 10640 Iron Bridge Road, Suite G Jessup MD 20794 (301) 575-1500 www.vscfs.com Important: Deficiencies, Comments and Explanations any FAIL or NEGATIVE responses are
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More information