VSC Fire & Security, Inc.
|
|
- Madlyn Shepherd
- 5 years ago
- Views:
Transcription
1 JOB#: VSC Fire & Security, Inc Iron Bridge Road, Suite G Jessup MD (301) Important: Deficiencies, Comments and Explanations any FAIL or NEGATIVE responses are indicated on the Work Acknowledgement attachment for this Service and/or Inspection. Frequency: Annual Inspection/Test: Fire Protection Systems Inspection Technician's Name: In Accordance With: Inspection Date: James Ivison, Anthony Ivison 7/10/17 Applicable NFPA, State and Local Codes and Standards Site and Billing Information Site Name, Account Number and Inspection Contract #: Site Address: 5701 Grosvenor Lane Owner/Customer Name: Bethesda Montgomery County Public Schools Billing Address: 8301 Turkey Thicket Dr Bldg A 1st Floor Contact Name: Patrick Schmidt Phone: Notifications MD notes 01088M0036 Gaithersburg (301) MD Patrick_M_Schmidt@mcpsmd.org Note: If checked this test/service does not involve disabling a Fire Alarm System and/or notifying a monitoring service. Date(s) put on test: 7/10/17 Time(s) put on test: 6am Date(s) restored: 7/10/17 Time(s) restored: 10am Operator 3831&3849 Monitoring Company and Operator Name(s) notified test and restoral: Name(s) Owner, Owner's Rep, Building Occupants and/or Tenants who were notified test, restoral and deficiencies: Building Services Local Emergency Services, AHJ or Insurance Representatives notified test, restoral or any impairments, if required: Montgomery County Fire and Rescue Comments regarding any known adverse conditions noted on Fire Protection System(s) existing prior to this inspection and test: FACP Normal upon arrival Comments regarding restoral, or conditions which preclude full restoral, Fire Protection System: FACP Normal upon departure
2 Monitoring Entity / Communication Signal Test Agency Name: ARK Phone #: Service Type: Phone Line Monitoring Agency verify sig received? Comm. Panel and components in service, free from damage? Operator ID #/Name, who verified receipt signals: Signal transmitted/received properly? Trouble signal tested this inspection? Time Sig Transmitted: Time Agency Received: Supervisory signal tested this inspection? Time Sig Transmitted: Time Agency Received: Alarm signal tested this inspection? Time Sig Transmitted: Time Agency Received:
3 Alarm System Panels Panel Information, Inspection and Test ID #/Area/Location Make FACP Building Service Manager Office Silent Knight Stware Revision 5820XL Revision Date 15.2 Panel Use Main FACP S/N Type System 04/16/2015 Visual Inspect Addressable Functional Test Power Supply Information Primary Power Supply Nominal Voltage 120 Overcurrent Protection Type Secondary Battery Power Supply Amp Rating 3 Battery Type Overcurrent Protection Rated Amps 2 Breaker Quantity Voltage Rating Overcurrent Protection Location (Panel #) Unknown Install Date Disconnecting Means Location (Breaker #) Unknown Discharge Test Amp Hour Rating 12 11/28/ Load Test Batt Charger Test Secondary Generator Power Supply or Emergency Power Supply System Emergency Standby Power Supply System, other than battery or dedicated generator secondary power supply? If yes, indicate which type Alarm System Panels Panel Information, Inspection and Test ID #/Area/Location Panel Use Make Stware Revision S/N Revision Date Type System Functional Test Visual Inspect Power Supply Information Primary Power Supply Nominal Voltage Amp Rating Secondary Battery Power Supply Battery Type Quantity Overcurrent Protection Type Overcurrent Protection Rated Amps Voltage Rating Amp Hour Rating Overcurrent Protection Location (Panel #) Install Date Load Test Disconnecting Means Location (Breaker #) Discharge Test Batt Charger Test Secondary Generator Power Supply or Emergency Power Supply System Emergency Standby Power Supply System, other than battery or dedicated generator secondary power supply? If yes, indicate which type
4 Supplementary Fire Alarm System Battery List (Additional batteries which are not previously listed on attached Panel Forms) Panel Type Battery Type Volt Rating Visual/Charge/Load Amp Install Date Rating Pass Fail N/A BPS in Boiler Room x2 NAC Booster Panel BPS in Stage Wire Closet x2 NAC Booster Panel EVS in Stage Wire Closet x2 Power Expander BPS in Wire Closet by BSM Office x2 NAC Booster Panel EVS in Wire Closet by BSM Office x2 Power Expander Dialer in Boiler Room Monitoring Panel
5 Supplementary Equipment List MAIN ENTRANCE Type Annunciator Panel
6 SMOKE DETECTION DEVICE INSPECTION AND TEST Note: Smoke Detection Device Sensitivity Testing performed only on a contracted basis at the frequency determined by the Customer/Building Owner. It is the Customer's/Building Owner's responsibility to have these services performed in accordance with your State and Local requirements, and the applicable version the NFPA 72 Standard. For more information, and to arrange Sensitivity Testing your Smoke Detection Devices, please call VSC Fire & Security, Inc. SMOKE DETECTION SENSITIVITY TEST LAST PERFORMED: Zone / Address ID# / Area / Location SMOKE DETECTION SENSITIVITY TEST PERFORMED THIS INSPECTION: Device Type M33:S001 Health Room M33:S002 Stage AHU 1 Supply Duct Smoke- M33:S003 Stage AHU 1 Return Duct Smoke- M33:S004 Stage AHU 2 Supply Duct Smoke- M33:S005 Stage AHU 2 Return Duct Smoke- M33:S006 Stage Wire Closet M33:S008 Fire door ZN 1/2 M33:S009 Fire door ZN 1/2 M33:S010 FACP Building Service Manager Office M33:S011 Fire door M33:S012 Fire door M33:S013 Wire Closet M33:S014 Fire door ZN2/3 M33:S015 Fire door ZN2/3 M33:S016 Main Entrance Sensitivity Range Test Value (if (if applicable) appl.)
7 Initiating Device List Zone or Address Device Type ML-796 ML-796 ML-761 ML-761 ML-917 ML-917 ML-736 ML-736 ML-791 ML-791 ML-797 ML-797 ML-462 ML-462 ML-763 ML-763 ML-794 ML-794 ML-795 M3:015 ML-795 ML-944 ML-944 ML-792 ML-792 MO-798 MO-798 MO-132 MO-132 MO-146 MO-146 MO-039 MO-039 MO-168 MO-168 M33:001 Corridor Exit by Classroom 3 M33:002 Classroom 3 M33:003 Main Entrance M33:004 Main Office
8 Initiating Device List Zone or Address Device Type M33:008 Multi-Purpose Room M33:009 Multi-Purpose Room M33:010 Kitchen Exit M33:011 Boiler Room Exit M33:019 Classroom 13 M33:020 Classroom 14 Exit M33:021 Corridor Exit by Classroom 14 M33:022 Corridor Exit by Library M33:024 Corridor Exit by Classroom 16 M33:025 Corridor Exit by Classroom 20 Portable B3 Restrooms (girls) Portable B3 Restrooms (girls) Portable B3 Restrooms (boys) Portable B3 Restrooms (boys) M33:S007 Boiler Room Carbon Monoxide Detector
9 Audible/Visual Appliance List Type B03 Restrooms Horn/ BO3 Restrooms Horn/ ML-791 Horn/ ML-797 Horn/ ML-761 Horn/ ML-917 Horn/ ML-944 Horn/ ML-462 Horn/ ML-763 Horn/ M0-039 Horn/ ML-794 Horn/ ML-795 Horn/ M Horn/ M0-146 Horn/ M0-798 Horn/ MO-132 Horn/
10 Audible/Visual Appliance List Type
11 Audible/Visual Appliance List Type
INSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital
More information109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:
109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr
More informationFire Alarm Testing and Inspection Report
Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL
More informationInspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY
FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:
More informationFIRE ALARM SYSTEM INSPECTION
13555 Wellington Center Circle Suite 123 Gainesville, VA 20155 T: 1-888-883-2867 F: 703-468-6070 www.vectorsecurity.com FIRE ALARM SYSTEM INSPECTION Upon arrival, contact Vector Security Service Dept.
More informationFacilities Management
Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationIdaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)
Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General
More informationFire Alarm System Inspection and Testing Report
Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local
More informationBuilding Name: Our Lady of Sorrows Date: July 10, 2013
1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable
More informationThe 2013 National Fire Alarm and Signaling Code
ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to
More informationVentura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department
Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA 93010 Purchasing Department TO: All Jobwalk Attendees July 19, 2018 FROM: Janice Kisch, Purchasing
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationInstallation Guide for AL800UL-ADA. NAC Power Extender. Rev
Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA
More informationUnified Fire Authority - Fire Prevention Bureau
Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance
More informationFire Alarm and Life Safety System Inspection Certificate
www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationLifeAlarm Fire Alarm Control Panels
LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient
More informationSeptember 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal
M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and
More informationAL800ULADA. NAC Power Extender. Installation Guide
AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery
More informationSkilled Healthcare Documentation Requirements Life Safety and Fire Protection
DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required
More information1111 Church Road Aurora, IL Tel: Fax: Web:www.adsalarm.com
Mail To: Service At: Account # - 25980 Plano Molding Co Plano Molding Company 431 E South St 431 E. South Street Plano, IL 60545 Plano, IL 60545 Tested in accordance with NFPA 72. IL License 127-000143.
More informationAlarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)
4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)
More informationFire Alarm, Water Flow Alarm & Signaling Systems
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving
More informationFire alarm system specification for multiple tenant retail buildings
Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationFMR Installation Instructions. Addressable Fire System Controller
FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3
More informationSECTION ADDRESSABLE FIRE ALARM SYSTEM
SECTION 16720 - ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationUpdate all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationAppendix B. Facilities Assessment Report
Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates
More informationPURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE
PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE 100 West Washington Street, Room 320 Hagerstown, MD 21740-4748 P: 240.313.2330 F: 240.313.2331 www.washco-md.net PUR-1331 ADDENDUM NO. 3 NOTICE TO PROSPECTIVE
More informationFIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL
FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii
More informationSECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101
More informationAL600ULADA. NAC Power Extender. Installation Guide
AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationCirculation Report for SIG-TMS Comments Document # 72
1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15
More informationUSAutomatic Sprinkler Corporation
Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationFire - Rescue. November 2016
Fire - Rescue Fire Alarm and Central Station Monitoring Plan Submittal Guidelines November 2016 Plan Submittal Guidelines are provided based on the 2015 International Fire Code, Policies, and Local Amendments.
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationMemphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.
Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency
More informationFamily Foster Home Fire Safety Evaluation Checklist Instructions
Family Foster Home Fire Safety Evaluation Checklist Instructions Please read these instructions prior to commencing your inspection. This checklist is provided to specific Foster Family Homes for the purpose
More informationDivision 28 - Electronic Safety and Security
Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationSupplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual
Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationSECTION FIRE ALARM
SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20
More informationProtecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant
Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationCOMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE
COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm
More informationFIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures
FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE
More information11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies
11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies Visible Signals Agenda 1. Physics 2. Installation Considerations
More informationPlan Review Check List Fire Alarm System
Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling
More informationThe CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)
The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater
More informationAddressable Fire Alarm Control Panel
PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable
More informationElectrical Inspection Special Electrical
0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm
More informationS AGE E NGINEERING A SSOCIATES, LLP
S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationArchitect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationFIRE IMPAIRMENT NOTICE
Notification of Fire System Isolation FIN NORA No. Complete Fire Impairment Notice (FIN) before any impairment. Note 3 business days notice is required. Submit the FIN to the BAC Airport Facilities on
More informationgood things in small packages
FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationMS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels
R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:
More informationNational Industrial Security Monitoring Station Evaluation
National Industrial Security Monitoring Station Evaluation Listing Evaluation During the UL Listing evaluation we will examine your the monitoring facility, signal handling, means of record keeping, and
More informationConcerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3
Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationSECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationPSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
More informationFinal EC Inspection Report 03/2010
2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers
More informationSILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05
SILENT KNIGHT Model SK-2/E & SK-4/E Fire Alarm Control Panel Installation and Operations Manual Part Number 52604 Rev. A ECN 05-276 08/08/05 Fire Alarm System Limitations An automatic fire alarm system
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
More information