1 September Edmonton, AB Technician Tools CAN/ULC-S CAN/ULC-S Presented By: Mark Wilson

2 Disclaimer The following presentation is in no way affiliated with, or presented on behalf of any particular company, brand name or product. The purpose of this presentation is to highlight the proper tools required and does endorse or recommend any particular brand or product that may be shown.

3 Introduction Verify Test Inspect

4 Why is this important? Case Study Villeray Apartment Fire (Aug ) It was the smell of smoke, not the sound of a fire alarm, that sent several residents of an apartment building in Villeray running from an early morning fire. When firefighters arrived at the scene around 4 a.m. Wednesday, they had to rescue at least a dozen people still trapped inside. Fire department will investigate why the building's smoke detectors did not go off

5 Who can benefit? Fire Alarm Technicians Supervisors Engineers/Consultants Building Operators Maintenance Staff The customer!

6 CAN/ULC-S During the verification of a newly installed or modified fire alarm system, certain tools will be required in order to meet the intent of the ULC standard. Artificial Smoke Heat Source Air Velocity Meter Decibel Meter Electrical Meter Audibility Meter Screen/Pattern UV/IR Test Lamp CO Gas Smoke Det. Sensitivity Meter VI Stickers

7 CAN/ULC-S During the test and inspection of an active fire alarm system, certain tools will be required in order to meet the intent of the ULC standard. Artificial Smoke Extendable Pole Heat Source Decibel Meter Electrical Meter Audibility Meter Screen/Pattern UV/IR Test Lamp CO Gas Smoke Det. Sensitivity Meter Vacuum Inspection Stickers

8 Similarities: Verification Test/Inspection Artificial Smoke Extendable Pole Heat Source Air Velocity Meter Decibel Meter Electrical Meter Screen/Pattern UV/IR Test Lamp CO Gas Two way radios Smoke Det. Sensitivity Meter Intelligibility Meter Verification Stickers Artificial Smoke Extendable Pole Heat Source Air Velocity Meter Decibel Meter Electrical Meter Screen/Pattern UV/IR Test Lamp CO Gas Two way radios Smoke Det. Sensitivity Meter Battery Capacity Meter Vacuum Inspection Stickers

9 Smoke Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instruction.

10 Heat Source Each heat detector shall be tested to confirm operability. NOTE: An open flame shall not be used for testing the operation of heat detectors.

11 Extendible Poles Can allow access up to 9m (30ft) without leaving the ground.

12 Multi-Stimulus Testers Smoke Heat CO Each combination type detector, using a combination of detection principles shall be tested to the requirements appropriate to each principle of operation and as recommended by the manufacturer.

13 Air Velocity Meter The positive airflow and/or sampling tube differential pressure in air duct type smoke detectors shall be tested to confirm that it is within manufacturer s specified limits.

14 Decibel Meter Appendix G (537-13) Sound Level Measurements G1.1 The sound level meter shall have a range as low as 35 dba. G2.1 The meter is to be held approx 1.5m above the floor and at least 0.5m away from hard reflecting surfaces. G2.2 The meter is to be set to the A weighted scale and to the fast response setting.

15 Electrical Multimeter

16 Beam Detector Testing Each beam type smoke detector shall be inspected and tested to confirm operability, including the following functions/features, as applicable: -Activation by the use of a manufacturer s recommended testing method for the device (e.g. screens, filters, etc.)

17 Flame Detector Testing Each flame detector shall be inspected and tested to confirm the operability as recommended by the manufacturer. All functions/features of the device shall be tested.

18 Testing CO Detectors Follow manufacturers recommendations for testing CO detectors

19 Two Way Radios

20 Smoke Sensitivity Tester Each smoke detector shall be tested to confirm that it is within its rated operating range using a test method described in clause Acceptable methods of determining the smoke detector sensitivity are: A- Manufacturers recommended test instrument, equipment, or method; B- Installed control units or transponders designed to test the sensitivity of individual smoke detectors; and C- Test instruments that provide calibrated sensitivity measuring operation as described in CAN/ULC-S529 Standard for Smoke Detectors for Fire Alarm Systems, acceptable to the AHJ.

21 Summary In order to complete the tests required by the ULC standards, we must ensure that the proper tools are made available for technicians to use. Being trained on what tools are required, as well as the proper way to use them is important. We owe it to our customers and the public to ensure that the life safety systems that are installed in buildings are installed properly, tested properly and will be ready to function when we need them.

22

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

SOME OF THE MOST COMMON TESTING MISTAKES MADE BY TECHNICIANS PERFORMING VERIFICATIONS TO CAN/ULC S537-04

SOME OF THE MOST COMMON TESTING MISTAKES MADE BY TECHNICIANS PERFORMING VERIFICATIONS TO CAN/ULC S537-04 SOME OF THE MOST COMMON TESTING MISTAKES MADE BY TECHNICIANS PERFORMING VERIFICATIONS TO CAN/ULC S537-04 OR Some of the things that I done have wrong and was told how stupid I was! Why is it hard to make

More information

Canadian Fire Alarm Association. Fire Alarm System Activation. Fire Alarm with malfunction history

Canadian Fire Alarm Association. Fire Alarm System Activation. Fire Alarm with malfunction history Canadian Fire Alarm Association Discussion topics False alarms Shut off notices Owner s responsibilities Documents required by AHJ Fire Alarm System Activation Fire detection (early warning at insipient

More information

AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS

AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS Building stairwell and vestibule pressurization systems must be retested and recertified

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

A Building Manager s Guide to Maintaining Fire Code Compliance

A Building Manager s Guide to Maintaining Fire Code Compliance A Building Manager s Guide to Maintaining Fire Code Compliance Know your role in conducting fire protection system inspections : Fire Alarm Codes and Standards Maintaining your compliance with fire code

More information

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015 Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015 UL and the UL logo are trademarks of UL LLC 2012 GOALS OF INSPECTING AND TESTING POWER SUPPLIES Verify/inspect

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN File: ULC-S527-11 ULC-G5.2 June 1, 2012 CERTIFICATION BULLETIN 2012-04 Effective Date Announcement CAN/ULC-S527-11, 3 rd Edition of the Standard for Control Unit for Fire Alarm Systems To: Subscribers

More information

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION

More information

solo detectortesters single testing system. complete range of testing tools. detectortesters testing technology from No Climb

solo detectortesters single testing system. complete range of testing tools. detectortesters testing technology from No Climb solo TM A A single testing system. complete range of testing tools. testing technology from No Climb solotm A complete range of test and maintenance equipment for smoke, heat and CO detectors. Testing

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed, CSFM Approved* Features Air aspiration duct smoke detection** system provides remote sensor location for ducts with difficult service access: Available as either

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

solo detectortesters single testing system. complete range of testing tools. testing technology from No Climb

solo detectortesters single testing system. complete range of testing tools. testing technology from No Climb TM A A single testing system. complete range of testing tools. testing technology from No Climb TM A complete range of test and maintenance equipment for smoke, heat and CO detectors. Testing equipment

More information

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE 100130 Description The first part of the course presents the requirements for fire alarm systems. It describes the buildings

More information

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS EN Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS Installation Instructions Trademarks Trademarks Chamber Check is a registered trademark of Bosch Security Systems

More information

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Note Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Document on Best Practice for Fire Detector Testing/Test Equipment 1. SCOPE OF THIS DOCUMENT... 3 2. COMPETENCY

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm

BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm 1 BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm Association 2 Presentation Overview The Codes Your responsibilities

More information

VERIFICATION OF FIRE ALARM SYSTEMS

VERIFICATION OF FIRE ALARM SYSTEMS DEVELOPMENT, BUILDINGS AND LICENSING Chief Building Official (CBO) and Building Code and Policy Building Policy Branch The intent of this bulletin is to clarify requirements of verification of the fire

More information

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01

More information

Smoke Detector Testing

Smoke Detector Testing Smoke Detector Testing Allen Hess CFAA Presentation April 2011 1 Building Technologies Agenda Requirements Consumer Needs Challenges with Industry Acceptance How siemens a Detector sans italic Works Effects

More information

Addressable Detectors & Bases

Addressable Detectors & Bases Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously

More information

Incident Summary (Reference # )

Incident Summary (Reference # ) Incident Summary (Reference #5605195) Incident Date September 13, 2016 Location White Rock Regulated industry sector Natural gas system and low voltage electrical system (30V to 750V) SUPPORTING INFORMATION

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

BUILDING CODE INTERPRETATION

BUILDING CODE INTERPRETATION BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

Latest update: Ordinance of the Ministry of Internal Affairs and Communications No. 25 of March 27, 2013

Latest update: Ordinance of the Ministry of Internal Affairs and Communications No. 25 of March 27, 2013 This translation is provisional translation for reference, formally refer to the original text. Ordinance for Technical Specifications pertaining to Transmitters (Ordinance of the Ministry of Home Affairs

More information

COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW?

COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW? COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW? By: Ark Tsisserev, P.Eng. Senior Technical Manager Applied Engineering Solutions Ltd. CFAA Technical Seminar April 15, 2015

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3 REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries

More information

275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO

275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com 275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO

More information

I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we

I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we appreciate your taking the time to learn more about this

More information

STANDARDS BULLETIN

STANDARDS BULLETIN June 2, 2008 STANDARDS BULLETIN 2008-08 CAN/ULC-S319-05, Electronic Access Control Systems FREQUENTLY ASKED QUESTIONS The following frequently asked questions (FAQ) is being issued in response to a request

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

Building Name: Our Lady of Sorrows Date: July 10, 2013

Building Name: Our Lady of Sorrows Date: July 10, 2013 1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

Presented to Resident Services, Operations and Personnel (RSOP) Committee September , 2015

Presented to Resident Services, Operations and Personnel (RSOP) Committee September , 2015 San Francisco Housing Authority (SFHA) Work Order, Inspection and Fire Safety Analysis August 215 Presented to Resident Services, Operations and Personnel (RSOP) Committee September ------, 215 Table of

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Canadian Fire Alarm Association (CFAA)

Canadian Fire Alarm Association (CFAA) An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems Canadian Fire Alarm Association (CFAA) CAN/ULC - S524-01 STANDARD FOR THE INSTALLATION OF FIRE ALARM SYSTEMS Installation

More information

Early Warning Fire Detection Engineering

Early Warning Fire Detection Engineering Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful

More information

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Id Number Title Year Organization Page 1 ANSI.CAN.UL. NULL 2016 ULC 64 1201 2 CAN.ULC- NULL 2016 ULC 176 60839-11-1-2016 3 CAN.ULC-IEC

More information

Elevator Emergency Equipment Instructor s Guide

Elevator Emergency Equipment Instructor s Guide Table of Contents Overview.......4 Sensory Inspection 11 Emergency Equipment in Elevator Systems..14 Fire Service Phase I & II 24 Summary..35 1 Icons Used In This Guide Agenda Topic # Topic Title Duration

More information

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability Fire Alarm Inspection, Testing, Maintenance Assuring the System s Operational Reliability What does AFAA-NE do? Education We supply the tools our members require to perform within the guidelines of our

More information

Intelligent Detection Devices

Intelligent Detection Devices Intelligent Detection Devices Multi-Criteria Fire Detector [with ASAtechnology TM ] Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena

More information

Detecting Your Needs Signaling Change

Detecting Your Needs Signaling Change Detecting Your Needs Signaling Change The 2016 CFAA Alberta Technical Seminar Wednesday, September 21, 2016 The Canadian Fire Alarm Association 85 Citizen Court, Units 3 & 4, Markham, Ontario L6G 1A8 www.cfaa.ca

More information

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection Guidance Note Fire Alarm Detector Applications and Documentation of the Selection Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF...

More information

DNRHS Intelligent Air Duct Smoke Detector

DNRHS Intelligent Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRHS Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:

More information

Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems

Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems Presented by Mike Locke, MechTech Inc. SIA All SIAs are listed in this presentation April 13, 2016 1 Reasons for Revisions

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue

OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE John Percy, Public Education Officer Waterloo Fire Rescue AGENDA: Fire Protection and Prevention Act and Ontario Fire Code Role of Assistants to

More information

TECHNICAL SPECIFICATIONS BUTTONS

TECHNICAL SPECIFICATIONS BUTTONS Maxlogic beam type smoke detector consists of 2 parts as a receiver and transmitter. Should be mounted as facing each other between the distance of 5-100 m. The detector works on the principle of light

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL. In view of section 62 of the Municipal Powers Act (R.S.Q., chapter C-47.

BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL. In view of section 62 of the Municipal Powers Act (R.S.Q., chapter C-47. VILLE DE MONTRÉAL BY-LAW RCG 12-003 BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL In view of section 62 of the Municipal Powers Act (R.S.Q., chapter C-47.1); In view of the Civil Protection

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Title: BFST1505 Syllabus

Title: BFST1505 Syllabus DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards and Training Title: BFST1505 Syllabus Revision: April 5, 2018 Section I - Course Information Course Title: Fire

More information

SMOKE DETECTOR TESTERS

SMOKE DETECTOR TESTERS SMOKE DETECTOR TESTERS efficient universal integrated safe lightweight 9m reach endorsed Why testing is required... Codes and standards throughout the world define the testing and maintenance of fire detection

More information

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies 11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies Visible Signals Agenda 1. Physics 2. Installation Considerations

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

SK-Duct Air Duct Smoke Detector

SK-Duct Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

A Comparison of Rate Compensated Heat Detector Test Methods

A Comparison of Rate Compensated Heat Detector Test Methods A Comparison of Rate Compensated Heat Detector Test Methods Overview of Rate Compensated Fire Detectors Thermal switch technology invented by Wilfred J. Turenne in the 1920 s Have been mass produced as

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

Guidance on Video Smoke Detection Technology (VSD)

Guidance on Video Smoke Detection Technology (VSD) Guidance Note Guidance on Video Smoke Detection Technology (VSD) Guidance on Video Smoke Detection Technology (VSD) SCOPE... 3 INTRODUCTION... 4 WHAT IS VSD?... 5 STANDARDS... 7 GENERAL GUIDANCE ON THE

More information

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved. TX7100 Intelligent Addressable Optical Smoke Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property,

More information

The six tests conducted included three smoldering and three fast flaming type tests.

The six tests conducted included three smoldering and three fast flaming type tests. The Mayfield Village Tests On May 9, May 12 and May 13, 2014 NEOFPA conducted six full-scale, real-world smoke alarm comparison tests in the city of Mayfield Village, Ohio. Tests 5 and 6 conducted on May

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Integrated electronic maximum-minimum thermometer, with factory programmed alarms, for vaccine refrigerators

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Installation Instructions

Installation Instructions 48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................

More information

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment SILENT KNIGHT IntelliKnight Smoke Detector Cleaning and Testing Instruction This document contains information necessary to properly test and clean analog photoelectric and ionization smoke detectors connected

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC PART 1 GENERAL 1.01 SUMMARY SECTION 23 08 00 COMMISSIONING OF HVAC A. This section covers the Contractor's and Commissioning Authority (CA) responsibilities for commissioning; each subcontractor or installer

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

Emis. Unit Description:

Emis. Unit Description: 1030459 88666 PERCHLOROETHYLENE DRY CLEANERS COMPLIANCE INSPECTION CHECKLIST INSPECTION TYPE: ANNUAL (INS1, INS2) COMPLAINT/DISCOVERY (CI) RE-INSPECTION (FUI) ARMS COMPLAINT NO: AIRS ID#:103 0459 Date:

More information

Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC

Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC Reliable Fire Alarm Monitoring Why is it important? Codes and Standards? What is a fire alarm monitoring?

More information

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670. AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian

More information

Instructions. Duct Mount Accessory Q Rev: 11/

Instructions. Duct Mount Accessory Q Rev: 11/ Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4

More information

Synco living combines individual room control with consumption data acquisition

Synco living combines individual room control with consumption data acquisition Synco living combines individual room control with consumption data acquisition Saving energy with innovative home automation Answers for infrastructure. Synco living so many ways to save energy You can

More information

BULLETIN BU/EL Revised August 11, 2015

BULLETIN BU/EL Revised August 11, 2015 BULLETIN 2000-019-BU/EL Revised August 11, 2015 TRANSMITTING UNIT FROM PROTECTED PREMISES TO FIRE SIGNAL RECEIVING CENTRE IN CONFORMANCE WITH CAN/ULC-S561 The intent of this bulletin is to clarify the

More information

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under

More information

DNR-AUS Duct Smoke Detector

DNR-AUS Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the

More information

Ice*Meister Model 9734-SYSTEM INDUSTRIAL ICE DETECTING SENSOR SYSTEM Technical Data Sheet

Ice*Meister Model 9734-SYSTEM INDUSTRIAL ICE DETECTING SENSOR SYSTEM Technical Data Sheet 1 Ice*Meister Model 9734-SYSTEM INDUSTRIAL ICE DETECTING SENSOR SYSTEM Technical Data Sheet Figure 1 Ice*Meister Model 9734-SYSTEM optical ice sensing detector system is easy to install and completely

More information

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among

More information

PRODUCT GUIDE. Fire Alarm & Life Safety Test & Maintenance Products

PRODUCT GUIDE. Fire Alarm & Life Safety Test & Maintenance Products PRODUCT GUIDE Fire Alarm & Life Safety Test & Maintenance Products SDi is the world s leading provider of specialized equipment for the fire protection and security industries. With a commitment to offering

More information

DUCT LEAKAGE (Page 1 of 3)

DUCT LEAKAGE (Page 1 of 3) (Page 1 of 3) Note: Submit one Certificate of Acceptance for each system that Enforcement Agency Use: Checked by/date must demonstrate compliance. HERS verification required. This form used for duct pressure

More information