Electrical, Instrumentation, Monitoring and Control Systems

Size: px
Start display at page:

Download "Electrical, Instrumentation, Monitoring and Control Systems"

Transcription

1 Electrical, Instrumentation, Monitoring and Control Systems Guidelines for Specifications LMW 8.2 S008 ACTEW Water a business name owned by ACTEW Corporation Limited ABN

2 Table Of Contents 1. Objective Scope Definitions References General Document Structure Approval Status during Development Specification Templates (Under Development) Specification Definitions of Specification Sub-Headings Standard logic: Tag name prefix: Location: Parent asset: General Description: ity: Drawings: Operator Interfaces: Operating modes: Automatic Sequences: Hard-wired interlocks: Software interlocks: Parameters, Alarms and Trends: Data Reporting: Control Source: References: A. Specification - EXAMPLES Apr of 43

3 4 Apr of 43

4 1. OBJECTIVE The aim of this document is to establish guidelines for the development of Process, System and Equipment Specifications for implementation within ActewAGL Treatment Branch Plant Control and SCADA Systems. Adherence to these guidelines will ensure a uniform standard of Specifications; in particular, appearance, format and content requirements. Adherence to these guidelines will also allow the Specifications to be maintained for the life of the processes, systems and equipment by ensuring that additions and other amendments can be integrated into existing functional specifications. 2. SCOPE These guidelines shall apply to Process, System and Equipment Specifications relating to ActewAGL Treatment Branch Plant Control and SCADA Systems. 3. DEFINITIONS The following abbreviations and definitions are used within these guidelines: Approved Quality Procedure LMWQCC SCADA FOIP HMI Approved by the Principal s Representative. Existing management system procedure, instruction, standards or specifications established by ActewAGL Treatment Branch Lower Molonglo Water Quality Control Centre. Supervisory Control And Data Acquisition. A primary means used to remotely monitor and control industrial processes, predominately from a central control room. Field Operator Interface Panel. A secondary means used to remotely monitor and control industrial processes, predominately closer to the equipment in the field. Human Machine Interface. A means used to remotely monitor and control industrial processes. This could be applied to both SCADA and FOIP. 4 Apr of 43

5 LCS Instrument Loop Local Control Station. A local means to control the equipment, usually located in the immediate vicinity of the related item and commonly consisting of push buttons/lamps/dials, etc An instrument loop consists of all items, cabling or pipe work used to measure, transmit, indicate or process an electrical or pneumatic analogue signal. An instrument loop generally consists of all items linked by a single current, voltage or pneumatic loop. For the purposes of simplicity the term instrument loop terminology may, however, also be extended to cover discrete digital signal control devices which do not relate to a single specific instrument loop or primary equipment item; i.e. Common pressure switch, flow switch, etc. Each instrument loop is identified as per ActewAGL Treatment Branch Quality Procedure TB 8.1 P601 (3.1.3) with reference to TB 8.1 P601 T3. Plant Equipment Item Each major item of plant equipment is identified as per ActewAGL Treatment Branch Quality Procedure TB 8.1 P601 (3.1.2) with reference to TB 8.1 P601 T3. Asset Hierarchy Essentially this procedure states that each item of equipment shall be uniquely identified according to its location and function. An ordered and structured list of plant equipment and instrument loops, with their equipment and loop numbers, arranged into a systematic hierarchy to bring together the various processes and systems within those processes by which the plant functions as a whole. 4 Apr of 43

6 4. REFERENCES ActewAGL Treatment Branch Electrical, Instrumentation, Monitoring and Control System Standards LMW 8.02 S001 Basis of Design LMW 8.02 S006 PLC/RTU Programming Guidelines LMW 8.02 S007 Citect Programming Guidelines ActewAGL Treatment Branch Quality System Procedures Treatment Identification and Registration of Plant Assets Instruction. TB 8.?? P??? Plant Control and SCADA Systems Software Management & Control TB 8.?? P??? Identification of Plant Control and SCADA Systems Software Miscellaneous EIP RF R007 EIP Report ACTEWAGL Logic Systems Review Phase 2, Specification Guidelines 4 Apr of 43

7 5. GENERAL The purpose of a Specification is to define the requirements of a control and SCADA system with enough clarity to allow a programmer to develop the PLC/RTU application program and the Operator Interface for the facility being controlled. A secondary purpose is to provide maintenance and operational personnel with a clear statement of the role played by each item of the plant and how each item within a system interacts with the other items Document Structure The structure of the Specification is based on the ActewAGL Treatment Branch Asset Hierarchy. A brief overview of the Asset Hierarchy as applicable to the Specification is detailed below: Level 1: Example: LMWQCC Level 2: Plant/Facility Major Processes (grouped by Plant/Facility) Example: Primary Treatment, Tertiary Treatment, Solids Management processes at LMWQCC Level 3: Systems (grouped by Major Process) Example: Backwash Water Supply, Waste Backwash Water systems within the Tertiary Treatment Process Level 4: Individual Items Of Equipment Or Instrument Loops (grouped by System) Example: 5301PU, 5302PU Backwash Supply Pumps, part of the Backwash Water Supply System Each plant/facility, major process, functional system and individual item of equipment and instrument loop shall have a functional specification developed. At the plant/facility and major process level the functional specification will normally be an overview description of the plant/facility or major process and will also identify each of the lower level major processes or functional systems respectively that constitute that grouping. 4 Apr of 43

8 Similarly, at the functional system level, the functional specification shall describe the operation and role of that system in the higher-level process, to which it belongs. The functional specification for each individual item of equipment and instrument loop shall describe in detail all aspects of the operation of that particular equipment item or instrument loop. The specific data and information requirements for each level of Specification are detailed in Section 6 of this document. Further to the requirements of Section 6, an extra component is included in the plant/facility level functional specification to identify the revision status and/or date of issue of the Plant s Asset Hierarchy used for the Specification. In addition to the plant/facility, major process, system and individual equipment/instrument loop components of the ActewAGL Treatment Branch asset hierarchy, the ActewAGL Treatment Branch Specification also includes an ActewAGL Treatment Branch Standards component (at Level 2). This component describes the standard equipment and instrument loop control and SCADA functionality to be applied in the plant control and SCADA systems. The ActewAGL Treatment Plant s Specification shall consist of a number of individual files residing in a common directory (e.g. LMWQCC on Jeeves /LMFunc-Spec). The filenames used shall be as defined by the ActewAGL Treatment Branch Operations & Process Manager based on established practice. The Specification files shall be written in Microsoft Word format. All references to Standard Logic, Sites, Systems, Processes and Equipment (as defined in the Asset Hierarchy) shall be hyperlinked to the appropriate document (refer Attachment A for examples) Approval Status during Development During development, all approved text shall be coloured auto (black on a white background, white on a black background). Text submitted for approval shall be coloured blue. Other colours may be applied to text under development, these colours and their usage is not defined Specification Templates (Under Development) ActewAGL is currently developing blank functional specification templates. When available, these will be issued to the functional specification developer so that consistent format/styles are adopted. Until these documents are issued, the functional specification shall use the same formatting styles contained within the examples in Attachment A. 4 Apr of 43

9 6. FUNCTIONAL SPECIFICATION The Specification shall be contained in the descriptive text and tables following the site, process, system and equipment item/instrument loop headings. The information in the specification shall be divided into the following sections using the following subheadings. The detail required is dependant on the aspect being described. The ticks ( ) show the sub-headings required for the various aspects (site, process, system, equipment item/instrument loop). The asterisk (*) indicates where a sub-heading should be included only where required for the particular application. For instance, there may be specific Data Archiving requirement at the site level such as plant throughput or plant availability. Where a required sub-heading has no meaning for that particular level, include the sub-heading with a note that it is Not Applicable. Equipment item - static is for use with items with structure but without plant process control system connections e.g. tanks & channels. Any value within a configurable table cell that is not applicable is not to be left blank, but shall be marked by the symbol -. If an entire row is not applicable, then the row is to be deleted. There is to be a top-level document, defined by the Site/Plant asset hierarchy labelling scheme, (e.g. WWG Googong Water Treatment Plant) linking all the separate documents forming the complete functional specification. See the following example: 4 Apr of 43

10 Sub-headings Site Process System Instrument Loop Equipment Item Equipment Item - Static Level Standard logic: Tag name prefix: Location: Parent asset: - General description: ity: ** Drawings: * * - Operator interfaces: - Operating modes: - - Automatic sequences: - - Hard-wired interlocks: Software interlocks: Parameters, Alarms and Trends: - - Data reporting: * * * - Control source: Apr of 43

11 References: * Indicates information is required only where applicable. ** refer O&M manuals for description of functionality The Specification is not limited to the use of the above sub-headings, however, where additional headings are proposed, ActewAGL Treatment Branch shall first approve this. Where multiple systems or equipment items/instrument loops have similar or identical functionality then the functional specification of all system parts shall be fully described Definitions of Specification Sub-Headings A guide to the required content of each of the above elements is provided below. Under each table, extra text may be inserted, where required, to clarify/describe a unique item/process. Examples are displayed in the attachment section Standard logic: Indicate if Standard logic functionality is used throughout the Site, Process or System. This section shall provide a link to the ActewAGL Treatment Branch PLC Logic Standards Tag name prefix: Identify the prefix to tag names to be used to identify variables in the PLC/RTU programming and the SCADA. Tag names shall be the same for both the PLC/RTU and Citect and be based on the current plant identification systems Location: Provide a basic description of where the item is physically located Parent asset: List the parent asset of the item, including asset number/identifier and description as defined within the asset master register. 4 Apr of 43

12 General Description: Provide a basic description of the process, system or item/loop including physical description and type, where applicable. If a drive is not started by Direct On Line (D.O.L.) method, then define its method of starting: Eg. Soft Starter or Variable Speed Drive ity: Describe the role that the process, system or item/loop plays within the plant including process related inputs and outputs. List any nonstandard local controls and indicators. At a system level (Level 3) or above, provide a description and summary of functionality Drawings: List the process or electrical drawings applicable to this process, system or unit, including P&I diagrams, networks, schematics, termination drawings, etc. Drawing number and description should correlate with the actual drawing details and attributes recorded within the Drawing Management System (DMS). Refer to Attachment A for worked examples. Drawing type Drawing description Drawing number P&I Diagram/s Description?????-???? Network/s?????-???? Description?????-???? Etc. Schematic/s?????-???? Description?????-???? Etc. IO connection/s Description Description Etc.?????-?????????-?????????-???? 4 Apr of 43

13 Operator Interfaces: Describe, in tabular and text format, the interface display requirements that the Operator needs for the safe and efficient control of this process, system or unit. The standard Operator Interface functionality is defined in LMW 8.2 S007 Citect Configuration Guidelines. SCADA project SCADA page(s) Standard SCADA pop-up used SCADA project 1 name Page 1 name Page 2 name Page 3 name Etc. SCADA project 2 name (if applicable) Page 1 name Page 2 name Etc. FOIP location(s) FOIP page(s) Standard FOIP pop-up used????cp brief description Page 1 name????cp brief description Page 2 name????cp brief description (if applicable) Etc. Page 1 name 4 Apr of 43

14 Location of local controls and indicators 1 st location 2 nd location Refer to Attachment A for worked examples. Description of local controls and indicators brief description of item 1 brief description of item 2 etc brief description of item 1 brief description of item 2 etc E-stop functionality Standard / Shunt trip Standard / Shunt trip 4 Apr of 43

15 Operating modes: Define, in tabular and text format, the operation modes of the process or item/loop, the default operating mode/state and the conditions under which the operating mode/state will be changed. The standard modes of control are defined in LMW 8.2 S001 Basis of Design. Level 3 (System) Mode Description Definition Mode 1 Provide a basic description of the mode List conditions that define the mode Mode 2 Provide a basic description of the mode List conditions that define the mode Mode 3 Provide a basic description of the mode List conditions that define the mode Mode 4 Provide a basic description of the mode List conditions that define the mode Etc. Etc. Etc. Level 4 (Instrument Loop/Equipment Items) Instrument loop Default mode Manual available Automatic available Cascade available Offline available Calibrate available Manual / Auto / Cascade Drives/Valves Default mode Local manual available Remote manual available Automatic available Offline available Local manual / RemoteManual / Auto 4 Apr of 43

16 Automatic Sequences: Identify all automatic sequences this unit performs or takes part in including start permissives, startup sequence, running sequence, shutdown sequence, emergency shutdown sequence, etc. Each item/equipment that is relevant is to be individually referenced, not referred to a generic group of equipment. E.g. do not use Start all lime sludge pumps. Instead, use Start : 1234PU Lime Sludge Pump 1, 1235PU Lime Sludge Pump 2, 1236PU Lime Sludge Pump 3, 1237PU Lime Sludge Pump 4 and 1238PU Lime Sludge Pump 5. Each automatic sequence shall be documented at the appropriate Level : Level 3 (System) where complex system wide sequences control multiple items/loops. Level 4 (Instrument Loop/Equipment Items) where a sequence involves a small number of items/loops that work to support a primary item of equipment. Eg. A pump and its related control valve. The recommended sequence step layout uses a Major step and minor step as follows: Step 0.00 may be used when the Mode is not active. Permissives should start at Each separate cycle within each mode should start at 1.01, 2.01, 3.01, etc. The sub-step (i.e. a, b, c, etc) is not part of the sequence, but is used to assist in reading of this document. It is only used on a step with many conditions. MODE 1 SEQUENCES Mode 1 permissives Step description Step description: a. Sub-step description, and b. Sub-step description, and c. Sub-step description Step description: a. Sub-step description, or 4 Apr of 43

17 b. Sub-step description Step description Etc. Mode 1 cycle 1 sequence 1.01 Step description Step description: a. Sub-step description, and b. Sub-step description, and c. Sub-step description Step description: a. Sub-step description, and b. Sub-step description. Mode 1 cycle 2 sequence 2.01 Step description Step description: a. Sub-step description, and b. Sub-step description, and c. Sub-step description. 4 Apr of 43

18 2.03 Step description: a. Sub-step description, and b. Sub-step description Step description Etc. The majority of sequences occur at either an equipment or system level, however in some instances a sequence may exist at a process or site level (eg. plant start-up or shutdown sequences) and should be documented at the appropriate level (i.e. Level 1 or 2). Where there are multiple Automatic sequences for a particular system (eg. Filter DAF sequence, Filter Backwash Sequence), each shall be clearly distinguished through the use of a unique title and description (refer template) Hard-wired interlocks: Define all process related hard-wired interlocks. Refer Attachment A for examples Software interlocks: Define all software interlocks. Refer Attachment A for examples Parameters, Alarms and Trends: Define any parameters, alarms and trends in tabular format with the default values that shall be used on the first PLC scan. Where applicable, Standard alarms are to be provided for Loops, Drives and Valves. The tables below shall be used in the functional specification and shall not be modified unless ActewAGL gives approval. All rows that are not applicable to the particular item shall be deleted. Refer to Attachment A for worked examples. An introductory sentence may be provided to outline non-standard, relevant information, further to that contained within the table. Refer to Attachment A for worked examples. 4 Apr of 43

19 Definition of Alarms Alarms shall be given one of five categories: 1. High (H) - alarms that need immediate attention. 2. Medium (M) - alarms that may interfere with the normal operation of the plant. 3. Low (L) - alarms that are of low importance and do not interfere with the running of the plant. 4. Events (E) - alarms that are not displayed on the alarms page. They appear on the summary page only. Includes events such as pumps starting and stopping. 5. Off-Normal (O) - alarms that are not displayed on the alarms page. They appear on the off-normal alarms page only. Off-normal alarms are for equipment that is not in the normal operating mode Field inputs Define whether field inputs (inputs that are physically wired to the PLC) that generate an alarm, deliver an active high or active low signal. Typically, most inputs are active high, i.e. a signal is received when the condition is true, e.g. the PLC receives a signal when the pump is running. However, some inputs are wired using a fail-safe method (active low), i.e. a signal is absent when the condition is true, e.g. the PLC loses a signal when an intruder is detected. This method provides additional signal reliability by attracting attention to an input failure, possibly caused by several factors, including; signal power failure, rodent interference or poor wiring. This information is only required for alarms based on direct field inputs, and may be left blank for all other alarms that are internally generated within the PLC Alarm Triggers An alarm may be generated when a Variable becomes either:, False or some other additional condition/s. The alarm may also have a delay before it is generated. Level 3 (System) Parameters 4 Apr of 43

20 Parameter description Minimum setting Maximum setting Default value Parameter 1 description?? units?? units?? units Parameter 2 description?? units?? units?? units Parameter 3 description?? units?? units?? units Etc.?? units?? units?? units Alarms Variable Field input active low Alarm triggers Alarm 1 description / False / List of combination of conditions initiating alarm Alarm 2 description / False / List of combination of conditions initiating alarm Alarm 3 description / False / List of combination of conditions initiating alarm Etc. / False / List of combination of conditions initiating alarm PLC Alarm delay (sec) Visible on HMI Alarm priority H/M/L/E/O/- H/M/L/E/O/- H/M/L/E/O/- H/M/L/E/O/- Control from HMI Additional notification Note 1: For Alarm Priority, the non-abbreviated description shall be provided in the functional specification document eg. High / Medium / Low / Event / Off-Normal. Refer to Attachment A for worked examples. 4 Apr of 43

21 Level 4 (INSTRUMENT LOOP) Instrument Loop configuration Description Type Process range From Process range To Engineering units Alarm deadband Input?? -?? ma or V / Comms units?? /-?? /- / RTD Type, Class / Virtual / 24 vdc Output?? -?? ma or V / Comms units?? /-?? /- / RTD Type, Class / Virtual / 24 vdc Extended loop parameter 1/ parameter 2 / Etc. Virtual units?? /-?? /- Refer to Attachment A for worked examples. Parameters Parameter description Minimum setting Maximum setting Default Value Visible on HMI Control from HMI Calibrate mode time remaining Yes No Automatic set-point Yes Process Variable Yes (Yes)* Cascade set-point Yes No 4 Apr of 43

22 Controller Output Yes No Manual Output Yes Yes Low Low alarm setting Yes Low alarm setting Yes High alarm setting Yes High High alarm setting Yes Safe value of controller output when Set to?? % / Hold last / loop faulted - No Safe value of controller output when offline Safe value of Analog Output when output module faulted Cut-in 1 Cut-out 1 Cut-in 2 Cut-out 2 Cut-in 3 Cut-out 3 PID Proportional gain Set to?? % / Hold last / - Set to?? % / Hold last / - No No Yes Yes Yes Yes Yes Yes No 4 Apr of 43

23 PID Integral (repeats/second or seconds/repeat) PID Derivative Auxiliary parameter 1 * Process Variable may only be set when the loop is in Calibrate mode. No No Additional information may be inserted here as required, e.g. Extended loop description of parameters or any complex calculations, eg. Cascade set-point, etc. Alarms Low Low alarm Low alarm High alarm High High alarm Variable Not in default mode (Replace default mode with either: Manual, Auto or Cascade) Field input active low Alarm triggers / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm PLC alarm delay (sec) Alarm priority (note (note (note (note Off normal Calibrate mode Off normal Additional notification 4 Apr of 43

24 Variable Field input active low Alarm triggers PLC alarm delay (sec) Alarm priority Offline mode Off normal Additional notification Faulted Event Open wire (note Under range Over range Sample failed (note (note (note IO module fault Medium Loop power supply failed / List of combination of conditions initiating alarm Auxiliary alarm 1 / False / List of combination of conditions initiating alarm (note H/M/L/E/O/- Note 1: For Alarm Priority, the non-abbreviated description shall be provided in the functional specification document eg. High/Medium/Low/Event/Off-Normal/-. Refer Attachment A for worked examples. Level 4 EQUIPMENT ITEM DRIVE 4 Apr of 43

25 Parameters Current Parameter description VSD Frequency Minimum setting Maximum setting Default Value?? Visible on HMI Drive reversible Yes Loadshed enabled No Restore delay preset (sec)?? No Restore delay time remaining (sec) Maximum no. of starts/hr No. of starts remaining within the hour No. of starts/hr time remaining till reset Restart delay preset (sec) Restart delay time remaining (sec) Duty set???? list equip that forms part of the duty set Default duty allocation 1 / 2 / 3 / 4 / 5 / 6 No Yes Yes Yes No Yes Yes No Yes No Control from HMI 4 Apr of 43

26 Parameter description Minimum setting Maximum setting Default Value Duty rotation type Cyclic (every?? operations) / Timed (Day, Time) VSD Contactor Reclosure Delay?? Visible on HMI No No Control from HMI Thermal capacity used Yes Auxiliary parameter 1?? Full listings of parameter settings for VSD s, E3 s, etc to be contained in O&M. Refer to Attachment A for worked examples. Alarms Variable Not in default mode (Replace default mode with either: Local manual, Remote manual or Auto) Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority Off normal Offline mode H/M/L/E/O/- Running Event Additional notification Faulted Event Available False Off normal 4 Apr of 43

27 Variable Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority E-stop lockout CB closed False Off normal Reversing / False Event Interlocked Event Startup sequence failed / List of combination of conditions initiating alarm Shutdown sequence failed Discrepancy trip Thermal overload Thermistor trip CB protective trip / List of combination of conditions initiating alarm If told to run and no running status; or if told to stop and still has running status 2 Additional notification 4 Apr of 43

28 CB residual trip Variable Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority E-stop shunt trip High Low flow / List of combination of conditions initiating alarm Seal failed High discharge pressure Under speed Low suction pressure Low discharge pressure / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm Additional notification 4 Apr of 43

29 Over speed Variable Field input active low Alarm triggers / List of combination of conditions initiating alarm PLC Alarm delay (sec) Alarm priority Load shed active Event No. of starts/hr exceeded Low IO module fault Medium Auxiliary alarm 1 / False / List of combination of conditions initiating alarm H/M/L/E/O/- Smart Motor Protection Test trip Shear pin failed Current imbalance Comms failed Comms idle SMP3/E3/SMC/Micom/- Additional notification 4 Apr of 43

30 Variable Non volatile memory fault Hardware fault Thermistor input trip RTD input Jam protection Stall protection Underload Ground fault Phase loss Thermal overload Field input active low Alarm triggers / List of combination of conditions initiating alarm PLC Alarm delay (sec) Alarm priority Additional notification 4 Apr of 43

31 RTD input Auxiliary alarm 2 Variable Advanced method of starting VSD / Soft-starter fault VSD warning Shear pin failed Jam protection Stall protection Underload Earth fault Field input active low Alarm triggers / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm VSD / Soft starter / List of combination of conditions initiating alarm PLC Alarm delay (sec) Alarm priority H/M/L/E/O/- H/M/L/E/O/- H/M/L/E/O/- Additional notification 4 Apr of 43

32 Phase loss Thermal overload VSD in local Variable VSD comms failed Auxiliary alarm 3 Field input active low Alarm triggers / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm PLC Alarm delay (sec) Alarm priority H/M/L/E/O/- H/M/L/E/O/- Additional notification Note 1: For Alarm Priority, the non-abbreviated description shall be provided in the functional specification document eg. High/Medium/Low/Event/Off-Normal/-. Refer to Attachment A for worked examples. 4 Apr of 43

33 VALVE Parameters Parameter description Safe analog output position when output module faulted Remote analog manual position set point Safe position when offline Safe position when faulted Software interrupter times Duty set Minimum setting Maximum setting Default Value Set to?? % / Hold last / - Set to?? % / Hold last / - Set to?? % / Hold last / - Set to?? % / Hold last / - Move for?? secs then stop for?? secs list equip that forms part of the duty set Visible on HMI Default duty allocation 1 / 2 / 3 / 4 / 5 / 6 /- No Duty rotation type Cyclic (every?? operations) / Timed (Day, Time) Auxiliary parameter 1 No Yes No No No No No Control from HMI Yes 4 Apr of 43

34 Alarms Variable Not in default mode (Replace default mode with either: Local manual, Remote manual or Auto) Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority Off normal Additional notification Offline mode Off normal Closing Event Opening Event Faulted Event Available False Off normal E-stop lockout (note CB closed False H/M/L/E/O/- Fully opened Event Fully closed Event 4 Apr of 43

35 Failed to open Failed to close Variable Field input active low Alarm triggers If told to open and fully opened status has not been reached. If told to close and fully closed status has not been reached. PLC Alarm delay (sec)???? Alarm priority (note (note Additional notification Position loop fault (note Thermal overload Thermistor trip Monitor relay fault (In Local or faulted) / False / List of combination of conditions initiating alarm (note (note H/M/L/E/O/- Interlocked Event Discrepancy trip If told to open and no opening status; If told to close and no closing status; or if told to stop and still has opening or closing status. 2 (note 4 Apr of 43

36 Variable Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority Additional notification CB protection trip (note CB residual trip (note Battery low Low Startup sequence failed Shutdown sequence failed / List of combination of conditions initiating alarm / List of combination of conditions initiating alarm (note (note IO module fault Medium Auxiliary alarm 1 / False / List of H/M/L/E/O/- combination of conditions initiating alarm Note 1: For Alarm Priority, the non-abbreviated description shall be provided in the functional specification document eg. High/Medium/Low/Event/Off-Normal/-. Refer to Attachment A for worked examples. 4 Apr of 43

37 OTHER MISCELLANEOUS ITEMS Parameters Parameter description Main incomer Non Essential Supply present Auxiliary parameter 1 Auxiliary parameter 2 Alarms Main incomer Variable Main incomer Non Essential Supply present Minimum Maximum Default Value setting setting Field input active low Alarm triggers PLC Alarm delay (sec) Visible on HMI Alarm priority (note Control from HMI Additional notification Supply A CB protection trip (note Supply A CB closed False Event Supply B CB protection trip (note Supply B CB closed False Event Busbar under volts (note 4 Apr of 43

38 Variable Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority Additional notification Circuit breaker 1 protective trip (note Circuit breaker 1 closed False Event Circuit breaker 2 protective trip (note Circuit breaker 2 closed False Event Supply equipment comms fault (note MCC fault (note Not in default mode (Replace default mode with either: Local manual, Remote manual or Auto) Off normal Non essential CB protection trip (note Non essential CB closed False Event Non essential CB contactor closed False Event Supply faulted (note Supply 1 under volts (note 4 Apr of 43

39 Variable Field input active low Supply 2 under volts Alarm triggers PLC Alarm delay (sec) Alarm priority (note Additional notification Lighting control Not in default mode (Replace default mode with either: Local manual, Remote manual or Auto) Off normal Other UPS general fault (note UPS line fault (note UPS battery fault (note Intruder detected (note Fire detected (note Chlorine leak 1 / False / List of combination of conditions initiating alarm (note 4 Apr of 43

40 Chlorine leak 2 Variable PLC to PLC comms failed Citect server to server comms failed FDIO comms failed DeviceNet comms failed Site comms failed Field input active low Alarm triggers / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm PLC Alarm delay (sec) Alarm priority (note (note (note (note (note (note Additional notification 4 Apr of 43

41 Variable Field input active low Alarm triggers PLC Alarm delay (sec) Alarm priority Site power failed (note Auxiliary alarm 1 Auxiliary alarm 2 / False / List of combination of conditions initiating alarm / False / List of combination of conditions initiating alarm H/M/L/E/O/- H/M/L/E/O/- Additional notification Data Reporting: Define any data reporting requirements in tabular format. Where applicable, standard drive and valve maintenance statistics shall be provided. Standard drive statistics: Hours Run, Hours Available, Number of Starts (FWD/REV), Hours Faulted, % Utilisation, % Availability, Average Current, Number of Faults and Fault History. Standard valve statistics: Number of Operations, Hours Operated, Hours Available, Hours Faulted, % Utilisation, % Availability, Number of Faults and Fault History. The tables below shall be used in the functional specification and shall not be modified unless ActewAGL gives approval. All rows that are not applicable to the particular item shall be deleted. Refer to Attachment A for worked examples. Averaging type Description Rolling /?? hours Value 4 Apr of 43

42 Description Value Averaging sample rate?? sec /?? min Totaliser 1 period Start and end times Totaliser 1 engineering units Unit of measurement Totaliser 2 period Start and end times Totaliser 2 engineering units Unit of measurement Data Warehouse Reporting requirements Maintenance statistics Standard drive statistics Standard valve statistics Special reporting requirements Detail requirements Operational statistics Report period Daily / monthly / other Averaging type is rolling Averaging sample rate?? sec /?? min Minimum value (with time) Maximum value (with time) Percentile?? th Totaliser Totaliser engineering units Unit of measurement Production or Consumption Ratio Define units of comparison Refer to Attachment A for worked examples Control Source: Identify the location of the I/O devices and the controlling PLC/RTU. PLC/RTU FDIO MCC 4 Apr of 43

43 ????PC????TC????MC References: List the references that will provide additional information to guide the programmer. Eg. Existing O&M manuals or third party operational documentation, etc. ATTACHMENTS A. FUNCTIONAL SPECIFICATION - EXAMPLES A typical vertical slice through the LMWQCC Specification will be provided upon request. This will be provided to illustrate the application of these Guidelines and shows the format, content and wording required in the development of the Specification. 4 Apr of 43

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

SEC 3500 OI- StatCast RS232 Gas Status Text Broadcast Configuration Manual

SEC 3500 OI- StatCast RS232 Gas Status Text Broadcast Configuration Manual SEC 3500 OI- StatCast RS232 Gas Status Text Broadcast August, 2006 Sensor Electronics Corporation 5500 Lincoln Drive USA (952) 938-9486 Table Of Contents: Intended Audience... 3 Purpose...3 Overview...

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-2 EFFECTIVE: 02/26/10 SUPERSEDES: 02/14/07 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Design Standard DS70-02

Design Standard DS70-02 Assets Delivery Group Infrastructure Design Branch Design Standard DS70-02 VERSION 1 REVISION 3 FEBRUARY 2017 FOREWORD Chlorine Design Standards are prepared to ensure that the Water Corporation s staff,

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Practical Distributed Control Systems (DCS) for Engineers & Technicians. Contents

Practical Distributed Control Systems (DCS) for Engineers & Technicians. Contents Practical Distributed Control Systems (DCS) for Engineers & Technicians Contents Chapter 1 Introduction to Computer Based Control Systems 1 1.1 Introduction to computer based measurement and control systems

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

V1.21: (Required for All Dryers with Static Sampler or Incoming MST Sensor, Good for All Dryers)

V1.21: (Required for All Dryers with Static Sampler or Incoming MST Sensor, Good for All Dryers) QuadraTouch Pro Software Update Change Log Official Release vs. Beta Release (How to tell): Tools -> System Tools -> System Information and look for Official Release or Beta Release in the bottom right

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch. Training Title ADVANCED GC PROCESS Training Duration 5 days Training Venue and Dates Advanced GC Process 5 17 21 February, 2019 $4,000 Dubai, UAE Trainings will be conducted in any of the 5 star hotels.

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR Section 11263 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of chlorine leak detectors as shown on Plans and specified herein. 1.02 MEASUREMENT AND PAYMENT No separate

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System UHF Partial Discharge Monitoring System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial

More information

QuadraTouch Pro Software Manual Dryer Control System

QuadraTouch Pro Software Manual Dryer Control System QuadraTouch Pro Software Manual Dryer Control System Software is constantly changing. Make sure you are up to date with Sukup s newest software. New software and manuals are available for download at:

More information

Sensaphone 400 Telemetry System Integration

Sensaphone 400 Telemetry System Integration Application Note 003 Version 001 07 Oct 2014 Sensaphone 400 Telemetry System Integration The Sensaphone Model 400 is an alarm dialer device that is capable of calling out to one or more telephone numbers

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

IE Code IE Competency Title Credit OAC Ref.

IE Code IE Competency Title Credit OAC Ref. Compulsory Workplace Competency Standards Level Four IE Code IE Competency Title Credit OAC Ref. IE119-4WC Design and draw electrical and electronic drawings including schematics, 4 F5 maintain documentation

More information

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS. CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS Table of Contents 2.A.1 SCADA Standards 2.5-2 2.A.1.1 Generators 2.5-2 2.A.1.2 Building

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

Ridley Terminals Canada. Site HMI Station. In Central Office. Prepared by: Wayne Leung Controls Specialist. QCA Systems Limited

Ridley Terminals Canada. Site HMI Station. In Central Office. Prepared by: Wayne Leung Controls Specialist. QCA Systems Limited QCA Systems Limited Operation Manual Ridley Terminals Canada In Central Office Prepared by: Wayne Leung Controls Specialist QCA Systems Limited Version: 0 Date: February 28, 2013 TABLE OF CONTENTS 1.0

More information

Tender Document. MR 193/ Design, Supply & Commission New Control Panel for Ruston 16RK270 Generator

Tender Document. MR 193/ Design, Supply & Commission New Control Panel for Ruston 16RK270 Generator Tender Document MR 193/2017 - Design, Supply & Commission New Control Panel for Ruston 16RK270 Fiji Electricity Authority Generation 17-Jul-17 Tender Submission - Instruction to bidders It is mandatory

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list OPERATOR'S MANUAL Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax:

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Functional Safety: the Next Edition of IEC 61511

Functional Safety: the Next Edition of IEC 61511 HazAus2015/1507 Functional Safety: the Next Edition of IEC 61511 Mirek Generowicz Engineering Manager I&E Systems Pty Ltd Level 2, 445 Hay Street Perth WA 6000 Abstract The functional safety standard IEC

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller MPT Electric Fire Pump Controller Alarm Messages and Guide This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for Metron MPT Fire Pump Controllers

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts

More information

MT Alliance Refrigeration Technician s Manual

MT Alliance Refrigeration Technician s Manual MICRO THERMO TECHNOLOGIES MT Alliance Refrigeration Technician s Manual Document No. 71-MTA-1007-R3.1 V4.1 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

DELOMATIC 400, DM-400 HYDRO

DELOMATIC 400, DM-400 HYDRO Delomatic 400 HYDRO controller OPERATOR S MANUAL DELOMATIC 400, DM-400 HYDRO Functional description User interface Log books Alarm handling Document no.: 4189340880A SW version 1.0 or later Table of contents

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

PRODUCT REVIEW Honeywell HC900 Hybrid Vacuum Furnace Control System

PRODUCT REVIEW Honeywell HC900 Hybrid Vacuum Furnace Control System PRODUCT REVIEW Honeywell HC900 Hybrid Vacuum Furnace Control System Making a Difference VAC AERO Control Systems With heat treaters under increasing pressure to maximize plant efficiency and minimize costs,

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS PROGRAMMABLE THERMOSTAT MODEL 3314080.000 BLACK 3314080.015 WHITE USA SERVICE OFFICE Dometic Corporation 1120 North Main Street Elkhart, IN 46514

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

E-16 Main Engine Remote Control System

E-16 Main Engine Remote Control System Guideline No.E-16 (201510) E-16 Main Engine Remote Control System Issued date: 20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC/TS 62443-1-1 Edition 1.0 2009-07 colour inside Industrial communication networks Network and system security Part 1-1: Terminology, concepts and models INTERNATIONAL ELECTROTECHNICAL

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options Table 4 External Maintenance Switch Configuration Options External Maintenance Switch Options Installed with Interlock Option Option Auxiliary Contact Status open = On Test position or Maintenance position,

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

w SYSTEM DESCRIPTION The Hu//Lyophi/izer System (LP-0106) performs the freeze-drying of liquid pharmaceutical product. It has a 300 ft2 shelf area

w SYSTEM DESCRIPTION The Hu//Lyophi/izer System (LP-0106) performs the freeze-drying of liquid pharmaceutical product. It has a 300 ft2 shelf area w SYSTEM DESCRIPTION The Hu//Lyophi/izer System (LP-0106) performs the freeze-drying of liquid pharmaceutical product. It has a 300 ft2 shelf area which will accommodate the processing of not less than

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Flostop TS D7E and A8E. Operation Manual

Flostop TS D7E and A8E. Operation Manual Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany

More information

Operation Manual. Programmable Logic Controller

Operation Manual. Programmable Logic Controller Operation Manual Programmable Logic Controller Part No. 9983-0000-E01 / January 2018 OPERATION MANUAL TABLE OF CONTENTS CUSTOMER SERVICE 3 CONTACT INFORMATION 3 ORDER INFORMATION 3 INTRODUCTION 4 THE PROCESS

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

Networked Access Control Panel. Installation Guide

Networked Access Control Panel. Installation Guide XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller Wallace & Tiernan s & Analysers ChemTrim Disinfection Introduction The ChemTrim Disinfection is a modern, dedicated controller incorporating the latest advanced electronics and process control application

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list OPERATOR'S MANUAL Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax:

More information

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011 October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Certification Report of the ST 3000 Pressure Transmitter with HART 6 Certification Report of the ST 3000 Pressure Transmitter with HART 6 Revision No.: 2.4 Date: Report Number: 2010-Mar-18 SAS-190/2006T Product: ST 3000 Pressure Transmitter with HART 6 Customer: Order Number:

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control MULTI-LINE 2 APPLICATION NOTES Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control Application description Needed options Wiring diagrams Functional description

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

VAC PLC. System Description

VAC PLC. System Description VAC PLC System Description Contents 1 General... 5 1.1 Expressions and phrases... 5 1.2 Locations... 5 1.3 Abbreviations and terms... 6 1.4 Function... 6 1.5 Parts... 7 1.5.1 PLC... 7 1.5.2 Point IO...

More information

MHC Series Sensors

MHC Series Sensors MHC - 4000 Series Sensors Smart Sensors for Permanent Installation Shaft Speeds above 30 RPM & 0.25-60 RPM Sigma Sensors for Intermittant Operation Kittiwake Holroyd Ltd A Kittiwake Group Company The MHC

More information

Automation and Energy Efficiency of Industrial Refrigeration Systems

Automation and Energy Efficiency of Industrial Refrigeration Systems Automation and Energy Efficiency of Industrial Refrigeration Systems E360 Forum Chicago, IL October 5, 2017 Mike Micak Director of Sales Logix Controls Introduction Management thinker Peter Drucker was

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

Ice Rink (Single and Dual Configurations) Custom Control Features

Ice Rink (Single and Dual Configurations) Custom Control Features & M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump

More information