Annexure - 1. Detectors: Fire Alarm Control Panel :

Size: px
Start display at page:

Download "Annexure - 1. Detectors: Fire Alarm Control Panel :"

Transcription

1 Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP), loop driver cards, Repeater Panel, Detectors and associated Testing kit, for performing the major functions as below: i) Detection of fire in its incipient stage and give an audio-visual annunciation at specified locations / backup location with quick and exact identification of the fire location as well as operate auxiliary devices as programmed. ii) Supervise and monitor all Analogue addressable detectors for normal, trouble and alarm conditions. iii) Display information associated with the fire alarm condition, including type and location within the protected premises. Detectors: Fire Alarm Control Panel : The detectors shall be Analogue Addressable type and suitable for connection to the control panel via a two-wire loop circuit (class A wiring). It shall have dual alarm and power LED s, which shall flash under normal conditions, indicating that the detector is operational and in regular communication with the control panel. Both LED s shall be placed into steady illumination mode by the control panel, indicating that an alarm condition has been detected. An output connection shall also be provided in the base to connect an external remote alarm/response LED. Compatible Plug in type bases shall be supplied with all the detectors, MCPs, sounders etc. The bases shall be equipped with field terminals capable of securing field wire sizes up-to 1.5 sqmm. The Networked Intelligent Addressable Fire Alarm Control Panel (FACP) shall consist of 3 nos. of addressable Loop driver cards, Communication card for repeater panel located at around 500 meter distance, TCP/IP Network card, 240V AC power supply input and in-built battery backup. The capacity of battery (AH) shall be selected so as to operate the Fire alarm system control panel, repeater panel, detectors and other components for 24 hours in standby mode plus 30 mins. in alarm mode. 1. The Fire Alarm Control Panel shall have a operator interface control and annunciation panel with a backlit liquid crystal display, individual colour coded system status LED s, and an alphanumeric keypad for the field programming and control of the fire alarm system. The FACP shall control and communicate with the addressable detectors, addressable modules, repeator panel, annunciators and other system controlled devices like Audio Alarm hooter, Fire Contact output and Alarm output. Annexure It shall be possible to. Enable, disable or adjust sensitivity of any addressable device through the system keypad or operator terminal and store events in a non-volatile memory and generate system status reports.. Provide Zoning facility (at least 10 nos of independent zones and their respective LED indications), Alarm threshold adjustment (for pre-signal alarm signal), Environmental Effect Compensation, Alarm verification, Disabling of detectors, detection of field wiring faults, detector mismatch, Power failure auto restart etc.. Test the functioning of all modules, detectors, healthiness of loop wiring, etc. and reporting of all the troubles online.. Remote Program, configuration and monitoring of FACP via TCP/IP network card (Relavant software to be provided by bidder). 3. Input Signal Processing at FACP. The control panel and loop cards shall have facility for connection via a fully supervised two-wire loop circuit (class A wiring).. Each loop driver card shall be able to handle detector inputs.. Reverse polarity or fault in the field wiring shall not damage the detector.. Reporting of fire alarms shall have priority over faults. However, provision shall be made to see all the fire and fault alarms. Page 1 of 4

2 Item Enclosure Other Components (i) Active Repeater Panel and compatible extension cable 4. Malfunction Monitoring in FACP All the detection line circuits shall be monitored against open circuit, short circuit and ground faults. If malfunction occurs in any detection line, the control panel shall indicate a trouble condition for that detection line. In addition, the following criteria shall also be met:. Fault in one detection line shall not affect the functioning of other detection lines. A single open circuit shall not inhibit the detection capability of a detection circuit; the remaining circuit should still remain functional.. A short circuit shall not inhibit the detection capability of a detection circuit.. A single Ground fault shall not inhibit the detection capability of a detection line.. The cabinets of FAS control panel shall be suitable for wall mounting.. The cabinets shall be primed and powder coated with a corrosion resistant pain with manufacturer's standard finish.. The panel shall have front door with standard industrial key-lock facility.. The cabinet shall have gasket sealing with ingress protection class IP31 or higher. Quantities as per BOQ Provision shall be made in the Fire alarm main control panel for connecting repeater panel which will be located at a backup location around 500 meters away. The repeater panel should be capable of displaying all essential LED indications available in the main control panel. It shall also be equipped with an in built hooter, which can be silenced locally or from the control panel itself. It shall be equipped with LCD display which should display the detector no, zone no. & messages in case of fire / trouble. It shall be an active unit, shall have push buttons for Silence / Mute, Acknowledge, Reset etc. Pressing any of these switches shall cause relevant action to be initiated from the control panel. Cable distance between Control panel & repeater panels shall be around 500 meter. Power for repeater panel shall be backed up by battery bank which may either be extended from FACP or a separate battery inside the repeater panel. This battery bank should able to operate the repeater panel for 24 hours in standby mode plus Half an Hour in alarm mode. Annexure - 1 Enclosure: (ii) Optical Smoke Detectors (iii) Multi-criteria Smoke Detectors. The cabinets of repeater panel shall be suitable for wall mounting.. The cabinets shall be primed and powder coated with a corrosion resistant pain with manufacturer's standard finish.. The panel shall have front door with standard industrial key-lock facility.. The cabinet shall have gasket sealing with ingress protection class IP31 or higher. Plug in type Addressable Photo electric-light scattering based Smoke detectors with detector mounting base & required accessories: Optical Smoke detectors shall respond quickly to optically dense smoke (light white smoke), It s sensitivity shall be set through the Fire Alarm Control Panel and Sensitivity may be automatically adjusted by the panel on a time-of-day basis. Using software in the FACP, detectors shall automatically compensate for dust accumulation and other slow environmental changes that may affect their performance. Plug in type Addressable Multiple criteria / Multi-Sensor detectors combined (Photo + Thermal) with detector mounting base & required accessories: The detectors shall incorporate, at least, two separate sensing elements, Infra red photo diode, a photoelectric smoke sensing chamber using the optical scatter principle and thermal detection using a thermistor/ temperature detector. It shall also be possible to configure the detector to work in a degraded mode such as only photoelectric type or only thermal type in case of failure of other sensing element. It shall have built-in automatic compensation for changes in ambient conditions. Page 2 of 4

3 Annexure - 1 Item (iv) Thermal/Heat Detectors (v) Remote/ Repeat Response Indicator (vi) Fault Isolator Module (vii) Manual Call Point [MCP] (viii) Electronic Sounder/ Hooter (ix) Cables (around 500 meters) Plug in type Addressable Heat Detector with detector mounting base & required accessories: The Thermal (heat) detector shall be rate of rise temperature type. It shall use thermistor and microprocessor technology to provide an alarm when the rate of rise in temperature exceeds 10 C/minute (typical) or if the temperature exceeds a threshold of around 58 C. Remote/ Repeat Response Indicator & required accessories: Repeat response indicators shall provide LED indication for the detectors to which it is connected. These are for detectors, whose visual indicators cannot be seen due to physical obstruction. The repeat response indicator shall be capable of working with simple 2- wire connection from the detector. Addressable Fault / Loop isolator module with Surface mounting base & required accessories: In case of a wire-to-wire short, the Fault Isolator Module shall automatically open-circuit (disconnect) the loop. When the short circuit condition is corrected, the Fault Isolator Module shall automatically reconnect the isolated section. It shall not be necessary to replace or reset the Fault Isolator Module after its normal operation. It shall provide LED flashing indication to indicate that the Isolator is operational and shall illuminate steadily to indicate that a short circuit condition has been detected and isolated. Addressable Manual Call Point module with mounting base & required accessories: Manual Call Points (MCP) shall be addressable and comprises of a push button placed in a suitable metallic enclosure with a break glass or fibre front cover, suitable for use in outdoor environment with a "Break glass" message on the glass. Addressable wall mounted electronic Sounder/Hooter with base and required accessories: The electronic Sounders shall have DB level of 90 dbs at 1 meter away. It shall be field programmable without the use of special tools and a multi tone facility. 2C x 1.5 Sq.mm Multistrand Copper, PVC insulated, Overall shielded, FRLS sheathed cable for Fire alarm system for field wiring between fire detectors and FAS Panel inside the existing 25 mm MS conduit or GI flexible conduits at end portions. The cable shall be confirming to IS : 2011 and the PVC insulated copper conductor cables shall be conforming to IS (x) Test Devices and 1. Telescopic Access Pole (1 no.), non-conductive with collapsible Non-whip type of concentric rods of arm length around 4.5 meters. Detector Removal/ 2. Fire Detector Test Devices: Safe test devices allowing testing of detectors compatible with telescopic access pole and the supplied Installation Tool detectors. This shall be include: a) Smoke detector tester - (1 no.) Aerosol Dispenser unit, with Spring-loaded mechanism, shall enable view of the detector LED while testing, including the supply of 3 nos. of Smoke/ aerosol generator canisters (around ml ), with synthetic aerosol to deliver particles replicating those found in real smoke, shall be Oil-free and non-flammable. b) Cordless Thermal detector tester (1 no.) Cordless Heat Detector Tester unit, based on hot air blower principle, capable for fixed temperature, rate-of-rise and combination detectors up to 90 C, along with battery and charging set.. 3. Supply of Detector Installation /Removal tool (1 no.) Installation & removal tool kit compatible for supplied detectors or diameter up to 110 mm and shall be Compatible with the supplied telescopic access pole. 4. Detector Duster (3 nos.) required for cleaning of detectors. it shall be Non-flammable and Non-abrasive. 5. Carrying case (1 No) To carry above safety test devices. Page 3 of 4

4 Annexure - 1 Item 2 Installation Part 2.1 Scope of Installation and commissioning 1. Installation as per drawings provided by NPCIL, testing & commissioning of 3 Loop Fire Alarm Control Panel with loop driver cards and Repeater Panel, all supplied items viz. addressable Detectors, Isolators, MCPs, Sounders with base plate and hardware accessories on turnkey basis. 2. Laying and termination of 2C x 1.5 Sq.mm FRLS cable (internal cabling between FAS panel and other components) with all necessary accessories like cable compression glands, lugs, ferruling, end termination, cable tags, through existing 25 dia MS conduits or supplied flexible conduits at end portions for all types of detectors and peripherals for connectivity with the FAS panel. 3. Installation of MS conduits in trench / wall including clamping / fixing of conduits (required MS conduit accessories to be provided by the vendor), Laying in MS conduits and termination of the supplied Cable between Repeater panel and Fire alarm Panel. 4. From the nearest available 240 V AC power supply source, the vendor has to extend power supply to the FAS Panel and Repeater panel. The required cabling, casing/capping locally is included in the scope of the vendor. 5. The control panel & repeater panel shall be anchored on wall. All non-conducting metallic parts shall be connected to a Grounding bus at the bottom of panels. The grounding bus shall be connected to the grounding system of the building. 2.2 Testing System Integration Test The Fire alarm equipment including various sub units shall be completely wired and interconnected for the purpose of integrated tests. (SIT) Fire and fault alarm conditions shall be simulated on each line and channel and the complete operational sequence shall be checked. The channels shall be tested for their capability for various detector combinations and types of detectors. The following tests shall be simulated, including any other test as required: i) Single Fire Alarm, Multiple alarms in single loop & multiple loops ii) Single fault and Multiple faults (Earth fault, open circuit and short circuit fault) iii) Multiple alarms & Multiple faults iv) System diagnostic tests v) System response time, time taken for sound mute/ acknowledge & reset actions at various locations etc. shall be checked. Acceptance criterion The reliable operation of the supplied FAS has to be demonstrated after testing and commissioning by conducting a test run of the entire system for one week (24x7), during which no failure of the system shall occur. 2.3 Documentation Submission of FAS manuals covering Specification, Installation, commissioning and troubleshooting, operation and maintenance manuals. This shall also include (i) As Built Drawings & Termination details. (ii) Equipment installation and tagging (iii) Factory test reports. (iv) International standard compliance certificates (v) Warranty certificate (vi) Site test (SIT) reports. 2.4 Training On site Training of the FAS configuration, layout, Troubleshooting and operation, preventive maintenance, fault identification and rectification to NPCIL persons shall be provided by persons authorised from OEM without any additional cost to NPCIL. Page 4 of 4

5 Annexure - 2 Compliance sheet to be submitted by Bidder along with the bid document Sl. No. Description Remarks for Compliance 1 As a part of technical offer, the Tenderer shall enclose the Catalogs / brochures of the offered equipment along with General Arrangement / drawings / Dimensional details of proposed Fire Alarm System (FAS) indicatng mounting arrangement of panels, detectors, cable entry, gland plates, etc. Thetype of batteries for the desired reliable operation, battery capacicty calculation to be submitted along with the bid. Any limiting factor in terms of cable length, cable resistance/capacitance or any other parameter shall be clearly specified. 2 The TENDERER shall confirm that the make / model offered FAS and other components are conforming to the Technical specifications and scope. Item wise Bill of material listing all devices indicating the make, type, applicable standards, quantity etc. to be enclosed. The FAS Shall Conform to any of the relevant Standards like UL/FMRC/VdS/EN54/IS 15908: 2011 for which the certificates shall be furnished. 3 In case the bidder is not an OEM of FAS systems, a certificate from the Original Equipment Manufacturer (OEM) shall be submitted indicating that, "The FAS system to be supplied is conforming to the technical specification requirements. Also other components to be supplied along with the FAS are suitable for the FAS control panel." 4 The FAS and associated equipments shall be covered under comprehensive on site warranty for 12 months including free maintenance and replacement of the faulty parts and labour from the date of the final acceptance at RAPP -7&8 site. During warranty period service support shall be extended in all working days and holidays and beyond working hours on requirement basis for maintenance services. The boarding/ lodging / transportation of the service personnel during the warranty period shall be included in scope of the bidder with out any additional cost to NPCIL. 5 A "letter of Assurance" from OEM to provide comprehensive Maintenance and service support, including replacement of defective parts and supply of spares for the FAS system at least for 10 years excluding the warranty period of 12 months to be submitted, indicating the authorised service centres in India along with name of incharge, address, phone nos. etc. for verification. Supply Part 6 One set of certified copy of the factory routine test reports of the FAS control panel, Repeater panel and detectors and Procedure and Checklist for Installation, commissioning and integrated testing of the FAS system and other components for NPCIL approval shall be furnished before despatching the equipment along with invoice copy, after which shipping release / Road permit will be issued. 7 Supply of any other components required for complete installation and commissioning of the FAS Panel, repeater panel, detectors and other items, including hardware accessories, clamps and connectors, glands and lugs, laying / termination of cables, earthing cables etc., not specifically indicated in the specifications are also included in the scope of the vendor without any additional cost to NPCIL. Bidder has to take the above into account while bidding. 8 Vendor shall arrange transit insurance coverage of the supplied equipment and accident insurance coverage of all service personnel. NPCIL shall not be responsible for any liabilities arising out of any accident / injury caused to vendor s personnel during installation, commissioning or maintenance services of the equipment. The vendor shall be responsible for any loss or damage during transportation, handling and storage of the system / equipment due to improper packaging / handling. In case of any damage is observed during on site inspection / at time of installation, the vendor has to repair / replace the same at his own cost. Installation and commissioning Part 9 The Supply, commissioning, testing and integration of the FAS system along with repeater panel and detectors, other components, demonstration of operational features shall be executed by a single vendor on turn-key basis under supervision of experienced personnel from the vendor / OEM in consultation with NPCIL representative. 10 Documentations are to be furnished in (1- soft copy in digital media and 1- hard copy for operation, maintenance and troubleshooting etc. after completion of the installation. This shall include Specifications, Block Diagram / GA drawings, description and operational features, Installation, Operation and maintenance manuals, Manufacturer instructions, Wiring diagram & Termination Drawings etc. for the supplied FAS System. 11 The installation of the FAS must be carried out by the vendor without disturbing the existing systems / works at RAPP- 7&8 site. The vendor s persons while working at NPCIL premises shall follow the security rules and regulations of NPCIL. To the extent possible the work shall be carried out during normal hours of NPCIL (9AM-6PM) from Monday to Saturday. However prior permission will be required to work on holidays and beyond office hours on working days. All the required manpower, machinery, tools & tackles for transportation from NPCIL stores to erection site / handling of the equipment during installation and commissioning at the site is included in the scope of the vendor without any additional cost to NPCIL. 12 On successful completion of installation, commissioning, submission of documentation, training covering Operation, Maintenance and Troubleshooting of the FAS system to NPCIL personnel and integrated trial run for 7 days, by authorized representatives of the OEM /Supplier, completion certificate will be issued to initiate the warranty.

6

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI FIRE PROTECTION 1 G.I.PIPES Supplying, installing, testing and commissioning of G.I Pipes confirming to IS 3589 Pt - I Heavy grade with painting, suitable type of supports, anchor fasteners, bolts nuts

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

ZXSe Range Data Sheet

ZXSe Range Data Sheet ZXSe Range Data Sheet Analogue addressable fire alarm control panel Product Overview The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Eligibility Criteria for Participation [Qualification Requirement (QR)]

Eligibility Criteria for Participation [Qualification Requirement (QR)] Eligibility Criteria for Participation [Qualification Requirement (QR)] 1. Only Manufacturers are eligible to Quote: a) Original manufacturers of High Voltage Detector in India will be eligible in the

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

ID50series. intelligent fire alarm panels

ID50series. intelligent fire alarm panels ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features Fire Safety ZXSe Range Analogue addressable fire alarm control panel The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and reliable microprocessor

More information

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GETCO/ENGG/TS/

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

PROJECT: IIT MADRAS RESEARCH PARK-CHENNAI, TECHNICAL SPECIFICATION FOR FIRE ALARM SYSTEM TENDER

PROJECT: IIT MADRAS RESEARCH PARK-CHENNAI, TECHNICAL SPECIFICATION FOR FIRE ALARM SYSTEM TENDER PROJECT: IIT MADRAS RESEARCH PARK-CHENNAI, TECHNICAL SPECIFICATION FOR FIRE ALARM SYSTEM TENDER INDEX S NO DESCRIPTION 1 Introduction 2 Standards & Regulations 3 Fire Detection System 1.0 INTRODUCTION

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

ACP10 & ACP50 Security Systems

ACP10 & ACP50 Security Systems ACP10 & ACP50 Security Systems System Configuration LCD Keypad LCD Keypad LED Keypad LED Keypad 4-wire Bus ACP10 & ACP50 AEX10* AEX10* AEX10* AEX10* * ACP50 Only Control Panels The ACP10 control panel

More information

Scope of Work and Other Terms & Conditions

Scope of Work and Other Terms & Conditions Annexture-II Scope of Work and Other Terms Conditions Sl. 1. Removal Disconnection (i) Removal of existing heating elements, insulation brickwork of the side walls, roof, the doors and the bogie hearth.

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Section 5 Operation To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Figure 5-1 Built-in Touchpad (Seven-Segment Display) Figure 5-2 Model 5230 Remote

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING MODEL ZAC-32 32 ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING 32 HARD WIRED ZONES CAN BE NORMALLY-OPEN OR NORMALLY-CLOSED ZONE WIRING RUNS CAN BE AS FAR AS 10,000 FEET FROM

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

Solution F2. Fire Alarm Control Panels one step ahead.

Solution F2. Fire Alarm Control Panels one step ahead. Solution F2 Fire Alarm Control Panels one step ahead. Sicherheitstechnik Sicherheitstechnik GmbH GmbH The Fire Alarm Control Panel Solution F2 Solution F2 in B2 enclosure (B01090-00) The Concept The Solution

More information

LF /2. Fire Alarm Control Panel. Features:

LF /2. Fire Alarm Control Panel. Features: LF-6100 1/2 Fire Alarm Control Panel Features: Microprocessor Based System Intelligent Distributed System Structure Quick Response Time Fire Alarm in less than 1 Second Capacity of 200/500 Addressable

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

MAZAGON DOCK SHIPBUILDERS LIMITED

MAZAGON DOCK SHIPBUILDERS LIMITED MAZAGON DOCK SHIPBUILDERS LIMITED (Formerly known as Mazagon Dock Ltd.) CIN : U35100MH1934GOI002079 (A Government of India Undertaking) Shipbuilders to the Nation Dockyard Road, Mazagon, Mumbai 400 010.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

ID3000 intelligent. fire alarm panel

ID3000 intelligent. fire alarm panel ID3000 intelligent fire alarm panel features certified to EN54 parts 2 and 4 expandable from 2 to 8 loop capacity up to 198 per loop (99 sensor and 99 modules) 255 fire zones per panel modular design supports

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

DC POWER DISTRIBUTION BOARD

DC POWER DISTRIBUTION BOARD DC POWER DISTRIBUTION BOARD February 2016 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS EED- 50-23 SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS ISSUING AUTHORITY DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI 110011 2 RECORD

More information

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Maintenance Guide 2015 EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

intelligent fire alarm ID60series panels

intelligent fire alarm ID60series panels intelligent fire alarm ID60series panels features LPCB approved to EN54 Parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports advanced detection such as

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

HEAD OFFICE, SECURITY DEPARTMENT

HEAD OFFICE, SECURITY DEPARTMENT BANK OF INDIA HEAD OFFICE, SECURITY DEPARTMENT RATE TO BE QUOTED BY THE VENDOR Sr. no. Description Make Model Unit Rate Tax Total Amount I BURGLAR ALARM SYSTEM A Burglar/Intruder Alarm System.B Control

More information

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 OPERATORS MANUAL AFP-300/400 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02) 9899-4155

More information

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range Fire Detection MINERVA Marine MX T2000 Panel Range Features: Enhances fire detection and eliminates unwanted alarms using fuzzy logic Assists fire fighting and training by providing on-screen risk management

More information

Date of Start and downloading the tender 12 sep 2018

Date of Start and downloading the tender 12 sep 2018 INDRAPRASTHA INSTITUTE OF INFORMATION TECHNOLOGY-DELHI (IIIT-DELHI) Okhla Industrial Estate, Phase III New Delhi 110020 (Tel No 011-26907400, Website: www.iiitd.ac.in) Notice Inviting Tender for Non Comprehensive

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual RE 102 RE - 104 Fire Alarm Control Panel Installation, Commissioning & Operating Manual 1 NOTES: 2 Table of Contents CHAPTER 1: Introduction......4 1.1: System Design & Planning...4 1.2: General....4 1.3:

More information

Addressable Fire Alarm Control System 2100 series

Addressable Fire Alarm Control System 2100 series Addressable Fire Alarm Control System 2100 series It adopts new generation high-speed microprocessor technology that has a data processing speed and a data storage capacity 100 times and 1000 times higher

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Protec Algo-TecTM 6100 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015 Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015 UL and the UL logo are trademarks of UL LLC 2012 GOALS OF INSPECTING AND TESTING POWER SUPPLIES Verify/inspect

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

Request for quotation (RFQ) for goods/services

Request for quotation (RFQ) for goods/services Request for quotation (RFQ) for goods/services Firefighting equipment s and alarm system for UNICEF Warehouse Khartoum - Soba RFQ No: SDPC/89588/SERVICES/RFQ-135 Request for quotation (RFQ) for (Firefighting

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

TENDER CRFQ NO (E-TENDER REF NO.13020)

TENDER CRFQ NO (E-TENDER REF NO.13020) ADDENDUM NO:2 AGAINST TENDER FOR DESIGN, ENGINEERING, SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND POST WARRANTY AMC OF RIM SEAL FIRE PROTECTION SYSTEM FOR BPCL- MUMBAI REFINERY (BPCL MR) TENDER CRFQ

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information