Report on Proposals F2007 Copyright, NFPA NFPA 59

Size: px
Start display at page:

Download "Report on Proposals F2007 Copyright, NFPA NFPA 59"

Transcription

1 Nonvoting LP-Gases at Utility Gas Plants Bruce A. Schwartz, Vienna, VA John L. Ritzmann, Chair (Member Emeritus) Consultant, VA [SE] William J. Young, Secretary Superior Energy Systems, Ltd., OH [M] Richard G. Fredenburg, State of North Carolina, NC [E] James R. Goodchild, Xcel Energy Inc., MN [U] Rep. American Gas Association Richard A. Hoffmann, Hoffmann & Feige, NY [SE] Stanley T. Kastanas, US Department of Transportation, DC [E] Jerry W. Lucas, Heritage Propane, OK [IM] Rep. National Propane Gas Association Thomas J. Macdissi, Metropolitan Utilities District, NE [U] Charlie G. McDaniel, GE Insurance Solutions, WV [I] Robert G. McNulty, Washington Gas Light Company, VA [U] Nancy C. Pehrson, CenterPoint Energy, Inc., MN [U] Kevin L. Ritz, Baltimore Gas & Electric Company, MD [U] Steven D. Ruffcorn, Standby Systems, Inc., MN [M] David J. Stainbrook, Engineered Controls International, Inc., NC [M] James H. Stannard, Jr., Stannard & Company, NJ [SE] Herbert F. Zepp, Smith & Norrington Engineering Corporation, NH [SE] Alternates David Bortnem, Duke Energy, OH [U] (Alt. to Thomas J. Macdissi) William R. Copes, Baltimore Gas & Electric Company, MD [U] (Alt. to Kevin L. Ritz) Swapan Kumar Hazra, Hindustan Aegis LPG Bottling Co., Ltd., India [U] (Alt. to Nancy C. Pehrson) Michael Lee Stroud, Vectren Energy Delivery Inc., IN [U] (Alt. to James R. Goodchild) Bruce J. Swiecicki, National Propane Gas Association, IL [IM] (Alt. to Jerry W. Lucas) Staff Liaison: Theodore C. Lemoff Committee Scope: This Committee shall have primary responsibility for documents on the design, construction, location, installation, operation, and maintenance of refrigerated and nonrefrigerated liquefied petroleum gas plants to the point of introduction into the utility gas distribution system or those plants that are subject to the requirements of Title 49, Code of Federal Regulations, Part 192, Pipeline Safety Law, issued pursuant to the laws in 49 U.S.C. et seq. This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes in the membership may have occurred. A key to classifications is found at the front of this book. The Report of the Technical Committee on LP-Gases at Utility Gas Plants is presented for adoption. This Report was prepared by the Technical Committee on LP-Gases at Utility Gas Plants and proposes for adoption, amendments to NFPA 59, Utility LP-Gas Code, 2004 edition. NFPA is published in Volume 4 of the 2006 National Fire Codes and in separate pamphlet form. This Report has been submitted to letter ballot of the Technical Committee on LP-Gases at Utility Gas Plants, which consists of 16 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report. 59-

2 _ 59-1 Log #79 Final Action: Reject (1.1 Scope) _ Submitter: Mike Osmundson, Lexicon Propane Group Recommendation: Add a new paragraph under 1.1 Scope: Installations that deliver undiluted LP-Gas vapor to two or more customers shall conform to NFPA 58 Liquefied Petroleum Gas Code. Revise the definition of Utility Gas Plant to read: Utility Gas Plant. A plant that stores and vaporizes LP Gas for distribution A fuel gas distribution facility that supplies multiple customers either LP-Gas or LP-Gas gas/air mixtures to a gas distribution system of 10 or more customers. as a supplemental fuel to natural gas or other fuel gas. Add a new paragraph to the Annex: A Some LP-Gas installations which deliver fuel to multiple customers fall under the jurisdiction of the Department of Transportation regulations under 49 CFR Part 192. These LP-Gas systems shall conform to NFPA 58 Liquefied Petroleum Gas Code. Substantiation: This proposal concerns the appropriate application of either NFPA 59 or NFPA 58 to LP-Gas vapor distribution systems and suggests changes to paragraphs 1.1 and The authors recommend that the changes to both paragraphs be considered by the committee as a whole and that the same action be taken on both paragraphs. The proposal is formulated based on certain facts and assumptions as listed: 2. A manual was prepared for the United States Department of Transportation, Research and Special Programs Administration, Office of Pipeline Safety by the National Association of Regulatory Utility Commissioners. The guide entitled, Training Guide for operators of Small LP Gas Systems also refers to NFPA 58 as the only standard which applies to vapor distribution systems. For the 2001 edition of NFPA 59, a proposal was made and accepted to change the definition of the term Utility Gas Plant. This sentence was added: In the United States, utility gas plants are subject to the requirements of Part 192 of the Code for Federal Regulations (49 CFR Part 192). The substantiation given for this proposal was The definition of Utility Gas Plant is revised to be consistent with actual practices. With respect to utility peak shaving plants, this proposal had no impact, however, utility peak shaving plants are not the only LP systems subject to 49 CFR Part 192. Most vapor distribution systems are also subject to Part 192. Changing the definition of Utility Gas Plant had the effect of changing the scope of NFPA 59 and moving the coverage of vapor distribution systems from NFPA 58 to NFPA 59. In effect, the scope of NFPA 59 was changed indirectly and this change is causing unintended consequences. A thorough review of the impact of this change has not been done. The authors of this proposal believe that NFPA 58 should be the governing standard for vapor distribution systems for the following reasons: 1. Vapor distribution systems being discussed here are gas systems which deliver un-diluted LPG vapor as a fuel gas to equipment, dwelling units, or facilities either not owned or not controlled by the person or organization that operates the LPG storage and distribution portions of the system. 2. There are potentially thousands of LPG vapor distribution systems in the US which are impacted by this discussion. For example, the states of New Hampshire, Maine, and Vermont have a combined total of over 1,000 vapor distribution systems. 3. Most vapor distribution systems are on the small end of the scale, delivering gas to relatively few customers. 4. The basic purpose of NFPA standards is to guide users and regulators in methods to minimize the risks inherent in specified activities. 5. The application of NFPA 58 or 59 is mutually exclusive. Only one of these standards governs any specific installation or activity. 6. The intention or requirements of 49 CFR Part 192 is not a direct concern of the application of NFPA 58 or The hazards inherent in operating an LPG vapor distribution are adequately addressed under NFPA 58. This includes storage, transfers, equipment design, installation, fire protection, and operations and maintenance. Any hazards related to delivering a fuel gas to multiple customers are addressed under 49 CFR Part 192 and do not need to be covered by NFPA. 2. When the definition of Utility Gas Plant was changed for 2001 and again for 2004, no information was provided with the proposals showing that NFPA 58 was inadequate in addressing the hazards of vapor distribution systems. The change was made without a thorough review of the effects. 3. Ken Wood of ETS Associates has extensive regulatory experience with vapor distribution systems and based on his experience, in the United States, 49 states currently approve and inspect vapor distribution systems under NFPA 58. Nevada uses NFPA 59 because Nevada rate-regulates these systems. 4. System owners and local AHJs responsible for approving or inspecting LPG systems are not aware of the change in scope between the standards because a user must read NFPA 59 in order to determine that vapor distribution systems do not fall under NFPA 58. Background: NFPA 58 was the original LPG standard first published in NFPA 59 was published beginning in 1949 and was clearly intended for natural gas or manufactured gas distribution utilities for peak shaving purposes. The introduction to the early versions of NFPA 59 states: Public utilities have been concerned about the shortage and steadily increasing demands for gas. To meet the problem, the utilities have increasingly turned to liquefied petroleum gas as a stand-by means to meet peak load requirements. The NFPA Standards on Liquefied Petroleum Gases (NFPA No. 58) as prepared by the Committee on Gases and published herein and in NFPA-NBFU pamphlets No. 58 were used as a general guide until these separate standards were adopted in Since the majority of all types of LPG installations in the United States fall under the scope of NFPA 58, there is far more experience and knowledge in the industry with this standard than with NFPA As a guide to users and regulators to reducing the risks at LPG installations, NFPA 59 presents much less information than NFPA 58. A substantial number of requirements appropriate to the safe operation of LPG systems are not specified in NFPA 59 but appear in NFPA Since many of the vapor distribution systems are owned by small operators and regulators often have multiple responsibilities, any assistance NFPA can give in understanding their standards is helpful. NFPA 58 has an excellent handbook available while NFPA 59 does not. From 1949 forward, vapor distribution systems were governed by NFPA 58 based on each State having the authority to determine which organizations were utilities and which were not. No guidance was given within NFPA 58 or 59 on this definition. The industry consensus was that NFPA 59 considered a utility to be a municipal or investor organization delivering natural gas or manufactured gas to large numbers of customers. This means that vapor distribution systems were included in NFPA 58 since they were excluded from NFPA 59. In 1970, the Federal Government established rules governing transportation of gas. In these rules, the term operator is used for organizations which transport gas. The term utility is not used but many operators are utilities. Since the DOT regulations also include very small gas distribution systems as operators, the definition of the word utility became muddied when compared to NFPA. Since confusion was arising on the subject of which standard applied to vapor distribution systems, two resources targeted to regulators, inspectors, and users addressed this issue: 1. An article was written by Ken Wood and Richard Marini to clarify which LP systems are jurisdictional. This article was published and included as Supplement 2 in the 1998, 2001, and 2004 Editions of the NFPA 58 Handbook and clearly identifies NFPA 58 as the governing standard. 8. The NFPA 58 committee has not felt the need to require relief valve testing for non-utility systems regardless of size. To move the coverage of vapor distribution systems under NFPA 59 will require all of these systems to test or replace relief valves every five years. For systems which must operate 24 hours a day, 365 days per year, changing relief valves will be a significant hardship since only the largest systems have Multiport style relief valves. A substantial portion of vapor distribution systems use one or more 1,000 gallon tanks for storage. Changing relief valves in all of these tanks every five years may actually increase the hazard at these installations. The proposed changes to paragraph definition of utility gas plant, remove references to 10 or more customers to prevent confusion with CFR 192. A reference to multiple customers is used to exclude industrial LP/air standby systems. Note: While not contained in this proposal, the authors of this proposal suggest that suitable language be inserted into NFPA 58 to identify NFPA 58 as governing vapor distribution systems. This is intended to allow readers to confirm which standard applies to vapor distribution systems without the necessity of reading both. Mike Osmundson of Lexicon Propane Group, Ken Wood of ETS Associates, and Chris Mohler of Chesmont Engineering are joint authors of this proposal. This is not original material; its reference/source is as follows: Material developed by proposal authors and others in the LP Gas industry. 59-2

3 are made or where LP-Gas is vented to the atmosphere in the course of transfer operations. [58:3.3.54] Portable Tank (or Skid Tank). A container of more than 1000-lb (454-kg) water capacity that is mounted on skids or runners, is equipped with protected container appurtenances, and is used to transport LP-Gas. [58:3.3.57] Pressure Relief Device. A device designed to open to prevent a rise of internal pressure in excess of a specified value due to emergency or abnormal conditions. [58:3.3.58] psi. Pounds per square inch. [58:3.3.59] psia. Pounds per square inch, absolute. [58:3.3.60] psig. Pounds per square inch gauge. [58:3.3.61] First-Stage Regulator. A pressure regulator for LP-Gas vapor service designed to reduce pressure from the container to 10.0 psig (69 kpag) or less. [58: ] UL. Underwriters Laboratories Inc. [58:3.3.0] Excess-Flow Valve (or Excess-Flow Check Valve). A valve designed to close when the liquid or vapor passing through it exceeds a prescribed flow rate. [58: ] * Internal Valve. A container primary shutoff valve having the following features: (1) The seat and seat disc remain inside the container so that damage to parts exterior to the container or mating flange does not prevent effective sealing of the valve; (2) The valve is designed for the addition of a means for remote closure and is also designed for automatic shutoff when the flow through the valve exceeds its maximum rated flow capacity or when pump actuation differential pressure drops to a predetermined point. [58: ] Pressure Relief Valve. A type of pressure relief device designed to both open and close to maintain internal fluid pressure. [58: ] Vaporizing Burner (Self-Vaporizing Liquid Burner). A burner that also vaporizes liquid LP-Gas prior to burning it. [58:3.3.74] Water Capacity. The amount of water at 60 F (16 C) required to fill a container. [58:3.3.77] Substantiation: Terms are used within NFPA 59 but are not defined in Chapter 3. in Part Accept all the proposed definitions except: Cylinder, Diameter, Vehicle Fuel Dispensers, DOT, Fixed Piping System, Magnetic Gauge, Piping System, First Stage Regulator, and Vaporizing Burner. Committee Statement: The terms not accepted are not used in NFPA Log #8 Final Action: Accept (3.3.2 Container) _ Complete extraction reference to read [58:3.3.14]. Committee Meeting Action: Reject Committee Statement: The committee disagrees with the addition of fuel gas distribution system to the definition. Fuel gas distribution systems are not within the scope of NFPA 59. The proposed deletion of 10 or more customers will cause confusion and expand the definition to facilities other than intended. Comment on Affirmative: RITZMANN, J.: Although I am affirming the committee s actions, I would welcome further discussion on this subject in the form of comments to reconsider or to consider additional changes to this statement of Scope. The changes that were made in the previous edition were an attempt to eliminate applying the code to some facilities but not others based on the ownership of the facility. Ownership was not seen as a relevant safety issue. There was no conscious attempt to expand or limit the applicability of the regulations. I believe this needs to be discussed further by representatives of all facets of the industry to resolve any outstanding dissention Log #7 Final Action: Accept in Part (Chapter 3) _ Recommendation: Add the following definitions to Chapter 3: API. American Petroleum Institute. [58:3.3.4] ASME. American Society of Mechanical Engineers.[58:3.3.6] ASME Code. The American Society of Mechanical Engineers Boiler and Pressure Vessel Code.[58:3.3.7] ASME Container. A container constructed in accordance with the ASME Code.[58:3.3.8] ASTM. American Society for Testing and Materials.[58:3.3.9] Cargo Tank. A container that is used to transport LP-Gas as liquid cargo and is either mounted on a conventional truck chassis or is an integral part of a cargo transporting vehicle.[58:3.3.11] Container Appurtenances. Devices installed in container openings for safety, control, or operating purposes.[58:3.3.15] Cylinder. A container constructed in accordance with U.S. Department of Transportation specifications, Title 49, Code of Federal Regulations.[58:3.3.17] Diameter. The length of a straight line passing through the center of a circle, terminating at the periphery. Vehicle Fuel Dispenser. A device or system designed to transfer and measure LP-Gas into engine fuel and mobile containers on vehicles.[58: ] DOT. U.S. Department of Transportation.[58:3.3.22] Fixed Piping System. Piping, valves, and fittings permanently installed in a location to connect the source of the LP-Gas to the utilization equipment.[58:3.3.25] Gallon. U.S. Standard. 1 U.S. gal = Imperial gal = 231 in.3 = L.[58:3.3.27] Fixed Liquid Level Gauge. A liquid level indicator that uses a positive shutoff vent valve to indicate that the liquid level in a container being filled has reached the minimum point at which the indicator communicates with the liquid level in the container.[58: ] Fixed Maximum Liquid Level Gauge. A fixed liquid level gauge that indicates the liquid level at which the container is filled to its maximum permitted filling limit.[58: ] Float Gauge. A gauge constructed with an element installed inside the container that floats on the liquid surface and transmits its position to a device outside the container to indicate the liquid level.[58: ] Magnetic Gauge. See Float Gauge. Rotary Gauge. A variable liquid level gauge consisting of a small positive shutoff vent valve located at the outside end of a tube that has a bent end inside the container and can be manually rotated to determine the liquid level in the container. It is equipped with a pointer and an outside dial to indicate the liquid level.[58: ] Slip Tube Gauge. A variable liquid level gauge in which a relatively small positive shutoff valve is located at the outside end of a straight tube, normally installed vertically, that communicates with the container interior.[58: ] ICC. U.S. Interstate Commerce Commission.[58:3.3.32] Industrial Occupancy. Includes factories that manufacture products of all kinds and properties devoted to operations such as processing, assembling, mixing, packaging, finishing or decorating, and repairing. [58:3.3.34] kpa. Absolute pressure in kilo-pascals. [58:3.3.35] kpag. Gauge pressure in kilo-pascals. [58:3.3.36] Maximum Allowable Working Pressure (MAWP). The maximum pressure at which a pressure vessel is to operate is described by the ASME Boiler and Pressure Vessel Code. [58:3.3.40] MPa. Absolute pressure in mega-pascals. [58:3.3.45] MPag. Gauge pressure in mega-pascals. [58:3.3.46] Piping Systems. Pipe, tubing, hose, and flexible rubber or metallic hose connectors with valves and fittings made into complete systems for conveying LP-Gas from one point to another in either the liquid or the vapor state at various pressures. [58:3.3.53] Point of Transfer. The location where connections and disconnections Log #9 Final Action: Accept (3.3.5 Fire Protection) _ Fire Protection for the purposes of this code standard shall be defined in the broad sense to include fire prevention, fire detection, and fire suppression. [58:3.3.24] Substantiation: Change makes extraction text identical. Reference is made specific. _ 59-5 Log #10 Final Action: Accept (3.3.6 Gas) _ Liquefied petroleum gas in either the liquid or vapor state. The more specific terms liquid LP-Gas or vapor LP-Gas are normally used for clarity. [58:3.3.28] Substantiation: Change makes extraction text identical. Reference is made specific.

4 59-6 Log #11 Final Action: Accept (3.3.7 Gas-Air Mixer) _ Log #19 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.29]. ( Vaporizer) _ Recommendation: Complete extraction reference to read [58:3.3.73] Log #12 Final Action: Accept (3.3.8 Liquefied Petroleum Gas) _ Log #20 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.37]. ( Direct-Fired Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #13 Final Action: Accept (3.3.9 Mounded Container) _ Log #21 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.43]. ( Electric Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #14 Final Action: Accept ( psia) _ Log #22 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.60]. ( Direct Immersion Electric Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #15 Final Action: Accept ( psig) _ Log #23 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.61]. ( Indirect Electric Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #16 Final Action: Accept ( Refrigerated LP-Gas) _ Log #24 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.63]. ( Indirect (or Indirect-Fired) Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #17 Final Action: Accept ( Sources of Ignition) _ Log #25 Final Action: Accept Recommendation: Complete extraction reference to read [58:3.3.67]. ( Waterbath (or Immersion-Type) Vaporizer) _ Recommendation: Complete extraction reference to read [58: ] Log #18 Final Action: Accept ( Special Protection) _ Recommendation: Complete extraction reference to read [58:3.3.68]. 59-4

5 and valves Log #CP6 Final Action: Accept (3.x Permitted) _ Log #26 Final Action: Accept Submitter: Technical Committee on LP-Gases at Utility Gas Plants, ( ) Recommendation: Add a new definition extracted from NFPA 58: Permitted. Allowed or acceptable, and not requiring a permit (a document granting permission) to be secured. Substantiation: To add a definition of a term used in the code. _ Recommendation: Delete The installation of lightning protection equipment shall not be required on LP Gas storage containers. [58: ] Substantiation: The section is redundant to the wording in Committee Statement: Accept the proposal and delete A Log #5 Final Action: Reject (4.1, 4.9, 7.9, , , (5), , (B)(4), (A)(O), , (7), ) _ Log #27 Final Action: Accept in Principle Submitter: Denyse DuBrucq, AirWars Defense ( ) Recommendation: Revise or add the following sections: in emergency procedures. Persons should know and understand use of Liquid Nitrogen portable and fixed fire control procedures and when each technique is appropriate. This training Regardless of source of ignition, were an explosion to occur or fire break out, Liquid Nitrogen fire control methods shall be employed to control, contain and end the crisis. 7.9 Protection of facility and its contents using Liquid Nitrogen will quell fires instantly and gel or solidify spillage for quick recovery and containment. It will freeze closed pipes spilling forth product, gaseous or liquid, so they can be capped or repaired immediately. Knowledge of location of portable units throughout the facility must be known to gather them to the scene of a crisis. Fixed Liquid Nitrogen Crisis Control equipment feeder locations and directing of Liquid Nitrogen flow procedures must be known and used by building personnel and local fire department personnel All buildings routinely storing and housing usage of gas products must be equipped with fixed Liquid Nitrogen crisis control equipment with instructions on its use and configuration to serve locations within posted on walls and in manual for local fire department Loading docks for trucks shall have portable Liquid Nitrogen crisis control equipment, and, where appropriate, fixed Liquid Nitrogen fire control installed (5) Location of portable Liquid Nitrogen crisis control equipment and instruction in use; and use, direction of flow and fire department instructions for fixed Liquid Nitrogen fire control systems Maintenance of portable Liquid Nitrogen crisis control equipment _ Recommendation: Delete Grounding and bonding shall not be required on LP Gas systems. [58: ] Substantiation: The section is in direct conflict with long established in Principle 1. Revise to read: * Grounding and bonding for static protection shall not be required on LP-Gas systems. 2. Revise A to read: A Because liquefied petroleum gas is contained in a closed system of piping and equipment, the system need not be electrically conductive or electrically bonded for protection against static electricity. [58: A ] Static grounding or bonding protection is not required where tank cars, tank vehicles, or marine equipment are loaded or unloaded by conductive or nonconductive hose, flexible metallic tubing, or pipe connections through or from tight outlets (top or bottom) where both halves of metallic couplings are in contact. For information on grounding and bonding for protection against static electricity, see NFPA 77, Recommended Practice on Static Electricity. 3. Delete A Committee Statement: The concept of the proposal is accepted and reference to static electricity is added. Relevant annex text from A is relocated. includes topping off Liquid Nitrogen twice a week being sure to top off every Log #28 Final Action: Accept in Principle unit on the premises and carried on vehicles associated with the premises. ( ) (B)(4) Fire protection Liquid Nitrogen or water systems (A)(O) Crisis control possible with portable Liquid Nitrogen equipment, and with fixed Liquid Nitrogen equipment with fire department _ Liquid Nitrogen supply. (This should precede (1) because once the shut down Fixed electrical equipment and wiring installed within a classified area or isolation occurs one cannot get in to control the situation with Liquid specified in Table shall be installed in accordance with NFPA 70, Nitrogen and you lose all the contents.) National Electrical Code. Fixed electrical equipment and wiring installed Leakages in piping may be repaired with freezing the contents in the within the classified areas specified in Table shall comply with Table pipe if a valve cannot stop leakage so repair or capping can be carried out and shall be installed in accordance with NFPA 70, National Electrical using portable Liquid Nitrogen equipment. Code, for hazardous locations. Substantiation: The text from was better suited for this section, and is (7) NFPA XX, Standard for fixed Liquid Nitrogen crisis control specific to hazardous locations. equipment. in Principle Nitrogen drowning must be recognized and its remedy defined in all Revise text to read as follows: personnel safety training opportunities Fixed electrical equipment and wiring installed within the classified If there is no odor, no cause for the individual to be passed out in a working areas specified in Table shall comply with Table and shall be environment, the person discovering the situation should yell to notify others installed in accordance with NFPA 70, National Electrical Code. and immediately get breathing equipment for him/herself and for the victim. Committee Statement: Accepted with the deletion of for hazardous Put the breathing apparatus on. Then approach the victim, install the breathing apparatus and begin artificial respiration. If no breathing apparatus is available use large plastic bags to contain fresh air for oneself and for the victim. Tie the locations, which is redundant. filled bag over one s face and have material to do the same to hold the filled bag of gas over the victim s face tying loosely at the neck so as not to strangle the victim. Then apply artificial respiration. Once victim is breathing, help him/ Log #82 Final Action: Accept in Principle in Part her up and take him from the location or carry victim out and get professional (Table , , , , , 5.9.3, , 8.2.3, ) EMT help to evaluate the victim s condition. _ THIS SHOULD BE POSTED ANYWHERE NITROGEN GAS CAN BE Submitter: Steven D. Ruffcorn, Standby Systems, Inc. Recommendation: Eliminate all dependencies within NFPA 59 upon nonextracted NFPA 58 provisions. Apparently affected NFPA 59 sections: Table RELEASED IN ITS PURE FORM. The above statement may be placed in the Annex A section, Explanatory ; ; ; ; ; 5.9.3; ; 8.2.3; ; *; Material, but it would be more noticed and useful in the text of the Code itself ; and Substantiation: One should be able to capture by extreme cooling if escaping Substantiation: Goal: Make NFPA 59 a complete, standalone resource. from tank, pipeline, or gas line if leak is evident to prevent explosion and *Note: A current proposal by this submitter for revising 59: eliminates repair part to quell by O2 starvation and cooling. one dependency. Note: Supporting material is available for review at NFPA Headquarters. Following are mandatory provisions of NFPA which include Committee Meeting Action: Reject Committee Statement: The proposal does not provide information on how the proposed system would work, nor its applicability to propane fire fighting. The reference to non-extracted text from NFPA This proosal seeks to eliminate NFPA 59 s dependency in this regard and thus create a complete, stand alone resource. This effort could extend to NFPA 59 s Appendices too. A use of liquid nitrogen could cause brittle failure of metal propane containers 59-5

6 current proposal by this submitter for revising 59: and extracting 58: as a new 59: eliminates one dependency. (Note: The following text was extracted from a review of this subject first published on January 24, 2005.) Table Electrical Area Classification...Footnote C... See A [of NFPA 58]. [58: Table ] The provisions of shall not apply to fixed electrical equipment at residential or commercial installations of LP Gas systems or to systems covered by Section 6.21 [of NFPA 58].[58: ] Only electrical lighting shall be used with the vehicles covered by this chapter. Wiring shall be insulated and protected from physical damage. Electrical equipment installed on LP-Gas cargo tank vehicles shall comply with Section 9.2 [of NFPA 58]. [58: ] When the provisions of through [of NFPA 58] are met, the minimum distance from an ASME container to a building shall be reduced by one-half for ASME containers of 2001 gal through 30,000 gal (7.6 m3 through 114 m3) water capacity. [58:6.3.2] Where all the provisions of Section 6.24 [of NFPA 58] are complied with, the minimum distances from important buildings and the line of adjoining property that can be built upon to underground and mounded ASME containers of 2001 gal through 30,000 gal (7.6 m3 through 114 m3) water capacity shall be reduced to 10 ft (3.0 m). [58: ] ASME Container Appurtenances. The provisions in through shall be required for ASME containers of 2001 gal through 30,000 gal (7.6 m3 through 114 m3) water capacity referenced in Section 6.24 [of NFPA 58]. [58:6.24.3] At cargo tank vehicle and railroad tank car transfer points, protection shall be provided in accordance with Section 6.10 [of NFPA 58] using approved emergency shutoff valves or backflow check valves or a combination of the two. [58: ] Structure or Building Heating. Heating shall be by steam or hot water radiation or other heating transfer medium, with the heat source located outside of the building or structure (see Section 6.20 [of NFPA 58]), or by electrical appliances listed for Class I, Group D, Division 2 locations, in accordance with NFPA 70, National Electrical Code. [58:10.2.3] Heat exchangers for waterbath vaporizers shall be equipped with a spring-loaded pressure relief valve that provides a relieving capacity in accordance with [of NFPA 58]. Fusible plug devices shall not be used. [58: ] Shutoff valves shall not be installed between pressure relief devices and the container unless a listed pressure relief valve manifold meeting the requirements of [of NFPA 58] is used. [58: ] If mounding is used, the provisions of of NFPA 58, Liquefied Petroleum Gas Code, shall constitute adequate protection If burial is used, the provisions of of NFPA 58 shall constitute adequate protection. in Principle in Part 1. Revise Table , Note c to read: (c) See A Reject any change to Reject any change to Accept in Principle the proposed change to Accept in Principle the proposed change to Accept in Principle the proposed change to Revise to read: At cargo tank vehicle and railroad tank car transfer points, protection shall be provided in accordance with Section 6.10 [of NFPA 58] using approved emergency shutoff valves or backflow check valves or a combination of the two. [58: ] 8. Accept in Principle the proposed change to Accept in Principle the proposed change to Accept in Principle the proposed change to Accept in Principle the proposed change to Accept in Principle the proposed change to Committee Statement: 1. The Annex text referred to is in NFPA 59, and the reference is provided. 2. Paragraph has been deleted in Proposal (Log #29). 3. Paragraph has been deleted in Proposal (Log #30). 4. Refer to Proposal (Log #CP2). 5. Refer to Proposal (Log #40). 6. Refer to Proposal (Log #CP3). 7. Reference to NFPA 58 is deleted and reference to identical text in NFPA 59 is added. 8. Refer to Proposal (Log #49). 9. Refer to Proposal (Log #54). 10. Refer to Proposal (Log #80). 11. Refer to Proposal (Log #75). 12. Refer to Proposal (Log #75) Log #29 Final Action: Accept ( ) _ Recommendation: Delete The provisions of shall not apply to fixed electrical equipment at residential or commercial installation of LP Gas systems or to systems covered by Section 6.21 (of NFPA 58). [58: ] Substantiation: The section is extracted from 58 and does not apply to Utility Gas Plants Log #30 Final Action: Accept ( ) _ Recommendation: Delete Electrical equipment installed on LP-Gas cargo tank vehicles shall comply with Section 9.2 (of NFPA 58). [58: ] Substantiation: The section is extracted from 58 and does not apply to Utility Gas Plants Log #31 Final Action: Accept in Principle (4.5.3) Recommendation: Delete the following from section and replace with text as outlined Open flames or other sources of ignition shall not be used or installed in pump houses, cylinder filling rooms, or other similar locations Direct-fired vaporizers or indirect-fired vaporizers attached or installed adjacent to gas-fired heat sources shall not be installed in pump houses or cylinder filling rooms Open flames, cutting or welding tools, portable electric tools, and extension lights capable of igniting LP-Gas shall not be installed or used within classified areas specified in Table * Open flames or other sources of ignition shall not be prohibited where LP-Gas facilities have been purged of all liquid and vapor. Move existing text in 4.8 and renumber to fit in section Smoking and nonprocess ignition sources within the protective enclosure shall be prohibited, unless in accordance with The owner shall identify, using sound engineering judgment, hazardous areas where smoking and other sources of ignition shall be prohibited except in accordance with through Smoking shall be permitted only in designated and properly signposted areas Welding, cutting, hot work, use of portable electric tools and extension lights, and similar operations shall be conducted only at times and places specifically authorized Welding and cutting shall be conducted in accordance with the provisions of NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work. Portable electric tools and extension lights capable of igniting LP-Gas shall not be permitted within the classified areas specified in Table Portable electric tools and extension lights capable of igniting LP-Gas shall be permitted where the LP-Gas facilities have been freed of all liquid and vapor or where special precautions are observed under carefully controlled conditions Vehicles and other mobile equipment that constitute potential ignition sources shall be prohibited within diked areas or within 50 ft (15 m) of containers that contain LP-Gas, flammable liquids, or flammable refrigerants, except where specifically authorized and under constant supervision or where loading or unloading at facilities specifically designed for the purpose * 4.5.5* If stray currents are present or if impressed currents are used on loading and unloading systems (such as for cathodic protection), protective measures shall be taken to prevent ignition. A.4.8.6* A For additional information, see API RP 2003, Protection Against Ignitions Arising out of Static, Lightning and Stray Currents * Open flames or other sources of ignition shall not be prohibited where LP-Gas facilities have been purged of all liquid and vapor. [58: ] Substantiation: Section is redundant or in direct conflict with the sections under 4.7 and For example; is covered by , is covered in 4.7.1, is covered in , is covered in Also replaced the text in with verbiage that will permit owners to better identify the areas of concern for this section. Also A was brought forth out of the Annex. Should delete reference on to old A

7 in Principle 1. Revise Section to read: Smoking shall be permitted only in designated and sign posted areas Welding, cutting, hot work shall be conducted in accordance with the provisions of NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work Portable electric tools and extension lights capable of igniting LP-Gas shall not be permitted within classified areas except where the area has been identified as free of flammable gases. 2. Revise to read: Vehicles and other mobile equipment that constitute potential ignition sources shall be prohibited within diked areas or within 50 ft (15 m) of containers that contain LP-Gas, flammable liquids, or flammable refrigerants, except where authorized and at loading or unloading at facilities specifically designed for the purpose. 3. Revise to read: 4.5.5* Where stray electrical currents are present or where impressed currents are used on loading and unloading systems such as for cathodic protection, protective measures shall be taken to prevent ignition. 4. Relocate A to A Committee Statement: The proposal is accepted with editorial revisions Log #32 Final Action: Accept (4.7.1) Recommendation: Delete the following text: Fixed electrical equipment and wiring installed within the classified areas specified in Table shall comply with Table and shall be installed in accordance with NFPA 70, National Electrical Code, for hazardous locations. Substantiation: Duplicates the text in amended Log #35 Final Action: Accept ( ) Containers shall be located in accordance with Table with respect to the distance between containers, the distance between containers and the nearest important building or group of buildings not associated with the LP- Gas Utility Gas plant, or a line of adjoining property that can be built upon. Substantiation: Utility Gas Plant is defined, LP Gas plant is not Log #CP2 Final Action: Accept ( ) Submitter: Technical Committee on LP-Gases at Utility Gas Plants, Recommendation: Revise to read: When the provisions of through [of NFPA 58] are met, the minimum distance from an ASME container to a building shall be reduced by one-half for ASME containers of 2001 gal through 30,000 gal (7.6 m 3 through 114 m 3 ) water capacity. [58:6.3.2] Substantiation: References in NFPA 59 are substituted for those in NFPA 58, Liquefied Petroleum Gas Code. The text is identical in both documents Log #36 Final Action: Accept ( ) Recommendation: Delete the following text: If insulation is used, it shall be capable of limiting the container temperature to not over 800 F (427 C) for a minimum of 50 minutes, as determined by test with insulation applied to a steel plate and subjected to a test flame substantially over the area of the test plate, and shall be resistant to weathering and the action of hose streams. (See Annex D.) Substantiation: The section is deleted here and moved to as it is more appropriate under Special Protection Log #38 Final Action: Accept in Principle ( ) Partially buried (or mounded) containers shall have not less than 12 in. (300 mm) of cover of earth, sand or other non-combustible material, and shall provide sufficient to provide surface drainage without erosion or other deterioration. Substantiation: Add wording to better define cover over the container. in Principle Revise text to read as follows: Partially buried (or mounded) containers shall have not less than 12 in. (300 mm) of cover of earth, sand or other noncombustible material, and shall provide sufficient to provide surface drainage without erosion or other deterioration. Committee Statement: The proposal is accepted with an editorial revisions Log #39 Final Action: Accept ( ) Containers shall be set level on a firm foundation and surrounded with earth or sand that is firmly tamped in place. Substantiation: Add level to assure bet placement of the container Log #37 Final Action: Accept ( ) Recommendation: Add the following text: Any damage to the coating shall be repaired before backfilling. Substantiation: Add this to ensure that containers are coated when buried Log #40 Final Action: Accept ( ) Where all the provisions of Section [of NFPA 58] are complied with, the minimum distances from important buildings and the line of adjoining property that can be built upon to underground and mounded ASME containers of 2001 gal through 30,000 gal (7.6 m³ through 114 m³) water capacity shall be reduced to 10 ft (3.0 m). [58: ] Substantiation: Reworded for clarity as NFPA 58:6.24 includes low emission transfer which is not a factor at Utility gas plants. This is because of stringent requirements existing at these facilities regarding transfer site location. This also provides consistency within NFPA Log #CP3 Final Action: Accept (5.9.3) Submitter: Technical Committee on LP-Gases at Utility Gas Plants, Recommendation: Revise to read: ASME Container Appurtenances. The provisions in through shall be required for ASME containers of 2001 gal through 30,000 gal (7.6 m3 through 114 m3) water capacity referenced in Section 6.24 [of NFPA 58] 5.9. [58:6.24.3] Substantiation: References in NFPA 59 are substituted for those in NFPA 58, Liquefied Petroleum Gas Code. The text is identical in both documents.

8 59-39 Log #42 Final Action: Accept (6.8) Recommendation: Delete the entire section. Substantiation: Delete the entire section of 6.8 as the sections 10.3, 10.6, , 10.4, covers everything that is in 6.8. Chapter 10 is the appropriate location for relief valve related standards. Also the extraction of NFPA 58 as it was setup in 6.8 does not benefit the 59 and puts the control of this standard in the 58 committee s hands Log #86 Final Action: Reject (6.8 and 10.3) Submitter: Steven D. Ruffcorn, Standby Systems, Inc. Recommendation: Delete and and move/renumber the remainder of Section 6.8 as 10.3 (with editorial renumbering of the balance of Chapter 10.) The effect of this proposal is to technically delete all of Section 6.8 and create new text at Section Only the following Section 6.8 provisions are actually deleted from NFPA 59: Safety relief valve discharge stacks or vents shall be designed and installed to prevent an accumulation of water, ice, snow, or other foreign matter and shall discharge vertically upward. [58: ] All refrigerated storage container pressure and vacuum relief devices shall be tested or replaced at intervals not to exceed 5 years. [58: ] Renumbered Section 6.8 text as Section The only change, other than the deletions noted above, is replacing 6.8 with 10.3 : 10.3 Relief Devices. [58:12.8] General. [58:12.8.1] All containers shall be equipped with pressure and vacuum relief devices in accordance with Section [58: ] Relief devices shall communicate directly with the atmosphere. Vacuum relieving devices shall be installed if the container can be exposed to a lower vacuum than the container is designed for. [58: ] Inlet and outlet piping connections to relief devices shall be included in the selection and sizing of relief devices. [58: ] A manually operated full opening stop valve shall be installed between each pressure and vacuum safety relief valve and the LP-Gas container. [58: ] All stop valves installed between a relief valve and a container shall be lockable or sealable in the fully open position. [58: ] A sufficient number of pressure and vacuum relief valves shall be installed on the LP-Gas container to allow each relief valve to be isolated individually while maintaining the full relieving capacities required. [58: ] Where only one relief device is required, either a full port opening three-way valve shall be installed between the container and two relief devices, or separate stop valves shall be beneath each relief device. [58: ] Stop valves under individual safety relief valves shall be locked or sealed when opened and shall not be opened or closed except by an authorized person. [58: ] No more than one stop valve shall be closed at one time. [58: ] Pressure Relief Device Sizing. The pressure relief devices shall be sized to relieve the flow capacity determined for the largest single contingency or any reasonable and probable combination of contingencies that follow: (1) Fire exposure (2) Operational upset, such as failure of a control device (3) Other circumstances resulting from equipment failures and operating errors (4) Vapor displacement during filling (5) Flash vaporization during filling, as a result of filling, or as a consequence of mixing of products of different compositions (6) Loss of refrigeration (7) Heat input from pump recirculation (8) Drop in barometric pressure [58:12.8.2] Vacuum Relief Device Sizing. [58:12.8.3] The vacuum relief devices shall be sized to relieve the flow capacity determined for the largest single contingency or any reasonable and probable combination of contingencies that follow: (1) Withdrawal of liquid or vapor at the maximum rate (2) Rise in barometric pressure (3) Reduction in vapor space pressure as a result of filling with subcooled liquid [58: ] Reduction in the vacuum relief capacity to allow for the rate of vaporization resulting from minimum normal heat gain to the contents of the container shall be allowed. [58: ] No vacuum relief capacity credit shall be allowed for gas-repressuring or vapor make-up systems. [58: ] Fire Exposure Sizing. [58:12.8.4] The pressure-relieving capacity required for fire exposure shall be computed by the following formula: where: W= relieving capacity in lb/hr or product vapor at relieving conditions. F= environmental factor from Table L= latent heat of vaporization of the stored liquid at the relieving pressure and temperature, in Btu/lb. A= exposed wetted surface area of the container in ft2. In the case of large containers, the exposed wetted area is the area up to a height of 30 ft above grade. Hn= normal heat leak in refrigerated tanks, in Btu/hr. [58: ] Table Environmental Factors Basis FFactor Base container 1.0 Water application facilities 1.0 Depressuring and emptying facilities 1.0 Underground container 0 Insulation or thermal protection Insulation or thermal protection (metric) Note: U is the overall heat transfer coefficient Btu/(hr ft 2 F) [W/(m 2 C)] of the insulation system using the mean value for the temperature range from T f to F (904 C). T f is the temperature of vessel content at relieving conditions, F ( C). [58: Table ] Where credit for insulation is taken in sizing of a relief valve for fire exposure, the insulation shall comply with the following: (1) Resist dislodgment by fire-fighting equipment (2) Be noncombustible (3) Not decompose at temperatures up to 1000 F [58: ] If the insulation does not meet the criteria of , no credit for the insulation shall be taken. [58: ] The equivalent airflow for relieving capacity shall be calculated by the following equation: where: SCFM (air) = equivalent airflow in standard ft3/min W= relieving capacity of product vapor at relieving conditions, lb/hr Z= compressibility factor product vapor at relieving conditions T= absolute temperature of product vapor at relieving conditions, R M= product vapor molecular weight [58: ] Substantiation: 6.8 is extracted from 58:12.8 and essentially duplicates the tobe-removed Section 10.3 through Moving Section 6.8 to Chapter 10 improves organization of relief devices. Requirements of and are covered in 10.6 (to be renumbered) and See comparison shown on the following pages for a side-by-side view of the relevant texts of Section 6.8 and Chapter 10. See also companion proposal to delete Section 10.3 through (Note: TIA #814 considered deletion through in 2005.) Committee Meeting Action: Reject Committee Statement: The proposed revisions are not needed as the intent is accomplished in Proposal (Log #42). 59-8

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Pursuant to the authority of Iowa Code section 101.1, the State Fire Marshal hereby adopts new Chapter 226, Liquefied Petroleum Gas, Iowa Administrative

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

Department of Public Safety

Department of Public Safety Terry E. Branstad Governor Kim Reynolds Lt. Governor Department of Public Safety Roxann M. Ryan Commissioner Liquid Propane Informational guide to submitting plans Plans are to be submitted to: State Fire

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Petroleum Gas Systems - 1 -

Petroleum Gas Systems - 1 - Petroleum Gas Systems - 1 - PHMSA's mission is to protect people and the environment by advancing the safe transportation of energy and other hazardous materials that are essential to our daily lives.

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

Changes for the New Edition. Senior Engineer, NFPA NFPA

Changes for the New Edition. Senior Engineer, NFPA NFPA Changes for the New Edition Denise Beach Senior Engineer, NFPA NFPA Overview NFPA 58-2014 Substantive Changes TIAs 2017 Edition NFPA 58-2014 Substantive Changes Bulk and Industrial Plants 3.3.10 Bulk Plant.

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

Above Ground Fuel Tank Requirements

Above Ground Fuel Tank Requirements FIRE DEPARTMENT in cooperation with Above Ground Fuel Tank Requirements The purpose of this document is to provide information about general Fire Code requirements for above ground storage within the unincorporated

More information

Compliance Guidance for non-technical managers

Compliance Guidance for non-technical managers 11699 Brookpark Road Cleveland, OH 44130 USA P: 888-826-3473 F: 216-398-8403 www.combustionsafety.com -WHITEPAPER- NFPA 56 (2012 Ed.) Standard for Fire and Explosion Prevention During Cleaning and Purging

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows: Technical Bulletin #18-002 February 2018 / 2017 OFC Mobile Food Units Referenced Codes and Standards: OAC 1301:7-7-3(T); OFC 320 OAC 1301:7-7-2(B); OFC 202 OAC 1301:7-7-9(F); OFC 906 NFPA 58 (2014) NFPA

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION DuPont Formacel Z-2 FOAM EXPANSION AGENT TECHNICAL INFORMATION Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications Flammability of Formacel Z-2 and Other Alternative

More information

NFPA 37 Public Comment Responses Page 1 of 32

NFPA 37 Public Comment Responses Page 1 of 32 of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are

More information

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 6 CENTRAL STATE HOSPITAL PLAN SUBJECT: SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: APRIL CSH SAFETY DIRECTOR LAST REVISION

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS RHODE ISLAND STATE BUILDING CODE SBC-4 State Mechanical Code Effective August 1, 2007 Replaces Regulation SBC-4 Dated September 1, 2004 STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS Department of Administration

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333 Paul Cabot Administrator National Fuel Gas Ms. Gabriella Davis Recording Secretary, IAPMO Standards Council International Association of Plumbing and Mechanical Officials (IAPMO) IAPMO Group World Headquarters

More information

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Liquefied Petroleum Gas Facility Written Fire Safety Analysis Liquefied Petroleum Gas Facility Written Fire Safety Analysis For INDEX Page Introduction 2 Conducting the WFSA 2 WFSA CHECKLIST Section I Facility Information 3 Section II Facility Storage Container Information

More information

Committee on NFPA 30A

Committee on NFPA 30A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Automotive and Marine Service Stations Patti Mucci, Administrative Assistant DATE: February 5, 00 SUBJECT: ROP Letter Ballot The ROP

More information

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Liquefied Petroleum Gas Facility Written Fire Safety Analysis Liquefied Petroleum Gas Facility Written Fire Safety Analysis For Completed by Facility manager Received by Fire Department/Emergency Response representative Date Date INDEX Page Introduction 2 Conducting

More information

Chapter FUEL GAS CODE*

Chapter FUEL GAS CODE* Chapter 19.09 FUEL GAS CODE* * Editors Note: Serial No. 2004-31, 1, adopted Oct. 11, 2004 amended Title 19 in its entirety to read as herein set out. See the editor's note at Tit. 19 and also the Code

More information

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES FLAME AND GAS DETECTION FOR LNG FACILITIES Liquefied natural gas (LNG) is a generic name for liquefied hydrocarbon gas composed primarily of methane. When natural gas is cooled to approximately -260 F,

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

AS/NZS :2008

AS/NZS :2008 AS/NZS 60079.29.2:2008 Australian/New Zealand Standard Explosive atmospheres Part 29.2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen AS/NZS 60079.29.2:2008

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or

More information

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS Town of Brighton Office of the Fire Marshal October 2018 Carbon Dioxide Systems for Beverage Dispensing Requirements Scope The intent

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

CHAPTER 10 STEAM AND HOT WATER BOILERS

CHAPTER 10 STEAM AND HOT WATER BOILERS CHAPTER 10 STEAM AND HOT WATER BOILERS 1001.0 Purpose. The purpose of this chapter is to establish and provide minimum standards for the protection of public welfare, health, safety, and property by regulating

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES Illustrated Commentary Office of the Ontario Fire Marshal Combustible Dust Illustrated Commentary 1 Mechanical Exhaust Systems 5.10.1.1.

More information

560- installation of associated storage, piping, and distribution equipment; and Ostrander, OH [U]

560- installation of associated storage, piping, and distribution equipment; and Ostrander, OH [U] Report on Proposals F2006 Copyright, NFPA NFPA 560 Report of the Committee on Committee Scope: This Committee shall have primary responsibility for Industrial and Medical Gases documents on the storage,

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 )

STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 ) STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( 92-98 MARPOL reg VI/15 ) MSC/Circ.585 16 April 1992 1 The Maritime Safety Committee, at its sixtieth session, recognized the necessity of the international

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS Pismo Beach, CA Municipal Code 8.08.010 Amendments; California Fire Code. Chapter 8.08 FIRE PREVENTION REGULATIONS The California Fire Code adopted in Section 8.04.010 is modified, amended and/or supplemented

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

This standard applies to new installations and to those portions of existing equipment and installations that are modified

This standard applies to new installations and to those portions of existing equipment and installations that are modified NFPA STANDARDS DEVELOPMENT SITE SECOND DRAFT REPORT Closing Date: July 19, 2013 NOTE: All Public Comment must be received by 5:00 pm EST/EDST on the published Closing Date. NFPA 37, Standard for the Installation

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL VS SERIES NH3 STEAM VAPORIZERS Revised March 1997 OPERATION MANUAL CONTENTS PAGE 1. GENERAL................................... 1 Figure 1-1 - VS Series Vaporizer......................... B How to Select

More information

Report on Proposals June 2013 NFPA 70

Report on Proposals June 2013 NFPA 70 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST DRY CLEANING Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved, R-Re-inspection

More information

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS INTERNATIONAL MARITIME ORGANIZATION E IMO ASSEMBLY 23rd session Agenda item 17 A 23/Res.951 25 February 2004 Original: ENGLISH Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED

More information

OUTLINE FOR FIRE PREVENTION ACTIVITY

OUTLINE FOR FIRE PREVENTION ACTIVITY OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion

More information

Iowa Propane Gas Association 2018 Training Descriptions

Iowa Propane Gas Association 2018 Training Descriptions Iowa Propane Gas Association 2018 Training Descriptions CETP Classes BASIC PRINCIPLES & PRACTICES OF PROPANE - 2 days Basic Principles and Practices is a prerequisite to the more advanced classes. The

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Industrial and Medical Gases Joanne

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

GENERAL ASSEMBLY OF NORTH CAROLINA SESSION 2007 SESSION LAW SENATE BILL 1924

GENERAL ASSEMBLY OF NORTH CAROLINA SESSION 2007 SESSION LAW SENATE BILL 1924 GENERAL ASSEMBLY OF NORTH CAROLINA SESSION 2007 SESSION LAW 2008-219 SENATE BILL 1924 AN ACT TO AUTHORIZE THE NORTH CAROLINA BUILDING CODE COUNCIL TO STUDY AND ADOPT PROVISIONS IN THE BUILDING CODE PERTAINING

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

Part I Extraction Process Equipment

Part I Extraction Process Equipment 745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this

More information

CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002

CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002 CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PALM BEACH GARDENS, FLORIDA, ADOPTING THE FLORIDA FIRE PREVENTION CODE; REPEALING ARTICLE III, "STANDARDS,"

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

AS/NZS 4745:2012. Code of practice for handling combustible dusts AS/NZS 4745:2012. Australian/New Zealand Standard. Superseding AS/NZS 4745:2004

AS/NZS 4745:2012. Code of practice for handling combustible dusts AS/NZS 4745:2012. Australian/New Zealand Standard. Superseding AS/NZS 4745:2004 AS/NZS 4745:2012 (Incorporating Amendment No. 1) Australian/New Zealand Standard Code of practice for handling combustible dusts Superseding AS/NZS 4745:2004 AS/NZS 4745:2012 AS/NZS 4745:2012 This Joint

More information

Section 2, Reference publications: Updated the referenced publications to the current editions.

Section 2, Reference publications: Updated the referenced publications to the current editions. Summary of Substantive Changes between the 2014 and the 2015 editions of ANSI Z21.10.3 CSA 4.3 Gas fired water heaters, volume III, storage water heaters with input ratings above 75,000 Btu per hour, circulating

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT Olof Bekker Pr. Eng. BSc. Eng. BML S.MSAIEE, M.NACE Engineering Manager, Electrical COMMITMENT

More information

Report of the Committee on Makhoul (Mike) T. Kadri, Automotive and Marine Service Stations Patrick A. McLaughlin, John S. Robison, Robert L.

Report of the Committee on Makhoul (Mike) T. Kadri, Automotive and Marine Service Stations Patrick A. McLaughlin, John S. Robison, Robert L. Report of the Committee on Automotive and Marine Service Stations John S. Robison, Chair Alabama State Fire Marshal s Office, AL [E] Rep. International Fire Marshals Association E. Joseph Bocci, US Department

More information