1 of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to : * The manual actuation device shall clearly identify the hazard protected and provide instructions for its use. Also, add the following new Annex material: A NFPA 96, Section 10.2, specifies that the automatic fire-extinguishing system is the primary protection for commercial cooking operations. It also requires that signage be provided at portable fire extinguishers stating that the fire protection system shall be activated prior to using the fire extinguisher. The correct response to a fire, particularly one involving a deep-fat fryer that contains a large quantity of hot grease, requires that the source of heat energy, whether electric or gas, be shut down so that the grease can cool. The fire-extinguishing system does that automatically on activation. Although a portable fire extinguisher might initially knock down the fire, it does not shut down the source of heat. Unless the grease cools below its autoignition temperature, the fire is likely to resume. Submitter Full Name: Sonia Barbosa Submittal Date: Wed Jul 29 14:18:44 EDT 2015 Committee Statement: Response Message: NFPA 17A does not accentuate the need for kitchen staff to be trained about the importance of taking action in the proper, most effective sequence. Too many commercial kitchen fires have gotten out of control due to inadequately trained staff. The first step in providing training to the staff is to provide signage that specifies the hazard protected by the fire extinguishing system and the instructions for its operation. The language needs to be absolute and why! Failure to activate the manual pull station will result in the delayed activation of the extinguishing system and more importantly, the de-energizing of the cook line appliances. Failure to de-energize will allow for continued heating of the involved and potentially involved fuels (critical with deep fat fryers).

2 of 25 7/30/2015 1:35 PM First Revision No. 50-NFPA 17A-2015 [ Detail ] Add the following section after 7.2.1: The system owner shall maintain the design and installation documents and maintenance manual or owner s manual on the premises and shall make them available for review, upon request, by the authority having jurisdiction. Submitter Full Name: Sonia Barbosa Submittal Date: Wed Jul 29 14:27:40 EDT 2015 Committee Statement: The design and installation documents are important to ensure the installations is still in compliance. Changes to the system or cooking operation after installation approval should be reviewed by the owner and inspectors for compliance with this documentation. Response Message: Public Input No. 3-NFPA 17A-2014 [New Section after 7.2.1]

3 of 25 7/30/2015 1:35 PM First Revision No. 44-NFPA 17A-2015 [ Section No. 1.3 ] 1.3* Application. Minimum requirements are specified for restaurant, commercial, and institutional hoods, plenums, ducts, and associated cooking appliances; mobile vehicle system applications are not currently addressed. Supplemental Information File Name A.1.3new.docx Description New Annex Material for Section A.1.3. Submittal Date: Sun May 17 20:16:34 EDT 2015 Committee Statement: Response Message: Revision addresses the updated Annex B which provides recommendations for installation of vehicle fire suppression system applications.

4 A 1.3 See Annex B for recommendations for installation of mobile vehicle fire suppression system applications.

5 of 25 7/30/2015 1:35 PM First Revision No. 12-NFPA 17A-2015 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA NFPA 70, National Electrical Code, edition. NFPA 72, National Fire Alarm and Signaling Code, edition. NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, edition. Submittal Date: Thu May 07 12:37:43 EDT 2015 : Updated in accordance with the NFPA Manual of Style. Response Message:

6 of 25 7/30/2015 1:35 PM First Revision No. 25-NFPA 17A-2015 [ Section No ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, 2005, revised Submittal Date: Fri May 08 08:04:11 EDT 2015 : Updated reference to the latest edition in accordance with the NFPA Manual of Style. Response Message: Public Input No. 61-NFPA 17A-2014 [Section No ]

7 of 25 7/30/2015 1:35 PM First Revision No. 13-NFPA 17A-2015 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 17, Standard for Dry Chemical Extinguishing Systems, edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, edition. NFPA 72, National Fire Alarm and Signaling Code, edition. NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 2017 edition. NFPA 820, Standard for Fire Protection in Wastewater Treatment and Collection Facilities, edition. Submittal Date: Thu May 07 12:44:49 EDT 2015 : Updated in accordance with the NFPA Manual of Style. Response Message:

8 of 25 7/30/2015 1:35 PM First Revision No. 1-NFPA 17A-2015 [ Section No ] Owner s Manual. A pamphlet containing the manufacturer s specifications for the proper recommendations for inspection and operation of the extinguishing system. Submittal Date: Thu May 07 08:41:44 EDT 2015 : The revision reflects the contents of an owner's document. Response Message: Public Input No. 23-NFPA 17A-2014 [Section No ]

9 of 25 7/30/2015 1:35 PM First Revision No. 46-NFPA 17A-2015 [ Section No ] Automatic Operation. Operation without human intervention. This operation includes, but is not limited to, heat, rate of heat rise, smoke, or pressure change. [25, ] Submitter Full Name: JACQUELINE WILMOT Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Thu Jun 18 08:48:43 EDT 2015 : Updated the definition to the current language in the 2017 edition of NFPA 25. Response Message:

10 of 25 7/30/2015 1:35 PM First Revision No. 47-NFPA 17A-2015 [ Section No ] Signal. A status An indication of a condition communicated by electrical, visible, audible, wireless, or other means. [72, ] Submitter Full Name: JACQUELINE WILMOT Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Thu Jun 18 08:51:17 EDT 2015 : Updated language to the 2017 edition of NFPA 72. Response Message:

11 0 of 25 7/30/2015 1:35 PM First Revision No. 5-NFPA 17A-2015 [ New Section after 4.1 ] Used components shall not be permitted to be installed in new systems unless approved by the authority having jurisdiction. Submittal Date: Thu May 07 10:08:53 EDT 2015 Committee Statement: Response Message: The AHJ should be aware of used systems components being used in new installation and have the authority to approve or disapprove of their use. Public Input No. 10-NFPA 17A-2014 [New Section after 4.1]

12 1 of 25 7/30/2015 1:35 PM First Revision No. 22-NFPA 17A-2015 [ Section No. 4.2 ] 4.2* Detectors. Detectors shall be listed or approved devices that are capable of detecting detect heat. Supplemental Information File Name A.4.2.docx Description Annex material for A.4.2. Submittal Date: Thu May 07 17:23:31 EDT 2015 Committee Statement: The term products of combustion is vague and is not appropriate for this application, whereas heat detection devices are appropriate. The annex material provides installation clarification to ensure brackets do not shield the detector from the heat of cooking appliances. Response Message: Public Input No. 37-NFPA 17A-2014 [New Section after ] Public Input No. 74-NFPA 17A-2015 [Section No. 4.2]

13 A 1.3 See Annex B for recommendations for installation of mobile vehicle fire suppression system applications.

14 A Piping and fittings should be installed in accordance with good commercial practices. Care should be taken to avoid possible restrictions due to foreign matter, faulty fabrication, or improper installation. The following is considered a good practice: (1) Prior to assembly, pipe should be reamed and cleaned internally by means of swabbing, utilizing a suitable nonflammable cleaner. (2) Once piping is assembled and prior to nozzle installation, the entire piping system should be blown out with nitrogen or dry air. (3) The piping system should be securely supported and should not be subject to mechanical, chemical, or other damage. (4) All piping should be installed in pipe hangers or brackets and fastened to rigid surfaces. (5) Piping mounting brackets, hangers and support fixtures should be installed in a manner that will ensure nozzles are properly aligned and prevent nozzles from being moved out of alignment. (6) A union should be installed between the extinguishing agent storage container and the supply line.

15 A NFPA 10, Annex A, provides recommendations for placards. [NFPA 96, 2017] :

16 A.4.2 Fixed temperature sensing element brackets should be installed so that brackets do not shield the detector from the heat of the cooking appliances.

17 First Revision No. 2-NFPA 17A-2015 [ Sections , ] Protective Covers for Discharge Nozzles All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture, environmental contaminants, or other foreign materials into the piping The protection device shall blow off, blow open, or blow out upon agent discharge. Submittal Date: Thu May 07 09:09:20 EDT 2015 : The revision was made to distinguish the material requirements for caps and nozzles. Response Message: Public Input No. 63-NFPA 17A-2014 [Sections , ] 2 of 25 7/30/2015 1:35 PM

18 3 of 25 7/30/2015 1:35 PM First Revision No. 3-NFPA 17A-2015 [ Section No ] Manual actuators shall not require a force of more than 40 lb lbf (178 N) to initiate operation. Submittal Date: Thu May 07 09:29:52 EDT 2015 : The revision clarifies requirement. Response Message: Public Input No. 12-NFPA 17A-2014 [Section No ]

19 4 of 25 7/30/2015 1:35 PM First Revision No. 4-NFPA 17A-2015 [ Section No ] Manual actuators shall not require a movement of more than 14 in. (356 mm) to secure initiate operation. Submittal Date: Thu May 07 09:43:42 EDT 2015 Committee Statement: Response Message: A revision was made to replace the word "secure" with "initiate" to be consistent with Section Public Input No. 24-NFPA 17A-2014 [Section No ]

20 5 of 25 7/30/2015 1:35 PM First Revision No. 29-NFPA 17A-2015 [ New Section after ] * A placard shall be conspicuously placed near each extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher. [ 96: ] Supplemental Information File Name PI-69_-_FR_29.docx Description Annex Material Submittal Date: Fri May 08 10:46:11 EDT 2015 : This revision correlates with the requirement in NFPA 96. Response Message: Public Input No. 69-NFPA 17A-2015 [New Section after ] Public Input No. 66-NFPA 17A-2015 [Section No ]

21 A.4.2 Fixed temperature sensing element brackets should be installed so that brackets do not shield the detector from the heat of the cooking appliances.

22 A 1.3 See Annex B for recommendations for installation of mobile vehicle fire suppression system applications.

23 A Piping and fittings should be installed in accordance with good commercial practices. Care should be taken to avoid possible restrictions due to foreign matter, faulty fabrication, or improper installation. The following is considered a good practice: (1) Prior to assembly, pipe should be reamed and cleaned internally by means of swabbing, utilizing a suitable nonflammable cleaner. (2) Once piping is assembled and prior to nozzle installation, the entire piping system should be blown out with nitrogen or dry air. (3) The piping system should be securely supported and should not be subject to mechanical, chemical, or other damage. (4) All piping should be installed in pipe hangers or brackets and fastened to rigid surfaces. (5) Piping mounting brackets, hangers and support fixtures should be installed in a manner that will ensure nozzles are properly aligned and prevent nozzles from being moved out of alignment. (6) A union should be installed between the extinguishing agent storage container and the supply line.

24 A NFPA 10, Annex A, provides recommendations for placards. [NFPA 96, 2017] :

25 6 of 25 7/30/2015 1:35 PM First Revision No. 30-NFPA 17A-2015 [ Section No ] All readily accessible manual operating devices shall identify the hazards they protect. (See ) Submittal Date: Fri May 08 10:52:19 EDT 2015 : The parenthetical reference to is confusing and unnecessary. Response Message: Public Input No. 25-NFPA 17A-2014 [Section No ]

26 7 of 25 7/30/2015 1:35 PM First Revision No. 41-NFPA 17A-2015 [ Section No ] On actuation of any cooking equipment fire-extinguishing system, all sources of fuel and electric power that produce heat to all equipment protected by the system shall be shut down. Submittal Date: Sun May 17 17:45:20 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and 96. The requirement for automatic shutdown is already covered by NFPA 96, Public Input No. 52-NFPA 17A-2014 [Section No ]

27 8 of 25 7/30/2015 1:35 PM First Revision No. 40-NFPA 17A-2015 [ Section No ] Gas appliances not requiring protection but located under the same ventilation equipment shall also be shut off. Submittal Date: Sun May 17 17:44:24 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and 96. Gas appliances located under hoods and not requiring protection to be shut off is covered by NFPA 96, Public Input No. 55-NFPA 17A-2014 [Section No ]

28 9 of 25 7/30/2015 1:35 PM First Revision No. 33-NFPA 17A-2015 [ Section No ] Steam supplied from an external source shall not be required to be shut down. Submittal Date: Fri May 08 11:54:32 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and 96. The requirement for steam tables to not shut down is already covered by NFPA 96, Public Input No. 53-NFPA 17A-2014 [Section No ]

29 0 of 25 7/30/2015 1:35 PM First Revision No. 34-NFPA 17A-2015 [ Section No ] Solid fuel cooking operations shall not be required to be shut down. Submittal Date: Fri May 08 11:55:53 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and 96. This requirement should be deleted from NFPA 17A and inserted as a new requirement in NFPA 96, Public Input No. 54-NFPA 17A-2014 [Section No ]

30 1 of 25 7/30/2015 1:35 PM First Revision No. 32-NFPA 17A-2015 [ Section No ] Exhaust fans and dampers shall not be required to be shut down on system actuation as the systems have been tested under both zero- and high-velocity flow conditions. A hood exhaust fan(s) shall continue to operate after the extinguishing system has been activated unless fan shutdown is required by a listed component of the ventilation system or by the design of the extinguishing system. [ 96: ] When the fire-extinguishing system activates, makeup air supplied internally to a hood shall be shut off. [ 96: 8.3.2] Submittal Date: Fri May 08 11:47:05 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and NFPA 96, the revised text is extracted from Chapter 8, Air Movement of NFPA 96. Public Input No. 13-NFPA 17A-2014 [New Section after 4.4.4]

31 2 of 25 7/30/2015 1:35 PM First Revision No. 35-NFPA 17A-2015 [ Section No ] Shutoff devices shall require manual resetting prior to fuel or power being restored. Submittal Date: Fri May 08 11:56:42 EDT 2015 Committee Statement: Response Message: To improve correlation between NFPA 17A and 96. Shutoff devices require manual reset. Similar text appears in NFPA 96, The requirement should only appear in one standard. Public Input No. 56-NFPA 17A-2014 [Section No ]

32 3 of 25 7/30/2015 1:35 PM First Revision No. 42-NFPA 17A-2015 [ Section No ] 4.5.4* Pipe, tubing, hose, and types of fitting materials shall be in accordance with the manufacturer's design, installation, and maintenance manual. Supplemental Information File Name A docx Description New Annex material for Section A Submittal Date: Sun May 17 18:14:03 EDT 2015 Committee Statement: Response Message: To avoid conflict with existing manufacturer s manuals, the proposed text would be more appropriately provided as advisory language in the annex. Public Input No. 22-NFPA 17A-2014 [New Section after 5.6.4]

33 A Piping and fittings should be installed in accordance with good commercial practices. Care should be taken to avoid possible restrictions due to foreign matter, faulty fabrication, or improper installation. The following is considered a good practice: (1) Prior to assembly, pipe should be reamed and cleaned internally by means of swabbing, utilizing a suitable nonflammable cleaner. (2) Once piping is assembled and prior to nozzle installation, the entire piping system should be blown out with nitrogen or dry air. (3) The piping system should be securely supported and should not be subject to mechanical, chemical, or other damage. (4) All piping should be installed in pipe hangers or brackets and fastened to rigid surfaces. (5) Piping mounting brackets, hangers and support fixtures should be installed in a manner that will ensure nozzles are properly aligned and prevent nozzles from being moved out of alignment. (6) A union should be installed between the extinguishing agent storage container and the supply line.

34 4 of 25 7/30/2015 1:35 PM First Revision No. 6-NFPA 17A-2015 [ Section No ] 4.6.1* The wet chemical used in the system shall be listed for the particular system, as specified by and the manufacturer of the wet chemical system shall be required to specify that particular chemical in the manufacturer s design, installation, and maintenance manual. Submittal Date: Thu May 07 10:23:07 EDT 2015 : Revised the format of to clarify the requirements. Response Message: Public Input No. 26-NFPA 17A-2014 [Section No ]

35 5 of 25 7/30/2015 1:35 PM First Revision No. 7-NFPA 17A-2015 [ Section No. 5.1 [Excluding any Sub-Sections] ] Wet chemical fire-extinguishing systems for use in the protection of cooking operations shall comply with be listed and shall meet or exceed the requirements of ANSI/UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment. Submittal Date: Thu May 07 10:28:02 EDT 2015 : The revision further clarifies the requirement in the standard. Response Message: Public Input No. 27-NFPA 17A-2014 [Section No. 5.1 [Excluding any Sub-Sections]]

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Second Revision No. 2-NFPA [ Section No ]

Second Revision No. 2-NFPA [ Section No ] Page 1 of 8 Second Revision No. 2-NFPA 410-2014 [ Section No. 10.2 ] 10.2* Fire Extinguishers. In addition to extinguishers required by NFPA 409, extinguishers shall be provided for aircraft maintenance

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM of 56 6/23/2016 11:34 AM Second Revision No. 1-NFPA 96-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Change all instances of flame resistant (hypobaric) to Limited-Combustible (material) in all instances in the document. 1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 29 6/9/2016 1:42 PM First Revision No. 7-NFPA 289-2016 [ Global Input ] Add comman between "reconstruction or research" throughout the document as follows: "reconstruction, or research" Submittal Date:

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement of 35 1/21/2016 7:56 AM First Revision No. 1-NFPA 30A-2015 [ Section No. 1.1.3 ] 1.1.3* This code shall not apply to those motor fuel dispensing facilities where only liquefied petroleum gas (LP-Gas),

More information

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ] of 46 11/6/2015 9:21 AM First Revision No. 208-NFPA 30-2015 [ Section No. 9.3.3.1 ] 9.3.3.1 Storage of liquids shall not physically obstruct a means of egress. Submittal Date: Wed Sep 09 18:24:20 EDT 2015

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification of 123 7/30/2015 1:48 PM Public Input No. 107-NFPA 96-2014 [ Section No. 1.3.2 ] 1.3.2 The authority having jurisdiction shall determine compliance with this standard and authorize equivalent deviations

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement Second Revision No. 11-NFPA 16-2014 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 2015 edition. NFPA 13, Standard

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

Jacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation

Jacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation Jacqueline Wilmot Fire Protection Engineer NFPA Road Map for Mobile Food Truck Regulation Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Hazards Multiple

More information

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Ships and marine technology Fireextinguishing. of galley cooking equipment

Ships and marine technology Fireextinguishing. of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction

More information

Data/ Specification Sheet

Data/ Specification Sheet Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel

More information

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

First Revision No. 22-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 22-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 28 2/2/2016 9:39 AM First Revision No. 22-NFPA 37-2015 [ Global Input ] Add the following definitions to chapter 3: 3.3.x Service Regulator. A pressure regulator installed by the serving gas supplier

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Committee Input No. 1-NFPA [ Chapter 2 ]

Committee Input No. 1-NFPA [ Chapter 2 ] of 35 11/4/2016 6:18 PM Committee Input No. 1-NFPA 80-2016 [ Chapter 2 ] The committee will review and update the editions of the referenced publications to the correct edition at the Second Draft meeting.

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Page 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M,

More information

Second Revision No. 1 NFPA [ Chapter 2 ]

Second Revision No. 1 NFPA [ Chapter 2 ] Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

CORE Protection Fire System Specification

CORE Protection Fire System Specification CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems Report of the Committee on Dry and Wet Chemical Extinguishing Systems Edward J. Kaminski, Chair Schirmer Engineering Corporation, NV [I] Paul E. Buchhofer, Building Inspection Underwriters, Inc., PA [E]

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement Committee Input No. 9-NFPA 2001-2016 [ Global Input ] Incorporate revisions per the attached file. Supplemental Information File Name 2001-CI_9.pdf Description Data and specific revisions presented at

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225. Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 105 1/21/2016 7:49 AM Public Input No. 2-NFPA 30A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages. of 123 6/10/2014 9:07 AM First Revision No. 117-NFPA 14-2014 [ Global Input ] 7.3.2.7.5 The distances in 7.3.2.2 shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information