Report on Proposals June 2013 NFPA 70

Size: px
Start display at page:

Download "Report on Proposals June 2013 NFPA 70"

Transcription

1 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever the intent of the requirement is to also include STRUCTURES as well as buildings. There is a flaw in the NEC. The term "building" is used over 1000 times in the NEC, and in most of the cases the words "or other structure" should follow and apply the same requirements to bridges, billboards, towers, tanks, and other structures that are by definition NOT BUILDINGS. One specific example I can use is section Wiring on Buildings. I believe that this section is also intended to be applied structures, but the wording "or other structures" is not in the heading or the paragraph. There are literally thousands of other instances throughout the code that this same problem exists. This can easily be seen by doing an electronic search for the word "building". In some cases the words "or other structure" (or similar wording) are present, but in the vast majority where the requirements should also be applied to structures other than buildings, the wording is not there. The submitter has not provided specific proposed text for his proposal in accordance with 4.3.3(c) of the Regulations Governing Committee Projects Log #921m NEC-P14 Joe Tedesco, Boston, MA The term "adequate" and "adequately" and "inadequately" and "inadequate" should be replaced with terms that can be properly enforced and understood. Terms are not defined and are considered vague and unenforceable per Table in the NEC Style Manaual. They are all "incorrect" 148 times in the NEC. The submitter has not provided specific proposed text for his proposal in accordance with 4.3.3(c) of the Regulations Governing Committee Projects. 1

2 14-3 Log #2638e NEC-P14 John R. Kovacik, Underwriters Laboratories Inc. Update the references to UL Standards in the Informational Notes as shown below: Equipment enclosed in a case that is capable of withstanding an explosion of a specified gas or vapor that may occur within it and of preventing the ignition of a specified gas or vapor surrounding the enclosure by sparks, flashes, or explosion of the gas or vapor within, and that operates at such an external temperature that a surrounding flammable atmosphere will not be ignited thereby. Informational Note: For further information, see ANSI/UL , For purposes of Articles 500 through 504 and Articles 510 through 516, the following definitions apply. Equipment enclosed in a manner that excludes dusts and does not permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure. Informational Note: For further information on dustignitionproof enclosures, see Type 9 enclosure in ANSI/NEMA ,, and ANSI/UL ,. Informational Note: For further information, see ANSI/UL ,. Informational Note No. 2: Female NPT threaded entries use a modified National Standard Pipe Taper (NPT) thread with thread form per ANSI/ASME B ,. See ANSI/UL ,. A circuit in which any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditions. Informational Note: Test conditions are described in ANSI/UL ,. For purposes of this article, the following definitions apply. Equipment enclosed in a manner that excludes dusts and does not permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure. Informational Note: For further information on dustignitionproof enclosures, see Type 9 enclosure in ANSI/NEMA ,, and ANSI/UL ,. References to UL Standards in the NEC should reflect the current edition. Accept all amendments to the publication dates of the referenced documents, but do not accept the deletion of "1203" in Informational Note 2 of 500.2(1). The panel notes that the submitter accidentally deleted the document number. Affirmative: 13 Negative: 2 SIMMONS, J.: The National Electrical Code Style Manual, 2011 edition, in Chapter 4 References and Extracts, Section 4.2 References to Other Standards, states that product standards shall be in an informative annex. Each of the 2

3 changes reflected in this proposal updates a reference to a product standard. The Style Manual, as I read it, prohibits standards from being referenced in informational notes. The notes should be deleted and not updated. There are numerous references to product standards located in informational notes throughout the NEC. Deletion of these references would help to eliminate clutter throughout the code book. Since these references appear in articles from more than one Technical Committee, clean up would be best served by a multi-panel task group assigned by the TCC. The proliferation of Information Notes throughout the NEC is, in many cases in conflicts with the National Electrical Code, 2011 edition, Article 90 - Introduction, 90.1 (C) Intention. This code is not intended as a design specification or an instructional manual for untrained persons. Including informational notes beyond Informative Annex A Product Safety Standards is allowing the National Electrical Code to become a design specification manual and an instructional manual. The use of unenforceable informational notes for product standards beyond their reference in Informative Annex A creates ambiguity in the document. Finally, the National Electrical Code Style Manual, 2011 Edition, Chapter 3 Editorial Guidelines, Informational Notes, states that if an informational note is needed to explain the text of the code, consideration should be given to rewriting the text of the code to make the rule clear. If a standard contains design and/or installation information that is needed for the practical safeguarding of persons and property from hazards arising from the use of electricity, then that information should be placed in code language where it is enforceable. WECHSLER, D.: Action should have been to reject. The proposal merely reflects a date change and lacks technical substation for this change. Code making panels need to have proper information upon which to make an informed decision of the continued applicability of the document to the Code process and therefore need to have an understanding of the document changes. As indicated in log , changes were made to the energy requirements for intrinsic safety which had nothing to do with a safety issue; just a business decision to harmonize. Perhaps if a full disclosure NFPA process had been followed, agreeing to the document change might not be supported by the Code panel. Lastly, it appears that of the Regulations Governing Committee Projects requires product standards contained in informational notes to have revision dates. This makes sense if these product standards reflect agreement by the CMP to use the defined products in hazardous classified locations. Therefore by implication the CMP endorses the product standard. However, adding a product standard reference or making changes to a formerly recognized product standard should then follow the NFPA NEC proposal submission process and provide clear justification for the product standard addition/ change. 3

4 14-4 Log #1611 NEC-P14 James F. Williams, Fairmont, WV That portion of a property where liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container. [ ] Informational Note: For further information, see NFPA ,. That portion of a property where liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container. [ ] Informational Note: For further information, see NFPA ,. The defined term is referenced in several articles of the NEC:,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The Tables cited in the submitter s substantiation contain references to Chapter 5 articles. The term bulk plant appears only in Article 515. The present location of the definition is correct. SIMMONS, J.: I voted to reject these items and I agree with the panel substantiation; however I feel there is a larger problem with the insertion of definitions into the NEC. The 2011 National Electrical Code Style Manual in Section states: In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the NEC. The statement uses a possibly unenforceable phrase (in general) with the mandatory word shall. As a result, there is some inconsistency in the placement of definitions throughout the Code. A CMP-14 task group was formed to look at the definitions in Articles The group found that the definitions which appeared in more than one of the articles in needed to remain where they were and that they fell under the in general rule of Section The consensus feeling was that the definitions found in Articles are specific to the special locations covered in those articles and that relocation to Article 100, to be mixed with the general definitions found there, could create confusion and misapplication. I would like to note, however, that confusion with the definitions is a global issue which would need a multi-panel task group assigned by the TCC to address. For example, the definition of portable equipment is found in five Articles (Sections 513.2, 520.2, 530.2, and 680.2). There is some inconsistency in the definition provided in some of the sections. This is a case where the inconsistency can cause confusion. The rule(s) for the placement of definitions in the NEC should be reviewed and changes made to provide for consistency. Any changes should however take into consideration the need to segregate definitions that apply to specialized installations, such as hazardous (classified) locations in an area of the NEC that will insure the reader understands the definition's association with the specific application. If a determination was made to place all definitions into Article 100, I would suggest a new Part III Hazardous Location and include all definitions associated with Articles in the new part which could be under the jurisdiction of CMP-14. 4

5 14-5 Log #1609 NEC-P14 James F. Williams, Fairmont, WV Equipment with electrical components suitable to be moved only with mechanical aids or is provided with wheels for movement by person(s) or powered devices. Equipment with electrical components suitable to be moved by a single person without mechanical aids Equipment with electrical components suitable to be moved only with mechanical aids or is provided with wheels for movement by person(s) or powered devices. Equipment with electrical components suitable to be moved by a single person without mechanical aids The defined term is referenced in several articles of the NEC:,,,,,,,,,,, (3),,,,,,, (2),, 513.2, & 513.,,, (8),,,,,, (1), (5),,, (6),,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The submitter did not provide substantiation to support the correctness of the proposed definitions. This is not in accordance with 4.3.3(d) of the Regulations Governing Committee Projects. Panel 14 also notes that portable and movable vary from product to product, and are defined in the various product standards. SIMMONS, J.: I voted to reject these items and I agree with the panel substantiation; however I feel there is a larger problem with the insertion of definitions into the NEC. The 2011 National Electrical Code Style Manual in Section states: In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the NEC. The statement uses a possibly unenforceable phrase (in general) with the mandatory word shall. As a result, there is some inconsistency in the placement of definitions throughout the Code. A CMP-14 task group was formed to look at the definitions in Articles The group found that the definitions which appeared in more than one of the articles in needed to remain where they were and that they fell under the in general rule of Section The consensus feeling was that the definitions found in Articles are specific to the special locations covered in those articles and that relocation to Article 100, to be mixed with the general definitions found there, could create confusion and misapplication. I would like to note, however, that confusion with the definitions is a global issue which would need a multi-panel task group assigned by the TCC to address. For example, the definition of portable equipment is found in five Articles (Sections 513.2, 520.2, 530.2, and 680.2). There is some inconsistency in the definition provided in some of the sections. This is a case where the inconsistency can cause confusion. The rule(s) for the placement of definitions in the NEC should be reviewed and changes made to provide for consistency. Any changes should however take into consideration the need to segregate definitions that apply to specialized installations, such as hazardous (classified) locations in an area of the NEC that will insure the reader understands the definition's association with the specific application. If a determination was made to place all definitions into Article 100, I would suggest a new Part III Hazardous Location and include all definitions associated with Articles in the new part which could be under the jurisdiction of CMP-14. 5

6 14-6 Log #1610 NEC-P14 James F. Williams, Fairmont, WV That portion of a property where motor fuels are stored and dispensed from fixed equipment into the fuel tanks of motor vehicles or marine craft or into approved containers, including all equipment used in connection therewith. [ ] Informational Note: Refer to Articles 510 and 511 with respect to electrical wiring and equipment for other areas used as lubritoriums, service rooms, repair rooms, offices, salesrooms, compressor rooms, and similar locations. That portion of a property where motor fuels are stored and dispensed from fixed equipment into the fuel tanks of motor vehicles or marine craft or into approved containers, including all equipment used in connection therewith. [ ] Informational Note: Refer to Articles 510 and 511 with respect to electrical wiring and equipment for other areas used as lubritoriums, service rooms, repair rooms, offices, salesrooms, compressor rooms, and similar locations. The defined term is referenced in several articles of the NEC:,,,,,,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The Tables cited in the submitter s substantiation contain references to Chapter 5 articles. The term motor fuel dispensing facility appears only in Article 514. The present location of the definition is correct. SIMMONS, J.: I voted to reject these items and I agree with the panel substantiation; however I feel there is a larger problem with the insertion of definitions into the NEC. The 2011 National Electrical Code Style Manual in Section states: In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the NEC. The statement uses a possibly unenforceable phrase (in general) with the mandatory word shall. As a result, there is some inconsistency in the placement of definitions throughout the Code. A CMP-14 task group was formed to look at the definitions in Articles The group found that the definitions which appeared in more than one of the articles in needed to remain where they were and that they fell under the in general rule of Section The consensus feeling was that the definitions found in Articles are specific to the special locations covered in those articles and that relocation to Article 100, to be mixed with the general definitions found there, could create confusion and misapplication. I would like to note, however, that confusion with the definitions is a global issue which would need a multi-panel task group assigned by the TCC to address. For example, the definition of portable equipment is found in five Articles (Sections 513.2, 520.2, 530.2, and 680.2). There is some inconsistency in the definition provided in some of the sections. This is a case where the inconsistency can cause confusion. The rule(s) for the placement of definitions in the NEC should be reviewed and changes made to provide for consistency. Any changes should however take into consideration the need to segregate definitions that apply to specialized installations, such as hazardous (classified) locations in an area of the NEC that will insure the reader understands the definition's association with the specific application. If a determination was made to place all definitions into Article 100, I would suggest a new Part III Hazardous Location and include all definitions associated with Articles in the new part which could be under the jurisdiction of CMP-14. 6

7 14-7 Log #2894 NEC-P14 James F. Williams, Fairmont, WV Equipment with electrical components intended to be moved from one place to another. Equipment with electrical components suitable to be moved by a single person without mechanical aids. The defined term is referenced in several articles of the NEC: 100 I Electric Sign, 110, 210, 250, 368, 400, 430, 490, 500, 501, 505, 511, 513, 514, 515, 516, 517, 518, 520, 525, 530, 545, 600, 640, 668, 680 It is defined in 513.2, 520.2, 530.2, 640.2, & Suggest that a single definition in 100 I is better. In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The submitter did not provide substantiation to support the correctness of the proposed definition. This is not in accordance with 4.3.3(d) of the Regulations Governing Committee Projects. Panel 14 also notes that the meaning of portable varies from Article to Article. The panel notes that the proposed change in the definition would have unintended and unsubstantiated changes to the application of portable equipment in aircraft hangars. SIMMONS, J.: I voted to reject these items and I agree with the panel substantiation; however I feel there is a larger problem with the insertion of definitions into the NEC. The 2011 National Electrical Code Style Manual in Section states: In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the NEC. The statement uses a possibly unenforceable phrase (in general) with the mandatory word shall. As a result, there is some inconsistency in the placement of definitions throughout the Code. A CMP-14 task group was formed to look at the definitions in Articles The group found that the definitions which appeared in more than one of the articles in needed to remain where they were and that they fell under the in general rule of Section The consensus feeling was that the definitions found in Articles are specific to the special locations covered in those articles and that relocation to Article 100, to be mixed with the general definitions found there, could create confusion and misapplication. I would like to note, however, that confusion with the definitions is a global issue which would need a multi-panel task group assigned by the TCC to address. For example, the definition of portable equipment is found in five Articles (Sections 513.2, 520.2, 530.2, and 680.2). There is some inconsistency in the definition provided in some of the sections. This is a case where the inconsistency can cause confusion. The rule(s) for the placement of definitions in the NEC should be reviewed and changes made to provide for consistency. Any changes should however take into consideration the need to segregate definitions that apply to specialized installations, such as hazardous (classified) locations in an area of the NEC that will insure the reader understands the definition's association with the specific application. If a determination was made to place all definitions into Article 100, I would suggest a new Part III Hazardous Location and include all definitions associated with Articles in the new part which could be under the jurisdiction of CMP-14. 7

8 14-8 Log #1612 NEC-P14 James F. Williams, Fairmont, WV An enclosure or insert within a larger room used for spray/coating/dipping applications. A spray booth may be fully enclosed or have open front or face and may include separate conveyor entrance and exit. The spray booth is provided with a dedicated ventilation exhaust but may draw supply air from the larger room or have a dedicated air supply. An enclosure or insert within a larger room used for spray/coating/dipping applications. A spray booth may be fully enclosed or have open front or face and may include separate conveyor entrance and exit. The spray booth is provided with a dedicated ventilation exhaust but may draw supply air from the larger room or have a dedicated air supply. The defined term is referenced in several articles of the NEC: (3)(2),, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The citation of 500.5(B)(3) by the submitter in the substantiation is an Informational Note, not in the Code text. This does not justify moving the definition from Article 516 to Article 100, as Article 516 is the only Article containing provisions for spray booths. SIMMONS, J.: I voted to reject these items and I agree with the panel substantiation; however I feel there is a larger problem with the insertion of definitions into the NEC. The 2011 National Electrical Code Style Manual in Section states: In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the NEC. The statement uses a possibly unenforceable phrase (in general) with the mandatory word shall. As a result, there is some inconsistency in the placement of definitions throughout the Code. A CMP-14 task group was formed to look at the definitions in Articles The group found that the definitions which appeared in more than one of the articles in needed to remain where they were and that they fell under the in general rule of Section The consensus feeling was that the definitions found in Articles are specific to the special locations covered in those articles and that relocation to Article 100, to be mixed with the general definitions found there, could create confusion and misapplication. I would like to note, however, that confusion with the definitions is a global issue which would need a multi-panel task group assigned by the TCC to address. For example, the definition of portable equipment is found in five Articles (Sections 513.2, 520.2, 530.2, and 680.2). There is some inconsistency in the definition provided in some of the sections. This is a case where the inconsistency can cause confusion. The rule(s) for the placement of definitions in the NEC should be reviewed and changes made to provide for consistency. Any changes should however take into consideration the need to segregate definitions that apply to specialized installations, such as hazardous (classified) locations in an area of the NEC that will insure the reader understands the definition's association with the specific application. If a determination was made to place all definitions into Article 100, I would suggest a new Part III Hazardous Location and include all definitions associated with Articles in the new part which could be under the jurisdiction of CMP-14. 8

9 14-9 Log #1999 NEC-P14 Eliana Brazda, ISA Add new text to read as follows: Electromagnetic radiation at wavelengths in vacuum between the region of transition to X-rays and the region of transition to radio waves, that is approximately between 1 nm and 1,000 ìm. Informational Note: For additional information on types of protection that can be applied to minimize the risk of ignition in explosive gas atmospheres from optical radiation in the wavelength range from 380 nm to 10 µm, see ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where visible or infrared radiation is incapable of producing sufficient energy under normal or specified fault conditions to ignite a specific hazardous atmospheric mixture. Informational Note: See ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where radiation is confined inside optical fibre or other transmission medium under normal constructions or constructions with additional mechanical protection based on the assumption that there is no escape of radiation from the confinement. Informational Note: See ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where radiation is confined inside protected or unprotected optical fibre or other transmission medium with interlock cut-off provided to reliably reduce the unconfined beam strength to safe levels within a specified time. Informational Note: See ANSI/ISA TR , Optical fibre cable protected from releasing optical radiation into the atmosphere during normal operating conditions and foreseeable malfunctions by additional armouring, conduit, cable tray or raceway. Informational Note: See ANSI/ISA TR , The 2011 edition of the NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. It does address optical fiber cables, but not from the perspective of the potential to cause ignition. ANSI/ISA-TR ,, contains published US national requirements that address the potential risk of ignition associated with optical radiation in Division classified areas. This ANSI/ISA standard is aligned with harmonized with ANSI/ISA ( ),, and IEC/EN :2006,, for Zone classified areas. ANSI/ISA-TR defines three types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. These types of protection are: 1) inherently safe optical radiation; 2) protected optical radiation; and 3) optical system with interlock. This proposal introduces these types of protection, along with the general term optical radiation and one of the more common applications of optical radiation in explosive atmospheres, protected optical fiber cable. Additional proposals are being submitted to introduce related, supporting text under and It should be noted that the sources of the optical radiation are electrical equipment. Therefore this proposal is necessary for inclusion in the NEC. There is no need to define terms that are not used in the Code. Affirmative: 14 Negative: 1 9

10 MASSEY, L.: The current NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. ANSI/ISA-TR defines types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. 10

11 14-10 Log #2007 NEC-P14 Eliana Brazda, ISA Dusttight Informational Note: ANSI/ISA , ANSI/ISA , Electrical and Electronic Equipment: ISA-RP , ANSI/ISA ,. Hermetically Sealed Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Circuit Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Component Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Equipment Informational Note: ANSI/ISA ANSI/ISA , Nonincendive Field Wiring Apparatus Informational Note: ANSI/ISA , ANSI/ISA , Remove the ISA standards date of publication to allow application of all appropriate versions. Accept the changes proposed by the submitter, but include the appropriate publication dates of The two references will read: ANSI/ISA , and ANSI/ISA , Paragraph of the Regulations Governing Committee Projects requires dated references to Standards. The current publication dates for ISA and are Affirmative: 13 Negative: 2 SIMMONS, J.: The intent of this proposal is to update the standard date and title of the existing informational note. My negative vote on this is based on my feeling that the informational note needs to be deleted and not updated. Section has seventeen definitions. Eleven of these definitions have informational notes, of which ten reference other standards. One of the standards is referenced in five of the informational notes. I then look at 500.4(B) Reference 11

12 Standards and I see five more informational notes referencing other standards. We have to use informational notes to reference the standards or they would become Code rules. Pages 368 and 369 of the 2011 NEC (softback) have approximately 45% of the print area covered with unenforceable information. The current tendency to proliferate the use of informational notes seems to be in conflicts with the National Electrical Code, 2011 edition, Article 90 - Introduction, 90.1 (C) Intention. This code is not intended as a design specification or an instructional manual for untrained persons. In my opinion, the majority of users will never look at the referenced standards nor will they need them to complete a safe installation; those who will already know where they are. It is my belief that we can improve the readability and usability of the NEC and still provide the user with the standards references provided in these informational notes by including the references in Informational Annex A. The Informational Annex A could be reorganized into a numbered list and sections such as 500.4(B) Reference Standards could simply state See Informational Annex A. List item numbers could be included, if deemed necessary by the technical committee. It is important to guide the Code user to other references that will provide the information needed to insure that final product provides a safe design and installation. In doing so, we must also remember the safe design and installation of an electrical project requires a Code document that the designer and installer can easily read and understand. WECHSLER, D.: Action should have been to reject. The proposal merely reflects a date change and lacks technical substation for this change. Code making panels need to have proper information upon which to make an informed decision of the continued applicability of the document to the Code process and therefore need to have an understanding of the document changes. As indicated in log , changes were made to the energy requirements for intrinsic safety which had nothing to do with a safety issue; just a business decision to harmonize. Perhaps if a full disclosure NFPA process had been followed, agreeing to the document change might not be supported by the Code panel. Lastly, it appears that of the Regulations Governing Committee Projects requires product standards contained in informational notes to have revision dates. This makes sense if these product standards reflect agreement by the CMP to use the defined products in hazardous classified locations. Therefore by implication the CMP endorses the product standard. However, adding a product standard reference or making changes to a formerly recognized product standard should then follow the NFPA NEC proposal submission process and provide clear justification for the product standard addition/ change. 12

13 14-11 Log #1219 NEC-P14 Marcelo M. Hirschler, GBH International Apparatus in which the circuits are not necessarily nonincendive themselves but that affect the energy in nonincendive field wiring circuits and are relied upon to maintain nonincendive energy levels. Associated nonincendive field wiring apparatus may be either of the following: (1) Electrical apparatus that has an alternative type of protection for use in the appropriate hazardous (classified) location (2) Electrical apparatus not so protected that shall not be used in a hazardous (classified) location Associated nonincendive field wiring apparatus has designated associated nonincendive field wiring apparatus connections for nonincendive field wiring apparatus and may also have connections for other electrical apparatus. : Associated nonincendive field wiring apparatus may be either of the following: (1) Electrical apparatus that has an alternative type of protection for use in the appropriate hazardous (classified) location (2) Electrical apparatus not so protected that shall not be used in a hazardous (classified) location The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this a Log #CP1411 NEC-P14 Code-Making Panel 14, In replace the current definition of Combustible Dust with the following: Combustible Dust. Dust particles of 500 microns or smaller (material passing a U.S. No. 35 Standard Sieve as defined in ASTM E 11, Standard Specification for Wire Cloth and Sieves for Testing Purposes) are considered to present a dust fire or dust explosion hazard unless determined otherwise. (See ASTM E 1226 or ISO 6184/1). [499:3.3.3] revised. Definition is extracted from NFPA 499 and the definition in the 2012 Edition of NFPA 499 has been Affirmative: 9 Negative: 6 CADD, J.: NFPA Standard 499 from which the extracted definition is being used is not published yet. GOODMAN, M.: The referenced standard NFPA has not been published. JONES, R.: NFPA Edition has not been published. KUCZKA, J.: Although we agree with the new definition, the 2012 edition of the referenced document has not yet been published. MASSEY, L.: Referenced standard, NFPA 499:2012 is not yet published. NEAGLE, J.: The document referenced in the substantiation, NFPA has not been published. 13

14 14-11b Log #CP1402 NEC-P14 Code-Making Panel 14, Add a new definition to 500.2, 505.2, and to read: Cord Connector. A fitting intended to terminate a cord to a box or similar device and reduce the strain at points of termination and may include an explosionproof, a dust ignition proof, or a flameproof seal. The existing term "cord connector" has different meanings in other places, which has caused confusion. The inclusion of this definition in these three articles makes it clear as to the meaning of the term as a mechanical device, not as an electrical device, and is based on the product standard ANSI/UL 514B. Affirmative: 12 Negative: 3 GOODMAN, M.: The term cord connector is not the appropriate term for the intent. The item is a fitting and the descriptive term cord fitting would be more appropriate. MCBRIDE, W.: The term cord connector is used in other places in the NEC as a wiring device such as in (A) where it permits a "cord connector" to be considered a receptacle outlet. Section defines a cord connector as a device for establishing a connection. The term fitting is commonly used in the NEC and product standards related to flexible cords products that are attached to enclosures. Section 400.7(B) uses the term cord connector body as device used to energize an attachment plug. The term "cord fitting", should be used in sections (B)(4), (4), (4), (5), (5) and anywhere else the term is used to describe the fitting. As presently used in these articles the term cord connector is confusing whether the term is defined differently (for no good reason) or not. The term "cord connector" is commonly used in the field to describe a wiring device that is connected to a cord. The term "fitting" is used in many other NEC sections to describe the product used to secure a cord to an enclosure. Users of Chapter 5 are not exempt from the requirements in Chapters 1 through 4, chapter 5 requirements can supplement or modify the general rules but creating using the same term to define different items should not be done and will create confusion and likely misinterpretation of the associated requirements. WECHSLER, D.: The panel action should have been to reject. If a change was going to be made, a better term selected might have been 'cord fitting' and not 'cord connector'. The term 'cord connector' is not appropriate in this case and a different term that includes the word "fitting" should be used as part of the term, not to describe something different. It is the product standard that is in need of change, not the NEC. ANSI/UL 514B is not limited for use in hazardous (classified) areas. The term fitting is widely used in UL product standards to refer to these and other types of products that are used to secure wiring methods and cords to equipment. The actual title of UL 514B uses the term fittings, not connectors "Conduit, Tubing, and Cable Fittings".Section 1.2 of UL 514B uses the phrase "fittings for flexible cord" Interestingly 1.4 states "These requirements do not cover FITTINGS intended for use in hazardous locations as defined in the National Electrical Code, ANSI/NFPA 70, the Canadian Electrical Code (CEC), Part I, CSA C22.1, and the Standard for Electrical Installations, NOM-001-SEDE." The term cord connector is used in other places in the NEC as a wiring device such as in (A) where it permits a "cord connector" to be considered a receptacle outlet. Section defines a cord connector as a device for establishing a connection. The term fitting is commonly used in the NEC and product standards related to flexible cords products that are attached to enclosures. Section 400.7(B) uses the term cord connector body as device used to energize an attachment plug. The term "cord fitting", flexible cord fitting" or something similar should be used in sections (B)(4), (4), (4), (5), (5) and anywhere else the term is used to describe the fitting. As presently used in these articles, the term cord connector is confusing whether the term is defined differently (for no good reason) or not. The term "cord connector" is commonly used in the field to describe a wiring device that is connected to a cord. Users of Chapter 5 are not exempt from the requirements in Chapters 1 through 4, chapter 5 requirements can supplement or modify the general rules but creating using the same term to define different items should not be done and will create confusion and likely misinterpretation of the associated requirements. The term "fitting" is used in many other NEC sections to describe the product used to secure a cord to an enclosure. 14

15 14-12 Log #1220 NEC-P14 Marcelo M. Hirschler, GBH International A component having contacts for making or breaking an incendive circuit and the contacting mechanism is constructed so that the component is incapable of igniting the specified flammable gas air or vapor air mixture. The housing of a nonincendive component is not intended to exclude the flammable atmosphere or contain an explosion. For further information, see ANSI/ISA , : The housing of a nonincendive component is not intended to exclude the flammable atmosphere or contain an explosion. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this Log #1221 NEC-P14 Marcelo M. Hirschler, GBH International Wiring that enters or leaves an equipment enclosure and, under normal operating conditions of the equipment, is not capable, due to arcing or thermal effects, of igniting the flammable gas air, vapor air, or dust air mixture. Normal operation includes opening, shorting, or grounding the field wiring. : Normal operation includes opening, shorting, or grounding the field wiring. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this. 15

16 14-14 Log #3186 NEC-P14 Stephen Crimaudo, American Petroleum Institute Replace "1997" date reference to ANSI/API RP500 to "2012" as indicated below. ANSIAPI RP , I, This and the companion proposals propose to update the date references to ANSI/API RP 500. The latest edition of ANSI/API RP 500 has been approved for publication and is expected to be published by API in early The 2012 edition of the referenced document has not been published yet Log #3187 NEC-P14 Stephen Crimaudo, American Petroleum Institute Replace "1997" date reference to ANSI/API RP500 to "2012" as indicated below., Informational Note No. 4: For further information on ventilation, see NFPA , and API RP This and the companion proposals propose to update the date references to ANSI/API RP 500. The latest edition of ANSI/API RP 500 has been approved for publication and is expected to be published by API in early The 2012 edition of the referenced document has not been published yet. 16

17 14-15a Log #CP1413 NEC-P14 Code-Making Panel 14, Classifications of Locations (A) Classifications of Locations. Locations shall be classified depending on the properties of the flammable gas, flammable liquid-produced vapor, combustible-liquid produced vapors, combustible dusts, or fibers/flyings that may be present, and the likelihood that a flammable or combustible concentration or quantity is present. Where pyrophoric materials are the only materials used or handled, these locations shall not be classified. Each room, section, or area shall be considered individually in determining its classification. Where pyrophoric materials are the only materials used or handled, these locations are outside the scope of this article. The language is being updated to be consistent with current language found in Section 506.5(A) and consistent with the fact that neither NFPA 497 or NFPA 499 currently address the use of pyrophoric materials Log #265 NEC-P14 Billy Breitkreutz, Fluor Corporation Add an Informational Note No. 3 to read as follows: Informational Note No. 3: Pyrophoric materials should be in containment systems designed to prevent contact between the pyrophoric material and air. The pyrophoric material might escape in very small amounts and combine with air at a level and temperature that would not cause spontaneous combustion. Ignition might be avoided if electrical equipment in the area is suitable for a classified location. Silane (SiH 4 ) is a pyrophoric gas that will not spontaneously ignite when mixed with air at a low level and temperature. Silane must be loaded into containers for transportation using a connection that might leak a very small quantity and mix with air at such a low level and temperature. Code Section 505.5(A) prohibits classification of the area. The Code does not prohibit installation of equipment suitable for a hazardous area in the non-hazardous area. The proposed change will make clear that installation of equipment suitable for a hazardous area in this non-hazardous is a recognized practice. The methods of protection identified in Articles 500, 505, and 506 do not provide a sufficient degree of protection for pyrophoric material. Pyrophoric materials are specifically excluded from the scopes of NFPA 497,., and NFPA 499, 17

18 14-17 Log #2167 NEC-P14 Marcelo M. Hirschler, GBH International ASTM D3175: new date is 2011 Standards update. This is extracted text and cannot be altered by Panel Log #3188 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA Log #2689 NEC-P14 Jeremy Neagle, US Bureau of Alcohol, Tobacco, Firearms & Explosives Informational Note No. 3: Certain dusts may require additional precautions due to chemical phenomena that can result in the generation of ignitible gases. See ANSI/IEEE C ,, Section 127A, Coal Handling Areas. IEEE is the organization responsible for the development of the National Electrical Safety Code. The current edition is This document is referenced in various sections throughout the NEC as either ANSI C2 or ANSI/IEEE C2. I suggest the NEC Technical Correlating Committee review these sections (110.31, , 225.1, , , , , , 500.6, , , , , ) and update as appropriate. 18

19 14-20 Log #2000 NEC-P14 Eliana Brazda, ISA Add new text to read as follows: This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon the number of faults applied as part of the protection technique evaluation. This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon whether or not additional mechanical protection is provided as part of the protection technique evaluation. This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon the confinement construction and upon the shut-down time in which the unconfined beam strength is reliably reduced to safe levels. The 2011 edition of the NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. It does address optical fiber cables, but not from the perspective of the potential to cause ignition. ANSI/ISA-TR ,, contain published US national requirements that address the potential risk of ignition associated with optical radiation in Division classified areas. This ANSI/ISA standard is aligned with harmonized with ANSI/ISA ( ),, and IEC/EN :2006,, for Zone classified areas. ANSI/ISA-TR defines three types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. These types of protection are: 1) inherently safe optical radiation; 2) protected optical radiation; and 3) optical system with interlock. This proposal introduces these types of protection, along with the general term optical radiation and one of the more common applications of optical radiation in explosive atmospheres, protected optical fiber cable. Additional proposals are being submitted to introduce related, supporting text under and It should be noted that the sources of the optical radiation are electrical equipment. Therefore this proposal is necessary for inclusion in the NEC. The technical report referenced in the substantiation does not establish that the testing criteria provided are indicative of typical installations in hazardous (classified) locations and there is no evidence that existing equipment in use should be tested to these additional standards. Affirmative: 14 Negative: 1 MASSEY, L.: The current NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. ANSI/ISA-TR defines types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. 19

20 14-21 Log #1171 NEC-P14 Jon D. Miller, Detector Electronics Corp. Change the text to the following : (1) Inadequate Ventilation. In a Class I, Division 1 location that is so classified due to inadequate ventilation, electrical equipment suitable for Class I, Division 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. ( 2) Interior of a Building. In a building located in, or with an opening into, a Class I, Division 2 location where the interior does not contain a source of flammable gas or vapor, electrical equipment for unclassified locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1 or Class I, Division 2, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. ( 3) Interior of a Control Panel. In the interior of a control panel containing instrumentation utilizing or measuring flammable liquids, J gases, or vapors, electrical equipment suitable for Class I, Division 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. The listing of the gas detector would include the gasses or vapors for which the detector is intended (not "encountered"). A Methane gas detector encounters Nitrogen (within air), but the Methane gas detector is not listed for Nitrogen. Gas detection equipment can be intended to detect, for example, a noncombustible gas or a combustible gas other than the one to be encountered, and that would not fulfill the requirements of using gas detection as a method of protection Log #3189 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA 499. The more general term "ignition temperature" is appropriate here, since this section addresses gases, vapors, dusts, and fibers/flyings. 20

Report on Proposals June 2013 NFPA 70

Report on Proposals June 2013 NFPA 70 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever

More information

AGENDA. NEC Code-Making Panel 14. Report on Proposal Meeting. January 16-21, Hilton Head, SC

AGENDA. NEC Code-Making Panel 14. Report on Proposal Meeting. January 16-21, Hilton Head, SC National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 14 Report on Proposal Meeting January 16-21,

More information

AGENDA. NEC Code-Making Panel 14. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA

AGENDA. NEC Code-Making Panel 14. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 14 Report on Comment Meeting November 28-December

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea DATE:

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

Overview of Hazardous Locations as They Relate to Solenoid Valves

Overview of Hazardous Locations as They Relate to Solenoid Valves Overview of Hazardous Locations as They Relate to Solenoid Valves Defined: Hazardous Location - "where fire or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED October 3rd, 2017 Vincent W. Wedelich, PE, MBA Project Manager Associate Electrical Engineer 10 Years

More information

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems Products Solutions Services CT287 Hazardous Area Classifications and Protection Systems Slide 1 Topics covered Types of Hazardous Area classifications with focus on North America Types of hazardous protection

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

Smoke detection in hazardous areas:

Smoke detection in hazardous areas: WHITE PAPER Smoke detection in hazardous areas: What you need to know Smoke detection in hazardous areas requires detectors that operate effectively and safely in explosive environments. Having the correct

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification September 2016 Electrical PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry

More information

Public Comment No. 13-NFPA [ Section No ]

Public Comment No. 13-NFPA [ Section No ] Public Comment No. 13-NFPA 30-2013 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 395/A395M, Standard

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT Olof Bekker Pr. Eng. BSc. Eng. BML S.MSAIEE, M.NACE Engineering Manager, Electrical COMMITMENT

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 80601-2-13 First edition 2011-08-01 Medical electrical equipment Part 2-13: Particular requirements for basic safety and essential performance of an anaesthetic workstation Appareils

More information

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates Note: While this material was originally prepared for presentation in February 1999, it has been updated to reflect the evolving technical requirements now applicable as of April 2003. UL Topic III Converting

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

CODE DIGEST CODE DIGEST. Solutions.Worldwide.TM Crouse-Hinds is a registered trademark of Cooper Industries, Inc. COOPER CROUSE-HINDS

CODE DIGEST CODE DIGEST. Solutions.Worldwide.TM Crouse-Hinds is a registered trademark of Cooper Industries, Inc. COOPER CROUSE-HINDS COOPER CROUSE-HINDS COOPER CROUSE-HINDS CODE DIGEST CODE DIGEST Article 500-516 of the National Electrical Code with product recommendations for use in hazardous (classified) areas. Distributed by: For

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI Technical Committee on Electrical Equipment Evaluation ROC Meeting Agenda September 28-29, 2010 Providence, RI Item 10-09-1 Call to Order Item 10-09-2 Introductions Item 10-09-3 Staff Remarks Item 10-09-4

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2014 CEC-18 [rev-11] Page 1 of 9 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Introduction to Hazardous Electrical Location Classifications

Introduction to Hazardous Electrical Location Classifications Introduction to Hazardous Electrical Location Classifications Introduction In North America the target audience for this white paper and the electrical code classification ratings for various types of

More information

Part I Extraction Process Equipment

Part I Extraction Process Equipment 745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin October 2007 Page 1 of 11 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification requirements

More information

Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code Oberon s suspended ceiling

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,

More information

Report on Public Input June 2014 NFPA 101

Report on Public Input June 2014 NFPA 101 101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and

More information

Report on Proposals June 2010 NFPA 70

Report on Proposals June 2010 NFPA 70 16-1 Log #4917o NEC-P16 Caleb M. Ferris, Chadwick Electric Add a diagram table after the scope of each article similar to the one in Article 430. For NEC user cost make the table layout diagram in 430.8

More information

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen IEC 60079-29-2 Edition 2.0 2015-03 REDLINE VERSION colour inside Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations Contents Executive Summary... 1 Regulatory Requirements in the Gulf of Mexico for Hazardous Locations... 2 Referenced Codes and Standards... 2 Memorandum of Agreement... 2 Bureau of Ocean Energy Management

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 15 FROM: Kimberly Shea DATE:

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Hazardous Locations Products No. 28 (Supersedes Electrical Certification Notice No. 544A) Date: January 3, 2018 See Attachment 1 for Effective Dates. See Attachment 1

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements Class Number 3600 November 1998 2002 FM Approvals LLC. All rights reserved. Foreword FM Approvals

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS ENCLOSURES. Select equipment enclosures to provide the following: To protect facility personnel from coming in contact with live parts.

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin June 2018 CEC-18 [rev-13] Page 1 of 6 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous locations Rule 18-006 Locations containing an explosive gas atmosphere

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 3 FROM: Kimberly Shea DATE:

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

Numerical Standards Listing

Numerical Standards Listing Numerical Standards Listing ISA-RP2.1-1978 - Manometer Tables ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification (Formerly ANSI/ISA-5.1-1984 [R1992]) ISA-5.2-1976 (R1992) - Binary Logic

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Fire Prevention Plan Program

Fire Prevention Plan Program Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,

More information

Meeting NFPA standards for

Meeting NFPA standards for 24 Fire safety Meeting NFPA standards for flame, smoke and gas detection Fire is one of the most critical hazards in any built environment, and industrial processes and facilities that involve volatile

More information

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC EUROPEAN ATEX DIRECTIVE > European Directive 2014/34/EU ATEX Directive 2014/34/EU is a "new approach" directive that applies to protective systems against explosions as well as all equipment used in or

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Articles , & National Electrical Code Review & Application Guide

Articles , & National Electrical Code Review & Application Guide Articles 500-506, 510-511 & 513-516 2011 National Electrical Code Review & Application Guide Established in 1913, Killark has become a global provider of harsh and hazardous location equipment. The Killark

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

Report on the activities of the ATEX consultant. Xavier Lefebvre. Contract : CENELEC/NA Consultant/2013-1

Report on the activities of the ATEX consultant. Xavier Lefebvre. Contract : CENELEC/NA Consultant/2013-1 Report on the activities of the ATEX consultant Xavier Lefebvre Contract : CENELEC/NA Consultant/2013-1 Period covered: from 1 January 2013 to 1 July 2013 1. Attended meetings Date Subject Location 2013.01.28

More information

Special Occupancy Requirements

Special Occupancy Requirements Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the

More information

Interpreting the National Electrical Code. By Tim Kuhlman, PE, RCDD

Interpreting the National Electrical Code. By Tim Kuhlman, PE, RCDD Interpreting the National Electrical Code By Tim Kuhlman, PE, RCDD CH2M HILL Interpreting the NEC The National Electrical Code is not written for the casual reader. To properly interpret the Code you must

More information

A Guide to Safe Electronic Weighing in Hazardous Locations

A Guide to Safe Electronic Weighing in Hazardous Locations SMART SOLUTIONS FOR DEMANDING INDUSTRIES Solutions for Process Weighing and Force Measurement Handbook TC0013 1. Hazardous Locations... 2 2. Methods of Protection... 3 3. Approval/Listing of Equipment...

More information

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Understanding Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Michigan Safety Conference April 11, 2017 Mike Snyder PE CSP CFPS Vice President Organizational

More information

INTERNATIONAL STANDARD NORME INTERNATIONALE

INTERNATIONAL STANDARD NORME INTERNATIONALE IEC 62031 INTERNATIONAL STANDARD NORME INTERNATIONALE Edition 1.0 2008-01 2 62031 IEC:2008 CONTENTS FOREWORD...3 INTRODUCTION...5 1 Scope...6 2 Normative references...6 3 Terms and definitions...7 4 General

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related

Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related Introduction One of the proposals to change the 2002 NEC adds a provision

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

THE USE OF COMBUSTIBLE GAS DETECTION IN HAZARDOUS LOCATIONS

THE USE OF COMBUSTIBLE GAS DETECTION IN HAZARDOUS LOCATIONS THE USE OF COMBUSTIBLE GAS DETECTION IN HAZARDOUS LOCATIONS Copyright Material IEEE Paper No. PCIC-PH-56 Allan Bozek, IEEE Senior Member EngWorks Inc. 1620 49 th Ave. SW Calgary, AB, T2T2T7 Canada abozek@engworks.ca

More information

Installation guide for hazardous areas

Installation guide for hazardous areas Installation guide for hazardous areas This installation guide should not be used as the controlling document for the installation of devices in a hazardous area. This guide is NOT A CONTROL DRAWING. Any

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

AS/NZS :2014. Electrical equipment for coal mines Introduction, inspection and maintenance AS/NZS :2014. Part 1: For hazardous areas

AS/NZS :2014. Electrical equipment for coal mines Introduction, inspection and maintenance AS/NZS :2014. Part 1: For hazardous areas AS/NZS 2290.1:2014 Australian/New Zealand Standard Electrical equipment for coal mines Introduction, inspection and maintenance Part 1: For hazardous areas Superseding AS/NZS 2290.1:2005 AS/NZS 2290.1:2014

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Report on Proposals Copyright, NFPA NFPA 505 Report of the Committee on

Report on Proposals Copyright, NFPA NFPA 505 Report of the Committee on Report of the Committee on Staff Liaison: James D. Lake Industrial Trucks Joseph John Dahlstrom, Chair UK and Associates, IL [SE] Lewis C. Barbe, World Safety Organization, MN [SE] Denise Beach, National

More information