1 SECTION COMMON WORK RESULTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The drawings and general provisions of the Contract, including General and Supplementary Conditions, General Requirements and all other Specification Sections apply to the work specified in this section. 1.2 SUMMARY A. This section includes the storm, soil, waste, drain, vent and domestic water systems from their source of supply or point of disposal to and including their connection to equipment and fixtures. B. Contractor shall coordinate required water, gas, foundation drainage, storm, and sanitary services with the general contractor. Contractor shall perform all work within the building and to a point five (5) feet from the building wall and shall be coordinated with civil work. C. Related Sections: 1. Section Project Management and Coordination. 2. Section Mechanical and Electrical General Provisions for common work requirements. 3. Section Motors for motors requirements. 4. Section Basic Materials and Methods for hangers, supports, piping, specialties, etc. 5. Section Mechanical Systems Insulation for plumbing equipment and piping insulation. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.4 CODES A. All plumbing work shall comply with the latest International Plumbing Code and the regulations of the South Carolina Department of Health and Environmental Control (DHEC), and the State of South Carolina. Obtain all approvals before starting plumbing work. Request all inspections during the course of work. B. Installation shall meet the regulations contained in the Safe Drinking Water Act (SDWA) concerning lead and copper concentrations. C. All residential type faucets, electric water coolers and drinking fountains shall meet the requirements of NSF Standard 61, Section 9. COMMON WORK RESULTS FOR PLUMBING

2 1.5 QUALITY ASSURANCE A. All building domestic and service water heating systems shall meet the mandatory provisions for performance as documented in ASHRAE The minimum performance requirements listed in ASHRAE must be met. B. All work shall be in accordance with the following industry standards and associations. 1. Air Conditioning, Heating, and Refrigeration Institute (AHRI) 2. American National Standards Institute (ANSI) 3. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 4. American Society of Plumbing Engineers (ASPE) 5. American Society of Sanitary Engineering (ASSE) 6. American Water Works Association (AWWA) 7. American Society of Mechanical Engineers (ASME) 8. ASME International (ASTM) 9. Cast Iron Soil Pipe Institute (CISPI) 10. Manufacturers Standardization Society (MSS) 11. NSF International (NSF) 12. Plumbing and Drainage Institute (PDI). 1.6 SERVICES A. Contractor shall arrange for and coordinate water, gas, storm, and sanitary services. Contractor shall perform all work within the building and to a point five (5) feet from the building wall and shall be coordinated with civil work. The building water main, natural gas, sanitary and storm sewers shall connect to site water mains, gas mains and sewers provided under another Division. B. Before any sewer work is done inside the property line, the Contractor shall uncover each street sewer at the point of connection and shall determine the actual sewer elevation. If actual elevation is such that the drainage systems cannot be installed as shown, notify the Architect before proceeding with any work. C. Gas service, regulator and seismic shut-off valve shall be provided by the plumbing contractor. 1.7 EQUIPMENT CONNECTIONS A. Provide all plumbing connections required by equipment which is provided on this project. Certain items of equipment shall be provided under this section and certain items will be furnished and set under other sections of the specifications. In all cases, provide valved water supplies, waste and vent lines, and, unless noted otherwise, make final connections after equipment is in place. COMMON WORK RESULTS FOR PLUMBING

3 PART 2 - PRODUCTS 2.1 PIPE, VALVES AND FITTINGS A. Provide materials as hereinbefore specified in Division 23, Section Basic Materials and Methods. All floor, wall and ceiling penetrations for piping shall be sealed with appropriate sealant. B. Unions or flanges shall be provided at all connections to each piece of plumbing equipment and on both sides of valves and other in-line devices that require removal for maintenance. Bronze adaptors shall be used at all copper to flanged or IPS connections. 2.2 CLEANOUTS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following, equal to the basis of design indicated below: 1. Josam Company; Josam Div. 2. Smith, Jay R. Mfg. Co. 3. Zurn Plumbing Products Group; Specification Drainage Operation. B. Cleanouts shall be placed in piping throughout the building, where noted and where required by code and at not greater than fifty (50) foot intervals. Cleanouts on piping below floors, at ends of runs and changes of direction of piping shall consist of Y branches, the full size of pipes to which they are connected with cleanout plugs and covers as listed below or as detailed. Extend cleanouts on concealed piping to finished walls, floors and grade. C. In concrete floors on grade (generally) J.R. Smith Series 4000 cleanout with cast iron cleanout with square, adjustable, scoriated, secured nickel bronze top, and adjustable frame. D. At base of vertical piping and in walls J.R. Smith Series 4000 cleanout tee with countersunk bronze threaded plug. Where risers are concealed, provide Series 4000 cleanout tee with plug and nickel satin access cover and frame. E. Cleanouts on exposed and above ceiling horizontal piping shall be J.R. Smith Series 4000 with bronze threaded plug. F. Cleanouts in exterior underground piping shall be countersunk set in four (4) inch extra heavy cast iron pipe extension to grade. Provide J.R. Smith Series 4000 set in twelve (12) inches by twelve (12) inches by eight (8) inches concrete finished flush with grade. G. Provide cleanouts in each exposed P-trap not integral with the fixture. H. Clean-outs shall be the same nominal size of the pipe for sizes 4 and smaller and 4 nominal size for larger pipe. 2.3 DRAINS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following, equal to the basis of design indicated below: COMMON WORK RESULTS FOR PLUMBING

4 1. Josam Company; Josam Div. 2. Smith, Jay R. Mfg. Co. 3. Zurn Plumbing Products Group; Specification Drainage Operation. B. Provide floor drains where indicated and shown on the drawings. Provide color and round/square shape to match Architect s final finishes. 1. FD-1 (Mechanical Rooms): JR Smith 2000 Series C. Drains receiving indirect waste shall be provided with ½ grates as required to receive discharge without splashing. D. Trap Guard: 1. Provide at each floor drain one (1) elastomeric, normally closed trap guard device which shall utilize a normally closed seal to prevent evaporation of the trap seal and also protect and allow liquid drainage to flow through into the building drain. Device shall be ProVent ProSet trap guard or prior approved equal. 2.4 PLUMBING FIXTURES A. Provide all plumbing fixtures indicated on the drawings and as specified herein. B. All exposed metal parts of all fixtures, including all trim and fittings, shall be brass, chromium plated. C. Each hot and cold water connection to each fixture shall be provided with a stop valve and all nipples shall be chrome plated red brass. D. Provide backflow devices on all faucets and fittings requiring same. Devices may be inline type when not provided integral with the faucet. E. All faucet handles, where possible, shall have color coded "indexes" identifying the service used. F. All "serrated" or slip hose connection spout outlets shall have Allen wrench operated volume controls to control "splashing" of water as it hits sink bottoms. G. Waste line for handicapped lavatories and sinks shall be offset as required. H. Water supplies for handicapped water closets shall be roughed-in for flush valve handles to be operated from the accessible side of the water closet. The Contractor shall coordinate and provide flush handles on the accessible side of all handicapped water closets. Provide offset flush connection as required to coordinate with wall mounted grab bars to all ADA water closets with flush valves. I. The Contractor shall provide metal supports necessary to adequately and substantially hang and set all fixtures subject to the approval of the Architect. No wood grounds, wood plugs, or expansion bolts shall be permitted for fixture support. Provide carriers where specified below and as required to hang fixtures. J. Insulate all exposed piping under handicapped lavatories and sinks with a white, fitted/molded antimicrobial undersink pipe cover equal to Truebro Lav Guard 2. Cover shall have internal, E- COMMON WORK RESULTS FOR PLUMBING

5 Z Tear-To-Fit trim feature for square, clean trimming (internal ribs) and built-in, concealed E-Z Grip fasteners (no cable-tie fasteners allowed). K. Water-Conserving Fixtures: Plumbing fixtures and fittings shall use in aggregate at least 30% less water than the water use baseline calculated for the building after meeting the Energy Policy Act of 1992 fixture performance requirements. Flow and flush rates shall not exceed the following: 1. Toilets: no more than 1.3 gallons per flush and have documented bowl evacuation capability per MaP testing of at least 400 grams. 2. Urinals: no more than 0.5 gallons per flush or use. 3. Lavatory Faucets: 0.5 gpm with automatic faucet controls. 4. Showerheads: no more than 1.5 gpm. L. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Water Closets: a. American Standard America. b. Crane Plumbing, L.L.C. c. Eljer. d. Kohler Co. e. Sloan Valve Company. 2. Toilet Seats: a. Bemis Manufacturing Company. b. Centoco c. Church Seats. 3. Flushometer Valves: a. American Standard America. b. Crane Plumbing, L.L.C. c. Eljer. d. Kohler Co. e. Sloan Valve Company. 4. Lavatories: a. American Standard America. b. Eljer. c. Kohler Co. d. Sloan Valve Company. 5. Faucets: a. American Standard America. b. Chicago Faucets. c. Crane d. Eljer e. Kohler Co. f. Sloan Valve Company. COMMON WORK RESULTS FOR PLUMBING

6 g. T & S Brass and Bronze Works, Inc. h. WaterSaver. 6. Stainless Steel Sinks: a. Franke b. Kindred 7. Drinking Fountains: a. Elkay Manufacturing Co. b. Halsey Taylor. c. Haws Corporation. d. Oasis International. 8. Mop Sinks a. Fiat. b. Acorn. 9. Drain Accessories: P-traps, strainers, angle stops, escutcheons and supplies a. Brasscraft b. Dearborn c. EBC d. McGuire 10. Icemaker Water Connection Outlet Boxes: M. Fixtures: a. Acom Engineering Company b. IPS Corporation c. LSP Products Group, Inc. d. Oatey. e. Plastic Oddities. 1. P-1 Water Closet: Fixture: Flush Valve: Seat: Remarks: Junior Floor Mounted Water Closet: Sloan Model ST Optima Plus solar-powered infrared sensor for automatic no hands operation, infrared sensor with multiple focused sensing fields for high and low target detection, latching solenoid operator, courtesy flush override button, sensor assembly powered by a solar cell, four size AA battery back-up source gpf closet flushometer. Bemis BB955CT Heavy-duty, open front less cover for baby bowl. Stainless steel check-hinge with gasket, metal flat washers, lock washers and stainless steel nuts. Shall comply with American Nation Standard Z124.5 Toilet Seats as a class Commercial Heavy Duty. Floor mounted, baby bowl, vitreous china, 10.75" rim height, 1 ½ top spud. COMMON WORK RESULTS FOR PLUMBING

7 2. P-2 Lavatory: Fixture: Faucet: Strainer: Trap: Supplies and Stops: Carrier: Remarks: Sloan SS-3003 wall hung lavatory with backsplash, white vitreous china, single hole, front overflow, ADA compliant. Sloan Optima Solis Model EAF-275-ISM solar powered, sensor activated electronic hand washing faucet with integral spout mixer, one (1) 6 VDC Lithium battery back-up and 0.5 gpm laminar spray head. Time out setting for faucet shall be set for 45 seconds. Faucet shall include factory calibrated mixing valve which conforms to ASSE 1070 not to exceed 110. McGuire 155-WC cast brass chrome plated offset wheelchair strainer with polished chrome cast brass elbow, 17 gauge 1-1/4 inch seamless brass offset tailpiece, heavy rubber basin washer and fiber friction washer. Offset lavatory strainer shall be in compliance with CSA or other recognized testing authority and bear both manufacturer and testing mark. McGuire 8902 cast brass chrome plated 1-1/4" x 1-1/2" P-trap with cleanout with 17 gauge tubular wall bend, cast brass slip nuts. Trap shall be in compliance with CSA and bear both manufacturer and testing mark. Chicago Faucets No CP, angle stop fitting with supply tube and loose key. Josam Series floor mounted support Contractor shall verify and coordinate rough-in locations. Installation shall meet the American with Disabilities Act guidelines and ANSI A117.1 Accessible and Usable Buildings and Facilities. 3. P-3 Classroom Sink: Fixture: Kindred model QSLA2031/8. A drop-in single-bowl sink, seamless 20 gauge, 18-8 stainless steel. Bright mirror finished rim and satin finished bowl. Smooth, fully coated underside. 8 deep, 3 hole, 1 ½ diameter, 4 center-to-center. Center drain punched for 3 ½ drain opening. Faucet: Strainer: Trap: Kindred model KF10, high arch gooseneck stainless steel, ceramic disc cartridge, faucet requires 1 ½ diameter hole, aerated stream flow, and flexible braided supply hose. McGuire 1151-WC cast brass chrome plated offset basket strainer with polished chrome cast brass elbow, 17 gauge 1-1/2 inch seamless brass offset tailpiece, heavy rubber basin washer and fiber friction washer. Offset basket strainer shall be in compliance with CSA or other recognized testing authority and bear both manufacturer and testing mark. McGuire 8912C cast brass chrome plated 1-1/2" x 1-1/2" P-trap with cleanout with 17 gauge tubular wall bend, cast brass slip nuts. Trap shall be in compliance with CSA and bear both manufacturer and COMMON WORK RESULTS FOR PLUMBING

8 testing mark. Supplies and Stops: Remarks: Chicago Faucets No CP, angle stop fitting with supply tube and loose key. Contractor shall verify and coordinate rough-in locations. Installation shall meet the American with Disabilities Act guidelines and ANSI A117.1 Accessible and Usable Buildings and Facilities. 4. P-4 Kitchen Sink: Fixture: Kindred modelqdla2233/8-a drop-in double-bowl sink, seamless 20 gauge, type 304, 18-8 stainless steel. Mirror finished rim and satin finished bowls. Smooth, fully coated underside. 8" deep, drains punched for 3-½ drain openings. Faucet: Strainer: Trap: Supplies and Stops: Remarks: Kindred model KF10A, High arch gooseneck stainless steel, Ceramic disc cartridge, faucet requires 1 ½ diameter hole, 1 GPM pressure compensating, aerated stream flow, and flexible braided supply hose. McGuire 1151-WC cast brass chrome plated offset basket strainer with polished chrome cast brass elbow, 17 gauge 1-1/2 inch seamless brass offset tailpiece, heavy rubber basin washer and fiber friction washer. Offset basket strainer shall be in compliance with CSA or other recognized testing authority and bear both manufacturer and testing mark. McGuire 8912C cast brass chrome plated 1-1/2" x 1-1/2" P-trap with cleanout with 17 gauge tubular wall bend, cast brass slip nuts. Trap shall be in compliance with CSA and bear both manufacturer and testing mark. Chicago Faucets No CP, angle stop fitting with supply tube and loose key. Contractor shall verify and coordinate rough-in locations. Installation shall meet the American with Disabilities Act guidelines and ANSI A117.1 Accessible and Usable Buildings and Facilities. 5. P-5 Water Cooler: Fixture: Remarks: Elkay EZH20 system Cooler/Bottle Filling Station Model LZS8WSLK electric single filtered water cooler with bottle filling station. Unit shall deliver 8 GPH of 50 F drinking water at 90 F ambient and 80 F inlet water. Cooler unit shall have stainless steel basin with integral drain, galvanized structural steel cooler chassis, front and side pushbar activation, 3000-gallon capacity filter with visual monitor. Cooler cabinet shall be Sandstone or Greystone to match building standard. Contractor shall verify and coordinate rough-in locations. Installation shall meet the American with Disabilities Act guidelines and ANSI A117.1 Accessible and Usable Buildings and Facilities. 6. P-6 Mop Sink: COMMON WORK RESULTS FOR PLUMBING

9 Fixture: Faucet: Strainer: Remarks: Fiat MSB02424, 24 x24 molded stone mop basin with 10 high sides and an integral 3 chrome plated drain with a seal for connection to the waste piping. Solid brass faucet with vacuum breaker and hose bracket. The mop basin shall be white drift in color and the faucet shall be mounted 36 above the finished floor. Chicago 897-CP or acceptable alternative product by Brass & Bronze. Fiat 1453BB stainless steel grid strainer. Fiat 832AA hose and hose bracket, Fiat 889-CC mop hanger, Fiat 1239BB stainless steel bumper guards and two (2) Fiat MSG stainless steel wall guards for corner installation. Contractor shall verify and coordinate rough-in locations. 7. P-7 Water Connection: Fixture: Remarks IPS Guy Gray Model MIB1HAAB ice maker/coffee maker water outlet box. 20 gauge box and 20 gauge faceplate, white powder coat on cold rolled steel finish, ¼ urn ball valve with ½ sweat connection and hammer arrestor. Provide plumbing connections in accordance with the manufacturer s written instructions. 2.5 WATER HAMMER ARRESTORS A. Basis-of-Design Product: Subject to compliance with requirements, provide J.R. Smith 5000 Hydrotol Series or comparable product by one of the following: 1. Josam Company. 2. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. 3. Zurn Industries, LLC; Plumbing Products Group; Specification Drainage Products. B. Standard: ASSE 1010 or PDI-WH 201. C. Type: Precharged, permanently sealed, all stainless steel water hammer arrester including bellows. D. Size: ASSE 1010, Sizes AA and A through F, or PDI-WH 201, Sizes A through F. E. Shock absorbers shall be the same size as the line on which they are installed, up to 1 pipe size. Pipe lines larger than 1 shall have one inch shock absorbers installed. F. Provide at all solenoid, remote operated and quick-closing valves and at each battery of plumbing fixtures. Install on both hot and cold water branch lines in an upright position as close as possible to the valve or valves being served. G. Pipe extensions shall not be used in place of shock absorbers. COMMON WORK RESULTS FOR PLUMBING

10 2.6 MASTER MIXING VALVE A. Basis-of-Design Product: Subject to compliance with requirements, provide Leonard New Generation High-Low system series or comparable product by one of the following: 1. Lawler 2. Symmons B. Materials: Lead-free bronze body, locked temperature regulator, copper encapsulated thermostat assembly with polymer thermoplastic shuttle, stainless steel springs, Buna-N O- rings, integral check valves on hot and cold inlets, compression fittings on inlets and outlet. C. Pressure-Temperature 1. Minimum Flow: 1 GPM 2. Maximum Pressure: 125 PSIG. 3. Maximum Hot Water temperature: 200 F. 4. Approach Temperature 5 F above set point. 5. Temperature Adjustment Range: 90 F -140 F D. ASSE 1017 certified. 2.7 THERMOSTATIC POINT OF USE MIXING VALVE A. Basis-of-Design Product: Subject to compliance with requirements, provide Leonard Model LF- 170 series or comparable product by one of the following: 1. Lawler 2. Symmons B. Materials: Lead-free bronze body, locked temperature adjustment cap (vandal resistant), copper encapsulated thermostat assembly with polymer thermoplastic shuttle, stainless steel springs, Buna-N O-rings, integral check valves on hot and cold inlets, compression fittings on inlets and outlet. 1. Pressure-Temperature 2. Minimum Flow: 0.25 GPM 3. Maximum Pressure: 125 PSIG. 4. Maximum Hot Water temperature: 200 F. 5. Approach Temperature 5 F above set point. 6. Temperature Adjustment Range: 90 F -120 F C. ASSE 1070 certified. PART 3 - EXECUTION 3.1 GENERAL A. All rough-in plumbing shall be sealed off with test plugs, caps, etc until plumbing fixtures are ready to be installed. COMMON WORK RESULTS FOR PLUMBING

11 B. All plumbing equipment shall be placed on a minimum 4 high housekeeping pad, unless otherwise noted. 3.2 CLEANOUTS A. Where soil, waste, or roof drainage risers connect to a sewer or drain extending from the building above the lowest floor, the fitting at the base of each stack or downspout shall be a sanitary tee or a combination Y and 1/8 bend with cleanout plug in the end of the run of the main. B. Each vertical soil, waste, and vent pipe and each downspout and roof drainage pipe which connects to horizontal drain piping below ground shall be fitted with a test tee above the lowest floor or ground. Where accessible, test tee may be installed in the horizontal pipe at the base of the riser. C. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated: 1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated. 2. Locate at each change in direction of piping greater than 45 degrees. 3. Locate at minimum intervals of 50 feet for piping NPS 6 and smaller and 100 feet for larger piping. 4. Locate at base of each vertical soil and waste stack. D. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with finished floor. E. For cleanouts located in concealed piping, install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall. 3.3 FLOOR DRAINS A. Floor drains shall be covered during periods of construction. If drains are not covered and it is suspected that dirt, debris or trash has entered the drainage system, the interior drainage system shall be professionally cleaned to the Architect s satisfaction and at no expense to the Owner. B. Set grates of drains flush with finished floor, unless otherwise indicated. C. Install floor-drain flashing collar or flange so no leakage occurs between drain and adjoining flooring. Maintain integrity of waterproof membranes where penetrated. D. Install individual traps for floor drains connected to sanitary building drain, unless otherwise indicated. E. Install deep-seal traps on floor drains. F. Floor drains installed where occupants walk shall have a grate for safety. G. Drains receiving indirect waste shall be provided with ½ grates as required to receive discharge without splashing. COMMON WORK RESULTS FOR PLUMBING

12 3.4 PLUMBING FIXTURES A. Examination 1. Examine roughing-in of water-supply and sanitary drainage and vent piping systems to verify actual locations of piping connections before shower installation. 2. Examine walls and floors for suitable conditions where showers will be installed. 3. Proceed with installation only after unsatisfactory conditions have been corrected. B. Installation 1. Install fixtures level and plumb according to roughing-in drawings. 2. Install accessible, wall-mounted fixtures at mounting height for handicapped/elderly, according to ICC/ANSI A Assemble fixture components according to manufacturers' written instructions. 4. Install water-supply piping with stop on each supply to each faucet. a. Exception: Use ball, gate, or globe valves if supply stops are not specified with shower. b. Install stops in locations where they can be easily reached for operation. 5. Install wall flanges or escutcheons at piping wall penetrations in exposed, finished locations. Use deep-pattern escutcheons if required to conceal protruding fittings. 6. Install wall-mounted, back-outlet water-closet supports with waste-fitting assembly and waste-fitting seals; and affix to building substrate. 7. Install lever-handle flushometer valves for accessible water closets and urinals with handle mounted on open side of water closet. 8. Install actuators in locations that are easy for people with disabilities to reach. 9. Install fresh batteries in battery-powered, electronic-sensor mechanisms at substantial completion. 10. Install protective shielding pipe covers and enclosures on exposed supplies and waste piping of accessible lavatories and sinks. 11. Set showers in leveling bed of cement grout. 12. Seal joints between showers and floors and walls using sanitary-type, one-part, mildewresistant silicone sealant. Match sealant color to fixture color. C. Connections 1. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures. D. Adjusting 1. Operate and adjust faucets and controls. Replace damaged and malfunctioning faucets, fittings, and controls. 2. Adjust water pressure at faucets to produce proper flow. E. Cleaning and Protection 1. After completing installation of fixtures, inspect and repair damaged finishes. 2. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods and materials. 3. Provide protective covering for installed fixtures and fittings. 4. Do not allow use of fixtures for temporary facilities unless approved in writing by Owner. COMMON WORK RESULTS FOR PLUMBING

13 3.5 INSTALLATION OF PIPING A. Interior Drainage Systems: 1. Soil, waste, vent, and drain piping for sanitary and storm drainage, shall be of the sizes noted, and shall be run as indicated. Pipes must be run in straight lines and have a uniform grade between elevations noted. No branch drain shall have a grade less than that indicated for the main drain to which it is connected. Where elevations are not given, horizontal pipes shall have a uniform grade of 1/4 inch per foot where possible but in no case less than 1/8 inch per foot and shall be installed to the inverts shown. All piping shall be adequately supported as specified in Division 23, Section Mechanical and Electrical General Provisions. All main vertical soil and waste stacks shall be extended as vents full size to approximately 18 inches above the roof of the building. Two (2) or more vent lines shall be connected together where practicable and extended as one (1) pipe through the roof. Vent pipes in roof spaces shall be run as close as possible to the underside of the roof without forming traps in pipes. Vent pipes may be connected to other vent pipes or to main vent stacks provided the connections are at least four (4) feet above the floor on which the fixtures are located so that no vent pipe can be used as a waste. Openings in roof for vent pipes shall be flashed and made watertight. Use vent stack flashing sleeves where applicable. Handicapped plumbing fixtures shall be roughin to suit the specific mounting of the fixture. Waste lines shall be offset for lavatories and sinks to accommodate wheelchair type strainers and traps shall be insulated. 2. Changes in direction shall be made by appropriate use of forty-five (45) degree wyes, 1/2 wyes, or long sweep 1/4, 1/6, 1/8, or 1/16 bends. Sanitary tees or short quarter bends may be used on vertical stacks of drainage lines where change in direction of flow is from horizontal to vertical; except use long turn tee wyes when two (2) fixtures have common drain. Straight tees, elbows, and crosses may be used on vent lines. Make no change in direction of flow greater than ninety (90) degrees. Where different sizes of drainage pipes or pipes and fittings are to be connected, use standard increasers and reducers of proper size. Reduction of size in horizontal drainage piping in direction of flow is prohibited. 3. Drilling and tapping of drains, soil, waste, or vent piping, and use of saddle hubs and bands are prohibited. 4. Connect piping to fixtures or equipment by couplings or unions so that devices may be replaced with no disturbance to piping. B. Exterior Drainage Systems: 1. See Division 23, Section Mechanical and Electrical General Provisions for Excavation and Backfill. 2. Pipe and fittings shall be moved to the trench, carefully lowered and set to line and grade. Pipe shall be laid on the shaped sub-grade. No blocking will be permitted and the bleeding shall be such that it forms a continuous bearing with a minimum width of bearing equal to 0.6 the outside diameter of the pipe for the full length of the pipe, except for that portion at the bell hole. No pipe or fitting shall be installed until sufficient trench has been completely excavated to satisfy the Architect that no unforeseen obstructions of any kind are likely to be encountered. Pipe shall be cut by the Contractor when required without any additional compensation. Special care shall be exercised by the Contractor to prevent damage to any pipe. Before placing in the trench, each pipe or fitting shall be carefully cleaned of any foreign substance which may have collected therein and shall be kept clean at all times thereafter. For this purpose, the open ends of all pipes and fittings in the trench shall be closed to the satisfaction of the Architect before leaving the work for the night and for all holidays or other items of interruption to the work. 3. Install horizontal lines to 1/8 inch per foot minimum grade, unless otherwise indicated. COMMON WORK RESULTS FOR PLUMBING

14 C. Water Piping Systems: 1. Water piping shall be complete from service connection to all fixtures, equipment, outlets, etc. Sizes of pipes shall be shown or as specified. 2. Chromium plated piping shall be threaded and made up carefully, and not more than one (1) full turn of thread shall be exposed beyond any fitting. 3. Ends of pipes or tubing and recesses of fittings to be bronzed or soldered shall be thoroughly cleaned. Joints shall be assembled without binding. Brazing material or solder shall penetrate fully and shall fill the joint completely. 4. All brass and copper pipe and tubing shall be free from cuts, dents or other surface damage at the time of final inspection. Damaged pipe or tubing shall be removed and replaced with new pipe or tubing. 5. Horizontal runs of brass and copper pipe and tubing over fifty (50) feet in length shall be anchored to wall or floor construction. Anchors shall be located near the midpoints of the runs so as to force the expansion equally to the ends or in a direction where expansion can take place without excessive strain. Swing joints, offsets, expansion joints, etc., shall be provided where necessary to accommodate expansion of piping, which will be approximately two (2) inches in 100 feet of brass or copper hot water piping. 6. Where non-ferrous metal piping and zinc-coated metal piping are jointed, dielectric (insulating) couplings, fittings or unions shall be provided. 7. Where pipe sizes shown or specified differ from the connection sizes of meters, pumps, fixtures, outlets, etc., reducing fittings shall be installed. 8. Water supplies for wall hung lavatories shall be roughed in as high as possible and still permit connections to the faucet. Water supplies shall be insulated for handicapped fixtures and rough-in shall be on accessible side of fixture for flush valves and flush handles. D. All rough-in plumbing shall be sealed off with test plugs, caps, etc., until fixtures are ready to be installed. 3.6 CLEANOUTS A. Where soil, waste, or roof drainage risers connect to a sewer or drain extending from the building above the lowest floor, the fitting at the base of each stack or downspout shall be a sanitary tee or a combination Y and 1/8 bend with cleanout plug in the end of the run of the main. B. Each vertical soil, waste, and vent pipe and each downspout and roof drainage pipe which connects to horizontal drain piping below ground shall be fitted with a test tee above the lowest floor or ground. Where accessible, test tee may be installed in the horizontal pipe at the base of the riser. 3.7 TRAPS A. Each fixture, floor drain and piece of equipment connected to the sanitary system shall be equipped with a trap. B. Provide traps for storm water lines where required by code. C. Each trap shall be placed as close to the fixture as possible and no fixture shall be double trapped. COMMON WORK RESULTS FOR PLUMBING

15 D. All traps on bell and spigot pipe shall be extra heavy cast iron and all traps on threaded pipe shall be galvanized cast iron recessed drainage type. END OF SECTION COMMON WORK RESULTS FOR PLUMBING

16

17

18

19

20 SECTION ELECTRIC, DOMESTIC-WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Commercial, electric, storage, domestic-water heaters. 2. Domestic-water heater accessories. B. Related Sections: 1. Section "Coordination Drawings." 1.3 PERFORMANCE REQUIREMENTS A. Seismic Performance: Commercial domestic-water heaters shall withstand the effects of earthquake motions determined according to ASCE/SEI The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified." 1.4 ACTION SUBMITTALS A. Product Data: For each type and size of domestic-water heater indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. B. LEED Submittals: 1. Product Data for Prerequisite EA 2: Documentation indicating that units comply with applicable requirements in ASHRAE/IESNA 90.1, Section 7, "Service Water Heating." C. Shop Drawings: 1. Wiring Diagrams: For power, signal, and control wiring. 1.5 INFORMATIONAL SUBMITTALS A. Seismic Qualification Certificates: For commercial domestic-water heaters, accessories, and components, from manufacturer. 1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation. ELECTRIC, DOMESTIC-WATER HEATERS

21 2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions. 3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements. B. Product Certificates: For each type of commercial and tankless, electric, domestic-water heater, from manufacturer. C. Source quality-control reports. D. Field quality-control reports. E. Warranty: Sample of special warranty. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For electric, domestic-water heaters to include in emergency, operation, and maintenance manuals. 1.7 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA C. ASME Compliance: Where ASME-code construction is indicated, fabricate and label commercial, domestic-water heater storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. D. NSF Compliance: Fabricate and label equipment components that will be in contact with potable water to comply with NSF 61, "Drinking Water System Components - Health Effects." 1.8 COORDINATION A. Coordinate sizes and locations of concrete bases with actual equipment provided. 1.9 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of electric, domestic-water heaters that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Structural failures including storage tank and supports. b. Faulty operation of controls. c. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. Warranty Periods: From date of Substantial Completion. a. Commercial, Electric, Storage, Domestic-Water Heaters: ELECTRIC, DOMESTIC-WATER HEATERS

22 1) Storage Tank: Three years. 2) Controls and Other Components: Three years. b. Electric, Tankless, Domestic-Water Heaters: Five year(s). c. Compression Tanks: Five years. PART 2 - PRODUCTS 2.1 COMMERCIAL, ELECTRIC, DOMESTIC-WATER HEATERS A. Commercial, Light-Duty, Storage, Electric, Domestic-Water Heaters: 1. Basis-of-Design Product: Subject to compliance with requirements, provide A.O. Smith Custom Xi or comparable product by one of the following: a. Bradford White Corporation. b. Lochinvar Corporation. c. PVI. d. Smith, A. O. Water Products Co.; a division of A. O. Smith Corporation. e. State Industries. 2. Standard: UL Storage-Tank Construction: Steel, vertical arrangement. a. Tappings: ASME B pipe thread. b. Pressure Rating: 150 psig. c. Interior Finish: Glass-lined with an alkaline borosilicate composition fused-to-steel by firing at a temperature of 1600 F. 4. Factory-Installed Storage-Tank Appurtenances: a. Anode Rod: Replaceable magnesium. b. Dip Tube: Required unless cold-water inlet is near bottom of tank. c. Drain Valve: ASSE d. Insulation: Comply with thermal efficiency and/or standby loss requirements of the U. S. Department of Energy and current edition of ASHRAE/IESNA e. Jacket: Steel with enameled finish. f. Heat-Trap Fittings: Inlet type in cold-water inlet and outlet type in hot-water outlet. g. Heating Elements: Two; electric, screw-in immersion type; wired for simultaneous operation unless otherwise indicated. h. Temperature Control: Adjustable thermostat. i. Safety Control: High-temperature-limit cutoff device or system. j. Relief Valve: ASME rated and stamped for combination temperature-and-pressure relief valves. Include relieving capacity at least as great as heat input, and include pressure setting less than domestic-water heater working-pressure rating. Select relief valve with sensing element that extends into storage tank. 2.2 DOMESTIC-WATER HEATER ACCESSORIES A. Domestic-Water Compression Tanks: 1. Basis-of-Design Product: Subject to compliance with requirements, provide Bell & Gossett PT series or comparable product by one of the following: ELECTRIC, DOMESTIC-WATER HEATERS

23 a. AMTROL Inc. b. Taco, Inc. 2. Description: Steel pressure-rated tank constructed with welded joints and factory-installed butylrubber diaphragm, FDA approved for domestic potable water. Include air precharge to minimum system-operating pressure at tank. 3. Construction: a. Tappings: Factory-fabricated steel, welded to tank before testing and labeling. Include ASME B pipe thread. b. Interior Finish: Comply with NSF 61 barrier materials for potable-water tank linings, including extending finish into and through tank fittings and outlets. c. Air-Charging Valve: NPTF system connection, and a.305"-32 charging valve connection (standard tire valve) to facilitate on-site charging of the tank to meet system requirements. B. Drain Pans: Corrosion-resistant metal with raised edge. Comply with ANSI/CSA LC 3. Include dimensions not less than base of domestic-water heater, and include drain outlet not less than NPS 3/4 with ASME B pipe threads or with ASME B garden-hose threads. C. Combination Temperature-and-Pressure Relief Valves: ASME rated and stamped. Include relieving capacity at least as great as heat input, and include pressure setting less than domestic-water heater working-pressure rating. Select relief valves with sensing element that extends into storage tank. D. Pressure Relief Valves: ASME rated and stamped. Include pressure setting less than domestic-water heater working-pressure rating. E. Vacuum Relief Valves: ANSI Z21.22/CSA 4.4. F. Shock Absorbers: ASSE 1010 or PDI-WH 201, Size A water hammer arrester. G. Domestic-Water Heater Mounting Brackets: Prefabricated engineered suspended seismic platform for wall mounting or suspension, capable of supporting domestic-water heater and water. 2.3 SOURCE QUALITY CONTROL A. Electric, domestic-water heaters will be considered defective if they do not pass tests and inspections. Comply with requirements in Section "Quality Requirements" for retesting and reinspecting requirements and Section "Execution" for requirements for correcting the Work. B. Prepare test and inspection reports. PART 3 - EXECUTION 3.1 DOMESTIC-WATER HEATER INSTALLATION A. Commercial, Electric, Domestic-Water Heater Mounting: Install residential, electric, domestic-water heaters on domestic-water heater mounting bracket. 1. Maintain manufacturer's recommended clearances. 2. Arrange units so controls and devices that require servicing are accessible. 3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 4. Install anchor bolts to elevations required for proper attachment to supported equipment. ELECTRIC, DOMESTIC-WATER HEATERS

24 5. Anchor domestic-water heaters to substrate. B. Install electric, domestic-water heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible. 1. Install shutoff valves on domestic-water-supply piping to domestic-water heaters and on domestichot-water outlet piping. C. Install commercial, electric, domestic-water heaters with seismic-restraint devices. D. Install combination temperature-and-pressure relief valves in top portion of storage tanks. Use relief valves with sensing elements that extend into tanks. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic-water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain. E. Install combination temperature-and-pressure relief valves in water piping for electric, domestic-water heaters without storage. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic-water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain. F. Install water-heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose-end drain valves at low points in water piping for electric, domestic-water heaters that do not have tank drains. G. Install thermometers on outlet piping of electric, domestic-water heaters. H. Install thermometers on inlet and outlet piping of residential, solar, electric, domestic-water heaters. I. Fill electric, domestic-water heaters with water. J. Charge domestic-water compression tanks with air. 3.2 CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Where installing piping adjacent to electric, domestic-water heaters, allow space for service and maintenance of water heaters. Arrange piping for easy removal of domestic-water heaters. 3.3 IDENTIFICATION A. Identify system components. 3.4 FIELD QUALITY CONTROL A. Perform tests and inspections. 1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. 2. Operational Test: After electrical circuitry has been energized, start units to confirm proper operation. ELECTRIC, DOMESTIC-WATER HEATERS

25 3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. B. Electric, domestic-water heaters will be considered defective if they do not pass tests and inspections. Comply with requirements in Section "Quality Requirements" for retesting and reinspecting requirements and Section "Execution" for requirements for correcting the Work. C. Prepare test and inspection reports. 3.5 DEMONSTRATION A. Train Owner's maintenance personnel to adjust, operate, and maintain commercial electric storage type and tankless type domestic-water heaters. END OF SECTION ELECTRIC, DOMESTIC-WATER HEATERS

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Shop Drawings: Include diagrams for power, signal, and control wiring.

B. Shop Drawings: Include diagrams for power, signal, and control wiring. SECTION224213.13 -COMMERCIAL WATERCLOSETS PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Water closets. 2. Flushometer valves. 3. Toilet seats. 1.2 ACTION SUBMITTALS Product Data: For each type of product.

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type. PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

More information

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 22 40 00 Plumbing Fixtures 1. General A. Definitions 1. Section includes a. Water closets and urinals b. Lavatories, sinks, and service sinks c. Electric water coolers, drinking fountains, d. Showers

More information

University of Rochester October 17, 2008 Brooks Landing Business Center

University of Rochester October 17, 2008 Brooks Landing Business Center SECTION 224200 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, equipment and services to perform operations required for the complete installation and related

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point. PART 1 - GENERAL 1.01 Toilet rooms and utility rooms to have floor drains at lowest point. 1.02 Utilize Exposed Flushometers. 1.03 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

More information

HWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

HWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS. ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE

More information

LAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

LAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS. ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE

More information

B. Shop Drawings: Include diagrams for power, signal, and control wiring.

B. Shop Drawings: Include diagrams for power, signal, and control wiring. SECTION 224213.13 - COMMERCIAL WATER CLOSETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Section Joint Sealants: Seal fixtures to walls and floors.

A. Section Joint Sealants: Seal fixtures to walls and floors. SECTION 224000 - PLUMBING FIXTURES PART 1 GENERAL 1.1 SECTION INCLUDES A. Water closets. B. Urinals. C. Lavatories. D. Sinks. E. Service sinks. F. Showers. G. Wash fountains. H. Eye wash fountains. 1.2

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties: SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following sanitary drainage piping specialties: 1. Backwater valves. 2. Cleanouts. 3. Floor

More information

1. Division 22 Section "Emergency Plumbing Fixtures." 2. Division 22 Section "Drinking Fountains and Water Coolers."

1. Division 22 Section Emergency Plumbing Fixtures. 2. Division 22 Section Drinking Fountains and Water Coolers. Page 224000-1 SECTION 224000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION DOMESTIC WATER PIPING SPECIALTIES

SECTION DOMESTIC WATER PIPING SPECIALTIES SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

2). Crane Co. 4). Kohler Co. 5). Universal-Rundle Corp. Revised September 29, 2017 Commercial Plumbing Fixtures

2). Crane Co. 4). Kohler Co. 5). Universal-Rundle Corp. Revised September 29, 2017 Commercial Plumbing Fixtures PART 1: GENERAL A. This Section provides design standards for plumbing fixtures and trim. Certification of compliance with specified ANSI, UL, and ASHRAE Standards will be required, as appropriate, for

More information

SECTION PLUMBING FIXTURES

SECTION PLUMBING FIXTURES CSUEB Pioneer Heights Phase r 15410 Page 1 SECTION 15410 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION PLUMBING FIXTURES AND TRIM. A. Types of plumbing fixtures required for the project include the following:

SECTION PLUMBING FIXTURES AND TRIM. A. Types of plumbing fixtures required for the project include the following: SECTION 15440 PART I - GENERAL 1.01 WORK INCLUDED A. Types of plumbing fixtures required for the project include the following: 1. Water Closets 2. Urinals 3. Lavatories 4. Mop Sink 5. Sinks 6. Electric

More information

A. General: comply with appropriate standards. 1. International Association of Plumbing and Mechanical Officials: IAPMO. 2. California State AB 1953.

A. General: comply with appropriate standards. 1. International Association of Plumbing and Mechanical Officials: IAPMO. 2. California State AB 1953. SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Water closets. 2. Urinals. 3. Lavatories. 4. Sinks. 5. Service sinks. 6. Electric water coolers. 7. Wash fountains.

More information

A. This Section includes the following emergency plumbing fixtures:

A. This Section includes the following emergency plumbing fixtures: Page 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. All fixtures shall meet the requirements of ANSI A117.1, ANSI Z124.2 and the State of Texas Accessibility Standards (TAS).

A. All fixtures shall meet the requirements of ANSI A117.1, ANSI Z124.2 and the State of Texas Accessibility Standards (TAS). PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION SECTION 224100 - RESIDENTIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

DOMESTIC WATER PACKAGED BOOSTER PUMPS

DOMESTIC WATER PACKAGED BOOSTER PUMPS DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot

More information

SECTION PLUMBING

SECTION PLUMBING SECTION 22 10 00 PLUMBING PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the sanitary sewer system (including soil and vent piping),

More information

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point. PART 1 - GENERAL 1.01 Toilet rooms and utility rooms to have floor drains at lowest point. 1.02 Utilize Exposed Flushometers. 1.03 Utilize wall hung toilet room fixtures. Urinals for handicapped may be

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Plumbing Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Plumbing Standards Date Description of Change Pages / Sections Modified ID 8/5/17 Entire document - mgl PART 1 - INTRODUCTION 1.1 This section applies to Plumbing for campus institutional facilities. A. Purpose: Yale University

More information

GENERAL PLUMBING REQUIREMENTS

GENERAL PLUMBING REQUIREMENTS 22 00 00 GENERAL PLUMBING REQUIRMENTS i. 00 00 07 Design Professional Design Process Requirements ii. 00 00 08 Design Professional Documentation Requirements and Deliverables iii. 01 81 00 Facility Performance

More information

SECTION PLUMBING SPECIALTIES

SECTION PLUMBING SPECIALTIES DIVISION 22 PART 1 GENERAL 1.01 SCOPE SECTION 22 0430 PLUMBING SPECIALTIES A. Domestic water, sewer, roof drainage and condensate drains, including piping, equipment and all necessary accessories as designated

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION FUEL-FIRED DOMESTIC WATER HEATERS

SECTION FUEL-FIRED DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Codes and Standards: A. Plumbing Code Compliance: Comply with applicable portions of National Standard Plumbing Code pertaining to selection and installation of Plumbing materials

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

DESIGN AND CONSTRUCTION STANDARDS July 2011

DESIGN AND CONSTRUCTION STANDARDS July 2011 PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design for new construction and renovations.

More information

GENERAL PLUMBING REQUIREMENTS

GENERAL PLUMBING REQUIREMENTS 22 00 00 GENERAL PLUMBING REQUIRMENTS 1. GENERAL A. Related sections: i. 00 00 07 Design Professional Design Process Requirements ii. 00 00 08 Design Professional Documentation Requirements and Deliverables

More information

SECTION BASIC MATERIALS AND METHODS

SECTION BASIC MATERIALS AND METHODS SECTION 15050 BASIC MATERIALS AND METHODS PART 1 1.1 SECTION INCLUDES A. General Conditions B. Supplementary Conditions C. Division 1 D. Mechanical basic requirements E. Electric Motors F. Pipe, Valve,

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

PLUMBING FIXTURES CHAPTER 27

PLUMBING FIXTURES CHAPTER 27 CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,

More information

PLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS

PLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS The Design Guidelines, which follow, are intended to supplement the Educational Specifications and State Requirements for Educational Facilities (SREF). Note: All fittings shall be installed by no less

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

TABLE OF CONTENTS DIVISION 22 - MECHANICAL

TABLE OF CONTENTS DIVISION 22 - MECHANICAL TABLE OF CONTENTS DIVISION 22 - MECHANICAL 22 00 00 PLUMBING WORK...1 22 00 01 GENERAL...1 22 00 02 REFERENCES, REGULATORY REQUIREMENTS...1 22 00 03 RELATED SECTIONS of the SPECIFICATIONS...1 22 00 04

More information

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18 NAVFAC PTS-D20 (February 2018) ------------------------------ Preparing Activity: NAVFAC SUPERSEDING PTS-D20 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D20 PLUMBING 02/18 NOTE: This section

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Protected with TechCoat finish. For Ceramic Tile Showers Cast iron Threaded for test nipple Extra heavy (.050) strainer DRAIN CONNECTION

Protected with TechCoat finish. For Ceramic Tile Showers Cast iron Threaded for test nipple Extra heavy (.050) strainer DRAIN CONNECTION QUICK CONNECT SHOWER DRAIN Protected with TechCoat finish Quick Clamping Gasket And Collar For Ceramic Tile Showers Cast Iron Clamping collar securely attaches drain to drain line Speeds installation Extra

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

PARTS STOCKED REPLACEMENT FAUCET BIBB SCREWS... SCREW ASSORTMENT MISC. 3 /8" BIBB LOC SCREW 1 /2" BIBB SCREW 1 /2" BIBB LOC SCREW 3 /8" BIBB SCREW

PARTS STOCKED REPLACEMENT FAUCET BIBB SCREWS... SCREW ASSORTMENT MISC. 3 /8 BIBB LOC SCREW 1 /2 BIBB SCREW 1 /2 BIBB LOC SCREW 3 /8 BIBB SCREW January 1, 2001 STOCKED REPLACEMENT FAUCET BIBB SCREWS... Parts-5L 3 /8" BIBB SCREW 6-32 GAUGE CHROME 35138- No. 1 3 /8" BIBB SCREW 10-24 GAUGE CHROME 35153- No. 16 3 /8" BIBB SCREW 8-32 GAUGE CHROME 35141-

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION PLUMBING - EQUIPMENT

2016 CDM Smith All Rights Reserved July 2016 SECTION PLUMBING - EQUIPMENT PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 22 30 00 PLUMBING - EQUIPMENT A. Furnish all labor and materials required and install the following Plumbing Equipment complete as specified herein and as shown

More information

WATERSTONE ASSISTED LIVING AND MEMORY CARE

WATERSTONE ASSISTED LIVING AND MEMORY CARE DOMESTIC WATER PIPING SPECIALTIES BATON ROUGE, LOUISIANA SECTION 22 11 19 SECTION 22 11 19 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS GENERAL: This document provides performance requirements and guideline information for Heat Exchanger equipment for Colorado College only, and is not

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

REFRIGERANT PIPING SYSTEM

REFRIGERANT PIPING SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The requirements of this section apply to the refrigerant piping system connecting refrigeration and HVAC equipment specified in other sections of these specifications.

More information

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING SECTION 23 23 00 (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. 3. Joining Materials. 4. Specialties. B. Related Sections: 1. Section 07 92 00 (07920)

More information

SUBCOURSE EDITION EN US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV)

SUBCOURSE EDITION EN US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV) SUBCOURSE EDITION EN5113 5 US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV) US ARMY PLUMBER MOS 51K SKILL LEVELS 1 AND 2 COURSE PLUMBING FIXTURES (PLUMBING IV) SUBCOURSE NO. EN5113 US Army Engineer

More information

DIVISION 10 SPECIALTIES

DIVISION 10 SPECIALTIES DIVISION 10 SPECIALTIES 11/11 SECTION 10 21 13.16 PLASTIC LAMINATE TOILET COMPARTMENTS PART 1 - GENERAL 1.01 SECTION INCLUDES Plastic laminate toilet compartments, urinal screens, head rail braced. 1.02

More information

SECTION DOMESTIC WATER AND DRAINAGE PIPING SPECIALTIES

SECTION DOMESTIC WATER AND DRAINAGE PIPING SPECIALTIES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

BRADLEY HALO EMERGENCY PLUMBING FIXTURES

BRADLEY HALO EMERGENCY PLUMBING FIXTURES BRADLEY HALO EMERGENCY PLUMBING FIXTURES Bradley Halo Emergency Plumbing Fixtures are a new generation in safety equipment, featuring separate supply and waste piping to eye/face wash, ergonomic hand activation

More information

Willoughby Industries - Security Products

Willoughby Industries - Security Products TOILET WASTE LOCATION (ECW)- WALL OUTLET (ECF)- FLOOR OUTLET TOILET ORIENTATION (L)- ANGLED LEFT (L)- OFFSET LEFT (R)- ANGLED RIGHT (R)- OFFSET RIGHT (C)- CENTER FIXTURE MOUNTING (OF)- OFF FLOOR (ON)-

More information

This Product MasterSpec Section is licensed by AVITRU, LLC to Haws Corporation ("Licensee").

This Product MasterSpec Section is licensed by AVITRU, LLC to Haws Corporation (Licensee). Copyright 2017 by The American Institute of Architects (AIA) Exclusively published and distributed by AVITRU, LLC for the AIA This Product MasterSpec Section is licensed by AVITRU, LLC to Haws Corporation

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 10 00 00 - SPECIALTIES 10 28 12 - TOILET PARTITIONS: Owner Preferences: Solid core phenolic, polymer based solid surfacing, and solid plastic toilet compartment and screen systems. No Stainless

More information

SECTION DOMESTIC WATER PIPING SYSTEMS. 0. Pipe and pipe fittings are specified in the following sections:

SECTION DOMESTIC WATER PIPING SYSTEMS. 0. Pipe and pipe fittings are specified in the following sections: SECTION 15411 January 7, 2004 DOMESTIC WATER PIPING SYSTEMS. RELATED SECTIONS 0. Pipe and pipe fittings are specified in the following sections:. Section 15061, STEEL PIPE AND FITTINGS.. Section 15062,

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008 SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Air separators B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS A. Section - Plumbing Piping Specialties B. Section

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18 NAVFAC PTS-D20 (February 2018) ------------------------------ Preparing Activity: NAVFAC SUPERSEDING PTS-D20 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D20 PLUMBING 02/18 NOTE: This section

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Ratio Architects, Inc. Section Refrigerant Piping

Ratio Architects, Inc. Section Refrigerant Piping SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant pipes and fittings. 2. Refrigerant piping valves and specialties. 3. Refrigerants. 1.2 ACTION SUBMITTALS

More information