technical data air conditioning systems DICN Daikin Integrated Chiller Network Hydronic Systems

Size: px
Start display at page:

Download "technical data air conditioning systems DICN Daikin Integrated Chiller Network Hydronic Systems"

Transcription

1 technical data DICN Daikin Integrated Chiller Network air conditioning systems Hydronic Systems

2 Hydronic Systems ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Specifications are subject to change without prior notice Zandvoordestraat 300 B Ostend Belgium Internet: EEDE /2002 Prepared in Belgium by Goekint Graphics

3 TABLE OF CONTENTS DICN 1 Features DICN setup example... 4 Single ring system with 1 pump... 4 Single ring system with separate pumps... 5 Double ring system with several pumps... 6 Temperature control with DICN Option name... 8 Hydronic Systems 1

4 1 Features With the DICN system, it is possible to control up to 4 chillers. Different chillers can be mixed through each other, as long as they stay within 1 of the 5 groups as mentioned below: 1. Aircooled chillers: EUWA*40-60KBXY (R-134a) 2. Aircooled chillers :EUWA*80-120KBXY (R-134a) 3. Aircooled chillers :EUWA*40-200MZY (R-407C) 4. Watercooled chillers: EUW*40-200MXY (R-134a) R-407C models R-134a models - EUWA*40,50,60,80,100,120,160,180,200MZY1 - EUWA*40,50,60,80,100,120KBXY1 - EUW*40,60,80,100,120,160,180,200MXY The D.I.C.N. option allows simultaneous operation of up to 4 chillers as if they were a single unit, in order to deliver the required cooling capacity. This results in precise and efficient capacity control. It is also possible to define units as manual or automatic standby units which is useful for back up purposes guaranteeing reliable operation of the chiller plant. With this option, up to a 2 Megawatt chiller plant can be operated as if they were a single unit. 1 Every chiller can either have an individual circulation pump or 1 pump can discharge water in a distributor that leads water to several chillers. (In both cases, all units must be foreseen by separate flowswitches in their water outlet pipe!) The use of D.I.C.N. results in following advantages: 1. Choise between common leaving or entering water control (thermostat function). For units with common leaving water control, an insertion hole must be foreseen for the additional water temperature sensor. Sensor and sensor holder are optional parts. 2. An intelligent temperature control: the system will react fast if the temperature is far from the setpoint and accurate control is kept if it is close to the setpoint. 3. Saving energy and increasing the lifetime of the pumps by means of flexible pump control, available as a voltage free contact on every unit. It is possible to choose between: - Pumpcontact closes if unit is switched ON. - Pumpcontact closes if compressor of the unit starts. In the lattter choice, the pump stops to operate when the chiller is in thermostat off mode. e.g. when every chiller is foreseen with its own pump, the customer might prefer to stop the pump, after stopping the chiller on thermostat. In the case that all chillers are configured to stop their pump when the chiller is in thermostat off mode, the system takes care that the pump of the latest chiller that goes into thermostat off mode, keeps running so that always the correct temperature is sensed at the mixed water outlet (cfr setup example). 2 Hydronic Systems

5 1 Features 4. A difference in running hours between the different units can be programmed. For every unit, the target difference in running hours between this unit and the unit with the smallest amount of running hours can be set. e.g. if following setting is made: Unit1=0 Unit 2 = 1000 Unit 3 = 2000 Unit 4 = 2000 then unit 3 and 4 will be operated most. They will get priority in operation as to reach 2000 running hours more than unit 1. Unit 1 will be the unit with the lowest running hours. Nota: This means that equal or sequential start up remains valid within 1 chiller. 5. For units with more than 2 circuits, the individual lead/lag setting of a unit - to determine the priority of the circuits - remain valid. Every unit should be configured as either a NORMAL, STANDBY or DISCONNECT unit. This setting will be mentioned on the display of each chiller. NORMAL: Normal operation STANDBY: The unit only operates if another unit is in alarm, or in case of capacity shortage of the other units in the system. Capacity shortage occurs when all units are running on full capacity, but the setpoint is not reached after a certain period. Also, more than 1 unit (up to 4) can be defined as a STANDBY unit. In that case, only the unit which is most near to it s target running hours will be considered as a STANDBY unit. This means, if a customer wants to have 1 particular unit always to be in off mode (except for alarm or capacity shortage of the other chillers), then he only has to define this 1 unit as STANDBY. But if a customer wants to have more than 1, or even all chillers to be a standby unit alternately (each on its turn), then more than 1, or all chillers should be defined as STANDBY. DISCONNECT: Besides this AUTOMATIC standby function, it is also possible to select a MANUAL standby function of a unit. Units which are defined as DISCONNECTED, can be put ON/OFF or set to MANUAL MODE independent from the other units. This can be very useful e.g. in case of servicing. When changing to NORMAL or STANDBY, the unit becomes part of the system again Night setback function: It is possible to reduce sound levels e.g. during night time, by limitation of the capacity of the system. For energy saving, it is also possible to work with dual setpoints (e.g. a lower or higher setpoint during night time). 7. Peak load limitation can be programmed to avoid too high energy consumption. 8. The chillers, grouped in a D.I.C.N., can also be integrated in a Building Management system (B.M.S.), using the B.M.S. options. 9. It is possible to put the controller remotely up to 300m distance from the unit. 10. Voltage free contacts are available for: - indication of general operation/compressor operation - Alarm indication Hydronic Systems 3

6 2 DICN setup example 2-1 Single ring system with 1 pump Example 1: Single ring system with 1 pump Purpose: Deliver constant flow at a constant temperature to a load. Keep 1 unit (slave 3) as a standby unit. Buffer tank Filter Load Fieldwiring: Terminals for fieldwiring Setup: The system is controlled on leaving water temperature. (additional sensor EKCLWS connected to the master in mixed water outlet required). The pump remains running as long as 1 of the units is ON. The pump in this example still runs for 120 after all units have been put to OFF. Slave 3 is configured to operate when its remote ON/OFF switch S6S (S3) is pushed by the operator. Slave 1, slave 2 and the master are put ON/OFF by remote ON/OFF switch S6S (M) connected to the master. The setpoint can be switched from OUTLSETP1 to OUTLSETP2 by the dual setpoint contact (S10S) connected to the master. NOTE 1: For models EUWA* KX* and EUW*40-200KX* the opening delay of the pump contact can be programmed. In this case it is not necessary to use a delay contactor. K1F may also be a 24V DC or a 230V AC contactor. NOTE 2: The additional sensor (R8T) must be directly connected to the MASTER PCB. Parameters setting units: Mode: Disconnect Normal Normal Normal Pump on if: Unit on Unit on Unit on Unit on Be sure to put the remote control parameter to Y on slave 3 and also on 1 of the units with mode NORMAL (slave 1, slave 2 or the master). Nota Slave 3 can be configured to start up AUTOMATICALLY if: One of the other units are in alarm or All other units are running on full capacity and setpoint is not reached. Therefore put its mode to STAND BY (S6S (S3) has no function in this case). Legend: (1) : Field wiring (2) : Earth wiring (3) Y:Terminal on unit F1 F20 Fuses K1F K4F Contactor K1P K4P Pump contact L1,L2,L3,N Main supply terminals M1P M5P Pump motor R8T Sensor for mixed outlet water temp. for DICN R9T Sensor for secondary circuit S1S Manual switch for pump of master unit S6S(M,S3) Remote start/stop switch S8L(M,S1,S2,S3) Flow switch S10S Dual setpoint selection switch Y1S 3 way valve 4PW A 4 Hydronic Systems

7 2 DICN setup example 2-2 Single ring system with separate pumps Example 2: Single ring system with separate pumps Purpose: Deliver constant flow at a constant temperature to a load. Keep 1 unit (slave 3) as a standby unit. Buffer tank Load Filter Filter Filter Filter Fieldwiring and terminals for fieldwiring: Setup: The system is controlled on leaving water temperature. (additional sensor EKCLWS connected to the master in mixed water outlet required). Pump 1, pump 2 and pump 3 are running as long as the master, slave 1 or slave 2 is ON. Pump 4 only starts running if slave 3 is put to ON. The pumps in this example still run for 120 after putting the chillers to OFF. Slave 3 is configured to operate when its remote ON/OFF switch S6S (S3) is pushed by the operator. Slave 1, slave 2 and the master are put ON/OFF by remote ON/OFF switch S6S (M) connected to the master. The setpoint can be switched from SETP1 to INLSETP2 by the dual setpoint contact S10S (M) connected to the master. NOTE 1: For models EUWA* KX* and EUW*40-200KX* the opening delay of the pump contact can be programmed. In this case it is not necessary to use a delay contactor. K*F may also be a 24V DC or a 230V AC contactor. NOTE 2: The additional sensor (R8T) must be directly connected to the MASTER PCB. Parameter setting units:: Mode: Disconnect Normal Normal Normal Pump on if: Unit on Unit on Unit on Unit on Be sure to put the remote control parameter to Y on slave 3 and also on 1 of the units with mode NORMAL (slave 1, slave 2 or the master). Nota Slave 3 can be configured to start up AUTOMATICALLY if: One of the other units are in alarm or All other units are running on full capacity and setpoint is not reached. Therefore put its mode to STAND BY (S6S (S3) has no function in this case). Legend: (1) : Field wiring (2) : Earth wiring (3) Y:Terminal on unit F1-F20 Fuses K1F-K4F Contactor K1P-K4P Pump contact L1,L2,L3,N Main supply terminals M1P-M4P Pump motor R8T Sensor for mixed outlet water temp. for DICN S6S(M,S3) Remote start/stop switch S8L(M,S1,S2,S3) Flow switch S10S Dual setpoint selection switch 4PW A Hydronic Systems 5

8 2 DICN setup example 2-3 Double ring system with several pumps Example 3: Double ring system with several pumps Purpose: Keep a buffer on a constant temperature. Feed from this buffer a load. Keep 1 unit (slave 3) as a standby unit. Buffer tank Load Filter Filter Filter Filter Fieldwiring and terminals for fieldwiring: Setup: The system is controlled on leaving water temperature. The pumps of the slaves only run when their compressor is running (energy saving). After stopping the compressor, the pump in this example still runs for 120. The pump of the master must run continuously as to sense the correct temperature. Slave 3 is configured to operate when its remote ON/OFF switch S6S (S3) is pushed by the operator. Slave 1, slave 2 and the master are put ON/OFF by remote ON/OFF switch S6S (M) connected to the master. The setpoint can be switched from INLSETP1 to INLSETP2 by the dual setpoint contact S10S (M) connected to the master. NOTE 1: For models EUWA* KX* and EUW*40-200KX* the opening delay of the pump contact can be programmed. In this case it is not necessary to use a delay contactor. K*F may also be a 24V DC or a 230V AC contactor. Parameter setting units:: Mode: Disconnect Normal Normal Normal Pump on if: Compr ON Compr ON Compr ON Compr ON Be sure to put the remote control parameter to Y on slave 3 and also on 1 of the units with mode NORMAL (slave 1, slave 2 or the master). Nota Slave 3 can be configured to start up AUTOMATICALLY if: One of the other units are in alarm or All other units are running on full capacity and setpoint is not reached. Therefore put its mode to STAND BY (S6S (S3) has no function in this case). Legend: (1) : Field wiring (2) : Earth wiring (3) Y:Terminal on unit F1-F20 Fuses K1F-K4F Contactor K1P-K4P Pump contact L1,L2,L3,N Main supply terminals M1P-M5P Pump motor R9T Sensor secondary circuit S1S Manual pump switch master unit S6S(M,S3) Remote start/stop switch S8L(M,S1,S2,S3) Flow switch S10S Dual setpoint selection switch Y1S 3 way valve 4PW A 6 Hydronic Systems

9 2 DICN setup example 2-4 Temperature control with DICN Quick and smooth startup Stable control High credibility When de temperature is far from the setpoint (at the moment of starting up the system), the network will start up and/or load up several chillers in a quick way as to pull down the system temperature as fast as possible. (ZONE 1) Starting up the chiller is done with a small time difference of 10 as to avoid excessive starting currents. Once the temperature is within the limits of the setpoint +/- the setpoint difference, stable control will be guaranteed by changing only 1 individual chiller capacity step at a time. (ZONE 2) Chillers with the lowest amount of running hours (minus their defined offset hours) will get priority to start up or load up, units with the highest amount of running hours (minus their defined offset) will get priority to loaddown and the system will run as few chillers as possible to maintain the desired temperature. If a unit is defined as STANDBY, then this unit will only start to operate when another unit is in alarm, (ZONE 3) or when the setpoint cannot be reached with all the other units of the DICN network in operation. Zone 1 Zone 2 Zone 3 Temperature ( C) stepdifference Setpoint stepdifference Master: status = normal Time (s) Cap. step Max. capacity Time (s) Slave 1: status = normal Cap. step Max. capacity Time (s) Cap. step Max. capacity Slave 2: status = standby Alarm of slave 1 Standby unit slave 2 takes over 3TW Time (s) Hydronic Systems 7

10 3 Option name For leaving water control: option kit EKCLWS 3 8 Hydronic Systems

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X EPCE00-10B Powerful air cooled Hydronic systems EUWA*40-200K(A)X Development Environment Technology 2 Daikin s pre-eminent position in air conditioning and chiller production has been built on over 70

More information

EPLE Water-cooled chillers Remote condenser chillers. EUW40-200MAXY EUWL40-200MXY Applied systems

EPLE Water-cooled chillers Remote condenser chillers. EUW40-200MAXY EUWL40-200MXY Applied systems EPLE04-24 Water-cooled chillers Remote condenser chillers EUW40-200MAXY EUWL40-200MXY Applied systems Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants

More information

EEDEN technical data EKRTR. Altherma. Altherma

EEDEN technical data EKRTR. Altherma. Altherma EEDEN08-720 technical data EKRTR Altherma Altherma Altherma Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental

More information

Water-cooled chillers Remote condenser chillers NEW

Water-cooled chillers Remote condenser chillers NEW Water-cooled chillers Remote condenser chillers NEW EWWD120-540MBYN EWLD120-540MBYN Applied systems Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants

More information

EWWD MBYN EWLD MBYN Applied systems

EWWD MBYN EWLD MBYN Applied systems Water-cooled chillers Remote condenser chillers EWWD120-540MBYN EWLD120-540MBYN Applied systems Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has

More information

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air technical data FT(Y)S-B Wall Mounted Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the

More information

technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air technical data FTXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect

More information

Parts introduction FRONT BACK

Parts introduction FRONT BACK Lando Industrial Water Chillers installation instructions Thank you for using the machine from Shenzhen Lando Technology Industrial Co.,Ltd.. Please read the installation instructions carefully before

More information

Capacity controller for water chiller AK-CH 650

Capacity controller for water chiller AK-CH 650 Capacity controller for water chiller AK-CH 650 Menu operation via AKM Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups

More information

DAIKIN Air Handling Unit Modular

DAIKIN Air Handling Unit Modular DAIKIN Air Handling Unit Modular Compact ventilation unit with heat recovery Energy efficiency and air quality Daikin air handling units, with their plug-and-play design and inherent flexibility, can be

More information

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air technical data RZQ-B ///Double Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help

More information

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air technical data FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDXS-CVMB TABLE OF CONTENTS FDXS-CVMB 1 Features.............................................................

More information

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air technical data FDKS-CVMB Concealed ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDKS-CVMB TABLE OF CONTENTS FDKS-CVMB 1 Features.............................................................

More information

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air EEDEN08-00 technical data FTXS-G2VB Indoor units air conditioning systems Split - Sky Air EEDEN08-00 technical data FTXS-G2VB Indoor units air conditioning systems Split - Sky Air Indoor Units R-40A FTXS-G2VB

More information

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW EEDE06-9 technical data Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW50-300 Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW50-300 The present publication is drawn up by way of information only and

More information

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air technical data FVXS-FV1B R-410A air conditioning systems Split Sky Air Indoor Units R-410A FVXS-FV1B TABLE OF CONTENTS FVXS-FV1B 1 Features.............................................................

More information

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air technical data FHYKP-B Ceiling Mounted Corner Cassette air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human

More information

WATER-COOLED CHILLERS and condenserless chillers

WATER-COOLED CHILLERS and condenserless chillers WATER-COOLED CHILLERS and condenserless chillers APPLIED SYSTEMS www.daikin.eu Cooling Only Heating Only EWWD340-C18EJYNN EWWD360-C12EJYNN/A EWLD320-C17EJYNN - ABOUT DAIKIN Daikin has a worldwide reputation

More information

water-cooled CHILLERS

water-cooled CHILLERS water-cooled CHILLERS APPLIED SYSTEMS www.daikin.eu cooling only heating only ABOUT DAIKIN Daikin has a worldwide reputation based on over 80 years experience in the successful manufacture of high quality

More information

FWV 04 FWL 05 FWM 06 FWB 07 FWD 08. Control 09. Accessories 10. Daikin Europe N.V.

FWV 04 FWL 05 FWM 06 FWB 07 FWD 08. Control 09. Accessories 10. Daikin Europe N.V. Daikin has a worldwide reputation based on over 80 years experience in the successful manufacture of high quality air conditioning equipment for industrial, commercial and residential use. Daikin Europe

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air technical data FHYP-B Ceiling Suspended Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and

More information

OJ Waterline control system

OJ Waterline control system OJ Waterline control system THERMOSTATS FOR COMFORT HEATING AND SNOW MELTING Product presentation Mk3 It s all about Room Temperature Control! The essential main goals are: Comfort Flexibility Reliability

More information

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 OPERATION MANUAL EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 EKHVMRD50+80ABV1 EKHVMYD50+80ABV1 CONTENTS Page 1. Definitions... 1 2. Introduction... 2 2.1. General information... 2 2.2. Scope

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Installation and operation manual Table of contents Page 1. Supplied accessories and intended use... 1 2. General layout and setup of a system... 2 3. Installation...

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q SIGNAL REPEATER RC2100 WI-CON Wireless Heating Control for Steam and Hot Water Boilers No sensor wiring required Intelligent sensing algorithm saves energy Low limit control and alarm alert operator of

More information

water-cooled CHILLERS

water-cooled CHILLERS water-cooled CHILLERS and condenserless chillers APPLIED SYSTEMS www.daikin.eu Cooling Only Heating Only EWWD170-600DJYNN EWWD190-650DJYNN/A EWLD160-550DJYNN - ABOUT DAIKIN Daikin has a worldwide reputation

More information

Electronic Pellet Burner Controller NPBC-V3M

Electronic Pellet Burner Controller NPBC-V3M Electronic Pellet Burner Controller NPBC-V3M SOFTWARE VERSION 3.3a/3.2 page of 27 CHANGES IN THE USER MANUAL OR IN THE CONTROLLER'S SOFTWARE Version of the user manual Changes Page 2.2. The software version

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Electronic Pellet Burner Controller NPBC-V3-1

Electronic Pellet Burner Controller NPBC-V3-1 Electronic Pellet Burner Controller NPBC-V3- SOFTWARE VERSION 3.2/3. page of 3 CHANGES IN THE TECHNICAL AND USER GUIDE OR IN THE SOFTWARE VERSION Technical and User Guide's version Changes Page 2.8. The

More information

SIMPLICITY BY DESIGN M52 CONTROLLER

SIMPLICITY BY DESIGN M52 CONTROLLER SIMPLICITY BY DESIGN M52 CONTROLLER CO-WORK TM CONNECTIVITY Our controller is at the heart of all of ClimateWorx product intelligence. Co-Work TM is based on a unique multi-master network system designed

More information

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel Daikin Applied UK Technically better... D-AHU Modular R Air handling units Compact air handling unit with heat recovery wheel Energy efficiency and air quality With their Plug & Play design and inherent

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Fan coil units EPCE04-25A

Fan coil units EPCE04-25A Fan coil units EPCE04-25A Product portfolio 2 Fan Coil FWV FWL FWM Reference 2-pipe 0 1 2 3 4 5 6 7 8 9 10 11 kw 4-pipe 2 4 6 8 10 12 14 16 18 20 22 24kW FWD 2-pipe 4-pipe Cooling Heating Pictogrammes

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102* User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02

More information

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air technical data FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help

More information

EEDEN technical data. Applied Systems. Air-cooled with heat recovery EWTP MBYN

EEDEN technical data. Applied Systems. Air-cooled with heat recovery EWTP MBYN EEDEN09-408 technical data Applied Systems Air-cooled with heat recovery EWTP0-540MBYN EEDEN09-408 technical data Applied Systems Air-cooled with heat recovery EWTP0-540MBYN l l i Chillers R-407C EWTP-MBY

More information

Full range. A class energy label. for your home WALL MOUNTED UNIT. air to air heat pumps. FTXS-G

Full range. A class energy label. for your home WALL MOUNTED UNIT. air to air heat pumps.   FTXS-G Full range A class energy label Air conditioners, heating & cooling for your home WALL MOUNTED UNIT air to air heat pumps www.daikin.eu FTXS-G FOR EVERY HOME, FOR EVERY ROOM unique features Full range

More information

The plug & play fresh Air Solution

The plug & play fresh Air Solution Daikin Modular ADT range The plug & play fresh Air Solution A preselected installation package for air handling and outdoor units Easy ordering of AHU + DX package The need for clean and fresh air The

More information

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls Applications PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Introduction Danfoss PM regulators have been on the market

More information

ETO 2 - Controller for ice and snow melting

ETO 2 - Controller for ice and snow melting ETO 2 - Controller for ice and snow melting Advantages Simple adjustment knob with two functions Illuminated display where you can easily see the temperature status and other values Controls both pumps

More information

Outdoor Reset IQ Option Card, p/n

Outdoor Reset IQ Option Card, p/n Outdoor Reset IQ Option Card, p/n 102723-01 Instruction Sheet CONTENTS Application... 1 General... 2 How it Works... 3 Installation.... 5 Wiring... 7 User Interface... 10 Using IQ Option Panel Display...

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

Outdoor Reset IQ Option Card, p/n

Outdoor Reset IQ Option Card, p/n Outdoor Reset IQ Option Card, p/n 102723-01 Instruction Sheet CONTENTS Application... 1 General... 2 How it Works... 3 Installation.... 5 Wiring... 7 User Interface... 10 Using IQ Option Panel Display...

More information

Air conditioners, heating & cooling for the retailmarket and offices

Air conditioners, heating & cooling for the retailmarket and offices Air conditioners, heating & cooling for the retailmarket and offices floor standing unit air to air heat pumps www.daikin.eu FVQ-B MAXIMUM RELIABILITY, MINIMUM ENERGY USE Advanced climate systems in modern

More information

technical data air conditioning systems FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit Split Sky Air technical data FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

Air Conditioners. Technical Data. Heating only hydrobox for VR V HXHD-A

Air Conditioners. Technical Data. Heating only hydrobox for VR V HXHD-A Air Conditioners Technical Data Heating only hydrobox for VR V E E D E N 1 1-2 0 4 HXHD-A Air Conditioners Technical Data Heating only hydrobox for VR V E E D E N 1 1-2 0 4 HXHD-A TABLE OF CONTENTS HXHD-A

More information

GRUNDFOS DATA BOOKLET MAGNA3. Circulator pumps 60 Hz

GRUNDFOS DATA BOOKLET MAGNA3. Circulator pumps 60 Hz GRUNDFOS DATA BOOKLET Circulator pumps 60 z Table of contents 1. Product introduction 3 Features and benefits 3 Applications 3 2. Performance range 4 4 D single-head operation 5 D twin-head operation 6

More information

EEDEN technical data. Applied Systems. Water-cooled EWWD MBYN

EEDEN technical data. Applied Systems. Water-cooled EWWD MBYN EEDEN09-43 technical data Applied Systems Water-cooled EWWD20-540N Water-cooled EWWD20-540N Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led

More information

High temperature heating system AIR TO WATER HEAT PUMPS. Renovation - Heating - Domestic hot water

High temperature heating system AIR TO WATER HEAT PUMPS. Renovation - Heating - Domestic hot water High temperature heating system AIR TO WATER HEAT PUMPS Renovation - Heating - Domestic hot water Daikin Altherma Heat pumps The solution with an eye to the future Renovating your heating system and wanting

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

MEDICAL CHILLER SYSTEMS

MEDICAL CHILLER SYSTEMS Mission Critical Chilled Water Systems Engineered to Exacting Standards Magnetic Resonance Imaging Systems CT Scanners Oncology Linear Accelerators Blood Cooling Systems Precise Laboratory Applications

More information

NATURAL VENTILATION CONTROL SYSTEMS

NATURAL VENTILATION CONTROL SYSTEMS ...... CI/SfB (57.9) Uniclass L755 September 2005 NATURAL VENTILATION CONTROL SYSTEMS... . 2 ...... Passivent ventilation control systems have been have been specially developed to meet the requirements

More information

EEDEN technical data ERHQ AA. Altherma. Altherma

EEDEN technical data ERHQ AA. Altherma. Altherma EEDEN08-720 technical data ERHQ0-06AA Altherma Altherma Altherma Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement

More information

. Creating Maximum Comfort

. Creating Maximum Comfort P P r o d u c t E X P L A N A T I O N M M a i n F E A T U R E S AA. Creating Maximum Comfort 1 Inverter technology The linear VRV system makes use of a variable Proportional Integral (PI) control system

More information

Commercial and Technical Data

Commercial and Technical Data Chillers Commercial and Technical Data Air Cooled Single Circuit Condensing Unit» Wide capacity range (120 kw - 490 kw)» One refrigerant circuit with single screw compressor» Two sound versions available»

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Installation and operation manual Table of contents Page. Supplied accessories and intended use.... General layout and setup of a system... 3. Installation... 3 3.. Mounting

More information

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502* User's Guide VI.7B.D5.02 2005.10 P20 *VI7BD502* *087R8014* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8014* *VI7BD502* Boiler controller P20 VI.7B.D5.02

More information

Air conditioners, heating & cooling for shops,restaurants and offices

Air conditioners, heating & cooling for shops,restaurants and offices Air conditioners, heating & cooling for shops,restaurants and offices 4-way blow ceiling suspended unit air to air heat pumps www.daikin.eu FUQ-B made by daikin : WORLD-FAMOUS FOR EFFICIENCY By purchasing

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

PRODUCT GUIDE

PRODUCT GUIDE PRODUCT GUIDE 01.2017 Cooling Heating CHAPTER 1 AIRCOOLED LIQUID CHILLERS AND HEAT PUMPS FOR RESIDENTIAL & LIGHT COMMERCIAL APPLICATION Power (kw) Page IACAK/II/WP 101.5 106 0 58 115 A CLASS energy efficiency

More information

The Book of AERMEC NRL Sequence of Operation

The Book of AERMEC NRL Sequence of Operation The Book of AERMEC NRL Sequence of Operation Heating and cooling operation. 2 Sequence of operation Aermec air to water chiller/heat pump use Hydronic s in conjunction with refrigerant to provide heating

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data W a l l m o u n t e d u n i t E E D E N 2-0 0 CTXS-K Indoor Unit Wall mounted unit CTXS-K TABLE OF CONTENTS CTXS-K Features.............................................................

More information

w w w. d a i k i n. e u ATXS-E

w w w. d a i k i n. e u ATXS-E Daikin air conditioners for your home WALL MOUNTED UNIT ATXS-E w w w. d a i k i n. e u Daikin s stylishly elegant wall mounted Siesta unit will grace the dining, living or bedroom of any home. Siesta will

More information

Largo & Allegro. Air Compressors. Largo & Allegro 31-90

Largo & Allegro. Air Compressors. Largo & Allegro 31-90 Largo & Allegro Air Compressors Largo & Allegro 31-90 ALUP Driven by technology. Designed by experience. ALUP Kompressoren has over 85 years of industrial experience. It is our ambition to offer compressed

More information

VRV The total solution. Integrated Climate Control

VRV The total solution. Integrated Climate Control VRV The total solution Integrated Climate Control Total Solution Concept The Daikin VRV Total Solution provides a single point of contact for the design and maintenance of your integrated climate control

More information

Air Conditioners. Technical Data FTXS-G

Air Conditioners. Technical Data FTXS-G Air Conditioners Technical Data I n d o o r u n i t s w w w. d a i k i n. e u FTXS-G Air Conditioners Technical Data I n d o o r u n i t s w w w. d a i k i n. e u FTXS-G Indoor Units R-410A FTXS-G TABLE

More information

air systems Roomtop RTC-RTH 15 to 30 - L

air systems Roomtop RTC-RTH 15 to 30 - L air systems Roomtop RTC-RTH 15 to 30 - L york air-conditioning products Roomtop RTC-RTH - L A complete range from 14.6 kw up to 27.0 kw YKN2open Features New YKN2open board Possibility to be installed

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

technical data air conditioning systems Indoor Units FBQ-C7VEB

technical data air conditioning systems Indoor Units FBQ-C7VEB technical data Indoor Units FBQ-C7VEB air conditioning systems technical data Indoor Units FBQ-C7VEB air conditioning systems Indoor Units R-40A FBQ-C7VEB TABLE OF CONTENTS FBQ-C7VEB Features.............................................................

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

GHS VSD+ SOLUTIONS FOR CENTRALIZED VACUUM

GHS VSD+ SOLUTIONS FOR CENTRALIZED VACUUM GHS VSD+ SOLUTIONS FOR CENTRALIZED VACUUM Some key components: the engine, brains and remote communication options of your central system described in detail THE ENGINE OF YOUR CENTRAL SYSTEM The engine

More information

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions DESCRIPTION The RC-90 is a precision digital thermostat designed for 24 VAC single stage heating and

More information

Applica. First Edition uly 2005

Applica. First Edition uly 2005 McQuay y Smart t Manager er Chilled Water System Applica pplication Manual First Edition Jul uly 2005 Introduction Introduction... Introduction-1 Section 1: Networ ork k Interface Module (NIM) and Netwar

More information

Service Manual. w/con X US Interface Models: WARNING

Service Manual. w/con X US Interface Models: WARNING FB-SER_100161013_2000004598 Rev R Service Manual w/con X US Interface Models: 2500-6000 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

Do you want a versatile solution

Do you want a versatile solution Do you want a versatile solution to make significant savings? ESTIA TOSHIBA AIR CONDITIONING RESIDENTIAL HEATING AIR-TO-WATER HEAT PUMP ESTIA hatever you need ESTIA TO MAKE SIGNIFICANT SAVINGS Toshiba

More information

Air to water Heat Pump System

Air to water Heat Pump System Air to water Heat Pump System 2 The heating and cooling systems of the future! A step in the right direction of reducing pollution and CO₂ emissions The increase of CO₂ and other green house gases is a

More information

EWAT-B. Multi scroll chiller with R-32 refrigerant. First air cooled chiller with environmental friendly R-32 refrigerant

EWAT-B. Multi scroll chiller with R-32 refrigerant. First air cooled chiller with environmental friendly R-32 refrigerant EWAT-B Multi scroll chiller with R-32 refrigerant First air cooled chiller with environmental friendly R-32 refrigerant Daikin, world s first company introducing a new generation of air cooled scroll chiller

More information

Water-cooled chillers with High Speed Centrifugal Compressors

Water-cooled chillers with High Speed Centrifugal Compressors Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and

More information

Service Manual. w/con X US Interface Models: Series: & WARNING

Service Manual. w/con X US Interface Models: Series: & WARNING 100208044_2000004590 Rev N w/con X US Interface Models: 751-6001 Series: 100-101 & 110-111 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

Heatrix Electric Duct Heater HXOB Installation Instructions

Heatrix Electric Duct Heater HXOB Installation Instructions Heatrix Electric Duct Heater HXOB Installation Instructions General: Heatrix HXOB Style Electric Duct Heater has been tested and listed for close-coupled application with a forced air system (straight

More information

Heating Zone Control. How to apply RESOL MX controller

Heating Zone Control. How to apply RESOL MX controller Heating Zone Control How to apply RESOL MX controller Basic Diagram Sensor No Description Relay No. Description S4 Boiler Supply Sensor R5 DHW Loading Pump S5 DHW Tank Temperature Sensor R6 Zone Valve

More information

Rollair. Air Compressors. Rollair 40 to 125 and Rollair 40 V to 125 V

Rollair. Air Compressors. Rollair 40 to 125 and Rollair 40 V to 125 V Rollair Air Compressors Rollair 40 to 125 and Rollair 40 V to 125 V Worthington Creyssensac Driven by technology. Designed by experience. Worthington Creyssensac has over 145 years of industrial experience.

More information

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning G2524en Heating controller Installation Instructions RVL471 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19 OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19 1. Application. Controller RK-2006LPP is designed for temperature control of solid fuel fired water boilers

More information

Service Manual Models:

Service Manual Models: FBII-SER Rev B Service Manual Models: 751-2001 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Installation

More information

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule # Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # Page 1 of 7 Performance Power Compressor 95 F Ambient, Entering Temperature: 54 F, Leaving

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

AIR CONDITIONERS, HEATING & COOLING for your home

AIR CONDITIONERS, HEATING & COOLING for your home AIR CONDITIONERS, HEATING & COOLING for your home SLIM CONCEALED CEILING UNIT air to air heat pumps www.daikin.eu FDXS-E FDXS-C COMFORTABLE AIR, THE WHOLE YEAR THROUGH A comfortable living space provides

More information

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road An ISO 9001-2000 Certified Company Dunkirk, NY 14048 www.argoindustries.com P/N 240005498A, Rev. 1.5 [02/07]

More information

T7984 A,B,C Electronic Modulating Control Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats T7984 A,B,C Electronic Modulating Control Thermostats FEATURES PRODUCT DATA APPLICATION These microprocessor-based thermostats provide proportional - integral (PI) individual room temperature control in

More information

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air technical data RMXS-E7V3B1 Super multi plus air conditioning systems Split Sky Air Outdoor Units R-410A RMXS-E7V3B1 TABLE OF CONTENTS RMXS-E7V3B1 1 Features.............................................................

More information

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units Precision control from the total provide Uncompromised precision More than ever data centers, server rooms, and

More information