SECTION PACKAGED ENGINE GENERATORS

Size: px
Start display at page:

Download "SECTION PACKAGED ENGINE GENERATORS"

Transcription

1 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION SECTION PACKAGED ENGINE GENERATORS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged engine-generator sets for emergency power supply with the following features and accessories: 1. Diesel engine 2. Unit-mounted cooling system 3. Remote-mounting annunciator and stop-switch 4. Outdoor enclosure 5. Battery Charger 6. Muffler 7. Exhaust piping external to set 8. Starting battery 9. Day tank B. Related sections include the following: 1. Division 26 Section "Transfer Switches" for transfer switches including sensors and relays to initiate automatic-starting and -stopping signals for engine-generator sets. 1.2 SUBMITTALS A. Product Data: Include data on features, components, ratings, and performance. Include the following: 1. Dimensioned outline plan and elevation drawings of engine generator set and other components specified. 2. Thermal damage curve for generator 3. Time-current characteristic curves for generator protective device B. Shop Drawings: Indicate fabrication details, dimensions, weights, loads, required clearances, and method of filed assembly, components, and location and size of each field connection. 1. Design Calculations: Signed and sealed by a qualified professional engineer. Calculate requirements for selecting vibration isolators and seismic restraints and for designing vibration isolation bases. 2. Vibration Isolation Base Details: Signed and sealed by a qualified professional engineer. Detail fabrication, including anchorages and attachments to structure and to supported equipment. Include base weights. 3. Wiring Diagrams: Detail wiring for power and control connections and differentiate between factory-installed and field-installed wiring. C. Qualification Data: For firms and persons specified in Quality Assurance Article. D. Field Test and Observation Reports: Indicate and interpret test results and inspection records relative to compliance with performance requirements. E. Certified summary of prototype-unit test report. F. Certified Test Reports: For components and accessories that are equivalent, but not identical, to those tested on prototype unit. SECTION Page 1 of 11

2 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION G. Factory Test Reports: For units to be shipped for this Project, showing evidence of compliance with specified requirements. H. Sound measurement test report. I. Certification of Torsional Vibration Compatibility: Comply with NFPA 110. J. Field test report of tests specified in Part 3. K. Maintenance Data: For each package engine generator and accessories to include in maintenance manuals specified in Division 1. Include the following: L. Detail operating instructions for both normal and abnormal conditions. M. Warranty: Special warranty specified in this Section. 1.3 QUALITY ASSURANCE A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project. B. Testing Agency Qualifications: Testing agency as defined by OSHA in 29 CFR or a member company of the InterNational Electrical Testing Association and that is acceptable to authorities having jurisdiction. C. Source Limitations: Obtain packaged engine generator and auxiliary components specified in this Section through one source from a single manufacturer. D. Manufacturer Qualifications: A qualified manufacturer. Maintain a service center capable of emergency maintenance and repairs at the Project with eight hours maximum response time. E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. F. Comply with ASME B15.1. G. Comply with NFPA 37. H. Comply with NFPA 70. I. Comply with NFPA 99. J. Comply with NFPA 110 requirements for Level 1 emergency power supply system. K. Comply with UL L. Engine Exhaust Emissions: Comply with applicable state and local government requirements. M. Noise Emission: Comply with applicable state and local government requirements for maximum noise level at adjacent property boundaries due to sound emitted by generator set including engine, engine exhaust, engine cooling-air intake and discharge, and other components of installation. SECTION Page 2 of 11

3 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period. 1. Warranty Period: minimum 2 years from date of Substantial Completion. 1.5 DELIVERY, STORAGE, AND HANDLING A. Deliver engine generator set and system components to their final locations in protective wrappings, containers, and other protection that will exclude dirt and moisture and prevent damage from construction operations. Remove protection only after equipment is safe from such hazards. 1.6 MAINTENANCE SERVICE A. Maintenance: At Substantial Completion, begin 12 months full maintenance by skilled employees of the manufacturer s designated service organization. Include quarterly exercising to check for proper, starting, load transfer, and running under load. Include routing preventive maintenance as recommended by manufacturer and adjusting as required for proper operation. Maintenance agreements shall include parts and supplies as used in the manufacture and installation of original equipment. 1.7 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Fuses: One for every ten of each type and rating, but not less than one of each. 2. Indicator Lamps: Two for every six of each type used, but not less than two of each. 3. Filters: One set each of lubricating oil, fuel, and combustion-air filters. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: C. Basis-of-Design Product: Subject to compliance with requirements, provide [the product indicated on Drawings] <Insert manufacturer's name; product name or designation> or a comparable product by one of the following: 1. Caterpillar, Inc; Engine Div. 2. Generac Power Systems, Inc. 3. Kohler Co.; Generator Division. 4. Onan/Cummins Power Generation; Industrial Business Group. 2.2 ENGINE-GENERATOR SET A. Factory-assembled and -tested, engine-generator set. SECTION Page 3 of 11

4 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION B. Mounting Frame: Maintain alignment of mounted components without depending on concrete foundation; and have lifting attachments. C. Capacities and Characteristics: 1. Power Output Ratings: Nominal ratings as indicated, with capacity as required to operate as a unit as evidenced by records of prototype testing. 2. Output Connections: Three-phase, four wire. 3. Nameplates: Each major system component is equipped with a conspicuous nameplate of component manufacturer. Nameplate identifies manufacturer of origin and address, and model and serial number of item. 4. Skid: Adequate strength and rigidity to maintain alignment of mounted components without depending on a concrete foundation. Skid is free from sharp edges and corners. Lifting attachments are arranged to facilitate lifting with slings without damaging any components. 5. Rigging Diagram: Inscribed on a metal plate permanently attached to skid. Diagram indicates location and lifting capacity of each lifting attachment and location of center of gravity. D. Generator-Set Performance: 1. Steady-State Voltage Operational Bandwidth: 4 percent of rated output voltage from no load to full load. 2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds. 3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency from no load to full load. 4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed. 5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-load increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds. 6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent. 7. Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 percent of rated full-load current for not less than 10 seconds and then clear the fault automatically, without damage to generator system components. 8. Start Time: Comply with NFPA 110, Type 10, system requirements 9. Steady-State Voltage Modulation Frequency: Less than 1 Hz. 2.3 ENGINE A. Fuel: Fuel oil, Grade DF-2. B. Rated Engine Speed: 1800 rpm. C. Maximum Piston Speed for Four-Cycle Engines: 2250 fpm (11.4 m/s). D. Lubrication System: Pressurized by a positive-displacement pump driven from engine crankshaft. The following items are mounted on engine or skid: SECTION Page 4 of 11

5 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow. 2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe. 3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances. E. Engine Fuel System: 1. Main Fuel Pump: Mounted on engine. Pump ensures adequate primary fuel flow under starting and load conditions. 2. Relief-Bypass Valve: Automatically regulates pressure in fuel line and returns excess fuel to source. F. Coolant Jacket Heater: Electric-immersion type, factory installed in coolant jacket system. Comply with NFPA 110 requirements for Level 1 equipment for heater capacity. G. Governor: Adjustable isochronous, with speed sensing. H. Engine Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine-generatorset skid and integral engine-driven coolant pump. 1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water, with anticorrosion additives as recommended by engine manufacturer. 2. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flow automatically to maintain optimum constant coolant temperature as recommended by engine manufacturer. I. Muffler/Silencer: Critical type, sized as recommended by engine manufacturer and selected with exhaust piping system to not exceed engine manufacturer's engine backpressure requirements. 1. Minimum sound attenuation of 25 db at 500 Hz. 2. Sound level measured at a distance of 10 feet (3 m) from exhaust discharge after installation is complete shall be 85 dba or less. J. Air-Intake Filter: Standard-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator. K. Starting System: 12-V electric, with negative ground. 1. Components: Sized so they will not be damaged during a full engine-cranking cycle with ambient temperature at maximum specified in Part 1 "Project Conditions" Article above. 2. Cranking Cycle: As required by NFPA 110 for system level specified. 3. Battery: Adequate capacity within ambient temperature range specified in Part 1 "Project Conditions" Article above to provide specified cranking cycle at least twice without recharging. 4. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 35-A minimum continuous rating. 5. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding. 6. Battery Cable: Size as required by generator set manufacturer for battery location within generator enclosure. Include required interconnecting conductors/connection accessories. 7. Battery Compartment: Factory fabricated of metal with acid-resistant finish and thermal insulation. Thermostatically controlled heater is arranged to maintain battery above 10 deg C regardless of external ambient temperature within range specified in Environmental Conditions SECTION Page 5 of 11

6 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION Paragraph in Service Conditions Article above. Include accessories required to support and fasted batteries in place. 8. Battery Charger: Current-limiting, automatic-equalizing and float-charging type. Unit shall comply with UL a. Operation: Equalizing-charging rate of 10 A is initiated automatically after battery has lost charge until an adjustable equalizing voltage is achieved at battery terminals. Unit then automatically switches to a lower float-charging mode and continues operating in that mode until battery is discharged again. b. Automatic Temperature Compensation: Adjusts float and equalizes voltages for variations in ambient temperature from minus 40 deg C to plus 60 deg C to prevent overcharging at high temperatures and undercharging at low temperatures. c. Automatic Voltage Regulation: Maintains output voltage constant regardless of input voltage variations up to plus of minus 10 percent. d. Ammeter and Voltmeter: Flush mounted in door. Meters indicate charging rates. e. Safety Functions: Include sensing of abnormally low battery voltage arranged to close contacts providing low battery voltage indication on control and monitoring panel. Also include sensing of high battery voltage and loss of ac input or dc output of battery charger. Either condition closed contacts that provide a battery-charger malfunction indication at system control and monitoring panel. f. Enclosure and Mounting: NEMA 250, Type 1, mounted in generator enclosure. 2.4 FUEL OIL STORAGE A. Comply with NFPA 30. B. Base-Mounted Fuel Oil Tank: Factory installed and piped, complying with UL 142 fuel oil tank. Features include the following: 1. Tank level indicator. 2. Capacity: Fuel for eight hours' continuous operation at 100 percent rated power output. 3. Vandal-resistant fill cap. 4. Containment Provisions: Comply with requirements of local AHJ and all applicable standards of the Texas Department of Aging and Disability Services. 2.5 CONTROL AND MONITORING A. Automatic Starting System Sequence of Operation: When mode-selector switch on the control and monitoring panel is in the automatic position, remote-control contacts in one or more separate automatic transfer switches initiate starting and stopping of generator set. When mode-selector switch is switched to the on position, generator set starts. The off position of same switch initiates generator-set shutdown. When generator set is running, specified system or equipment failures or derangements automatically shut down generator set and initiate alarms. Operation of a remote emergency-stop switch also shuts down the generator set. B. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common control and monitoring panel mounted on the generator set. Mounting method shall isolate the control panel from generator-set vibration. C. Indicating and Protective Devices and Controls: As required by NFPA 110 for a Level 1 system, and the following: 1. AC voltmeter. SECTION Page 6 of 11

7 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION AC ammeter. 3. AC frequency meter. 4. DC voltmeter (alternator battery charging). 5. Engine-coolant temperature gage. 6. Engine lubricating-oil pressure gage. 7. Running-time meter. 8. Ammeter-voltmeter, phase-selector switch(es). 9. Generator-voltage adjusting rheostat. 10. Fuel tank derangement alarm. 11. Fuel tank high-level shutdown of fuel supply alarm. 12. Generator overload. D. Supporting Items: Include sensors, transducers, terminals, relays, and other devices and include wiring required to support specified items. Locate sensors and other supporting items on engine or generator, unless otherwise indicated. E. Common Remote Audible Alarm: Comply with NFPA 110 requirements for Level 1 systems. Include necessary contacts and terminals in control and monitoring panel. 1. Overcrank shutdown. 2. Coolant low-temperature alarm. 3. Control switch not in auto position. 4. Battery-charger malfunction alarm. 5. Battery low-voltage alarm. F. Remote Alarm Annunciator: Comply with NFPA 99. An LED labeled with proper alarm conditions shall identify each alarm event and a common audible signal shall sound for each alarm condition. Silencing switch in face of panel shall silence signal without altering visual indication. Connect so that after an alarm is silenced, clearing of initiating condition will reactivate alarm until silencing switch is reset. Cabinet and faceplate are surface- or flush-mounting type to suit mounting conditions indicated. 2.6 GENERATOR OVERCURRENT AND FAULT PROTECTION A. Generator Circuit Breaker: Molded-case, thermal-magnetic type; 100 percent rated; complying with NEMA AB 1 and UL Tripping Characteristic: Designed specifically for generator protection. 2. Trip Rating: Matched to generator rating. 3. Shunt Trip: Connected to trip breaker when generator set is shut down by other protective devices. 4. Mounting: Adjacent to or integrated with control and monitoring panel. 2.7 GENERATOR, EXCITER, AND VOLTAGE REGULATOR A. Comply with NEMA MG 1. B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotated integrally with generator rotor. C. Electrical Insulation: Class H or Class F. D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required. SECTION Page 7 of 11

8 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION E. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, overspeed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity. F. Enclosure: Dripproof. G. Instrument Transformers: Mounted within generator enclosure. H. Voltage Regulator: Solid-state type, separate from exciter, providing performance as specified. 1. Adjusting rheostat on control and monitoring panel shall provide plus or minus 5 percent adjustment of output-voltage operating band. I. Strip Heater: Thermostatically controlled unit arranged to maintain stator windings above dew point. J. Windings: Two-thirds pitch stator winding and fully linked amortisseur winding. K. Subtransient Reactance: 12 percent, maximum. 2.8 OUTDOOR GENERATOR-SET ENCLOSURE A. Description: Vandal-resistant, weatherproof steel housing, wind resistant up to 100 mph (160 km/h). Multiple panels shall be lockable and provide adequate access to components requiring maintenance. Panels shall be removable by one person without tools. Instruments and control shall be mounted within enclosure. B. Engine Cooling Airflow through Enclosure: Maintain temperature rise of system components within required limits when unit operates at 110 percent of rated load for 2 hours with ambient temperature at top of range specified in system service conditions. 1. Louvers: Fixed-engine, cooling-air inlet and discharge. Storm-proof and drainable louvers prevent entry of rain and snow. 2. Automatic Dampers: At engine cooling-air inlet and discharge. Dampers shall be closed to reduce enclosure heat loss in cold weather when unit is not operating. C. Convenience Outlets: Factory wired weatherproof, GFCI. Arrange for external electrical connection. 2.9 FINISHES A. Indoor and Outdoor Enclosures and Components: Manufacturer's standard finish over corrosion-resistant pretreatment and compatible primer SOURCE QUALITY CONTROL A. Prototype Testing: Factory test engine-generator set using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories. 1. Tests: Comply with NFPA 110, Level 1 Energy Converters and with IEEE Report factory test results within 10 days of completion of test. SECTION Page 8 of 11

9 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION PART 3 - EXECUTION 3.1 INSTALLATION A. Comply with packaged engine-generator manufacturers' written installation and alignment instructions and with NFPA 110. B. Install packaged engine generator to provide access, without removing connections or accessories, for periodic maintenance. C. Install packaged engine generator with elastomeric isolator pads having a minimum deflection of 1 inch (25 mm) on 4-inch- (100-mm-) high concrete base. Secure sets to anchor bolts installed in concrete bases. Concrete base construction is specified in Division 26 Section "Vibration and Seismic Controls for Electrical Systems." D. Install Schedule 40, black steel piping with welded joints and connect to engine muffler. Install thimble at wall. Piping shall be same diameter as muffler outlet. Flexible connectors and steel piping materials and installation requirements are specified in Division 23 Section "Hydronic Piping." 1. Install condensate drain piping to muffler drain outlet full size of drain connection with a shutoff valve, stainless-steel flexible connector, and Schedule 40, black steel pipe with welded joints. Flexible connectors and piping materials and installation requirements are specified in Division 23 Section "Hydronic Piping." E. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not specified to be factory mounted. F. Piping installation requirements are specified in Division 23 Sections. Drawings indicate general arrangement of piping and specialties. G. Connect fuel, cooling-system, and exhaust-system piping adjacent to packaged engine generator to allow service and maintenance. H. Connect engine exhaust pipe to engine with flexible connector. I. Connect fuel piping to engines with a gate valve and union and flexible connector. 1. Natural-gas piping, valves, and specialties for gas distribution are specified in Division 23 Section "Facility Natural-Gas Piping." 2. LP-gas piping, valves, and specialties for gas piping are specified in Division 23 Section "Facility Liquefied-Petroleum Gas Piping." J. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems." K. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and Cables." L. Identify system components according to Division 23 Section "Identification for HVAC Piping and Equipment" and Division 26 Section "Identification for Electrical Systems." 3.2 FIELD QUALITY CONTROL A. Perform tests and inspections and prepare test reports. SECTION Page 9 of 11

10 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. B. Tests and Inspections: 1. Perform tests recommended by manufacturer and each electrical test and visual and mechanical inspection for "AC Generators and for Emergency Systems" specified in NETA Acceptance Testing Specification. Certify compliance with test parameters. 2. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to those specified here including, but not limited to, single-step full-load pickup test. 3. Battery Tests: Equalize charging of battery cells according to manufacturer's written instructions. Record individual cell voltages. a. Measure charging voltage and voltages between available battery terminals for fullcharging and float-charging conditions. Check electrolyte level and specific gravity under both conditions. b. Test for contact integrity of all connectors. Perform an integrity load test and a capacity load test for the battery. c. Verify acceptance of charge for each element of the battery after discharge. d. Verify that measurements are within manufacturer's specifications. 4. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-charging conditions. 5. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine-generator system before and during system operation. Check for air, exhaust, and fluid leaks. 6. Exhaust Emissions Test: Comply with applicable government test criteria. 7. Voltage and Frequency Transient Stability Tests: Use recording oscilloscope to measure voltage and frequency transients for 50 and 100 percent step-load increases and decreases, and verify that performance is as specified. 8. Harmonic-Content Tests: Measure harmonic content of output voltage under 25 percent and at 100 percent of rated linear load. Verify that harmonic content is within specified limits. 9. Noise Level Tests: Measure A-weighted level of noise emanating from generator-set installation, including engine exhaust and cooling-air intake and discharge, at four locations on the property line, and compare measured levels with required values. C. Coordinate tests with tests for transfer switches and run them concurrently. D. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. E. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. F. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. G. Remove and replace malfunctioning units and retest and re-inspect as specified above. H. Retest: Correct deficiencies identified by tests and observations and retest until specified requirements are met. I. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory completion of tests. SECTION Page 10 of 11

11 PACKAGED GENERATORS BATON ROUGE, LOUISIANA SECTION DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators. Refer to Division 01 Section "Demonstration and Training." END OF SECTION SECTION Page 11 of 11

12 AUTOMATIC TRANSFER SWITCH BATON ROUGE, LOUISIANA SECTION SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 WORK INCLUDED A. Furnish and install an automatic transfer switch for transferring selected emergency loads from normal utility source to on site generator upon loss of normal power and back to utility source upon return of normal power. The transfer switch shall be as indicated on the drawings and as specified herein. The transfer switch together with the package engine generator set specified in Section shall automatically provide continuous electrical power for the duration of any failure of the normal utility power supply. B. In the event that any item is not available exactly as specified, the contractor shall so notify the Architect in writing as early as possible to allow ample time for an alternate item to be selected without delay to the project. 1.2 SHOP DRAWINGS A. Submit six (6) sets of shop drawings and manufacturer's data which show the following items in tabulated form in accordance with Section Wiring diagrams (both internal and external) 2. Physical arrangements 3. Accessories list 4. Operating instructions 5. Test data 1.3 ENVIRONMENTAL CONDITIONS A. The equipment specified is intended for application in an environment as described below: 1. Altitude: 564 feet above sea level. 2. Maximum Temperature: 95 degrees F. 3. Minimum Temperature: 2 degrees F. PART 2 - PRODUCTS 2.1 ACCEPTABLE MANUFACTURERS A. Russelectric B. ASCO C. Onan D. Kohler E. Zenith 2.2 RATINGS A. The automatic transfer switch shall have the following ratings when installed at the specified site and all SECTION Page 1 of 3

13 AUTOMATIC TRANSFER SWITCH BATON ROUGE, LOUISIANA SECTION derating factors including those for temperatures and altitude are considered. 1. Current Capacity: as specified. 2. Voltage: 120/ Phase: 3 4. Poles: 3 5. Frequency: 60 Hz 6. Enclosure: NEMA 1 wall mounted. 2.3 QUALIFICATIONS OF SUPPLIERS A. The transfer switch shall be manufactured by a company who is regularly engaged in the manufacture of similar units and who has been in business for at least ten (10) years. B. The local representative of the transfer switch equipment shall have full service capability for the equipment including a factory trained technician located within one hours drive from job site, equipment to service and test the transfer switch. 2.4 COORDINATION WITH OTHER EQUIPMENT A. The equipment supplied under this section shall be fully coordinated with and form a complete operational system with equipment supplied under other sections. The contractor shall coordinate between suppliers to insure compatibility of equipment for the intended function. 2.5 AUTOMATIC TRANSFER A. The transfer switch shall be inherently double pole and shall be actuated by a single electrical operator, either solenoid or motor device. B. The switch shall be mechanically interlocked to assure only one position can be obtained (normal or emergency) and that no intermediate positions can be obtained. C. The electric operator shall be energized from the source to which the load is to be transferred. D. Contacts shall be silver alloy complete with arc chutes. E. A manual operator with handle shall be furnished with mechanism to insure acceptable transfer time when manually activated. F. Controls shall be either electro-mechanical or electronic. Controls shall be capable of being accurately field adjusted without need for special testing or timing apparatus. Controls may be mounted in switch cabinet or on cabinet door but must be accessible while energized with complete operator safety. G. Switches which are manufactured using circuit breakers or parts of circuit breakers as main contact mechanisms are not acceptable. H. Where neutral is switched, the neutral contacts shall be full phase capacity. Nonoverlapping neutral contacts are preferred, however, overlapping neutral contacts are acceptable providing overlap time does not exceed 100 milliseconds. I. The automatic transfer switch or prototype thereof shall have passed all requirements of UL Standard UL1008 as a complete enclosed unit. J. The automatic transfer switch shall be provided with the following accessories. 1. Time delay to override momentary outages, adjustable 0-5 min. 2. Time delay retransfer to normal source, adjustable 0-30 min. with bypass push-button. 3. Unloaded running time delay (cool down) adjustable 0-5 min. 4. Time delay transfer to emergency, adjustable 0-1 min. SECTION Page 2 of 3

14 AUTOMATIC TRANSFER SWITCH BATON ROUGE, LOUISIANA SECTION Close differential voltage sensing on all phases of normal source, adjustable. 6. Engine start contact. 7. Test switch to simulate source failure with "load-no load" selector. 8. Auxiliary contacts on shaft: 1 closed in normal position. 1 closed in emergency position. 9. Exercise timer. K. Lugs for connection of power conductors shall be provided to accommodate the cabling indicated on the drawings. L. The enclosure shall be fabricated of heavy gauge sheet steel and shall be finish painted in accordance with the manufacturer s standards. Enclosures shall be suitable for the intended environment. Enclosures for indoors shall be NEMA 1. Suitable room for cable termination and bending shall be provided. Pilot devices for control functions shall be mounted on the front of the hinged door and shall be clearly labeled with black lamacoid nameplates with white letters screwed to the sheet steel. Pilot devices shall be of the "oil-tight" type. Miniature type lights and switches are not acceptable. PART 3 - EXECUTION 3.1 INSTALLATION A. Install the automatic transfer switch in accordance with the drawings and these specifications. Make all necessary connections. B. Final connections and control checkout shall be done under supervision of equipment manufacturer's field representative. C. Manufacturer's wiring diagrams shall be used to connect the equipment. All wiring and conduit shall be as called for in these specifications. 3.2 TESTING A. Manufacturers standard factory tests shall be performed prior to shipment. Records of these tests shall be certified and submitted to the Architect/Engineer for his review. B. On site tests shall be performed as follows: 1. Control check to show that all control functions are operational. Provide certified documentation of results of this test. 2. Load building testing, as specified in Section 16210, shall be done with the transfer switch specified herein connected to the system and operational. During and immediately after the testing, the transfer switch shall be inspected for evidence of overheating and malfunction. Any abnormalities shall be reported to the Architect. 3.3 WARRANTY A. The total equipment installation shall be warranted for a period of one year from date of final test or acceptance. All parts and labor shall be covered under the terms of the warranty. END OF SECTION SECTION Page 3 of 3

15 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION SECTION SURGE PROTECTION DEVICES (SPD s) PART 1 GENERAL 1.1 SCOPE A. These specifications describe the electrical and mechanical requirements for a hybrid electrical Surge Protection Device/filter system integrating both surge protection devices(spd s) and electrical high frequency noise filtering for exposure locations as defined in the latest edition of ANSI/IEEE C REFERENCE STANDARDS A. ANSI/IEEE C and C62.45 B. UL rd Edition 2009 Revision (effective 9/29/2009) C. UL 1283 D. NEC NFPA 70 E. NEMA LS1 and LS2 F. NFPA G. OSHA H. IEEE Std QUALITY ASSURANCE A. The unit shall be designed and assembled in the USA by a qualified manufacturer of TVSS products and line conditioning equipment. The manufacturer shall have been engaged in the design and manufacture of such products for a minimum of 10 years. 1.4 SUBMITTALS A. Submittals shall be in accordance with Division 1 and shall include: 1. Manufacturer's catalog information showing dimensions, configurations, and specifications. 2. Copies of independent test reports UL 1449 and NEMA LS1 and LS2. B. Provide actual UL 1449, Third edition Type 1 20kA nominal discharge current documentation showing the Voltage Protection Ratings (VPR) as well all engineering considerations for the specific catalog number submitted. Typical UL 1449 data is not acceptable. SECTION Page 1 of 7

16 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION C. Provide third party test documentation demonstrating that the device is capable of surviving the specified maximum surge current rating without failure or component degradation greater than 10%. Test documentation shall clearly show that tests were performed on a complete device including all necessary fusing and disconnects. D. Provide data confirming that the device is capable of surviving the published number of repetitive ANSI/IEEE 62.41, Category C3, 20kV/10KA impulses without failure or performance degradation. E. Provide test documentation demonstrating that the device is capable of surviving the specified short circuit fault current rating. F. Provide a complete test documentation package per the recommendations of NEMA LS1 and LS2. G. Line by Line compliance matrix demonstrating adherence to these specifications. PART 2 PRODUCTS 2.1 ACCEPTABLE MANUFACTURERS A. Liebert Corporation B. Current Technology C. Siemens D. Square D E. Cutler Hammer 2.2 SERVICE ENTRANCE SWITCHBOARD (1200 amperes and LARGER) Protective DEVICE A. General 1. Unit Operating Voltage. The nominal unit operating voltage and configuration shall be as indicated on the drawings. 2. Maximum Continuous Operating Voltage (MCOV). The MCOV shall be greater than 115% of nominal voltage for all products. 3. Operating frequency range shall be Hertz. 4. Surge Rating shall be 200kA per mode 5. Monitoring System shall include as a minimum, this monitoring shall include one set of status monitoring lights that will provide visual indication of voltage present to the SPD for each phase of protection. The lights shall also indicate when suppressor protection has degraded to any value of less than 50%. Status indicator lights that simply indicate the presence of voltage, and provide no indication of performance, will be unacceptable. Additionally, the unit shall include an audible alarm with battery backup, a current-sensing surge counter, and two sets of Form C contacts for remote monitoring. Additionally, the unit shall include a visual status of suppression protection available, shown in a percentage from 0% to 100%; indication of the number of swells (voltage > 110% of nominal); surges (voltage > 130% of peak voltage); sags (voltage < 90% of nominal); and outages (power interruptions > 1 cycle) the device has encountered. 6. Acceptable Products shall be, no substitutions: SECTION Page 2 of 7

17 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION a. Liebert # SI040 Series b. Current Technology # TG200 Series. B. Physical 1. Enclosure: The specified system shall be provided in a heavy duty NEMA 4 dust-tight, drip-tight enclosure with no ventilation openings. 2. Provide a plastic lexan cover with lock for outdoor applications. C. Electrical 1. Unit shall be UL1449, 3rd Edition (September 29, 2009) Type 1 20kA nominal discharge current Listed. A SPD that is a UL Recognized component will not be accepted. 2. Each surge suppression and filter element shall be individually fused so that a failure of one element and/or fuse shall not affect nor operate any other fuse element. SPD shall have a shortcircuit rating of 200kAIC. Devices that accomplish this rating by requiring or providing additional fusing to the SPD system will not be accepted. 3. All fusing elements shall be UL Listed or Recognized as a complete fusing system. 4. Unit shall include solid-state, long-life externally mounted LED visual status indicators that indicate the on-line status and operational integrity of the unit. 5. Unit shall have a Form C summary alarm output contact rated for at least 1 amp at 120VAC for remote annunciation of SPD status. D. Performance 1. Rated Single Pulse Surge Current Capacity. The rated single pulse surge current capacity, in amps, for each mode of protection of the unit shall be no less than 200,000 Amps per mode, based on ANSI/IEEE C62.41 Standard 8X20 µsec current waveform. 2. Tested Single Pulse Surge Current Capacity. Suppression filter systems shall be single pulse surge current tested in all modes at rated surge currents by an industry-recognized independent test laboratory. The test shall include a UL1449 Third Edition surge defined as a 1.2X50 µsec, 6000V open circuit voltage waveform and an 8X20 µsec, 3000A short circuit current waveform to benchmark the unit s suppression voltage, followed by a single pulse surge of maximum rated surge current magnitude with an 8X20 µsec waveform. To complete the test, another UL1449 surge shall be applied to verify the unit s survival. Survival is achieved if the suppression voltage measured from the two UL1449 surges does not vary by more than 10%. 3. Minimum Life Cycle Rating. Per ANSI/IEEE C62.41 and ANSI/IEEE C62.45, Test suppression filter systems in every mode utilizing a 1.2X50 µsec, 20 KV open circuit voltage, 8X20 µsec, 10 KA short circuit current Category C3 bi-wave at one minute intervals without suffering performance degradation of more than 10% deviation of clamping voltage. Tested life under these conditions shall be no less than 5,000 impulses per mode. 4. UL1449Voltage Protection Rating. All suppression filter system clamping voltages shall be in compliance and listed by UL1449 3rd edition Type 1 with a nominal discharge current of 20kA. Maximum listed clamping voltages shall be as follows: a. Unit shall provide maximum UL1449 3rd Edition Voltage Protection Rating (VPR) for 208Y/120 Volt systems as follows: L-N = 700V L-G = 700V N-G = 700V L-L = 1000V b. Unit shall provide maximum UL1449 3rd Edition Voltage Protection Rating (VPR) for 480Y/277 Volt systems as follows: L-N = 1000V L-G = 1200V N-G = 1000V L-L = 1800V SECTION Page 3 of 7

18 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION Noise Attenuation - The unit shall be UL1283 in Type 2 locations Listed as an electromagnetic interference filter. The filter shall provide 41dB at 100kHz, 31dB at 1MHz, 35dB at 10MHz, 53dB at 100MHz, per 50 Ohm Insertion Loss Methodology from MIL 220A. The system shall provide up to 120-dB insertion loss from 100 khz to 100 MHz when used in a coordinated facility system. 6. Overcurrent Protection - Each suppression element shall be individually fused such that the failure of a single component or the operation of a single fuse element remains isolated and does not render the entire mode, or product, deficient by more than 5%. Fusing shall be present in all modes, including Neutral-to-Ground. The device shall be capable of withstanding the full single pulse surge current capacity for every mode without the operation or failure of overcurrent / fault current protection or fuses. 7. Internal Conductor Path. All full magnitude transient current shall be conducted utilizing lowimpedance copper bus bar. No plug-in component modules or quick-disconnect terminals shall be used in surge current-carrying paths. 2.3 DISTRIBUTION PANEL (400 AMPERES TO 1200 AMPERES) Protective DEVICE A. General 1. Unit Operating Voltage. The nominal unit operating voltage and configuration shall be as indicated on the drawings. 2. Maximum Continuous Operating Voltage (MCOV). The MCOV shall be greater than 115% of nominal voltage for all products. 3. Operating frequency range shall be Hertz. 4. Surge Rating shall be 80kA per mode 5. Monitoring shall include: As a minimum, this monitoring shall include one set of status monitoring lights that will provide visual indication of voltage present to the SPD for each phase of protection. The lights shall also indicate when suppressor protection has degraded to any value of less than 50%. Status indicator lights that simply indicate the presence of voltage, and provide no indication of performance, will be unacceptable. Additionally, the unit shall include an audible alarm with battery backup, and a set of Form C contacts for remote monitoring. 6. Acceptable Products shall be, no substitutions: a. Liebert #AII Series. b. Current Technology #TG80 Series. B. Physical 1. Enclosure: The specified system shall be provided in a heavy duty NEMA 4 dust-tight enclosure with no ventilation openings. 2. Provide a plastic lexan cover with lock for outdoor applications. C. Electrical 1. Unit shall be UL1449, 3rd edtion (September 29, 2009) Type 1 with a nominal discharge current of 20kA Listed. A SPD that is a UL Recognized component will not be accepted. 2. Each surge suppression and filter element (MOV) shall be individually fused so that a failure of one element and/or fuse shall not affect nor operate any other fuse element. SPD shall have a short-circuit rating of 200kAIC. Devices that accomplish this rating by requiring or providing additional fusing to the SPD system will not be accepted. 3. All fusing elements shall be UL Listed or Recognized as a complete fusing system. 4. Unit shall include solid-state, long-life externally mounted LED visual status indicators that indicate the on-line status and operational integrity of the unit. 5. Unit shall have a Form C summary alarm output contact rated for at least 1 amp at 120VAC for remote annunciation of SPD status. SECTION Page 4 of 7

19 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION D. Performance 1. Rated Single Pulse Surge Current Capacity. The rated single pulse surge current capacity, in amps, for each mode of protection of the unit shall be no less than 80,000 Amps per mode. 2. Tested Single Pulse Surge Current Capacity. Suppression filter systems shall be single pulse surge current tested in all modes at rated surge currents by an industry-recognized independent test laboratory. The test shall include a UL1449 Third Edition surge defined as a 1.2X50 µsec, 6000V open circuit voltage waveform and an 8X20 µsec, 3000A short circuit current waveform to benchmark the unit s suppression voltage, followed by a single pulse surge of maximum rated surge current magnitude with an 8X20 µsec waveform. To complete the test, another UL1449 surge shall be applied to verify the unit s survival. Survival is achieved if the suppression voltage measured from the two UL1449 surges does not vary by more than 10%. 3. Minimum Life Cycle Rating. Per ANSI/IEEE C62.41 and ANSI/IEEE C , Test suppression filter systems in every mode utilizing a 1.2X50 µsec, 20 KV open circuit voltage, 8X20 µsec, 10 KA short circuit current Category C3 bi-wave at one minute intervals without suffering performance degradation of more than 10% deviation of clamping voltage at the specified surge current. Tested life under these conditions shall be no less than 4,000 impulses per mode. 4. UL1449Voltage Protection Rating. All suppression filter system clamping voltages shall be in compliance and listed by UL1449. Maximum listed clamping voltages shall be as follows: a. Unit shall provide maximum UL1449 3rd Edition Voltage Protection Rating (VPR) for 208Y/120 Volt systems as follows: L-N = 600V L-G = 700V N-G = 600V L-L = 900V b. Unit shall provide maximum UL1449 3rd Edition Voltage Protection Rating (VPR) for 480Y/277 Volt systems as follows: L-N = 1000V L-G = 1000V N-G = 900V L-L = 1800V 5. Noise Attenuation. The unit shall be UL1283 Listed in Type 2 locations as an electromagnetic interference filter. The filter shall provide 30dB at 100kHz, 60dB at 500kHz, 40dB at 1MHz, 12dB at 10MHz, per 50 Ohm Insertion Loss Methodology from MIL 220A. The system shall provide up to 120- db insertion loss from 100 khz to 100 MHz when used in a coordinated facility system. 6. Overcurrent Protection. Each suppression element shall be individually fused such that the failure of a single component or the operation of a single fuse element remains isolated and does not render the entire mode, or product, deficient by more than 5%. Fusing shall be present in all modes, including Neutral-to- Ground. The device shall be capable of withstanding the full single pulse surge current capacity for every mode without the operation or failure of overcurrent / fault current protection or fuses. 2.4 BRANCH PANEL (100 amperes to 225 amperes) Protective DEVICE A. General 1. Unit Operating Voltage. The nominal unit operating voltage and configuration shall be as indicated on the drawings. 2. Maximum Continuous Operating Voltage (MCOV). The MCOV shall be greater than 115% of nominal voltage for all products. 3. Operating frequency range shall be Hertz. 4. Surge rating shall be 65kA per Mode 5. Monitoring: Status LED s and Form C contacts. 6. Acceptable Products shall be, no substitutions: a. Current Technology #TG60 Series. b. Liebert #ACV Series. SECTION Page 5 of 7

20 SURGE PROTECTION DEVICES BATON ROUGE, LOUISIANA SECTION B. Physical 1. Enclosure: The specified system shall be provided in a heavy duty NEMA 4 dust-tight, drip-tight enclosure with no ventilation openings. 2. Provide a plastic lexan cover with lock for outdoor applications. C. Electrical 1. Unit shall be UL1449, 3rd Edition (September 29, 2009) Type 1 20kA nominal discharge current Listed. A SPD that is a UL Recognized component will not be accepted. 2. Unit shall include solid-state, long-life externally mounted LED visual status indicators that indicate the on-line status and operational integrity of the unit. 3. Unit shall have a Form C summary alarm output contact rated for at least 1 amp at 120VAC for remote annunciation of SPD status. D. Performance 1. Rated Single Pulse Surge Current Capacity. The rated single pulse surge current capacity, in amps, for each mode of protection of the unit shall be no less than 65,000 Amps per mode. 2. Tested Single Pulse Surge Current Capacity. Suppression filter systems shall be single pulse surge current tested in all modes at rated surge currents by an industry-recognized independent test laboratory. The test shall include a UL1449 Third Edition surge defined as a 1.2 X 50 µsec, 6000V open circuit voltage waveform and an 8X20 µsec, 3000A short circuit current waveform to benchmark the unit s suppression voltage, followed by a single pulse surge of maximum rated surge current magnitude with an 8X20 µsec waveform. To complete the test, another UL1449 surge shall be applied to verify the unit s survival. Survival is achieved if the suppression voltage measured from the two UL1449 surges does not vary by more than 10%. 3. Minimum Life Cycle Rating. Per ANSI/IEEE C62.41 and ANSI/IEEE C , Test suppression filter systems in every mode utilizing a 1.2X 50 µsec, 20 KV open circuit voltage, 8X20 µsec, 10 KA short circuit current Category C3 bi-wave at one minute intervals without suffering performance degradation of more than 10% deviation of clamping voltage at the specified surge current. Tested life under these conditions shall be no less than 2,500 impulses per mode. 4. UL1449 Voltage Protection Rating. All suppression filter system clamping voltages shall be in compliance and listed by UL1449. Maximum listed clamping voltages shall be as follows: a. Unit shall provide maximum UL rd Edition Voltage Protection Rating (VPR) for 208Y/120 Volt systems as follows: L-N = 600V L-G = 700V N-G = 600V L-L = 900V b. Unit shall provide maximum UL1449 3rd Edition Voltage Protection Rating (VPR) for 480Y/277 Volt systems as follows: L-N = 1000V L-G = 1000V N-G = 900V L-L = 1800V 5. Noise Attenuation the unit shall be UL 1283 for type 2 locations Listed as an electromagnetic interference filter. The filter shall provide 30dB at 100kHz, 60dB at 500kHz, 40dB at 1MHz, 12dB at 10MHz, per 50 Ohm Insertion Loss Methodology from MIL 220A. The system shall provide up to 120- db insertion loss from 100 khz to 100 MHz when used in a coordinated facility system. SECTION Page 6 of 7

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features: SECTION 16231 - PACKAGED ENGINE GENERATOR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 3323 - CENTRAL BATTERY EQUIPMENT [for Evanston campus only] PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05 SECTION 16230 - GENERATOR ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Provide factory test, startup by a supplier authorized by the manufacturer, and on-site testing of the system. B. The generator set

More information

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) PART 1 GENERAL 1.01 Scope Furnish and install manual transfer switches (3MTS) with number of poles, amperage, voltage, and withstand

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

performed by City of Virginia Beach Public Utilities

performed by City of Virginia Beach Public Utilities City of Virginia Beach Public Utilities Sanitary Sewer Pump Station Specifications - Amendments Section Sub-Section Name Date Modification 1502 3.01 Pump Station Flow Control 6/24/2014 Add the following

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-26 28 21.00 40 (August 2008) ----------------------------------- Preparing Activity: NASA Superseding UFGS-26 28 21.00 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install automatic transfer switch (ATS) with number of poles, amperage, voltage and withstand current ratings as shown

More information

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx: UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK 40 Dale Street West Babylon, NY 11704 Ph: 631-753-9550 Fx: 631-753-9560 www.unionconnector.com Emergency Automatic Transfer System STANDARD SPECIFICATIONS

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input April 2006 SCR-SCRF Utility & General Industry Switchgear Alarm Systems Engine Starting Railroad Emergency

More information

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution

More information

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 28 21.00 40 (August 2014) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 28 21.00 40 (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION INTERIOR LIGHTING

SECTION INTERIOR LIGHTING SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

This Addendum includes the following changes and clarifications to the Contract Documents:

This Addendum includes the following changes and clarifications to the Contract Documents: August 17, 2018 IFB#: 2018-01 IFB Closing on: August 28, 2018 ADDENDUM NO. FIVE TO THE CONTRACT DRAWINGS AND SPECIFICATIONS FOR THE REFERENCED PROJECT, DATED JULY 11, 2018, AS PREPARED BY GRIMM + PARKER

More information

SECTION (13730) - INTRUSION DETECTION

SECTION (13730) - INTRUSION DETECTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 16 00 (13730) - INTRUSION DETECTION 1. Intrusion Detection Sensors 2. Signal Equipment 3. System Controls 4. Alarm Displays 5. Alarm Indicating

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

SECTION EMERGENCY POWER SYSTEMS

SECTION EMERGENCY POWER SYSTEMS SECTION 16620 EMERGENCY POWER SYSTEMS A. Standby Engine/Generator Systems 1. Installations of stationary engine/generator (e/g) systems shall be designed in strict accordance with ANSI/NFPA 70 - National

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 2416 - PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system. SECTION 480V PACKAGED GENERATOR SYSTEMS 1.01 SCOPE PART 1 - GENERAL A. Provide complete factory assembled EPA certified low emission stand-by generator set equipment compatible for paralleling with the

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

ENGINE GENERATORS AND ACCESSORIES

ENGINE GENERATORS AND ACCESSORIES ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

FLOAT BATTERY CHARGERS

FLOAT BATTERY CHARGERS FLOAT BATTERY CHARGERS UNFILTERED SCR SERIES FILTERED SCRF SERIES SINGLE PHASE INPUT THREE PHASE INPUT Applications for: UTILITY & GENERAL INDUSTRY Switchgear Engine Starting Emergency Lighting Alarm Systems

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF FIRST DRAFT REPORT Document: NFPA 110 (EPS-AAA) Revision Cycle: A2018 Meeting Date(s):

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

A. Product Data: Include rated capacities, furnished specialties and accessories.

A. Product Data: Include rated capacities, furnished specialties and accessories. BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified

More information

16620 EMERGENCY POWER SYSTEMS

16620 EMERGENCY POWER SYSTEMS 16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing piping heat tracing for freeze prevention, domestic hot-water-temperature maintenance, and

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ASCO Series 185 Power Transfer Switches

ASCO Series 185 Power Transfer Switches ASCO Series 185 Power Transfer Switches 24-hour protection no matter when trouble strikes ASCO Series 185 POWER TRANSFER SWITCHES An Automatic Transfer Switch helps prevent... Your business or home from

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-42 22 16.00 40 (August 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-42 22 16.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

STATEMENT OF WORK I. SCOPE OF WORK:

STATEMENT OF WORK I. SCOPE OF WORK: STATEMENT OF WORK Purchase and Installation of Diesel Standby Generator Set and Service Entrance Rated Automatic Transfer Switch for Sewage Treatment Plant Nockamixon State Park (Bucks County) I. SCOPE

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information