Data Bulletin. Hospital Isolated Power Systems. Dual Output Voltage Isolation. Class 4817 INTRODUCTION

Size: px
Start display at page:

Download "Data Bulletin. Hospital Isolated Power Systems. Dual Output Voltage Isolation. Class 4817 INTRODUCTION"

Transcription

1 Data Bulletin June 2002 Nashville, TN, USA Hospital Isolated Power Systems Dual Output Voltage Isolation Panels Class 4817 INTRODUCTION The dual output voltage hospital isolation panel is a single, ungrounded hospital isolation panel that can supply two different output voltages simultaneously. Similar to a standard distribution panel or load center, it can supply both 120 V and 208 V or 120 V and 240 V of ungrounded, isolated, single-phase power using only one isolation transformer. Other hospital isolation panels can supply only one output voltage. Typically, the 208 V or 240 V circuits of the dual output voltage panel supply power to operating room equipment such as mobile X-ray machines or surgical lasers. Simultaneously, the panel s 120 V circuits can supply power to convenience receptacles, surgical lights, X-ray film illuminators, sterilizers, and other 120 V appliances commonly found in operating rooms. This panel is ideally suited as a power supply to power/ground modules and X-ray indicator/receptacle modules, also manufactured by Square D. The Dual Output Voltage Panel is factory equipped with eight 20 A, 2-pole branch circuit breakers for the 120 V applications and is field expandable up to 16 circuits (Square D Catalog number QO220). The 208 V and 240 V application has one main breaker fed from a transformer rated at 15 kva only and two branch breakers (20 A, 2-pole through 60 A, 2-pole). The panel is sized according to the 120 V kva requirements and coordinating the 208 V and 240 V requirements (See Table 2). The panel is designed to supply ungrounded power to only one operating room. Use of the panel to supply power to more than one room may conflict with National Fire Protection Association (NFPA) 99, Standard for Health Care Facilities, paragraph (d) The transformer s overall power rating in the dual output voltage isolation panel is the sum of the two secondary windings. The 208 V and 240 V secondary winding is always rated at 60 A, while the 120 V secondary winding can be rated at 5.0, 7.5, or 10.0 kva. All applications include a primary main circuit breaker as well as secondary main circuit breakers for both windings (208 V and 240 V, and 120 V). The 208 V and 240 V secondary main circuit breaker is always rated at 60 A, while the 120 V secondary is rated to comply with the size rating of the 120 V secondary winding. Figure 1: Dual Output Voltage Isolation Panel

2 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Standard Features June 2002 STANDARD FEATURES The dual output voltage hospital isolation panel offers the following standard features: Primary main circuit breaker Secondary main breaker(120 v) Optional accessories Secondary circuit breaker (Type QO, 2-pole 1 60 A, 208 V) ISO-GARD Line Isolation Monitors Ground receptacles (30 A) Receptacles (208 V, A) Receptacles (120 V, 20 A) NEMA Type 1 enclosure with 4-gauge stainless steel Dual output voltage isolation transformer Figure 2: Features Low leakage, copper-wound, dual output voltage isolation transformer with electrostatic shield manufactured by Square D. One 120 V load center with eight factory-installed 20 A, 2-pole branch circuit breakers, field expandable to 16 circuits. One 208 V and 240 V load center with space for two 10 A, 2-pole through 60 A, 2-pole field-installed branch circuit breakers. NEMA Type 1 enclosure with Type 304 stainless steel trim. Two ISO-GARD microprocessor-controlled line isolation monitors (LIMs) manufactured by Square D. Factory-installed primary and secondary main circuit breakers. Factory-installed, copper reference ground bar. 2

3 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Optional Accessories OPTIONAL ACCESSORIES ADVANTAGES CATALOG NUMBERS Interior Optional accessories include: Panel mounted indicator alarms for the panel s line isolation monitors. Alarms are commonly used when the panel is mounted within the operating room. Panel mounted receptacles. Up to six hospital grade, 120 V, convenience receptacles and up to two 208 V and 240 V receptacles can be mounted on the face of the panel Panel mounted 30 A, green ground jacks for grounding of non-electrical equipment. Advantages of dual output voltage isolation panel: Lower labor costs installation is simpler when one panel can be substituted for two separate panels. Lower material cost one panel rather than two separate panels reduces material costs. No bothersome inter-lock system the dual output voltage panel eliminates the need for interlocks that are common on conventional isolation panels designed for mobile X-ray and laser isolation panels. Lower leakage currents on 208 V and 240 V circuits because branch circuit conductors are shorter, leakage current is reduced. Easier maintenance only one isolation panel needs to be maintained. Less confusion during emergencies all circuit breakers are in one panel and one location rather than two or more panels or locations. To order dual output voltage hospital isolation panels, specify the correct catalog number for the following items: interior trim transformer back box NOTE: The interior, trim, transformer, back box, and optional panel mounted accessories for the LIM must be ordered separately. Only the accessories are optional. The interior catalog number is a combination of codes, which are described in Table 1 on page 4. An example of a completed catalog number for the interior is shown below in Figure 3. Interior Code Numbers (1) (2) (3) (4) (5) (6) (7) (8) Interior Catalog Number DVP 2 B R X D 208 V and 240 V Receptacle # 2 is NEMA Type 6 50R 208 V and 240 V Receptacle # 1 is Hubbell IN V Receptacles Colored Red Six 120 V Receptacles Six 30 A Green Ground Jacks Size Rating of 120 V Transformer Secondary is 7.5 kva Output Voltage is 120 V and 240 V Figure 3: Interior Catalog Numbers Primary Voltage 208 V 3

4 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Catalog Numbers June 2002 To complete a catalog number, fill in the parenthesis from the selections numbered 1 8 in Table 1. Table 1: Interior Catalog Number Selections Selection Number Options Selection Number Options (1) Primary voltage of dual output voltage isolation panel V 240 V 277 V 480 V (5) Number of 120 V power receptacles one two three four five six none (2) Output voltages A B 120 V and 208V 120 V and 240V (6) Type of 120 V power receptacles R I B T L 0 20 A, red hospital-grade duplex (NEMA 5 20R) 20 A, ivory hospital-grade duplex (NEMA 5 20R) 20 A, black hospital-grade duplex (NEMA 5 20R) 20 A, brown hospital-grade duplex (NEMA 5 20R) 20 A, black hospital only, locking-type receptacle (Hubbell #23000HG or equivalent) No 120 V receptacles (3) Size rating of 120 V secondary winding (kva) NOTE: Eight 20 A, 2-pole branch circuit breakers are installed at the factory in the 120 V section of panel s interior. The section is field expandable to 16 branch circuit breakers by ordering additional circuit breakers, Square D catalog no. QO kva 7.5 kva 10.0 kva (7) Configuration of 208 V or 240 V receptacle #1 NOTE: The correct circuit breaker that matches the selected receptacle is installed at the factory in the 208 V or 240 V section of the panel s interior. If no receptacle is selected, the section is field expandable to two branch circuit breakers by ordering additional circuit breakers, Square D catalog no. QO210 through QO260. X A B C D E F G 0 Hubbell #IN16494 (equivalent to Hubbell #25603) NEMA #6-15R NEMA #6-20R NEMA #6-30R NEMA #6-50R NEMA #L5-15R NEMA #L6-20R NEMA #L6-30R No 208 V or 240 V receptacle Installation of circuit breakers rated higher than 60 A voids the UL Listing. (4) Number of 30 A green ground jacks one two three four five six none (8) Configuration of 208 V or 240 V receptacle #2. The correct circuit breaker that matches the selected receptacle is installed at the factory in the 208 V or 240 V section of panel s interior. If no receptacle is selected, the section is field expandable to two branch circuit breakers by ordering Square D catalog no. QO210 through QO260. X A B C D E F G 0 Hubbell #IN16494 (equivalent to Hubbell #25603) NEMA #6-15R NEMA #6-20R NEMA #6-30R NEMA #6-50R NEMA #L6-15R NEMA #L6-20R NEMA #L6-30R No 208 V or 240 V receptacle Installation of circuit breakers rated higher than 60 A voids UL Listing. 4

5 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Catalog Numbers Transformers All transformers for the dual output voltage isolation panels are single-phase only. Table 2: Transformer Catalog Number 120 V Winding Rating (in kva) Primary Voltage Secondary Voltages Catalog Number Recommended Maximum Feeder and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT and 120 DVT Trim Back Box The trim catalog number is DVC. The back box catalog number selections include: Flush back box DVBF Surface back box DVBS H1 H2 X4 X3 X2 X1 120 V 10 kva, 7.5 kva, 208 V or 240V 15 kva or 5 kva Figure 4: Primary 208 V, 240 V, 277 V, or 480 V Total of Both Secondary 20 V, 22.5 V, or 25 V 5

6 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Dimensional Drawing June 2002 DIMENSIONAL DRAWING Dimensions are shown in inches and millimeters Back Front INCHES Millimeters Shaded area denotes conduit entrance Left Side Maxiumum Above Floor Right Side Finished Floor Figure 5: Dimensions of Dual Output Voltage Isolation Panel 6

7 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Electrical Connections ELECTRICAL CONNECTIONS Primary Circuit Breaker Electrostatic Shield H1 H2 X1 X2 X3 X4 Secondary Main Primary Panel is field expandable to 16 secondary branch circuit breakers (QO220) Secondary Main Panel is field expandable to 2 secondary branch circuit breakers (QO) To Ground Bus 208 V Circuit Ground Bus (space for 25, 6-24 A WG including 1 lug for 1/0) 120 V Circuit L1 L2 L3 Ground RS-232 Test Meter LIM Common 12 V Common 12 V Hazard 12 V Safe K1 Safe K1 Common K1 Hazard LIM Terminal Board To Ground Bus L1 L2 L3 Ground RS-232 Test Meter LIM Common 12 V Common 12 V Hazard 12 V Safe K1 Safe K1 Common K1 Hazard LIM Terminal Board To Ground Bus Figure 6: Electrical Connections 7

8 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications June 2002 SPECIFICATIONS Part 1 General Refer to Square D Specification Section at under Specification (SCSI Standards) NOTE: Items in brackets are selections. Choose only one for your specific application Section Includes: A. Dual Output Voltage Hospital Isolation Panels B. Remote Indicator Alarms C. Power/Ground Modules D. Laser/Portable X-ray Receptacles 1.02 References: A. NFPA 70 National Electrical Code, Article 517 B. NFPA 99 Standard for Health Care Facilities C. UL1022 Line Isolation Monitors D. UL1047 Isolated Power System Distribution Equipment E. ANSI/IEEE Standard 602 Electric Systems in Health Care Facilities 1.03 Submittals A. Product Data: Provide ratings, transformer sound level, transformer impedance, transformer voltage regulation, transformer temperature rise, dimensions, knockout sizes and locations, materials, fabrication details, finishes, and accessories. B. Manufacturer s Instructions: Indicate application, conditions and limitations of use stipulated by product testing agency specified under Regulatory Requirements. Include instructions for storage, handling, protection, examination, preparation, and installation of Product Quality Assurance A. Perform work in accordance with National Electrical Contractors Association (NECA) Standard of Installation. B. Maintain [one copy] [_ copies] of this document on site Qualifications A. Manufacturer: 1. Supplier asking consideration as an approved equal shall submit full guaranteed performance data on similar units in service for one or more years. 2. Performance data to be submitted on each size required and received by the engineer no less than ten days before bid due date in order to allow acceptance by addendum. 3. All bids are to be based on specified equipment and show credit to be allowed to the owner if an approved substitute is used Regulatory Requirements A. Conform to current requirements of ANSI/NFPA 70 and NFPA 99. Contractor shall obtain and keep at the job site a current copy of NFPA 99. Contractor shall demonstrate familiarity with NFPA 99 to the specifying engineer. B. Furnish products listed and classified by [UL] [testing firm acceptable to authority having jurisdiction] as suitable for purpose specified as shown. 8

9 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications Part 2 Products 2.01 Manufacturers Dual Output Voltage Hospital Isolation Panels A. Manufacturers: Approved manufacturer for the various components of a complete isolated power distribution system shall be as listed herein. 1. Transformer shall be a shielded, low-leakage, dual output voltage, isolating transformer specifically manufactured for the use in hospital isolated systems, Class 7450 Isolating Transformer manufactured by the Square D Company. 2. Line isolation monitors (LIM) shall be ISO-GARD line isolation monitors (no exceptions) manufactured by Square D Company. 3. Circuit breakers shall be Type QO, QOB, Q1, FAL, or KAL as manufactured by Square D Company. 4. Remote alarm indicator shall be Square D Company Type IA-1C. 5. Power/ground modules shall be Square D Company catalog numbers RM-120-4NI,RMD-120-4NI, GS-120-4NI, RM-50-4NI, RMS-50-4NI, or RMD-50-4NI. 6. Laser/X-ray receptacle shall be Square D Company catalog number XR-IAI. B. Description NOTE: Paragraphs marked with asterisks (*) are alternatives. Select only those alternatives required for your specific application. 1. The panels shall be specifically designed for the purpose of supplying ungrounded power for use in hospital operating rooms. The panel shall consist of a flush- or surface-mounted back box, stainless steel trim, an ungrounded isolation transformer with two separate secondary windings (sized as indicated in the panel schedule or drawings), a primary main circuit breaker (sized in accordance with Article 450-3(b)(1) of NFPA 70), two secondary main circuit breakers, branch 2-pole circuit breakers as shown in the panel schedule or drawings, and two line isolation monitors (LIMs). 2. The LIM used in these units shall indicate, by alarm, when the total hazard current exceeds 5 ma. When the panel is mounted outside of the operating room, a two-station remote indicator alarm unit shall be located in the operating room and connected to the panel supplying power to the circuits in that room. When panel is located within the operating room, the indicator alarms shall be mounted within the cover of the panel. Location of the remote alarms within the operating room is as indicated on the drawings. 3. *A second indicator alarm unit shall be built into an annunciator containing indicator alarm units for all LIMs in the operating suite. This annunciator will be located at the operating room (OR) supervisor s station. 4. Power/ground modules as specified herein shall be used to distribute 120 V ungrounded power throughout the operating room. 5. Combination laser/portable X-ray receptacle with built-in indicator alarm for the LIM shall be used to distribute power for the laser or portable X-ray machine in the operating room. 9

10 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications June Components The following components shall be provided by the manufacturer of the operating room hospital isolation panels as one integral unit. A. Isolation Transformers 1. The transformer shall be copper-wound with an electrostatic shield between the primary and secondary windings. The shield shall be grounded to the enclosure and the reference ground bar in the isolation panel. The electrostatic shield will be designed to prevent direct shorting of the primary winding to the secondary winding, and to reduce the coupling of harmonic distortions between the primary and secondary circuits. 2. The total leakage current to ground from the isolation transformer shall not exceed the values shown in Table 29.2 of UL Regulation to be certified not to exceed 2.5% at 0.8 power factor (PF) at 20 C above the full load continuous operating temperature in accordance with NEMA/ANSI standards. 4. The transformer is to be single-phase, 60 Hz. The isolation transformer shall be specifically designed with two secondary windings and voltages, either 120 V and 208 V or 120 V and 240 V. Refer to panel schedule, drawings, or both for correct primary and secondary voltages. The size rating of the 120 V secondary winding shall be as shown in the panel schedule, drawings, or both. The size rating of the 208 V or 240 V secondary winding shall be capable of supplying 60 A at the rated voltage. The use of isolation transformers with only one secondary winding and taps for the two required voltages will not be accepted. 5. Class H rated insulation shall be used in the manufacture of the transformer and the temperature rise will be limited to 80 C above ambient under full load conditions, when tested in accordance with NEMA/ANSI standards. Transformers must have a 180 C, UL Recognized insulation system. 6. The core shall be of stacked design and securely clamped and bolted. The core and coils shall be internally isolated from the enclosure by means of a suitable vibration dampening system, varnish impregnated, and shall have a final wrap of insulating material to prevent exposure of bare conductors. 7. The design sound level of the completed isolation panel shall not exceed 35 db. Certified sound level reports shall be furnished for each individual unit upon the request of the consulting engineer. B. Circuit Breakers 1. All circuit breakers must be 2-pole with a minimum interrupting capacity of 10,000 A. Panels shall have a maximum capacity of 16 secondary circuit breakers for 120 V equipment and a maximum capacity of two secondary circuit breakers for 208 V or 240 V loads such as lasers or portable X-ray equipment. Refer to the panelboard schedule for quantity and sizes of circuit breakers. All circuit breakers shall be thermal-magnetic type. Thermal-only type circuit breakers will not be accepted. C. Line Isolation Monitors (LIM) 1. The LIMs shall be the ISO-GARD Series D LIMs manufactured by Square D. The panel shall contain two LIMs, one for the 120 V secondary winding and one for the 208 V or 240 V secondary winding. The LIMs shall use microprocessor-based digital signal processing to continually monitor the impedance from all secondary 10

11 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications conductors of the isolated power systems to ground. The LIM shall be capable of measuring all combinations of capacitive and resistive faults including balanced, unbalanced, and hybrid faults. LIMs that internally switch between either line and ground will not be accepted. The LIM shall not contribute more than 15 microamperes to the total hazard current of the system being monitored. 2. The LIMs shall have the following specifications: a. Operating voltage to 265 Vac b. Accuracy % or better c. Alarm level or 5 microamperes (selectable) d. Alarm bandwidth Zero (0) e. Alarm hysteresis (on/off).. 50 microamperes f. Mode Single- or three-phase g. Monitor hazard current microamperes h. Operating frequency or 60 Hz 3. All of the listed LIM specifications shall be contained within one unit and be user selectable, allowing the LIMs to be interchanged from system to system. 4. The LIMs shall incorporate a momentary test switch. When pressed, it shall check and recalibrate the unit. Additionally, the test switch shall perform a complete test of all indicating lamps and meters on the face of the LIM and at any remote indicating stations. 5. The LIMs shall use digital signal processing to determine the hazard current of the system being monitored. The microprocessor within the LIM shall be #MC68HC16Z1 as manufactured by Motorola. The algorithms used to determine the system hazard current shall be preprogrammed into the LIM s microprocessor. At least every 65 minutes, the unit shall recheck its calibration and recalibrate the system to original performance specifications. Additionally, when the LIM s momentary test switch is pressed, an immediate check and recalibration of the LIM shall be performed. 6. If internal components are more than 30% out of original specifications because of aging or failure, the LIM shall notify the user by displaying a unique error code, eliminating the need for periodic manual testing to determine the unit s integrity. LIMs that use analog signal processing technology and/or require manual testing or recalibration will not be accepted. 7. The LIMs shall have an optical infrared LED-type serial port on the face of the unit for transmitting pertinent LIM and isolated power system data directly to a personal computer (PC). The transmission of data shall not require any mechanical or direct electrical connection to the LIM. The protocol of data transmission shall be compatible with all Hewlett Packard palmtop personal computers including Hewlett Packard models HP95LX, HP100LX, and HP200LX. 8. The LIMs shall provide both analog and digital indication of hazard current of the isolated power systems. Digital indication shall be provided by a digital meter and analog indication shall be provided by an LED bar-graph type meter calibrated from 0 (zero) to 160% of the alarm setting of the LIM. LIMs with only analog or only digital indicating will not be accepted. 9. The LIMs shall have a green safe light and red hazard light on the front panel. The red hazard light shall remain illuminated for the duration when the isolated power system hazard current is above the 11

12 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications June 2002 selected alarm level of the LIM. An audible alarm shall be incorporated into the unit and shall activate in conjunction with the red hazard light. The audible alarm shall have high, low, and off settings. A silence button shall be provided on the face of the unit to silence the audible alarm during fault conditions. When the audible alarm is silenced, a yellow indicating light shall illuminate to indicate the audible alarm has been silenced. The red hazard light and yellow silence light shall automatically reset when the fault condition is eliminated. During fault conditions, the red hazard light and all red segments of the LED bar graph shall blink at a constant rate. All lamps are to be long-life LED type. 10. A set of normally open and normally closed contacts, rated 3 A at 120 Vac shall be provided on the LIMs for use with external alarm systems. The LIM shall also provide a 12 Vac output signal rated at 10 VA to power remote indicator alarm units. This 12 Vac output signal shall not increase the hazard current of the system being monitored. Provisions for connection of the remote metering shall also be provided as part of the LIM. These connections shall have the ability to operate either an analog or digital type remote meter. 11. The LIMs shall incorporate a loss-of-ground feature which will activate the audible and visual alarms when connection is lost with the reference ground of the isolated power system being monitored. In addition to activating the alarm, the unit shall display an error code in the digital display of the LIM. 12. All switches, meters, and indicating lamps shall be flush with the face of the LIMs to provide a neat and clean appearance. The entire front face of the unit shall have a polymer overlay that protects the unit from the intrusion of housekeeping cleaning agents. LIMs with exposed fuses, meters, switches, or circuit breakers will not be accepted. 13. The design of the LIM shall consist of two circuit boards interconnected by a ribbon connector. The two boards shall contain all of the unit s electrical components and be mounted in the rear housing of the LIM. A phenolic cover shall complete the assembly. The unit shall not contain any components, such as circuit breakers, meter, switches or indicating lamps, which are mounted on or attached to the front cover of the LIM. Access to the inside of the LIM shall be through the front of the unit, eliminating the need to remove the unit from its mounting position to change any of the settings. Unique fasteners shall attach the front cover of the unit to prevent unauthorized access to the interior of the LIM. 14. The LIMs shall be specifically designed for the connection of two units to one isolation transformer. The units shall not give false readings nor interfere with each other s hazard current measurement process when both are simultaneously connected to one isolation transformer. 15. Dual output voltage isolation panels with only one LIM monitoring both voltages will not be accepted. 16. The LIMs shall be manufactured by Square D Company, UL Component Recognized under UL1022 Standard for Line Isolation Monitors, and UL Recognized as meeting CSA 22.2, the Canadian Standard for Line Isolation Monitors. D. Optional Panel Mounted Power/Ground Module The panel shall be designed to accommodate not more than six 30 A green equipment ground jacks, six 120 V, 20 A hospital-grade power receptacles (either single, duplex, or hospital-only type configuration) and 12

13 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications two 208 V and 240 V, 10 A through 60 A power receptacles for laser or portable X-ray use. Refer to the drawings, panel schedule, or both for exact quantity, color, circuiting, and NEMA configuration of the receptacles. E. Remote Indicator Lamp 1. The remote indicator alarm shall be flush mounted and have a brushed stainless steel front trim. When the hazard current is within the predetermined limit for the circuits being monitored, a constant green light will remain illuminated. When the limit is exceeded, the green light will extinguish, a red indicator will illuminate, and an audible signal will sound. 2. A silencing switch for the audible signal shall be provided. When pressed, it will cause a yellow warning light to illuminate, indicating that the audible signal has been silenced. When the current flow to ground returns to an acceptable level, the unit will automatically reset. The wiring from the LIM to the indicator alarm shall not contribute any leakage current to the isolated system Construction A. Enclosures 1. The enclosure shall be 14-gauge steel which is degreased, phosphatized, primed, and finished with baked enamel paint. The front trim shall be Type 304 stainless steel with a #4 brushed finish and shall completely cover all components of the isolation panel including the LIM and circuit breakers. The enclosure will be flush mounted unless otherwise stated on the plans. The front trim shall have a hinged door, with keyed lock, to allow access to the circuit breakers, the LIM, and to provide for testing. For life support purposes and to prevent unauthorized access to the LIM or circuit breakers, panel trim designs that do not completely cover these items, or do not have a lockable door, will not be accepted. 2. For purposes of infectious bacterial growth control, the front panel trim shall not contain any grille, louver, or opening of any type for ventilation. The isolation panel shall be a totally enclosed nonventilated type design. The panel and transformer shall be so designed that heat generated by the transformer under full load conditions shall not affect the normal operation of the circuit breakers and LIM. The maximum front panel temperature shall not exceed 30 C rise under full load continuous operation. Certification of this temperature test shall be provided to the consulting engineer upon request. The entire section behind the hinged door shall be of a dead front design. All hinges will be concealed. B. Wiring 1. Manufacturer s wiring within all panels shall meet all applicable National Electric Code (NEC) and UL Standards. Low leakage insulation shall be used on all secondary wiring. The total leakage for the isolation panel shall not exceed the values shown in Table 29.1 of UL Total leakage of the manufactured isolation panel shall include the following items: isolation transformer, load center, branch circuit breakers, and any panel mounted accessories. Field wiring by the installing contractor shall not be included. 2. Upon request of the specifying engineer, the panel manufacturer shall provide certified test data on each individual panel as to maximum leakage of each complete assembly. 13

14 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications June Accessories A. Remote Power /Ground Cables 1. For the correct location and quantity of remote modules, refer to the drawings. The module back box shall be fabricated of mild steel. When the module is surface mounted, the back box shall have a finished appearance, all seams are to be welded, and the weld seams ground smooth with the outer surfaces of the box. Boxes shall be degreased, primed, and receive a final coat of baked enamel. The trim shall be 14-gauge, Type 304 stainless with a #4 brushed finish. 2. The only exposed screws on the trim of the module shall be the four screws holding the trim to the back box. All receptacles shall be firmly attached with concealed fasteners that do not appear on the surface of the trim. The ground bus contained in these modules shall be of heavy copper bar, and it shall contain lugs suitable for connection of up to #1/0 wire. These are for connection and grounding of nonelectrical conductive surfaces in the area, as well as connection of the ground terminal on all power receptacles within the module or in the area. All wiring in the module shall be color-coded in compliance with the NEC and NFPA 99. The module shall be capable of containing 30 A green ground jacks, hospital-grade duplex receptacles, or locking hospital-type receptacles. Modules shall be mounted between 42 and 60 inches above finished floor. B. Combination laser/portable X-ray Receptacle and C Indicator Alarm 1. Combination laser/portable X-ray receptacle and Indicator Alarm shall be Square D catalog no. XR-IAI, with back box catalog no BB. The unit shall contain a 60 A receptacle for laser or portable X-ray use and indicator alarm connected to the LIM in the isolation panel that is monitoring the 208 V or 240 V portion of the isolation transformer. The receptacle shall be configuration equivalent to Hubbell # Entire unit shall be mounted between 42 and 60 inches above the finished floor. Part 3 Execution 3.01 Installation A. The contractor shall furnish and install the dual output voltage isolation panels, power/ground modules, laser receptacles, and portable X-ray receptacles in the locations and elevations as indicated on the drawings. Location and elevation of these items cannot be changed without written permission from the specifying/consulting electrical engineer and architect. B. The panel(s) shall be factory wired and tested and include a shielded lowleakage isolation transformer, primary and secondary circuit breakers, LIMs, receptacles, ground jacks, and ground bars. C. To help prevent bacterial growth, back boxes for panels, accessories, switches, receptacles, and fixed equipment shall be cleaned of any accumulated dirt, dust, plaster, and debris before installation of front trims. D. The contractor shall wire all external receptacles to the panels using copper stranded conductor having a cross-linked polyethylene insulation or equivalent with a dielectric constant of 3.5 or less. Under no circumstances shall wire pulling compound be used when pulling the conductors for the branch circuits. All wiring shall be color-coded in accordance with the applicable paragraphs of the current editions of the NEC and NFPA 99. All branch circuit conduit runs shall be installed using the shortest path possible to the intended load or receptacle to minimize leakage currents. Contractor shall measure and demonstrate compliance with the requirements of Impedance of Isolated Wiring as described in Chapter 3 of NFPA 99 (no exceptions). The contractor shall submit wire 14

15 June 2002 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Specifications manufacturer s product data sheets to the specifying engineer for approval before installation of any isolated power branch circuit conductors. E. Connecting conduits shall not be used to support the panels, remote indicators, power/ground modules, or laser/portable X-ray receptacles. F. Steel support members as required shall be provided and installed by the electrical contractor for mounting the panels. G. All equipment shall be aligned, leveled, and securely fastened to the support members. H. Any unused conduit opening or other unused holes in the back boxes shall be properly closed by the contractor before final owner acceptance Testing By The Manufacturer A. The contractor shall include the cost of, and make all arrangements for, testing all underground isolated systems in the hospital by a qualified factory technician provided by the manufacturer of the isolation systems. The testing shall include a complete inspection of all connections and materials used. The contractor shall be prepared to demonstrate to the factory technician that proper polarity was observed, and installation practices were in accordance with the drawings and specifications for these systems. B. The factory technician shall check and record system current leakages. The factory technician shall further simulate faults on the isolated system of a magnitude high enough to bring the total system leakage, which the LIM detects, above the calibrated point, thus verifying correct operation of the LIM. The faults simulated shall be combinations of resistive and capacitive faults. C. The factory technician shall check the resistance between the ground point of each receptacle and the reference point, and it shall be less than 0.1 ohms. The voltage potential difference between any exposed conductive surfaces in the patient vicinity shall be checked, the difference to be no more than 40 millivolts. These tests are required by NFPA 99 for new construction areas. D. The factory technician shall instruct the hospital maintenance staff in the use of the following: 1. The panel and LIM as a leakage measuring device 2. How instrument leakage can be measured by use of the LIM 3. How to perform leakage tests E. The technician shall also test the system impedance of the entire isolated power system to ensure compliance with the applicable sections in Chapter 3 of NFPA 99. The measured system impedance shall become part of the permanent logged records of each panel. F. After all tests are complete, a letter shall be given to the hospital and the consulting engineer. The letter shall state that the system conforms with all codes, good installation practices, and the specifications. G. Upon completion of all tests, the factory technician shall meet with hospital medical and maintenance staff to thoroughly explain the operation of the equipment installed, and the need and procedure for periodically testing and logging test results. The technician shall furnish log books to the maintenance department, enter the first readings of all panels in these log books, and clearly instruct the hospital maintenance staff how to enter future readings. H. All questions from the hospital staff shall be answered completely and thoroughly at this time. The consulting engineer shall be notified of the dates and times of all tests so the consulting engineer may witness any of the tests or meetings conducted by the factory technician. 15

16 Hospital Isolated Power Systems, Dual Output Voltage Isolation Panels Data Bulletin June 2002 Square D Company 1010 Airpark Center Drive Nashville, TN SquareD ( ) Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. June 2002 Replaces 4817PD9601 dated 10/96. 16

Isolated Power Panels Line Isolation Monitor (LIM) Remote Indicators/Displays Accessories 15-6

Isolated Power Panels Line Isolation Monitor (LIM) Remote Indicators/Displays Accessories 15-6 Table of Contents Section Medical Products Operating Room Isolated Power Panel (see page -2) Isolated Power Panels -2 Operating Room Panels -2 ICU/CCU Panels -2 Controlled Panels -3 X-ray and Laser Receptacles

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

Isolated Power Panels Duplex Panels Surgical Facility Panels Dual Output Voltage Panels Accessories 16-6

Isolated Power Panels Duplex Panels Surgical Facility Panels Dual Output Voltage Panels Accessories 16-6 Table of Contents Section Isolated Power Panels -2 Operating Room Panels -2 ICU/CCU Panels -2 Controlled Isolation Power Panels (For X-ray and Laser Receptacles) -2 Duplex Panels -3 Duplex Power Panels

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

ISOLATED POWER ACCESSORIES

ISOLATED POWER ACCESSORIES ISOLATED POWER ACCESSORIES THE POWER BEHIND OPERATING ROOM SAFETY MASTER GROUND MODULES WITH CUSTOM BACK BOXES INCLUDED MAKE THE RIGHT CONNECTION WITH PG LIFELINK ISOLATED POWER ACCESSORIES These units

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

Schneider Electric ibusway for Data Center: Schneider Electric Powerbus Plug-In Busway

Schneider Electric ibusway for Data Center: Schneider Electric Powerbus Plug-In Busway Schneider Electric ibusway for Data Center: Schneider Electric Powerbus Plug-In Busway THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT.

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Isolated Power Systems Equipment

Isolated Power Systems Equipment 2 Isolated Power Systems Equipment For Hospitals and Critical Care Areas Brochure NAE2091010 / 10.2012 BENDER Isolated Power System Equipment Isolated Power System with Line Isolation Monitor for hospitals

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 3323 - CENTRAL BATTERY EQUIPMENT [for Evanston campus only] PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels B. Wire and cable markers C. Conduit markers 1.2 REFERENCES A. NFPA 70 - National Electrical

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) PART 1 GENERAL 1.01 Scope Furnish and install manual transfer switches (3MTS) with number of poles, amperage, voltage, and withstand

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications:

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications: CONTROLLER CABINETS, POLE MOUNTED - Item No. Special Provision No. 682S27 June 2017 1. SCOPE This Special Provision covers the requirements for the installation of pole mounted controller cabinets and

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

Data Bulletin. Determining the Cause of AFCI Tripping Class 760

Data Bulletin. Determining the Cause of AFCI Tripping Class 760 Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document

More information

Line Isolation Monitor (LIM) LIM2000plus

Line Isolation Monitor (LIM) LIM2000plus Line Isolation Monitor (LIM) LIM2000plus for Single and Three Phase Systems TDB207005usa/10.2008 BENDER Group Line Isolation Monitor LIM2000plus for Single and Three Phase Systems LIM2000plus Device features

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL)

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) SECTION 27 52 23 HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) PART 1 - GENERAL 1.1 SECTION INCLUDES A. Basic System Requirements B. Stations C. Master Stations/Consoles D. Annunciators,

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADP Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR 737-4787

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

Fax (724) Main St.; P. O. Box 248 West Middlesex, PA IMPORTANT NOTICE

Fax (724) Main St.; P. O. Box 248 West Middlesex, PA IMPORTANT NOTICE Phone (724) 528-9559 Cimco Electronics, Inc. Fax (724) 528-1108 26 Main St.; P. O. Box 248 West Middlesex, PA 16159 Oct., 2002 IMPORTANT NOTICE Dear Customer, We would like to make you aware of a few hardware

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install automatic transfer switch (ATS) with number of poles, amperage, voltage and withstand current ratings as shown

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S Revised 04/13/16 SPECIFICATIONS - DETAILED PROVISIONS Section 17210 - Magnetic Flowmeters C O N T E N T S PART 1 - GENERAL... 1 1.01 GENERAL REQUIREMENTS... 1 1.02 PROJECT SPECIFIC REQUIREMENTS... 1 1.03

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on

More information

DGC-500 DIGITAL GENSET CONTROLLER

DGC-500 DIGITAL GENSET CONTROLLER DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized

More information

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

PowerWave 2 Busway System

PowerWave 2 Busway System PowerWave 2 Busway System Guide Specifications (Revision 004, 11/17/2017) 1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening,

More information

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADD MKIII Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 2416 - PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS SECTION 275116 - PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Preamplifiers. 2. Power amplifiers. 3. Microphones. 4. Control console. 5. Loudspeakers.

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM SECTION 40 71 66 ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM PART 1-GENERAL 1.01 SUMMARY A. Ultrasonic clamp-on flow measurement system designed for non-intrusive external to pipe measurement

More information

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) System for preventing frost heave in freezers, cold rooms and ice arenas with temperature control, monitoring,

More information

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg. WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1 GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive

More information

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire

More information