Case 8 Basic Performance of Screw Compressor

Size: px
Start display at page:

Download "Case 8 Basic Performance of Screw Compressor"

Transcription

1 Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually the bare rating of the compressor without any discharge and suction penalties, not even include the pressure drops of the standard option of the discharge valve, discharge check valve, suction valve suction strainer and etc. In order to understand the basic performance of the screw compressor, it is best to know the performance table published by the compressor manufacturer and make the compressor selection by using these performance table and curves. The followings are three different inquiry examples; each requires using the performance table to make screw compressor selection, by compare the selection results, it shall provide a better understanding of the basic performance of the screw compressor given by the manufacturer. Inquiry No. 1: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, power supply. Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. 10ºF liquid subcooling in condenser. No economizing is allowed. 10ºF suction superheat. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Inquiry No. 2: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, power supply.

2 Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. Flash type economizing is used. 10ºF suction superheat. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Inquiry No. 3: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, power supply. Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. Flash type economizing is used. 20ºF suction superheat. Discharge external piping pressure drop is 3.7 Psi. External suction piping pressure drop is 1.3 Psi. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Compare the compressor sizes, power consumptions and BHP/TR for the above three inquiries of 1.0, 2.0 and 3.0: Compressor Size Selected Power Consumption BHP BHP/TR Inquiry No. 1 Inquiry No. 2 Inquiry No. 3 No Economizing No ext. pres. drop With economizing No ext. pres. drop With economizing With ext. pres. drops

3 Related Technical Data and Engineering Information for the Case: Figure 8-1 Performance Table for WB-II-222E Compressor R-717 (Model with Economizer)

4 Figure 8-2 Performance Table for WB-II-270 Compressor R-717 (Model without Economizer)

5 Figure 8-3 Performance Table for WB-II-270E Compressor R-717 (Model with Economizer)

6 Figure 8-4 Performance Table for WB-II-316 Compressor R-717 (Model without Economizer)

7 Figure 8-5 Performance Table for WB-II-316E Compressor R-717 (Model with Economizer)

8 Figure 8-6 Performance Table for WB-II-399 Compressor R-717 (Model without economizer)

9 Figure 8-7 Typical Part Load Power Input Constant Condensing Temperature for High Stage Compressor

10 Figure 8-8 Typical Part Load Power Input with Falling Condensing Temperature for High Stage

11 Figure 8-9 Standard Pre-Lube System Limit for High Stage

12 Clarifications for Performance Ratings of WB-II Compressor Units 1.0 Standard Conditions for the High Stage Ratings: 2.0 Selection Procedure for High Stage Compressors: 3.0 Condenser Liquid Subcooling Correction Factors for High Stage Compressors:

13 4.0 Suction Superheat Correction Factors for High Stage Compressors:

14 Cogitation: 1.0 Inquiry No. 1: Refrigeration capacity: 252 TR Saturated condensing temperature: 105 F (CT) Saturated suction temperature: -15 F (Same as ET) Refrigerant: R-717 Power compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. 10 F Liquid subcooling in condenser. 10 F Suction superheat. No economizing. This shall be a standard rating for high stage compressor except that the compressor is driven by a 50 Hz motor at 2,950 RPM compressor speed. (See No. 1 and No. 2 of the Clarifications for Performance Ratings of WB Compressors): Capacity and power consumption correction factor is Converting the capacity to 60 Hz, 3,550 RPM compressor speed rating, it shall be 252/0.833 = TR. From the compressor performance table Figure 8-6, compressor without economizer: WB-II-399 at CT 105 F and ET of -15 F at 60 Hz: Capacity Power consumption = TR = BHP Correction Factor Capacity and power consumption is for 50 Hz of 2,950 RPM compressor speed: Corrected Capacity = x Corrected Power consumption = x = TR = BHP At the rated capacity of 252 TR as specified, the compressor is actually at partial load; refer to Figure 8-7, the partial load power input with constant condensing temperature at evaporative temperature of 15 F, the power consumption is calculated as the following: Percent of capacity = (252/299.7) = The power consumption correction factor = 0.88 Therefore, power consumption at 252 TR is calculated:

15 = x 0.88 = BHP Conclusion: Compressor selected: Capacity at rated conditions: Power consumption: WB-II TR 608 BHP 2.0 Inquiry No. 2. Refrigeration capacity: 252 TR Condensing temperature: 105 F Evaporative temperature: -15 F Refrigerant: R-717 Power compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. 10 F Suction superheat. Flash type economizing is used. Capacity Correction Factor for 0 F liquid subcooling for condenser: (See No. 3 of the Clarifications for Performance Ratings of WB Compressors): S.C.C.F. = 1 + (S.C F) x = 1 + (0 10) x = Correction Factors for 50 Hz of 2,950 RPM compressor speed: Capacity Correction Factor: Power Consumption Correction Factor: The capacity of the compressor at 60 Hz 252 = = TR x From the Figure 8-5, the standard ratings for WB-II-316E compressor, the compressor model with economizer at condensing temperature of 105 F and evaporative temperature of -15 F at 60 Hz:, the capacity and power consumption for the compressor are as the following:

16 Capacity Power consumption = TR = BHP Correct the capacity and power consumption for 50 Hz operation: Corrected Capacity = x x Corrected Power consumption = x = TR = BHP At the rated capacity of 252 TR as specified, the compressor is actually at partial load; refer to Figure 8-7, the partial load power input with constant condensing temperature at evaporative temperature of 15 F, the power consumption is calculated as the following: Percent of capacity = (252/275.6) = The power consumption correction factor = 0.93 Therefore, power consumption at 252 TR is calculated: = x 0.93 = BHP Therefore: Compressor selected: Capacity at rated conditions: Power consumption: WB-II-316E 252 TR 553 BHP 3.0 Inquiry No. 3 Refrigeration capacity: 245 TR Condensing temperature: 105 F Evaporative temperature: -15 F Refrigerant: R-717 Power , compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. 20 F Suction superheat. Flash type economizing is used. Discharge external piping pressure drop is 3.7 Psi. External suction piping pressure drop is 1.3 Psi.

17 The condensing pressure at 105 F is Psig, discharge external piping pressure drop is 3.7 Psi. Compressor discharge pressure: = PSI = PSIG The saturated evaporative pressure at 6.2 F is 6.2 Psig, the external piping pressure drop is 1.3 Psi Compressor suction pressure: = PSI = 4.9 PSIG From the compressor performance table of Figure 8-5, model with economizer: WB-II-316E at condensing pressure of Psig and suction pressure of 4.9 Psig: Capacity Power consumption = TR = BHP Correction for 50 Hz of 2,950 RPM compressor speed: Capacity Correction Factor: Power Consumption Correction Factor: Capacity Correction Factor for 0 F liquid subcooling for condenser: (See Selection Guide, Rule No. 3: S.C.C.F. = 1 + (S.C F) x = 1 + (0 10) x = From No. 4 of the Clarifications for Performance Ratings of WB Compressors, Suction Superheat Correction Factors for for 20 F suction superheat: 1 SHCF = (S.H. 10 F) x (0.0027) 1 = (20 10 F) x (0.0027) = Corrected capacity = x x x = TR

18 Corrected Power consumption = x Therefore: Compressor selected: Capacity at rated conditions: Power consumption: = BHP WB-II-316E 252 TR 587 BHP Comparisons: Compare the compressor sizes, power consumption and BHP/TR for the above Inquiries of 1.0, 2.0 and 3.0: Question No. 1 Question No. 2 Question No. 3 No economizing No ext. pres. drop With economizing No ext. pres. drop With economizing With ext. pres. drop Compressor Size Selected WB-II-399 WB-II-316E WB-II-316E Power Consumption BHP BHP/TR Conclusion; (A) (B) (C) (D) Inquiry No. 1: The compressor is without economizer. The compressor is larger and having higher power consumption, even no external piping pressure drops are included. Inquiry No. 2 is the compressor with economizer, but, without external piping pressure drops being considered. The selection results in smaller size compressor and lower power consumption than the Inquiry No. 1. The compressor size of Inquiry No. 3 has higher power consumption than the Inquiry No. 2, because external piping drops and superheat are included in the operating conditions; yet the compressor size and the power consumption are smaller than the compressor for Inquiry No. 1. The operating conditions for Inquiry No. 1 and No. 2 are idea cases; it does not reflect the actual working condition. In an actual system design, discharge, suction external piping pressure drop and suction superheat must be included.

Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger

Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger Copy Right By: Thomas T.S. Wan ) Sept. 17, 2010 All Rights Reserved Case Background: A screw refrigeration system was originally

More information

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to

More information

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case: Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool

More information

Copy Right By: Thomas T.S. Wan

Copy Right By: Thomas T.S. Wan Chapter 10 System Balancing Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved The major components of a refrigeration system are the compressor, condenser and the evaporator. These

More information

Partial Load Performance Of Refrigeration System

Partial Load Performance Of Refrigeration System Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,

More information

Chapter 4 Compressors Overview & System Annual Power Consumption

Chapter 4 Compressors Overview & System Annual Power Consumption Chapter 4 Compressors Overview & System Annual Power Consumption Copy Right By: Thomas T.S. Wan 温 Sept. 3, 2008 All rights reserved (Cor. 07-08-12) Compressor is the heart of the refrigeration system.

More information

Case 13 Food Storage & Processing Center

Case 13 Food Storage & Processing Center Case 13 Food Storage & Processing Center Copy Right By: Thomas T.S. Wan ( ) Feb. 2, 2002 All Rights Reserved Case Background: The refrigeration system is for a food processing and storage facility. The

More information

Refrigerant Cycle. Performance Data 1) Electric. Acoustic Pressure Level. Compressor. Connections, Dimensions

Refrigerant Cycle. Performance Data 1) Electric. Acoustic Pressure Level. Compressor. Connections, Dimensions TECHNICAL DATA SHEET HP08L-M-WEB Performance Data 1) A-7W35 A2W35 A10W35 A2W50 Heating capacity 8,67 kw 11,14 kw 14,91 kw 9,87 kw Cooling capacity 6,16 kw 8,58 kw 12,33 kw 6,43 kw Input 2,51 kw 2,56 kw

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Figure 1: Schematic of internal heat exchanger vapor-injection cycle Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor

More information

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed

More information

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1) Table 1. European Reciprocating Chiller (CR1). Point Type Description

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

FOR SERVICE TECHNICIAN S USE ONLY

FOR SERVICE TECHNICIAN S USE ONLY F SERVICE TECHNICIAN S USE ONLY NOTE: This sheet contains important Technical Service Data. Tech Sheet Do Not Remove Or Destroy DANGER Electrical Shock Hazard Only authorized technicians should perform

More information

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Executive Summary. Number of Low Number of High Number of Faults , Number of OK Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS THE FIVE W s WHO: WHAT: WHERE: WHY: SYSTEMES LMP MECHANICAL SUB-COOLING I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS WHEN: TIME LAPSE May 2013 to May 2014 Système LMP`s

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Daikin VRV Service & Troubleshooting

Daikin VRV Service & Troubleshooting Daikin VRV Service & Troubleshooting Participant Guide EGVUSE09-07C EDUS 39-600 - F3 Engineering Data Engineering Data VRV Systems Basic Operation Guide Engi- DAIKIN AC (AMERICAS), INC. DACA EGVUSE09-07C

More information

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE INSTRUCTIONS AND COMPETITION DETAILS INSTRUCTIONS ET DÉTAILS DU CONCOURS REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE 1. Test Project Details This

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This

More information

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc. The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative

More information

Check valve Types NRV and NRVH

Check valve Types NRV and NRVH Check valve s NRV and NRVH NRV and NRVH can be used in liquid. suction and hot gas lines in refrigeration and air conditioning plant with HCFC. HFC and HC flammable refrigerants. The valves ensure the

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT Service Facts Split System Heat Pump 4A6H5042G1000A CAUTION IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this

More information

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS Cooling Capacity from 115,000 to 670,000 Btu/hr Btu/hr Smartwise Innovations... Towards Green, Quality & Reliability Solutions SERIES INTRODUCTION

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet Thermostatic Expansion valves, type A/AE REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type A/AE Contents Page Introduction... Features... Standard range... Technical

More information

Control of FGB (Flash Gas Bypass) in Start-Up and Transients. Mr. Nemanja Dzinic, Pega Hrnjak CTS, USA & MPG-KGH d.o.o., Serbia

Control of FGB (Flash Gas Bypass) in Start-Up and Transients. Mr. Nemanja Dzinic, Pega Hrnjak CTS, USA & MPG-KGH d.o.o., Serbia Control of FGB (Flash Gas Bypass) in Start-Up and Transients Mr. Nemanja Dzinic, Pega Hrnjak CTS, USA & MPG-KGH d.o.o., Serbia Background Microchannel evaporators widely used in MAC systems and increasingly

More information

Checking the Charge on a Heat Pump in the Winter

Checking the Charge on a Heat Pump in the Winter Checking the Charge on a Heat Pump in the Winter When you ask many people nowadays how to check the charge on a heat pump during low outdoor temps they will say that you need to weigh in and weigh out

More information

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/ 1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5

More information

Sporlan Valve Division Parker Hannifan/CIC Group

Sporlan Valve Division Parker Hannifan/CIC Group www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves

More information

Thermostatic expansion valves for ammonia Type TEA

Thermostatic expansion valves for ammonia Type TEA Data sheet Thermostatic expansion valves for ammonia Type TEA Thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. Injection is controlled by the refrigerant superheat.

More information

JCseries EVAPORATIVE CONDENSER. engineering data

JCseries EVAPORATIVE CONDENSER. engineering data JCseries EVAPORATIVE CONDENSER engineering data Recold JC Series Evaporative Condenser Contents 2 Construction... 3 Schematic... 4 Engineering Data... 5 Selection Procedure... 6-9 Multi-Circuited Selection

More information

Split System Heat Pumps

Split System Heat Pumps Split System Heat Pumps Split System Heat Pumps 7 1/2-20 Tons - 60 Hz Air Handlers 5-20 Tons - 60 Hz SSP-PRC001-EN Introduction Split System Heat Pump Units... Designed With Your Needs In Mind. The Trane

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/ Service Facts Split System Heat Pump 4TWB4024E1000A IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit.

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

Refrigerant Glide and Effect on Performances Declaration

Refrigerant Glide and Effect on Performances Declaration Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential

More information

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability ETS Colibri brings to the market one of a kind, uniquely designed electric expansion valve. Innovative Design

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

Refrigerants and lubricants

Refrigerants and lubricants Refrigerants and lubricants GENERAL INFORMATION When choosing a refrigerant, different aspects must be taken into consideration: Legislation (now and in the future) Safety Application envelope in relation

More information

A new concept at refueling CNG stations

A new concept at refueling CNG stations A new concept at refueling CNG stations The Aspro SCA-50 compressors concentrate in one single product all the functions of a traditional refuelling station, allowing to compress, store and deliver CNG

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01

More information

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Pump technology: Improved energy efficiency in refrigeration plants. Dr. R. Krämer

Pump technology: Improved energy efficiency in refrigeration plants. Dr. R. Krämer Technical Report Improved energy efficiency in refrigeration plants According to the European EDL directive (final energy efficiency and energy services), 9 % energy savings over a nine-year-period in

More information

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES Service Facts Split System Heat Pump 4A6H5049E1000B IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit.

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

RSMV Technical Guide

RSMV Technical Guide RSMV Technical Guide TABLE OF CONTENTS OVERVIEW... 4 Features and Applications... 4 Module Dimensions... 5 INSTALLATION & WIRING... 6 Input Wiring... 6 Suction Pressure Sensor...6 Head Pressure Sensor...6

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Chillers. Technical Data. EWYD-BZ 250~580 kw

Chillers. Technical Data. EWYD-BZ 250~580 kw Chillers Technical Data A i r C o o l e d C h i l l e r w w w. d a i k i n. e u EWYD-BZ 250~580 kw Daikin Europe N.V. About Daikin Daikin has a worldwide reputation based on over 80 years experience in

More information

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons 007-014 Single- Package Rooftop Units - 50 Hz 6 to 12 Nominal Tons Product Data Single package rooftop cooling units with electric heat option. Compact, horizontal discharge units (vertical discharge option),

More information

FOR SERVICE TECHNICIAN S USE ONLY

FOR SERVICE TECHNICIAN S USE ONLY FOR SERVICE TECHNICIAN S USE ONLY NOTE: This sheet contains important Technical Service Data. Tech Sheet Do Not Remove Or Destroy DANGER Electrical Shock Hazard Only authorized technicians should perform

More information

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 Due to continuous product improvement, specifications are

More information

Liebert CRV Warranty Inspection Check Sheet

Liebert CRV Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation

More information

Tube-in-tube heat exchanger Type HE

Tube-in-tube heat exchanger Type HE MAKING MODERN LIVING POSSIBLE Data sheet Tube-in-tube heat exchanger Type HE Tube-in-tube heat exchanger type HE is used primarily for heat transfer between the liquid and suction lines of the refrigeration

More information

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw) Product Data 38AH024-134 Commercial Air-Cooled Condensing Units 50/60 Hz 20 to 130 Nominal Tons (63 to 390 Nominal kw) a38-4143ef 38AH044-134 These dependable split systems match Carrier s 40RM or 39 Series

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

The Saturation process

The Saturation process SOUTH METROPOLITAN TAFE WA The Saturation process Dennis Kenworthy 8/5/2016 A student study guide to measuring and interpreting the saturation process of refrigeration and air-conditioning equipment System

More information

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Compact, Self-Contained unit that offer low installation cost plus dependable performance. 0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water

More information

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1 We ve looked at VFDs on Evaporators and compressors, what is

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE Service Facts Customer Property: Contains wiring and service information. Please retain. WC*240-SF-1H Library Service Literature Product Section Unitary Product Package Air Conditioner Model WC* Literature

More information

THERMOSTATIC EXPANSION VALVES Part 1

THERMOSTATIC EXPANSION VALVES Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 1 Revised by Loren Shuck, CMS INTRODUCTION The thermostatic expansion valve (frequently

More information

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127. Product Data GEMINI 38AKS028-044 Commercial Air-Cooled Split Systems 50/60 Hz 25 to 40 Nominal Tons (82.8 to 127.0 kw) These dependable split systems match Carrier s indoor-air handlers with outdoor condensing

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Danfoss scroll compressors SH- In parallel installation

Danfoss scroll compressors SH- In parallel installation MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll compressors SH- In parallel installation 50 Hz - 60 Hz - R410A www.danfoss.com CONTENTS General overview...4 Benefits... 4 Scope...

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Refrigeration/Troubleshooting Manual

Refrigeration/Troubleshooting Manual Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 P/N: 2300100910 Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information