R E P O R T W R G D I N E N

Size: px
Start display at page:

Download "R E P O R T W R G D I N E N"

Transcription

1 R E P O R T W R G D I N E N Test laboratory Test object Customer Scope of assignment Date of receipt of test object TÜV SÜD Industrie Service GmbH Center of Competence for Refrigeration and Air Conditioning Air Conditioning and Ventilation Central ventilation unit with heat recovery type Smarty 2X P of the company SALDA UAB SALDA UAB Ragainės g.100, Šiauliai LT Litauen Tests according to DIN EN : Date: Our reference: IS-TAK3-MUC/ bu Document: wrg443 SALDA Smarty 2X P REPORT EN bukl.docx Test period Test location Expert Munich Nuremberg Thomas Busler / Heiko Mirring Test specification DIN EN : DIN EN ISO 5801: DIN EN 308: This document consits of 9 Pages + 30 Appendices Page 1 of 9 Excerpts from this document may only be reproduced and used for advertising purposes with the express written approval of TÜV SÜD Industrie Service GmbH. The test results refer exclusively to the units under test.. Headquarters: Munich Trade Register Munich HRB VAT ID No. DE Information pursuant to Section 2(1) DL-InfoV (Germany) at Supervisory Board: Karsten Xander (Chairman) Board of Management: Ferdinand Neuwieser (CEO), Dr. Ulrich Klotz, Thomas Kainz Phone: Fax: is-tak@tuev-sued.de TÜV SÜD Industrie Service GmbH Center of Competence für Kälte- und Klimatechnik Klima- und Lufttechnik Ridlerstraße München Deutschland

2 Page 2 of 9 1. Scope of testing The company SALDA UAB ordered tests to be conducted on a ventilation unit with heat recovery type Smarty 2X P in accordance with the standard DIN EN : Description of the ventilation unit type Smarty 2X P The structure of the ventilation unit with heat recovery is pictured in figure 1. Bypass optional el. heater Extract air G4 F7 Outdoor air Supply air Exhaust air Figure 1: Schematic diagram of the central ventilation unit with heat recovery, type Smarty 2X P of the company SALDA UAB Images of the ventilation unit with heat recovery are shown in appendices A. Data pertaining to the tested ventilation unit and its built-in components are listed in appendices B. The operation range declared by the manufacturer of the ventilation unit is limited to new and redeveloped single-family houses. The ventilation unit can be mounted on the floor, a wall or at the ceiling. The mounting can be realized with the additional mounting accessories. Exhaust air condensate can be discharged through an open drainage.

3 Page 3 of 9 3. Procedure of the tests The tests were performed at the test facilities of the Center of Competence for Refrigeration and Air Conditioning of the TÜV SÜD Industrie Service GmbH. The tests comprise the reception inspection, the tightness tests, the ventilation tests, the thermodynamic tests, a cold climate test and acoustic tests. The acoustic tests were performed at the Test lab No. DGA-PL A list of the used measurement equipment is deposited at the test centre Reception inspection The relevant technical data of the ventilation unit were recorded during the reception inspection Leakage test External leakage test The external leakage of the ventilation unit was determined by means of establishing a pressure difference between the interior of the unit and its environment. The measured air volume flow required to maintain the pressure difference constitutes the external leakage Internal leakage test In order to determine the leakage volume flow between the exhaust air / extract air side and the outdoor air / supply air side, the exhaust air / extract air side of the unit were pressurised and a volume flow was supplied to or extracted from the outdoor air / supply air side, so as to keep the differential pressure between the environment and the outdoor air / supply air side at zero. As there is no differential pressure between the environment and the outdoor air / supply air side, the leakage volume flow corresponds to the ingoing or outgoing volume flow which exists when the specified differential pressures are adjusted Ventilation test The ventilation test was conducted with a test chamber in accordance with the standard DIN EN ISO 5801: The air temperature during the test was 21 C +/- 2 K. The measurement of the air flows was done at both airflow directions simultaneously at the same pressure level. The measured air flow curves include the following working points: q min at 50 Pa 0.7 x q vd at 50 Pa q vd at 100 Pa The recorded real electric power consumption values relate to the entire unit and are not corrected by the density of the air. The specific power input of the ventilation unit was related to the mean value of the extract and supply air flow.

4 Page 4 of Filter-bypass leakage By the reception inspection, the filter bypass leakage will be visually checked. The filter and the filter frame shall be constructed in order to achieve an easy change of the filter and a tight fitting of the filter. The tight fitting of the filter shall not be influenced by humidity Thermodynamic test The thermodynamic test was conducted in a double climate chamber. The data pertaining to the incoming and outgoing airflow (temperature, humidity, air volume flow) and the total real electric power consumption of the ventilation unit were recorded at the system boundaries of the central ventilation unit. Hereby the caloric mean temperature 1 was determined in accordance with the standard DIN EN 308: The entrance of the extract air into and the outlet of the exhaust air, as well as the entrance of the outdoor air into and the outlet of the supply air of the ventilation unit, were defined as system boundaries. A scheme of the thermodynamic test setup is shown in Figure 2. Symbols: Group 1 Measuring device Group 2 Measuring device F Volume flow R Recording T Temperature E Electrical Data X Humidity P Static pressure Figure 2: Scheme of the thermodynamic test, 1 The caloric mean temperature describes the mean temperature of the temperature probes at the system boundaries of the unit, which is the basis for the calculation of the energy content of the air flows.

5 Page 5 of 9 The thermodynamic tests were performed at the following conditions: Symbol Condition 1 Condition 2 Outdoor air dry bulb temperature t 21 7 C 2 C Outdoor air wet bulb temperature twb 21-1 C Extract air dry bulb temperature t C 20 C Extract air wet bulb temperature twb C 15 C Here the following air flows and external static pressures were preset: q min 40 m³/h at 50 Pa 0.7 x q vd 142 m³/h at 50 Pa q vd 203 m³/h at 100 Pa 3.6. Cold Climate test The cold climate test was done with an external electrical preheater. The cold climate test was carried out following the thermodynamic test. Here, the outside air temperature, starting from 2 C, is gradually decreased and determines the switch-on temperature frost protection strategy. In addition, the effectiveness of the frost protection strategy was investigated within the scope of a cycle test. The test was carried out with the reference volume flow 0.7 x q vd and under the following conditions: Symbol Condition Outdoor air dry bulb temperature t C Outdoor air wet bulb temperature twb 21 - Extract air dry bulb temperature t C Extract air wet bulb temperature twb C 3.7. Acoustic test The acoustic tests were conducted in a reverberation room. The tests were performed at the reference volume flow and a static pressure of 50 Pa. The radiated sound power of the unit and the sound power of the connecting ducts were measured according to the DIN EN ISO :

6 Page 6 of 9 4. Test results 4.1. Reception inspection The identified relevant technical data of the ventilation unit and its installed components are listed in Appendices B. The visual inspection of the central ventilation unit yielded the following results: - Unit labelling - The unit was equipped with a type plate. - The unit was marked with a CE sign. - The type plate contented no information s about the address of the manufacturer. - Electrical safety - The electrical parts were accessible if the cover of the unit was open. - By opening the unit cover the ventilation unit is not switched off via a contact switch. - Tools are required for opening the unit cover. - Mechanical safety - Rotating parts of the unit were accessible when the unit was open. - Components with hot surfaces were accessible when the unit was open. - The unit will not be cut out by opening the unit cover. - Tools are required for opening the unit cover. - Operation and installation - The unit can operated by control panels of the types Ptouch, Stouch or by Mod Bus gateway (MB Gateway). - With the control panel type Ptouch it is possible to set up further service applications on the ventilation unit. - The Stouch control panel is only used to switch between the four available fan speeds - About the MB Gateway it is possible to adjust the parameters of the device via web browser. This variant was used to conduct the tests. - The device controllers are equipped with four different fan speeds to which different fan voltages can be assigned. - To balance the two air flow rates it is possible to adjust different voltages on the fans. - Maintenance - The filters are situated at the outdoor and extract side. They can be removed over the Filter access panels. - The unit was equipped with a run time based filter control. At the end of the adjustable time interval, the user will be informed through the control panel of the unit.

7 Page 7 of Tightness test The results of the external and internal tightness test are listed in Appendix C. The leakage related to the maximum declared air volume flow of 203 m³/h is: -250 Pa +250 Pa Leakage class external leakage F7 / G4 1.3 % 1.2 % A1 Filtercombination Filtercombination -100 Pa +100 Pa Leakage class internal leakage F7 / G4 0.5 % 0.5 % A1 According to the standard DIN EN : , the leakage class is A Ventilation test The pressure-airflow curves of the exhaust air / extract airside and the outdoor air / supply air side are shown in Appendices D. The values measured in the ventilation test are listed in Appendices E Filter-bypass leakage The tight fitting of the filter was checked by a visual inspection. The material of the filter is water-repellent Thermodynamic test Thermodynamic test points are shown in Appendix F. The measurements and calculated values from the thermodynamic test are listed in Appendices G Cold climate test The tests to describe the behaviour of the ventilation unit in frost protection case were carried out with an external electric preheater. The outdoor air temperature the cold climate strategy was activated was approximately -8.0 C with electric preheating. The cycle tests to verify the effectiveness of frost protection carried out at an outdoor air temperature of approximately -15 C showed that the frost protection strategies are effective. A description of the frost protection strategy is given in Appendix H. Diagrams illustrating the test sequence are shown in Appendix I Acoustic test The results of the acoustic test are shown in Appendix J.

8 Page 8 of 9 5. Summary 5.1. Reception inspection The unit was equipped with a type plate and marked with a CE sign. The type plate provides no information about the address of the manufacturer and the year of production The fans are situated on the exhaust air side and the supply air side. The unit was equipped with a run-time based filter control 5.2. Tightness test The leakage class according to the standard DIN EN : is A Ventilation test The pressure-airflow curves of the exhaust air / extract airside and the outdoor air / supply air side are shown in appendices D. The values measured in the ventilation test are listed in Appendices E Filter-bypass leakage The tight fitting of the filter was checked by a visual inspection. The material of the filter is water-repellent Thermodynamic test For the ventilation unit the following type specific data were determined: (see also Appendices G): Temperature ratio related to supply Air volume flow side η θ,su in % Θ outdoor air = 7 C Θ outdoor air= 2 C q min x q vd q vd Temperature ratio related to Air volume flow exhaust side η θ,exh in % Θ outdoor air = 7 C Θ outdoor air= 2 C q min x q vd q vd

9 Page 9 of 9 Spezific elect. power input p el in Air volume flow W/(m³/h) 2 Θ outdoor air= 7 C Θ outdoor air= 2 C q min x q vd q vd Cold climate test The outdoor air temperature the cold climate strategy was activated was approximately -8.0 C with electric preheating. The cycle tests to verify the effectiveness of frost protection carried out at an outdoor air temperature of approximately -15 C showed that the frost protection strategies are effective. 5.7 Acoustic test The determined acoustical values are shown Appendix J. Center of Competence for Refrigeration and Air Conditioning Head of Laboratory Expert Andreas Klotz Thomas Busler Appendices Appendices A1 to A16 Appendices B1 to B3 Appendix C Appendices D1 and D2 Appendices E1 and E2 Appendix F Appendix G1 and G2 Appendix H Appendix I Appendix J Images of the test sample Data pertaining to the tested unit Results of the tightness tests Pressure-airflow curves Measurements from the ventilation test Thermodynamic test points Measurements and calculated values from the thermodynamic test Description of the cold climate strategy Diagram of the cold climate test Results of the acoustic tests 2 To determine the specific power input, the average of the supply and extract air flow rate was used.

10 Appendix A1 Images of the test sample Figure A-1: Drawing of the ventilation unit

11 Appendix A2 Images of the test sample Supply Extract Outdoor Exhaust Figure A-2: Front view of the ventilation unit Outdoor Exhaust Figure A-3: Bottom of the ventilation unit

12 Appendix A3 Images of the test sample Extract Supply Figure A-4: Top of the ventilation unit Figure A-5: View of the ventilation unit without front cover

13 Appendix A4 Images of the test sample Figure A-6: View of the ventilation unit without front cover, filter and drain Figure A-7: View of the ventilation unit without front cover, filter, drain and heat exchanger

14 Appendix A5 Images of the test sample Figure A-8: View of the ventilation unit without front cover, filter, drain and heat exchanger Figure A-9: Front Cover of the ventilation unit

15 Appendix A6 Images of the test sample Figure A-10: outdoor air filter (class F7) of the ventilation unit Figure A-10: extract air filter (class G4) of the ventilation unit

16 Appendix A7 Images of the test sample Figure A-12: Supply air fan of the ventilation unit Figure A-13: Type plate of the supply fan of the ventilation unit

17 Appendix A8 Images of the test sample Figure A-14: Exhaust air fan of the ventilation unit Figure A-15: Type plate of the exhaust fan of the ventilation unit

18 Appendix A9 Images of the test sample Figure A-16: Drain of the ventilation unit Figure A-17: Heat exchanger of the ventilation unit

19 Appendix A10 Images of the test sample Figure A-18: Heat exchanger of the ventilation unit and type plate Figure A-19: Type plate of the bypass motor

20 Appendix A11 Images of the test sample Figure A-20: Bypass of the ventilation unit Figure A-21: Type plate of the external electrical preheater

21 Appendix A12 Images of the test sample Figure A-22: External electrical preheater without cover Figure A-23: External electrical preheater

22 Appendix A13 Images of the test sample Figure A-24: Temperature sensor of the electrical preheater Figure A-25: Electrical assembly of the ventilation unit

23 Appendix A14 Images of the test sample Figure A-26: P-touch controller of the ventilation unit Figure A-27: S-touch controller of the ventilation unit

24 Appendix A15 Images of the test sample Figure A-28: Mod Bus Gateway of the ventilation unit Figure A-29: Type plate of the ventilation unit

25 Appendix A16 Images of the test sample Figure A-30: Mounting options

26 Appendix B1 Data pertaining to the tested unit Specifications according to ventilation unit's type plate Manufacturer: SALDA Type: AHU Smarty 2X P 1.1 Address of the company: - Voltage: 230 V / 50 Hz ~1 Current consumption: Total Power consumption: 0.85 A 0.10 kw Serial number: Gu / Product number: Year of production: 2016 Weight: - Dimensions of the ventilation unit Test laboratory indications Height Width Depth 1010 mm 590 mm 250 mm

27 Appendix B2 Data pertaining to the tested unit Filter Type Quantity Filter class Dimensions Outdoor air filter: 1 F7 185 mm x 168 mm x 25 mm Extract air filter: 1 G4 185 mm x 168 mm x 25 mm Fans Exhaust fan Quantity: 1 Design: radial Manufacturer: Soler & Palau Type: CRBB/3-133/060 E11 BP16 Voltage/Frequency: 230 V 50/60 Hz Current consumption: 0.40 A Real power consumption: 0.05 kw Speed: / min Supply fan Quantity: 1 Design: radial Manufacturer: Soler & Palau Type: CRBB/3-133/060 E11 BP16 Voltage/Frequency: 230 V 50/60 Hz Current consumption: 0.40 A Real power consumption: 0.05 kw Speed: / min

28 Appendix B3 Data pertaining to the tested unit Heat exchanger Quantity: 1 Design: cross counter flow Material: PET Manufacturer: recutech Type: REP H-32 Serial No.: Humidityrecovery: No Dimensions: Width 170 mm Length mm L2 L1 Length 2 Depth 250 mm 360 mm Width Plate spacing 5.8 mm Air connections Extract air: DN 160 Exhaust air: DN 160 Outdoor air: DN 160 Supply air: DN 160

29 Appendix C Results of the tightness test The leakage related to the maximum declared air volume flow of 203 m³/h is: Measurement P stat external leakage leakage volume flow leakage internal leakage leakage volume flow leakage Nr. [Pa] [m³/h] % [m³/h] % leakage voluem flow [m³/h] 12,0 10,0 8,0 6,0 4,0 2% 2,0 0,0-2,0-4,0-6,0-8,0-10,0-12,0 testpressure [Pa] % external leakage internal leakage

30 Appendix D1 Pressure-airflow curves (extract air) ρ = 1.2 kg/m³ stat. pressure [Pa] x qvd qvd 100 qvmin air volume flow [m³/h]

31 Appendix D2 Pressure-airflow curves (supply air) ρ = 1,2 kg/m³ stat. pressure [Pa] x qvd qvd 100 qvmin air volume flow [m³/h]

32 Appendix E1 Measurements from the ventilation test q vmin with the parameter: 31.0 % at the supply fan and 28.0 % at the exhaust fan p stat. SU-OU p stat. EXT-EXH P el spec. el. power input [W/(m³/h)] 3 ρ = 1,2 kg/m³ supply ρ = 1,2 kg/m³ extract ρ = 1,2 kg/m³ ρ = 1,2 kg/m³ [Pa] [m³/h] [Pa] [m³/h] [W] [W] [W/(m³/h)] W/(m³/h)] ,7xq vd with the parameter: 58.5 % at the supply fan and 49.0 % at the exhaust fan p stat. SU-OU p stat. EXT-EXH P el spec. el. power input [W/(m³/h)] ρ = 1,2 kg/m³ supply ρ = 1,2 kg/m³ extract ρ = 1,2 kg/m³ ρ = 1,2 kg/m³ [Pa] [m³/h] [Pa] [m³/h] [W] [W] [W/(m³/h)] W/(m³/h)] The specific power input of the ventilation unit was related to the supply air flow. p el = power input of the unit / supply air flow

33 Appendix E2 Measurements from the ventilation test q vd with the parameter: % at the supply fan and 73.0 % at the exhaust fan p stat. SU-OU p stat. EXT-EXH P el spec. el. power input [W/(m³/h)] 3 ρ = 1,2 kg/m³ supply ρ = 1,2 kg/m³ extract ρ = 1,2 kg/m³ ρ = 1,2 kg/m³ [Pa] [m³/h] [Pa] [m³/h] [W] [W] [W/(m³/h)] W/(m³/h)] The specific power input of the ventilation unit was related to the supply air flow. p el = power input of the unit / supply air flow

34 Appendix F Thermodynamic test points ρ = 1.2 kg/m³ Supply air Extract air P el stat. pressure [Pa] test point at 0.7 x q vd test point at q vd power input [W] 100 test point at q vmin air volume flow [m³/h]

35 Appendix G1 Measurements and calculated values from the thermodynamic test Calculation based on DIN EN Heatexchanger w ith humidity transfer no A7 measured values q Vmin q Vn q Vd temperature extract Θ 11 C temperature exhaust Θ 12 C temperature outdoor Θ 21 C temperature supply Θ 22 C rel. humidity extract ϕ 11 % rel. humidity exhaust ϕ 12 % rel. humidity outdoor ϕ 21 % rel. humidity supply ϕ 22 % abs. humidity extract x 11 g/kg abs. humidity exhaust x 12 g/kg abs. humidity outdoor x 21 g/kg abs. humidity supply x 22 g/kg wetbulb temperature extract Θw 11 C wetbulb temperature outdoor Θw 21 C volume flow extract q V11 m³/h volume flow exhaust q V12 m³/h volume flow outdoor q V21 m³/h volume flow supply q V22 m³/h mass flow extract q m11 kg/s mass flow exhaust q m12 kg/s mass flow outdoor q m21 kg/s mass flow supply q m22 kg/s pressure extract / exhaust p tu1 Pa pressure outdoor / supply p tu2 Pa ambient temperature Θ amb C ambient pressure p amb Pa 96,014 96,045 96,050 power input total P E W result q Vmin q Vn q Vd mass flow ratio m SU/ m EXT q m22/ temperature ratio (supply) η ΘSU % humidity ratio (supply) η xsu % temperature ratio (exhaust) η ΘEX % humidity ratio (exhaust) η xex % spec. electr. Power input related to (qv22) P E /q V22 W/(m³/h) The calculation is based on following constants: c p,l [kj/(kgk)] c p,d [kj/(kgk)] r 0 [kj/kg] c p,w [kj/(kgk)]

36 Appendix G2 Measurements and calculated values from the thermodynamic test Calculation based on DIN EN Heatexchanger w ith humidity transfer no A2 measured values q Vmin q Vn q Vd temperature extract Θ 11 C temperature exhaust Θ 12 C temperature outdoor Θ 21 C temperature supply Θ 22 C rel. humidity extract ϕ 11 % rel. humidity exhaust ϕ 12 % rel. humidity outdoor ϕ 21 % rel. humidity supply ϕ 22 % abs. humidity extract x 11 g/kg abs. humidity exhaust x 12 g/kg abs. humidity outdoor x 21 g/kg abs. humidity supply x 22 g/kg wetbulb temperature extract Θw 11 C wetbulb temperature outdoor Θw 21 C volume flow extract q V11 m³/h volume flow exhaust q V12 m³/h volume flow outdoor q V21 m³/h volume flow supply q V22 m³/h mass flow extract q m11 kg/s mass flow exhaust q m12 kg/s mass flow outdoor q m21 kg/s mass flow supply q m22 kg/s pressure extract / exhaust p tu1 Pa pressure outdoor / supply p tu2 Pa ambient temperature Θ amb C ambient pressure p amb Pa 95,534 95,580 95,560 power input total P E W result q Vmin q Vn q Vd mass flow ratio m SU/ m EXT q m22/ temperature ratio (supply) η ΘSU % humidity ratio (supply) η xsu % temperature ratio (exhaust) η ΘEX % humidity ratio (exhaust) η xex % spec. electr. Power input related to (qv22) P E /q V22 W/(m³/h) The calculation is based on following constants: c p,l [kj/(kgk)] c p,d [kj/(kgk)] r 0 [kj/kg] c p,w [kj/(kgk)]

37 Appendix H Description of the frost protection climate strategy The unit was equipped with an electrical preheater situated on the suction side of the outdoor fan. To regulate the frost protection of the air ventilation unit the activation temperature of the frost protection (AF_SET), the temperature difference to deactivate the frost protection (AF_DEACTIVATION_DIFF) as well the activation time of the frost protection (CHANGING_TIME) have to be specified in the controller of the unit. The controller is comparing the activation Temperature (AF_SET) to the current outside air temperature inside of the ventilation unit (T_Fresh). If the current temperature (T_Fresh) is on a lower level than the setting of the activation temperature on the outdoor air side (AF_SET) the controller activate the frost protection of the unit. After the activation interval (CHANGING_TIME) has been expired the controller is calculating the difference between the temperatures (T_Fresh) and (AF_SET). If the difference between the temperatures (T_Fresh) and (AF_SET) is greater than the value set under (AF_DEACTIVATION_DIFF) the frost protection will be deactivated. As long the temperature difference is equal or lower the frost protection remains activated and the calculation and evaluation of the difference between the temperatures (T_Fresh) and (AF_SET) will be repeated after the activation interval (CHANGING_TIME) has been expired During the tests the following values were set in the controller of the unit. Variables: AF_SET Heat exchanger s anti-frost Set Point -6.5 C AF_DEACTIVATION_DIFF difference of anti-frost de activation temperature from activation temperature 15 K T_fresh Outdoor air temperature (preheated) current CHANGING_TIME- activating time 30 min

38 Appendix I Diagram of the cold climate test with electrical preheater

39 Appendix J Results of the acoustic tests Environmental conditions: rel. humidity: 48 % barometric pressure: 980 hpa air temperature: 23 C voltage: 230 V centre frequency [Hz] sound power level [db] exhaust outdoor air extract supply unit L W L WA static pressure [Pa] (OU/SU) / (EXT/EXH) 48 / / / / / 53 air volume flow [m³/h] OU SU EXH EXT with L W L WA sound power level A-weighted sound power level Sound power levels written bold indicate a difference between background noise and noise of source under test below 6 db. The accuracy of those results is reduced. The stated value is the upper bound for the sound power level.

R E P O R T D I N E N

R E P O R T D I N E N R E P O R T W R G 3 9 6 D I N E N 1 3 1 4 1-7 Test laboratory Test object Customer Scope of assignment TÜV SÜD Industrie Service GmbH Center of Competence for Refrigeration and Air Conditioning Air Conditioning

More information

Acoustic Verification Report

Acoustic Verification Report Acoustic Verification Report Invacare XPO 2 Portable Oxygen Concentrator Type XPO100B-EU for Date: 2013-12-10 Our reference: IS-ATC2-MUC/js Document: Report Invacare VR.600010074.002.12 - Revision 2.docx

More information

Center of Competence Refrigeration and Air conditioning

Center of Competence Refrigeration and Air conditioning k Center of Competence Refrigeration and Air conditioning Information sheet air handling unit Basic requirements The unit which should be tested has to be delivered completely with all necessary equipment.

More information

AIR HANDLING UNITS. AmberAir Compact Smarty RIS EKO 3.0 RIRS EKO 3.0

AIR HANDLING UNITS. AmberAir Compact Smarty RIS EKO 3.0 RIRS EKO 3.0 Residential/commercial units selection program: http://salda.lt/en/selection/ahu AmberAir Compact units selection program VentMaster: http://salda.lt/en/pros/category/download_page/ WWW.SALDA.LT Rotor

More information

NEW SECTION: ROTARY HEAT EXCHANGER WITH A HEAT PUMP Effective and smart!

NEW SECTION: ROTARY HEAT EXCHANGER WITH A HEAT PUMP Effective and smart! NEW SECTION: ROTARY HEAT EXCHANGER WITH A HEAT PUMP Effective and smart! WWW.SALDA.LT 2016 Ver. A SECTION OF THE ROTARY HEAT EXCHANGER WITH THE HEAT PUMP: ideal solution targeting multiple goals In conventional

More information

Energy recovery unit. Projection documents

Energy recovery unit. Projection documents Energy recovery unit Projection documents 1. Technical charakteristics 1.1. Function and uses The energy recovery unit Futura is a device designed for controlled ventilation and interior adjustment of

More information

MRXBOX90 - WHOLE HOUSE HEAT RECOVERY UNIT

MRXBOX90 - WHOLE HOUSE HEAT RECOVERY UNIT - WHOLE HOUSE HEAT RECOVERY UNIT 95% efficient, SAP Appendix Q compliant heat recovery unit.. 29 285 82 BENEFITS High efficiency 95% efficient, with DC motors using 5% less energy than traditional fans.

More information

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06) C 416/16 EN Official Journal of the European Union 11.11.2016 Commission communication in the framework of the implementation of Commission Regulation (EU) No 1253/2014 implementing Directive 2009/125/EC

More information

Heat and energy recovery ventilators

Heat and energy recovery ventilators Description is recommended for use in residential houses with max. area of 200m2. The most important key features of : Heat recovery up to 95% according to EN 308 - TUV SUD Plastic counterflow heat exchanger

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and

More information

Certified Passive House Component For cool, temperate climates, valid until 31 December 2017

Certified Passive House Component For cool, temperate climates, valid until 31 December 2017 Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2017 Category: Manufacturer: Product name: Heat recovery unit DencoHappel GmbH 44625 Herne, GERMANY Series

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades

More information

SYSTEM VENTECH LG 250

SYSTEM VENTECH LG 250 SYSTEM VENTECH LG 50 COMFORT VENTILATION ErP 08 EU Regulation 5/0 The specified energy efficiency is applicable when controlled to local requirements and is valid up to the specified maximum air flow volume.

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units

Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units Ralf Dott, Thomas Afjei and Carsten Wemhöner Institute of Energy in Building, University of Applied Sciences Northwestern Switzerland,

More information

EC A1/L2 RIS P EKO RIS 400 P E 0.9 EKO 3.0 AIR HANDLING UNITS. Application

EC A1/L2 RIS P EKO RIS 400 P E 0.9 EKO 3.0 AIR HANDLING UNITS. Application EC A1/L2 Application Ventilation of houses, offices or other heated premises (classrooms, apartments, conference rooms, etc.) Description 3. is a range of heat recovery units with high-efficiency counter-flow

More information

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses NEW! REC Temovex Blue 4 Experts on indoor climate in low-energy houses REC Temovex Blue 4 Third generation of our Temovex units! - Dual counterflow heat exchangers with over 9% efficiency * - SFP < 1,

More information

Decentralised comfort ventilation unit Zehnder ComfoSpot 50

Decentralised comfort ventilation unit Zehnder ComfoSpot 50 Application Zehnder ComfoSpot 50 is a decentralised comfort ventilation unit with heat and humidity recovery using synchronous supply or extract air operation. It is often used in apartment renovations

More information

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses REC Temovex 4S-EC-RS Experts on indoor climate in low-energy houses RT 4S-EC-RS REC Temovex 4S-EC-RS ECO2 control system for low-energy and passive houses Comprises: - Air flow boost for warm and cold

More information

EC L2. and humidity sensors. All units are supplied tested and ready to install.

EC L2. and humidity sensors. All units are supplied tested and ready to install. EC L2 Application Description Ventilation of small public buildings, offices, other larger heated premises (sport facilities, conference rooms, shops, etc.) RIS H EC 3.0 and RIS H EC 3.0 SSK are designed

More information

Vallox Oy. manufactures ventilation units Vallox TSK Multi 80 MC. over Vallox TSK Multi 80 MC

Vallox Oy. manufactures ventilation units Vallox TSK Multi 80 MC. over Vallox TSK Multi 80 MC Vallox TSK Multi 80 MC Vallox TSK Multi 80 MC Vallox Oy manufactures ventilation units Vallox TSK Multi 80 MC Certificate No VTT-C-11032-14 Translation 1 (2) Vallox TSK Multi 80 MC is intended to be used

More information

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION 2 AERECO DX system DX SYSTEM A COMPLETELY NEW HEAT RECOVERY VENTILATION RANGE With the experience of a very innovative room-by-room demand

More information

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans!

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans! AIR HANDLING UNITS RIS P EKO 3.0 1 2 3 4 fans! Efficient EC E f f i c i e n c y up to 94%! E x t r e m e l y low height! New range - 5 sizes, 20 models! Contents Basic features 4 RIS P EKO 3.0 full range

More information

Desiccant Cooling with Solar Energy

Desiccant Cooling with Solar Energy Desiccant Cooling with Solar Energy Gerrit Höfker 1,2, Ursula Eicker 2, Kevin Lomas 1, Herbert Eppel 1 1 De Montfort University Leicester, Institute of Energy and Sustainable Development 2 Hochschule für

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

HRU ECO 4. System 4 Continuous Mechanical Supply and Extract Ventilation with Heat Recovery Appendix Q Eligible

HRU ECO 4. System 4 Continuous Mechanical Supply and Extract Ventilation with Heat Recovery Appendix Q Eligible HRU ECO 4 System 4 Continuous Mechanical Supply and Extract Ventilation with Heat Recovery Appendix Q Eligible Weight As a result of the unique clamping construction in combination with the plastic/synthetic

More information

RIS V EKO A1/L2 RIS 700 V E L EKO 3.0 AIR HANDLING UNITS. Application

RIS V EKO A1/L2 RIS 700 V E L EKO 3.0 AIR HANDLING UNITS. Application EC A1/L2 7 1 19 2 75 Application Ventilation of houses, offices or other heated premises (classrooms, apartments, conference rooms, etc.) Description RIS V EKO 3. is a range of heat recovery units with

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 300 m 3 /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

Installation of a Brunner fireplace. General Indications

Installation of a Brunner fireplace. General Indications Installation of a Brunner fireplace General Indications CONTENTS 1 Basic informations...3 2 Safety precautions...4 3 Combustion air...5 4 Requirements for location... 6 5 Overview of fire safety and heat

More information

Zehnder ComfoAir flat 150

Zehnder ComfoAir flat 150 Use The comfort ventilation unit was specially developed for space-saving ceiling installation in residential and commercial buildings with high ventilation demand. It is thus excellently suited for conversions

More information

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system Comfort air conditioning 56/58 Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system 58 3 0 - simplified illustration Automatically selects the most economical

More information

AIR HANDLING UNITS ver B

AIR HANDLING UNITS ver B AIR HANDLING UNITS www.salda.lt 2013 ver B EC High efficiency air handling units are supplied with crosscounter flow plate heat exchangers. AHU is used for ventilation of houses and other heated areas.

More information

Auxiliary Equipment and Accessories

Auxiliary Equipment and Accessories http://www.ventilation-alnor.co.uk/index/products_en/heat-recovery-%e2%80%93-air-handling-units/ Description is recommended for use in residential houses with max. area of 200m2. The most important key

More information

Resolair 62 and 66. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 1,200 4,300 m³/h

Resolair 62 and 66. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 1,200 4,300 m³/h Comfort air conditioning unit with highly efficient regenerative heat storage packages 62 26 01 - simplified illustration Automatically selects the most economical operating mode! 62 and 66 AIR OLUME FLOW:

More information

EASYAIR COMPACT DEVICE THE EASY WAY OF AIR HANDLING.

EASYAIR COMPACT DEVICE THE EASY WAY OF AIR HANDLING. EASYAIR COMPACT DEVICE THE EASY WAY OF AIR HANDLING. EASYAIR THE EASY WAY OF AIR HANDLING Independently VDI 6022 tested and certified down to the last detail The new generation of EASYAIR compact devices

More information

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25 Residential Heat Recovery Ventilation REHVA European Guidebook No 25 REHVA European Guidebook No 25 2 Limited to mechanical supply and exhaust ventilation Targeted to engineers, HVAC consultants and contractors

More information

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing Field of application Description Advantages Range Technical details Installation Remote controls Servicing Remote control ErP * ** Conpliance compliance. ErP ready. Advantages Reversible connections. Ventilation

More information

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION 2 AERECO Room-by-room demand controlled heat recovery ventilation REVOLUTION IN THE WORLD OF HEAT RECOVERY VENTILATION Through its new ventilation

More information

Product Data Sheet 4114 N/17HH-218. The engineer's choice

Product Data Sheet 4114 N/17HH-218. The engineer's choice The engineer's choice 4114 N/17HH-218 INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 4 3.1 Electrical Operating Data... 4 3.2 Electrical Interface - Output

More information

exhaust air intake air

exhaust air intake air CLIMOS / DC COMFORT VENTILATION MVHR UNIT FOR INSTALLATION IN CEILING VIOD Programmer (external) for automatic control L x W x D (mm): 8 x x control cable angle bracket (x) snap locks (x) hinges on opposite

More information

Heat Recovery Unit HERU. web-version

Heat Recovery Unit HERU. web-version Heat Recovery Unit HERU web-version HERU 50 and 75 Heat recovery unit HERU is designed to suit places like houses, offices and other buildings where there is a big demand for high temperature efficiency,

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

Performance Rating of Active Chilled Beams

Performance Rating of Active Chilled Beams AHRI Standard 1241 (SI) 2016 Standard for Performance Rating of Active Chilled Beams IMPORTANT SAFETY RECOMMENDATIONS AHRI does not set safety standards and does not certify or guarantee the safety of

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

KN-KWL 110 SE-EC Kontrollierte Wohnraumlüftung KN

KN-KWL 110 SE-EC Kontrollierte Wohnraumlüftung KN KN-KWL 110 SE-EC Kontrollierte Wohnraumlüftung KN 2014-07 Druck-, Satzfehler und techn. Änderungen vorbehalten - Subject to change Seite 1 2014-07 Druck-, Satzfehler und techn. Änderungen vorbehalten -

More information

Technical documentation Comfort domestic ventilation system

Technical documentation Comfort domestic ventilation system Technical documentation Comfort domestic ventilation system CWL Excellent CWL-T Excellent CWL-F Excellent 2 CWL unit options Type CWL-F-150 Excellent CWL-F-300 Excellent CWL-180 Excellent CWL-300 Excellent

More information

AIR HANDLING UNITS MANDÍK

AIR HANDLING UNITS MANDÍK AIR HANDLING UNITS MANDÍK 2 CONTENTS MANDÍK, a. s. The Company... 3 Photo Gallery... 4 Unit Description... 6 Air handling unit parameters according to Eurovent... 7 Product Range of the Air Handling Units...

More information

Test Report No.: Page 2 of 14

Test Report No.: Page 2 of 14 Test Report No.: 15039191 001 age 2 of 14 Test item particulars: Class of protection... : Degree of protection... : Class of temperature... : Testing: Class I IX0 Date of receipt of test item... : 2010.06.28

More information

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing Vipac Engineers & Scientists DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption The physical testing Sydney 16 August 2016 Introduction to Vipac AGENDA

More information

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES The experimental system established in the present study to investigate the transient flow boiling heat transfer and associated bubble characteristics of

More information

Sound Performance Rating of Non-ducted Indoor Airconditioning

Sound Performance Rating of Non-ducted Indoor Airconditioning AHRI Standard 350 2015 Standard for Sound Performance Rating of Non-ducted Indoor Airconditioning and Heat Pump Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger Daniel Soto 1 and Daniel Corona 2 California Polytechnic State University, San Luis Obispo, San Luis Obispo, California,

More information

MODEL URS-1: FACTORY RETROFIT PROGRAM

MODEL URS-1: FACTORY RETROFIT PROGRAM MODEL URS-1: FACTORY RETROFIT PROGRAM The USR-1 unit has gone through extensive testing in order to attain maximum performance. It has been determined that in order to set the unit for all weather operation,

More information

2013 innovation. Room-by-room demand controlled heat recovery ventilation

2013 innovation. Room-by-room demand controlled heat recovery ventilation 2013 innovation Room-by-room demand controlled heat recovery ventilation 2 Revolution in the world of heat recovery ventilation Through its new ventilation system, which combines heat recovery and room-by-room

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES Homepage > Products > Air Diffusers > Ceiling diffusers > Ceiling swirl diffusers > Type TDF-SilentAIR Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

More information

Technical documentation. ComfoAir XL The latest generation of ventilation units with heat recovery

Technical documentation. ComfoAir XL The latest generation of ventilation units with heat recovery Technical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery Heating Cooling Ventilation Filtering Service and recommendations The latest heat recovery range

More information

Koja Oy. manufactures ventilation units Fair 80 ec

Koja Oy. manufactures ventilation units Fair 80 ec Koja Fair 80 ec Koja Fair 80 ec Koja Oy manufactures ventilation units Fair 80 ec Certificate No VTT-C-8424-12 Translation 1 (2) Fair 80 ec is intended to be used as a ventilation unit of a dwelling. Efficiency

More information

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery Datasheet For part no. and prices: see pricelist VITOVENT 300-F Mechanical ventilation system with heat recovery for demanddependent

More information

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h Comfort air conditioning 76 Comfort air conditioning unit with counterflow plate heat exchanger Automatically selects the most economical operating mode! 76 13 76 01 13 with 01 - Adiabatic simplified Pro

More information

Package Hygienic Air Handling Units. PHK Series

Package Hygienic Air Handling Units. PHK Series Package Hygienic Air Handling Units PHK Series 1 PHK Series PHK : Standard PHK HP : Heat Pump PHK TO : Clean Room Air Handling Unit Up to 11.000 m 3 /h Airflow Complying with DiN 1946/4 Hygiene Criteria

More information

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION Swegon CASA W130 Ventilation unit with counter-flow plate heat exchanger Ventilation unit for residential houses under 250 m². The unit has counter-flow plate heat exchanger. Suitable also for renovation

More information

Ventilation unit Zehnder ComfoAir 200

Ventilation unit Zehnder ComfoAir 200 Use The Zehnder ComfoAir 200 comfort ventilation unit was developed for use in residential settings with high ventilation demand. It combines maximum comfort, simple operation and high efficiency with

More information

FOUR-FHR Counter Flow Heat Recovery Unit. is a registered trademark of Doğu İklimlendirme A.Ş.

FOUR-FHR Counter Flow Heat Recovery Unit. is a registered trademark of Doğu İklimlendirme A.Ş. FOUR-FHR is a registered trademark of Doğu İklimlendirme A.Ş. Venues Breathe with DOGU HVAC Systems! DOGU HVAC founded in 1999, started its activities in order to manufacture HVAC Equipment and Air Handling

More information

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment AHRI Standard 1120 (formerly ARI Standard 1120) 2007 Standard for Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment IMPORTANT SAFETY RECOMMENDATIONS It is

More information

Rotors overview. Quick guide GOST VDI 6022

Rotors overview. Quick guide GOST VDI 6022 Rotors overview Quick guide GOST VDI 622 Rotors overview Rotor type Heat recovery Preferred application Wave heigh Thickness of material Condensations Rotor P/PT [ C] % Summer Winter - - [g/kg] 5 15 only

More information

Heat Exchanger Earny Type

Heat Exchanger Earny Type Big Dutchman International GmbH Heat Exchanger Earny Type 4. Efficiency of heat recovery under practical conditions DLG Test Report 614 F Revision 1: Amendment(s) see page 1 Assessment summary The DLG

More information

VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER

VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER Journal of Ecological Engineering Volume 17, Issue 5, Nov. 2016, pages 163 172 DOI: 10.12911/22998993/65466 Research Article VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER Vyacheslav Pisarev 1, Sławomir

More information

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue cert. n. 0545 Product is subject to and complies with Regulation (UE) N.327/2011 Fan Coil Unit Cassette SkyStar Jumbo ECM technical catalogue SkyStar Jumbo ECM Table of contents SkyStar Jumbo ECM TABLE

More information

MRXBOXAB-ECO4 100% and Opposite Handed version. Typical Installation

MRXBOXAB-ECO4 100% and Opposite Handed version. Typical Installation NUAIRE MVHR and Opposite Handed version ACHIEVES 100% DUTY IN BYPASS MODE The has been designed with automatic 100% bypass as listed on the SAP Product Characteristics Database (PCDB). Due to its intelligent

More information

Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods

Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods (1) Under Directive 2009/125/EC ecodesign requirements should be set by the Commission for energy-related

More information

VERSO DOMEKT. Residential ventilation units m³/h. Non residential ventilation units m³/h

VERSO DOMEKT. Residential ventilation units m³/h. Non residential ventilation units m³/h VENTILATION equipment VENTILATION equipment content DOMEKT Residential ventilation units 50 1 000 m³/h 15 VERSO Non residential ventilation units 1000 34 000 m³/h 61 Domekt R 17 Domekt R 200 V 19 Domekt

More information

ENERGY RECOVERY VENTILATION (ERV)

ENERGY RECOVERY VENTILATION (ERV) Home/Other Products/Obsolete Ranges ENERGY RECOVERY VENTILATION (ERV) 2 model sizes covering 500 to 1500m3/hr Choice of 90% or 55% efficient aluminium energy recovery cell High performance EC/DC motors

More information

FOUR-HOME-CEILING Ceiling Type Residential Heat Recovery Unit. is a registered trademark of Doğu İklimlendirme A.Ş.

FOUR-HOME-CEILING Ceiling Type Residential Heat Recovery Unit. is a registered trademark of Doğu İklimlendirme A.Ş. FOUR-HOME-CEILING Ceiling Type Residential Heat Recovery Unit is a registered trademark of Doğu İklimlendirme A.Ş. Plastic Spigot F7 Filter Counter Flow Heat Recovery Exchanger Control Box Plastic Spigot

More information

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General Complete HVAC substation for air handling, cooling, heating and hot tap water Text and figures in red are preliminary and may be adjusted General TELLUS is a complete, modular substation that can be installed

More information

Constant climate chambers. KBF 240 (E5.2) - Constant climate chamber. Performance features and equipment:

Constant climate chambers. KBF 240 (E5.2) - Constant climate chamber. Performance features and equipment: Constant climate chambers KBF 240 (E5.2) - Constant climate chamber The KBF series was particularly designed for absolutely reliable stability tests and precise maintenance of constant climatic conditions.

More information

ErP. The ErP Directive. New values for fans

ErP. The ErP Directive. New values for fans The Directive New values for fans THE DIRECTIVE AND BAHCIVAN FANS Review the Regulations of 640/2009 (IEC motors) and 327/2011 (Fans) and the new directive 1253/1254 (Air Handling Units) With the adoption

More information

l i nda b we si mpl i f y c onstr u ction Conforms ErP Ecodesign Lot 6 Residential and non-residential air handling units

l i nda b we si mpl i f y c onstr u ction Conforms ErP Ecodesign Lot 6 Residential and non-residential air handling units l i nda b we si mpl i f y c onstr u ction Conforms ErP 2 0 16 Ecodesign Lot 6 Residential and non-residential air handling units What is ErP and Ecodesign? ErP stands for Energy Related Products. ErP is

More information

Sound Performance Rating of Outdoor Unitary Equipment

Sound Performance Rating of Outdoor Unitary Equipment 2015 Standard for Sound Performance Rating of Outdoor Unitary Equipment AHRI Standard 270 WITH ADDENDUM 1, Sound Performance Rating of Outdoor Unitary Equipment March 2016 Note: This addendum is not ANSI

More information

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout 14 Drying Oldřich Holeček, Martin Kohout I Basic relations and definitions Drying is a process which is used for removing the liquid from the solid material. In standard chemical engineering practice drying

More information

MRXBOXAB-ECO3 MRXBOX-ECO3

MRXBOXAB-ECO3 MRXBOX-ECO3 NUAIRE MVHR MRXBOX-ECO3 and Opposite Handed versions ACHIEVES 100% DUTY IN BYPASS MODE The has been designed with automatic 100% bypass as listed on the SAP Product Characteristics Database (PCDB). Due

More information

Smart air handling unit for swimming pools IN CONFORMITY WITH THE REQUIREMENTS OF

Smart air handling unit for swimming pools IN CONFORMITY WITH THE REQUIREMENTS OF Smart air handling unit for swimming pools IN CONFORMITY WITH THE REQUIREMENTS OF PERSONALIZED CORROSION-RESISTANT SAVING AmberAir Pool FOR A COMFORTABLE MICROCLIMATE AT A SWIMMING POOL AmberAir Pool units

More information

MRXBOXAB-ECO2 MRXBOX-ECO2

MRXBOXAB-ECO2 MRXBOX-ECO2 NUAIRE MVHR MRXBOX-ECO2 and Opposite Handed versions ACHIEVES 100% DUTY IN BYPASS MODE The has been designed with automatic 100% bypass as listed on the SAP Product Characteristics Database (PCDB). Due

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

Eco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W: T:

Eco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W:   T: Eco Active Heat Recovery Penthouse Turret W: www.gdl.co.uk T: 01457 861538 Heat Recovery Penthouse Turret The HRPT provides ventilation into spaces all year round. The unit provides 100% fresh air whilst

More information

Compact. Efficient. TROX.

Compact. Efficient. TROX. Compact. Efficient. TROX. The art of handling air TROX understands the art of handling air like no other company. Since its foundation in 1951, TROX has been developing and manufacturing sophisticated

More information

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions)

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions) NUAIRE MVHR (including opposite handed versions) ACHIEVES 100% DUTY IN BYPASS MODE and MRXBOXAB- ECO-LP1-OH are specically designed for apartment applications where space is a premium. The new MRXBOX95-LP1

More information

Vallox Oy. manufactures. over LOW POWER EFFICIENCY Specific electrical

Vallox Oy. manufactures. over LOW POWER EFFICIENCY Specific electrical Vallox 150 Effect SE MLV Vallox 150 Effect SE MLV Vallox Oy manufactures Certificate No VTT-C-3514-08 Translation 1 (2) ventilation units Vallox 150 Effect SE MLV (preheating with ground heat) Vallox 150

More information

Consumer vacuum breast-pumps

Consumer vacuum breast-pumps Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de M.Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com

More information

ECV SP GUE ALO CAT ICAL TECHN

ECV SP GUE ALO CAT ICAL TECHN TECHNICAL CATALOGUE ECV SP TAILOR MADE FOR UNITS FITTED WITH VRF SYSTEMS Models: 1001 1502 1602 2003 2303 10.16 Ref. 207609 Rev.105 CONTENT INTRODUCTION... 3 GENERAL DESCRIPTION... 3 CABINET... 3 HEAT

More information

Masters in energy efficiency

Masters in energy efficiency KBA Metal Decorating Masters in energy efficiency 2-Piece Ovens The new benchmark in economy and efficiency GB 2-Piece Ovens Optimised drying solutions for 2-piece cans KBA-MetalPrint GmbH KBA-MetalPrint

More information

LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD

LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD Proceedings of the National Seminar & Exhibition on Non-Destructive Evaluation NDE 2011, December 8-10, 2011 LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS

More information

DAIKIN Air Handling Unit Modular

DAIKIN Air Handling Unit Modular DAIKIN Air Handling Unit Modular Compact ventilation unit with heat recovery Energy efficiency and air quality Daikin air handling units, with their plug-and-play design and inherent flexibility, can be

More information

Ultrasonic Clamp-On Flow Meter Testing

Ultrasonic Clamp-On Flow Meter Testing Ultrasonic Clamp-On Meter Testing Carried out for Micronics Ltd By Colin Judd Ultrasonic Clamp-On Meter Testing Carried out for: Micronics Ltd Unit B4 Business Centre Davies Way Loudwater High Wycombe

More information

GEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion

GEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion Close Climate Control for IT Environments GEA Ultra-Denco Reliability with low power consumpstion GEA Heat Exchangers / HVAC Systems Numerical Flow simulation Velocity / Pressure field / Turbulence high

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

Constant climate chamber with ICH-compliant illumination

Constant climate chamber with ICH-compliant illumination KBF P series (E5.2) Constant climate chambers Constant climate chamber with ICH-compliant illumination The BINDER KBF P constant climate chamber, equipped with ICH-compliant illumination, is the expert

More information

Customer id 2452 Project 1152 Unit 189 ACON From Inspection Side. Unit name AHU-22 R.05 Supply air EU m³/sec Exhaust air

Customer id 2452 Project 1152 Unit 189 ACON From Inspection Side. Unit name AHU-22 R.05 Supply air EU m³/sec Exhaust air From Inspection Side 2018-10-27 Acon 2.7.130319.1 Page 1/11 Customer id 2452 Project 1152 Unit 189 Project name JSL Prosafe GVA 3000E AU Unit name AHU-22 R.05 Supply air EU-21 1.13 m³/sec Exhaust air From

More information