EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

Size: px
Start display at page:

Download "EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT"

Transcription

1 EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Plot #92 (Partial) DEPZ Extention Area-02 Ganakbari, Ashulia, Savar Uttaron 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page 1/10

2 10 Feb 2014 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/10

3 10 Feb 2014 GENERAL INFORMATION General Information Factory Country: Province: City: Bangladesh Dhaka Ashulia, Savar Zip Code: 1349 Audit Duration: Re-Audit: Draft Report Date : Final Report Date : Are all action items from previous assessment complete? : Buildings in Complex : Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Approximate Ancillary Structures Area (SF) : 2 Days Re-Audit After 0 Months 10-Feb-2014 Update once final report is complete ( after all comments incorporated). N/A One Owned Three Total area of the main factory building is 22,669 sf No None None Number of Occupants : The occupancy of the factory is 210. The Alliance for Bangladesh Worker Safety Page 3/10

4 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page 4/10

5 10 Feb 2014 ASSESSMENT FINDINGS Electrical System Maintenance A transformer oil analysis is routinely completed on main service transformers. Low A transformer oil analysis shall be routinely completed to endure uninterrupted service without major shutdowns. Visual Assessment: Oil test report not found. Complete an oil analysis on applicable transformers at appropriate intervals based on voltage and power. Alliance Standard Part 10 Section Electrical Inspections Electrical System Conditions Shielding or additional insulation is provided for wiring exposed to external heat sources. High In order to avoid the effects of heat from external sources one of the following methods shall be used to protect wiring systems: (1) shielding; (2) placing 900 mm (36 in.) from the source of heat; (3) selecting a system with due regard for the additional temperature rise which may occur; (4) local reinforcement or substitution of insulating material. Visual Assessment: Insulation is not provided for the cables and wiring where needed. Provide insulation for cables and wiring where required. 31 Aug 2014 Alliance Standards Part 10 Section External heat sources. Do switchboards and/or distribution boards have capacity information labels? The Alliance for Bangladesh Worker Safety Page 5/10

6 10 Feb 2014 Non-Compliance Level: 3 Capacity labels shall describe the maximum number of protective devices that can be accommodated, and the capacity of the boxes shall be described on the information label. Means to prevent installation exceeding the designed number of devices is described in section of, NFPA Per NFPA , a panel board shall be provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. A 2-pole circuit breaker or fusible switch shall be considered for two over current devices; a 3-pole circuit breaker or fusible switch shall be considered for three over current devices. Location: ALL LT,MDB,DB,SDBs Visual Assessment: Switchboards and/or distribution boards have no capacity information labels. Provide capacity information labels (Maximum current rating, no of circuit breakers etc.) for Switchboards and distribution boards. 31 Aug 2014 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation Are all internal components of switchboards and/or distribution boards properly concealed (No missing circuit breaker or knockout covers)? Non-Compliance Level: 2 Switchboard and distribution board shall be connectied properly. Location: LT Panel /GF, DB-1/GF, SDB-1/1st Floor, DB-1/2nd Floor, SDB-1/2nd Floor Visual Assessment: All internal components of switchboards and/or distribution boards are not properly concealed Provide covers or blanks to conceal all live internal components of switchboards and/or distribution boards. 15 Aug 2014 Alliance Standard Part 10 Section Sub-Distribution Boards Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. Non-Compliance Level: 2 No physical means wear found to limit the installation of additional over current protective devices. All DBs. The Alliance for Bangladesh Worker Safety Page 6/10

7 10 Feb 2014 Visual Assessment: Physical means wear found. Ensure switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed following NFPA 70 section Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Each circuit is provided with a dedicated neutral. Non-Compliance Level: 2 Circuits are not provided with a dedicated neutral for each load. The use of common neutral for more than one circuit is not permitted by the standard. Location: LT Panel /GF, DB-1/GF, SDB-1/1st Floor, DB-1/2nd Floor, SDB- 1/2nd Floor Visual Assessment: Circuits arenot provided with a dedicated neutral for each load. Provide dedicated neutrals for each circuit. Alliance Standards Part 10 Section 10.3 Electrical Wiring and Cabling Stranded conductors having a nominal cross-sectional area 6mm2 or greater are provided with cable sockets. Conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. Non-Compliance Level: 2 In MDB/DB/SDBs cables shall be attached using splicing joint at their busbar with using cable lugs. Per and (c) of BNBC-2006 Cables shall be connected to terminals only by soldered or welded lugs, unless the terminals are designed to securely clamp without cutting away cable strands. Location:DB-01/2nd FL, SDB-01/1st FL, DB-01/GF, LT-Panel/GF Photograph: Cable sockets not used to terminate the cables in MCCB and busbar terminals for for some of the distribution boards. Reconnect with proper size of cable sockets. The Alliance for Bangladesh Worker Safety Page 7/10

8 10 Feb 2014 Alliance Standards Part 10 Section Cable Ends Electrical connections at equipment, fixtures, etc are properly secured. Non-Compliance Level: 2 Connections between conductors and between conductors and other equipment shall provide durable electrical continuity and adequate mechanical strength and protection. Location: LT Panel /GF, DB-1/GF, SDB-1/1st Floor, DB-1/2nd Floor, SDB-1/2nd Floor Visual Assessment: All connection are not secured. If flexible metallic hose is used for wiring to motors and other equipment, the wiring shall be enclosed full length, and the hose secured properly by approved means. 31 Aug 2014 Alliance Standards Part 10 Section Electrical Connections Are electrical insulation mats provided in front of substation, switchboards and/or distribution boards? Low Graded insulation/rubber mats shall be provided in front of all switchboards and distribution boxes to prevent electrical shocks. Location: SDB-1/1st Floor, DB-1/2nd Floor Photograph: Electrical insulation mats are not provided in front of substation, switchboards and/or distribution boards Provide electrical insulation mats in front of distribution boards. 15 Aug 2014 Alliance Standard Part 10 Section Inspection of the Installation. The Alliance for Bangladesh Worker Safety Page 8/10

9 10 Feb 2014 Phase separators are provided between terminals on circuit breakers. Low Phase separators are required to provide for the terminals of circuit breakers to prevent arcing and short circuit between phases. Location: SDB-01/2nd FL, DB-01/2nd FL, SDB-01/1st FL, DB-01/GF, LT-Panel/GF Photograph: Phase Separator is not fixed on circuit breakers. Install phase separators between terminal connections at the noted locations. Alliance Standard Part 10 Section Electrical Connections Emergency Power System Are inspection, maintenance, and testing procedures of the emergency generator being completed and documented? Low Inspection, maintenance, and testing procedures of the generator shall be documented. Visual Assessment: Inspection, maintenance, and testing procedures of the generator were not found on site. Establish a routine maintenance and testing program for the emergency generator. The program shall be based on all of the following: (1) Manufacturer's recommendations (2) Manufacturer's Instruction manuals (3) Requirements of NFPA 110 Chapter NFPA 110 Chapter 8 Are inspection, maintenance, and testing procedures of the UPS being completed and documented? Low Inspection, maintenance, and testing procedures of the UPS shall be performed and documented Visual Assessment: No record found on inspection, maintenance, and testing The Alliance for Bangladesh Worker Safety Page 9/10

10 10 Feb 2014 procedures of the UPS The routine maintenance and operational testing program shall be based on all of the following: (1) Manufacturer's recommendations (2) Instruction manuals (3) Minimum requirements of NFPA 110 Chapter 8 (4) Alliance Standards and local authority having jur Alliance Standard Part 13 Section NFPA 111 Chapter 8 NFPA 70B Chapter 28 The Alliance for Bangladesh Worker Safety Page 10/10

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/6 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17 11 Feb 2015 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 154 Kamrabad, Atarar Depot Chittagong Chittagong Chittagong The Alliance for Worker Safety Page 1/7 Introduction to the Report The following report contains

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/15 19

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/10 09 Jun 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory 81, Kalmessar, "Jalal Shopping Complex" Board Bazar, Gazipur. 20 May 2014 The Alliance for Bangladesh Worker Safety Page 1/21 20 May 2014 Introduction

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory RR Washing Limited (previously Freshtex Pvt Ltd (Washing)) Beximco Industrial Park Sarabo, Kashimpur, Gazipur Gazipur Dhaka 12 Jun 2014 The Alliance

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIDKO LIMITED PLOT NO. 36, ROAD NO. 46, GULSHAN NORTH C/A, DHAKA. Factory List: 1. N. A. Garments 2. 3. Sidko Apparels 4. Delta Ties Ltd. Inspected on April 17, 2014

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIKDER APPAREL HOSIERY LTD. Khadun (Dug No. 342/343), Tarabo, Rupgonj, Narayanganj, Bangladesh. Factory List: 1. Sikder Apparel Hosiery Ltd. Inspected by: Pema Wangdi

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MILLENNIUM TEXTILES (SOUTHERN) LTD., Bara Rangamatia, Ashulia, Savar, Dhaka 1341, Bangladesh Factory List: MILLENNIUM TEXTILES (SOUTHERN) LTD., Inspected on April 8,

More information

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear IEC/PAS 62271-109 Edition 1.0 2002-07 High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches PUBLICLY AVAILABLE SPECIFICATION INTERNATIONAL ELECTROTECHNICAL

More information

NFPA Edition Review

NFPA Edition Review This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton

More information

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS By Thomas Smith, Product Specialist, Brady Corporation Last updated: February, 2015 The Occupational Safety and Health Administration

More information

NZQA registered unit standard version 1 Page 1 of 5

NZQA registered unit standard version 1 Page 1 of 5 Page 1 of 5 Title Plan and carry out low voltage (LV) and extra-low voltage (ELV) electrical installations to substation equipment Level 4 Credits 4 Purpose People credited with this unit standard are

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

AS/NZS :2003 Luminaires - Part 1: General requirements and tests

AS/NZS :2003 Luminaires - Part 1: General requirements and tests Menu Home About this portal Latest updates Print Save Email Resource detail Citations AS/NZS 60598.1:2003 Luminaires - Part 1: General requirements and tests Table of Contents View on Information Provider

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A Electrical Installation & Test Engineers DETAILS OF THE CLIENT Client / Freshco Food Stores, Kiln Park Business Estate, Milton Keynes, MK3 5FS ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with

More information

SolderSleeve Insulated Electrical Termination Devices

SolderSleeve Insulated Electrical Termination Devices Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-1404 ISSUE 9 April 20, 2000 ISSUE 8 1.0 INTRODUCTION SolderSleeve Insulated Electrical

More information

PERIODIC ELECTRICAL TESTING POLICY

PERIODIC ELECTRICAL TESTING POLICY PERIODIC ELECTRICAL TESTING POLICY Originator: Policy and Strategy Team Approval date: 19 July 2016 Review date: d July 2017 1 Introduction 1.1 1.2 Pine Court Housing Association (PCHA) treats the health

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Introduction Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Who are Certsure? Where do we come from? 1923 - A National Register created 1956 - NICEIC established as a Charity

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60364-4-43 Second edition 2001-08 Electrical installations of buildings Part 4-43: Protection for safety This English-language version is derived from the original bilingual

More information

Electrical Management

Electrical Management 5 WHS PROCEDURE P23-01 Page 1 of 9 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment within the mission

More information

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products 1.0 Scope This specification covers the design, performance and qualification requirements for Raychem Side Entry Insulation Damage Repair Sleeve. 1.1 Description. Raychem SEIDRS covered by this specification

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61810-1 Second edition 2003-08 Electromechanical elementary relays Part 1: General and safety requirements Relais électromécaniques élémentaires Partie 1: Exigences générales

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

Neil Hewitt Electrical & Air Conditioning P/L

Neil Hewitt Electrical & Air Conditioning P/L VISUAL SAFETY EXAMINATION / INSPECTION CHECKLIST Examination / inspection checklist Customer:... Date:... Address:... Phone:...... Mobile:... Contact:... Inspection Activity Yes No NA General Basic protection

More information

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND ADMINISTRATION ADMINISTRATION 301.1.2 LP-Gas installations. Whenever there is a conflict between this code and NFPA 54 and B+NFOA 58 as adopted by the Nevada LP-Gas

More information

NFEC FIRE SAFETY SEMINAR Krish Mysore

NFEC FIRE SAFETY SEMINAR Krish Mysore NFEC FIRE SAFETY SEMINAR 2018 Krish Mysore krish.mysore@schneider-electric.com Agenda 1 Electrical Fire Stats 2 Types of Electrical Fires 3 Electrical Risk Management 4 Electrical Health Check Assessment

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAGPIE COMPOSITE TEXTILE LTD. 832/833, DEWAN IDRIS ROAD, AMTOLI, ASHULIA, SAVAR, DHAKA OTHER FACTORIES: NONE May 17, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/17/2014

More information

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical

More information

NFPA 70E Electrical Safety in the Workplace

NFPA 70E Electrical Safety in the Workplace NFPA 70E Electrical Safety in the Workplace Objectives What NFPA 70E covers Understand Arc Flash, Incident Energy, & Flash Protection Boundary Standards, Enforcement, & Safe Practices Arc Flash Hazard

More information

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing

More information

Chapter 18 Welding Table of Contents

Chapter 18 Welding Table of Contents Chapter 18 Welding Table of Contents 18.1 Foreword 18.2 Introduction 18.3 Applicability of Standard 18.4 Other Policies that Might Apply 18.5 Approved Areas for Welding and Cutting 18.6 Other Areas 18.7

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT Page 1 FIRE SAFETY INSPECTION REPORT Impress Fashion Ltd. ACCORD ID: 12245 Dag No. 2224, Matuial, Konapara, Katherpool, Jatrabari, Dhaka-1362 Other Factories: None Date: August 27, 2015 Sl No. Category

More information