EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

Size: px
Start display at page:

Download "EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT"

Transcription

1 EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25 Feb 2014 The Alliance for Bangladesh Worker Safety Page 1/20

2 Factory 25 Feb 2014 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/20

3 25 Feb 2014 GENERAL INFORMATION General Information Factory Address: Country: Province: City: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Bangladesh Dhaka Ashulia, Savar Zip Code: 1349 Audit Duration: Re-Audit: Draft Report Date : Final Report Date : Are all action items from previous assessment complete? : Buildings in Complex : Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Approximate Ancillary Structures Area (SF) : 4 Days Re-Audit After 0 Months 25-Feb Jan-2015 N/A Two(1 Main building, 1 ancillary building). Owned Main factory Building: 1 storied R.C building. Total area of the main factory building is 20,700 SF.( GF: 5,100 SF, 1st: 5,200 SF, 2nd: 5,200 SF, 3rd: 5,200 SF.) Twenty years ago(1994). No 1 storied shed building with mezzanine floor. Total area of the ancillary building is 128,600 SF( GF: 107,000SF; Mezzanine: 21,600 SF) The Alliance for Bangladesh Worker Safety Page 3/20

4 25 Feb 2014 Number of Occupants : Total occupancy is 344. (main factory building: GF: 28;1ST: 25; 2ND: 32; 3RD: 21) ( Ancillary building: GF: 218; Mezzanine: 39) The Alliance for Bangladesh Worker Safety Page 4/20

5 25 Feb 2014 ASSESSMENT FINDINGS Electrical System Information Are as-built electrical drawings indicating information such as panel and circuit locations throughout the building(s) available for review? No Electrical approved as build drawings were available on site Document Review: No drawings found Obtain or create a full set of electrical system drawings, seek authority approval and store on site for further and future reference 15 Jan 2015 Alliance Standard Part 10 Section Electrical System Maintenance Have workers that operate and maintain the electrical system received electrical safety training? Is training documentation on site? Workers that operate and maintain the electrical system received no electrical safety training and no related documents were found at the site. Training is required for workers who deal with electrical equipment. Uploaded Document: No record found., Visual Assessment, Uploaded Document: No record found., Visual Assessment Develop and implement an electrical safety program. Include key topics such as lock-out/ tag-out procedures, personal protective equipment requirements, etc. Reference NFPA 70E for example program requirements. Reference NFPA 70e for example Is a periodical Insulation Resistance Measurement Program established and recorded? The Alliance for Bangladesh Worker Safety Page 5/20

6 25 Feb 2014 Periodic electrical maintenance inspections were not observed. Document Review: No records found A planed program maintenance (PPM) system shall be developed and executed to rectify electrical system issues before they become safety hazards. 15 Jan 2015 Alliance Standard Part 10 Section Insulation Tests and Electrical Inspections Is the electrical switchgear and panel boards inspected on an annual basis to ensure that the equipment is installed in accordance with the listed ratings? Periodic electrical maintenance inspections not observed Document Review: No documents seen A planed program maintenance (PPM) system shall be developed and executed to rectify electrical system issues before they become safety hazards. 15 Jan 2015 Alliance Standards Part 10 Section Electrical Inspections Are thermographic scans of electrical equipment completed at least every three years? Thermo graphic scans of electrical equipment are required at least every three years to ensure the proper maintenance of the electrical equipment. Such programs have not been witnessed in this factory. Visual Assessment: No previous thermo graphic scan report was found. Complete thermo graphic scans at least on a three year cycle. Thermo graphic scans shall be completed in accordance with the Standard for Infrared Inspection of Electrical Systems & Rotating Equipment and NFPA 70B. The Alliance for Bangladesh Worker Safety Page 6/20

7 25 Feb 2014 Alliance Standards Part 10 Section Electrical Inspections Are periodic safety inspections of the electrical system components completed and documented? Periodic electrical maintenance inspections not were observed Document Review: No documents or practices were seen A planed program maintenance (PPM) system shall be developed and executed to rectify electrical system issues before they become safety hazards. 15 Jan 2015 Alliance Standard Part 10 Section Inspection and Testing and Part 13 Section 13.6 Housekeeping A transformer oil analysis is routinely completed on main service transformers. Low Non-Compliance Level: 1 Oil test record was not found. Visual Assessment: Oil test record was not found. Complete an oil analysis on applicable transformers at appropriate intervals based on voltage and power. A transformer oil analysis shall be routinely completed to ensure uninterrupted service without major shutdowns. Alliance Standard Part 10 Section Electrical Inspections Electrical System Conditions All equipment is efficiently earthed and properly connected to the required number of earth electrodes. All equipment is not efficiently earthed. Location: LT-01/Sub-Station/1st FL, LT-02/Sub-Station/1st FL, DB-P-06,SDB-04/Lab, SDB-05/Lab, SDB-06/Lab, SDB-07/Lab, SDB-08/Lab,SDB-09/Office, SDB-10/Office, SDB-11/Office, SDB-04/Knitting,SDB-03/Comp. Room, SDB-02/ Bianca, SDB-03/Mixer Room The Alliance for Bangladesh Worker Safety Page 7/20

8 25 Feb 2014 Visual Assessment: All equipment is not efficiently earthed. Provide earthling of equipment at required locations and connect to required number of electrodes. Refer to the BNBC for required number of electrodes. In general all parts of equipment and installation other than live parts shall be earth potential, thus Alliance Standard Part 10 Section Inspection of Substation Installations. Is a readily accessible single point of disconnect provided for each main electrical service feed? A readily accessible single point of disconnect is not provided for each main electrical service feed. Location: SDB-04/Lab, SDB-06/Lab, SDB-09/Office, SDB-10/Office, SDB-11/Office Photograph: A readily accessible single point of disconnect is not provided for each main electrical service feed. Install a readily accessible single point of disconnect for each main electrical service feed. Main feeds for panels shall be equipped with disconnect and shall be installed at accessible height, maximum 6 feet. BNBC Main Switch and Switchboards Are switchboards and/or distribution boards installed in compliant locations? The installed heights of some switchboards are over 2 meters from FFL. Visual Assessment: As seen on site Engage a licensed electrician or electrical contracting firm to rectify all non conforming and unsafe electrical works throughout the entire complex. 15 Nov 2014 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Indications of overheating, overloading, or signs of burning were not observed. The Alliance for Bangladesh Worker Safety Page 8/20

9 25 Feb 2014 Details are in the thermo graphic report. Visual Assessment: Thermo graphic report Engage a licensed electrician or electrical contracting firm to rectify all non conforming and unsafe electrical works throughout the entire complex. 15 Nov 2014 Alliance Standard Part 10 Section Is electrical wiring/cables sized according to capacity of circuit breakers (No higher rated circuit breakers with lower rated wiring)? Cables sized according to capacity of CBS are not provided on site. Location: LT-01/Sub-Station/1st FL, LT-02/Sub-Station/1st FL, DB-N-01,DB-N-03, DB-N- 04, DB-N-05, DB-N-06, DB-N-07, DB-N-09, DB-P-01,DB-P-02, DB-P-03, DB- P-04, DB-P-05, DB-P-06, SDB-02/Lab, SDB-03/Lab, SDB-05/Lab, SDB- 07/Lab,SDB-08/Lab, SDB-09/Office, SDB-11/Office, SDB-01/Knitting Sec.,SDB-02/Knitting Sec., SDB- 04/Knitting, SDB-02/New Rapid,SDB- 03/New Rapid, SDB-01/Jigger, SDB-01/GF, SDB-01/Jigger/Office,SDB- 01/Jigger/Office, SDB- 01/Comp.Room-01, SDB-03/Comp. Room, SDB- 01/Inspection, SDB-01/Inspection/GF,SDB-01/Workshop, SDB-02/Bianco, SDB-04/Boiler Room Visual Assessment: er rated circuit breakers with lower rated wiring was found. Consult with a qualified Electrical Engineer and ensure electrical cables are sized according to capacity of circuit breakers. Protective devices shall be provided to break any overload current flowing in the circuit conductors before such a current could 30 Sep 2014 Alliance Standard Part 10 Section Electrical Connections. The Alliance for Bangladesh Worker Safety Page 9/20

10 25 Feb 2014 No multi looping of wiring/cables observed at circuit breakers within switchboards and/or distribution boards. Multiple cables are installed at single points. Multiple and looping are found at circuit breakers in the distribution boxes at every floor. Photograph: Multiple and looping cables were found at MCCB & bus bar terminals.. Separate the multiple cables so that only one circuit lands on each circuit breaker. Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling All metal in the building is connected to the building earthing/grounding system such as metal rebar in concrete, metal frame of building, or metal water pipe. All metal in the building is not connected to the building earthing/grounding system. Visual Assessment: All metal in the building is not connected to the building earthling/grounding system. Provide earthing/grounding system for All metal in the building. In general all parts of equipment and installation other than live parts shall be earth potential, thus ensuring that persons coming in contact with these parts shall also be at earth potent Alliance Standard Part 10 Section Earthing Light fixtures without protective covers are not installed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Naked light fixtures are installed in storage areas. Visual Assessment: Naked light fixtures installed in storage areas. The Alliance for Bangladesh Worker Safety Page 10/20

11 25 Feb 2014 Remove light fixtures without protective covers from storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Light fixtures without protective covers (otherwise known as naked lights) shall not b 31 Jul 2014 Alliance Standards Part 10 Section Naked Lights No circuits are drawn for loads without the incorporation of a overcurrent protection device (circuit breaker). Non-Compliance Level: 1 Circuit breakers were not identified with ratings. Location: DB-P-02, DB-P-04 Visual Assessment: Found protective device without identification of their ratings. Provide protective devices (circuit breakers) for all circuits drawn for loads. Install appropriate protection at switchboards and distribution boards for all circuits and sub circuits against short circuit and over current. The protective device shall be Alliance Standards Part 10 Section 10.9 Protection of Circuits Shielding or additional insulation is provided for wiring exposed to external heat sources. Non-Compliance Level: 1 Insulation is not provided for the cables and wiring as required. Visual Assessment: Insulation is not provided for the cables and wiring where needed. Provide insulation for the cables and wiring as required. One of the following methods shall be used to protect wiring systems from heat: (1) shielding; (2) placing 900 mm (36 in.) from the source of heat; (3) selecting a system with due regard for the ad 31 Aug 2014 Alliance Standards Part 10 Section External heat sources. Are all switchboards and/or distribution boards properly grounded (earthed)? The Alliance for Bangladesh Worker Safety Page 11/20

12 25 Feb 2014 All switchboards and/or distribution boards are not properly grounded (earthed). Location: LT-01/Sub-Station/1st FL, DB-N-02,DB-N-04, DB-N-05, DB-N-07, DB-N-09, DB-P-01, DB-P-03, DB-P-04,SDB-01/Lab, SDB-02/Lab, SDB-03/Lab, SDB-04/Lab, SDB-05/Lab,SDB-06/Lab, SDB-08/Lab, SDB- 09/Office, SDB-10/Office, SDB-11/Office, SDB-02/New Rapid,SDB-03/New Rapid, SDB-01/Jigger, SDB-01/Jigger/Office, SDB-03/Comp. Room, SDB- 01/Inspection/GF, SDB-01/Workshop, SDB-02/Standard-04, SDB-04/Boiler Room Photograph: All switchboards and/or distribution boards are not properly grounded (earthed) Provide grounding (earthling) for distribution boards as per BNBC section Panel board cabinets and panel board frames, if of metal, shall be in physical contact with each other and shall be grounded. Where the panel board is used with nonmetallic r Alliance Standard Part 10 Section Circuit and System Earthing Do switchboards and/or distribution boards have capacity information labels? Switchboards and/or distribution boards have no capacity information labels. Location: All DBs. Visual Assessment: Switchboards and/or distribution boards have no capacity information labels. Provide capacity information labels (Maximum current rating, no of circuit breakers etc.) for Switchboards and distribution boards. Capacity labels shall describe the maximum number of protective devices that can be accommodated and the capacity of the bo 31 Aug 2014 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation Are switchboards and/or distribution boards free of dust and debris? Switchboards were found with dust and foreign materials The Alliance for Bangladesh Worker Safety Page 12/20

13 25 Feb 2014 Visual Assessment: As seen on site A planed program maintenance (PPM) system shall be developed and executed to rectify electrical system issues before they become safety hazards. 15 Jan 2015 Alliance Standard Part 10 Section Enclosures Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. No physical means were found to limit the installation of additional over current protective device. Location: All DBs. Visual Assessment: No physical means were found. Switchboards and/or distribution boards shall be provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed following NFPA 70 section Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Each circuit is provided with a dedicated neutral. Circuits are not provided with a dedicated neutral for each load. The use of common neutral for more than one circuit is not permitted in the standard. Location: LT-01/Sub-Station/1st FL, LT- 02/Sub-Station/1st FL, DB-N-02,DB- N-05, DB-N-06, DB-N-07, DB-N-08, DB-N-09, DB-P-01, DB-P-03,DB-P-04, SDB-01/Lab, SDB-02/Lab, SDB-03/Lab, SDB-04/Lab, SDB-05/Lab, SDB- 06/Lab, SDB-07/Lab, SDB-08/Lab, SDB-09/Office, SDB-10/Office, SDB- 11/Office, SDB- 01/Knitting Sec., SDB-02/Knitting Sec., SDB-01/Jigger, SDB- 01/GF,SDB-01/Jigger/Office, SDB-01/Inspection, SDB- 01/Inspection/GF, SDB-02/Standard-04, SDB-02/Standard- 04, SDB-03/Mixer Room Visual Assessment: Circuit is not provided with a dedicated neutral for each load. Provide dedicated neutral for each circuit. The Alliance for Bangladesh Worker Safety Page 13/20

14 25 Feb 2014 Alliance Standards Part 10 Section 10.3 Electrical Wiring and Cabling Are electrical wiring/cables properly identified? Electrical wiring/cables are not properly identified. Location: DB-N-02, DB-N- 03, DB-N-04, DB-N-05, DB-N-06, DB-N-07, DB-N-08, DB-N-09, DB-P-02, DB- P-03, DB-P-04, DB-P-05, DB-P-06, SDB-01/Lab, SDB-02/Lab, SDB-04/Lab, SDB-05/Lab, SDB-06/Lab, SDB-07/Lab, SDB-08/Lab, SDB-09/Office, SDB- 10/Office, SDB-11/Office, SDB- 01/Knitting Sec., SDB-02/Knitting Sec., SDB- 04/Knitting, SDB- 02/New Rapid, SDB-03/New Rapid,SDB-01/Jigger, SDB- 01/GF, SDB- 01/GF, SDB-01/Jigger/Office, SDB-03/Comp. Room, SDB- 01/Inspection, SDB-01/Inspection/GF, SDB-01/Workshop, SDB- 02/Bianca,SDB-02/Standard-04, SDB-03/Mixer Room, SDB-04/Boiler Room Photograph: Electrical wiring/cables are not properly identified. Maintain color code for all cables. For phase conductors use Red, Yellow, Blue, For Neutral conductors use black and For Grounding cable use green dotted yellow. Bangladesh Electricity Rules 1937 Rule 51 and 56 Cable joints are through porcelain/pvc connectors with PIB tape wound around joint. Improper cable joints were found. Location: DB-N-05/Knitting/GF, SDB- 03/New Rapid/GF Photograph: Improper cable joints were found. Re-install cable joints through porcelain/pvc connectors with PIB tape wound around joint. Cable joints shall be installed in accordance with the direction described in the standards to avoid loose connections. Alliance Standards Part 10 Section Cable Joints The Alliance for Bangladesh Worker Safety Page 14/20

15 25 Feb 2014 Electrical connections at equipment, fixtures, etc are properly secured. All connections are not secured. Location: LT-01/Sub-Station/1st FL, LT- 02/Sub-Station/1st FL, DB-N-01, DB-N-02, DB-N-03, DB-N-04, DB-N-06, DB- N-08, DB-N-09, DB-P-01, DB-P-02, DB-P-03, DB-P-05, DB-P-06, SDB- 01/Lab, SDB-02/Lab, SDB-03/Lab, SDB-07/Lab, SDB-02/New Rapid, SDB- 03/New Rapid, SDB-01/Jigger, SDB-01/GF, SDB-01/Jigger/Office, SDB- 01/Comp.Room-01, SDB-01/Inspection, SDB-01/Inspection/GF, SDB- 01/Workshop, SDB-03/Mixer Room, SDB-04/Boiler Room Photograph: All connection are not secured If flexible metallic hose is used for wiring to motors and other equipment, the wiring shall be enclosed to the full length, and the hoses secured properly by approved means. Connections between conductors and between conductors and other equipment shall 31 Aug 2014 Alliance Standards Part 10 Section Electrical Connections Is all electrical wiring/cable properly terminated at its point of termination (No un-terminated wires, lugs are provided at terminals, etc)? Cables are connected without lugs. Location: DB-N-03/GF/Jigger Sec., DB-N- 01/Boiler-01/GF Photograph: Cables are connected without lugs Ensure all electrical wiring/cable properly terminated at its point of termination. Unterminated cables may lead to electrical short circuits. Cables shall be connected to terminals only by soldered or welded lugs, unless the terminals are designed to sec Alliance Standards Part 10 Section Wiring of Sub-distribution Boards The Alliance for Bangladesh Worker Safety Page 15/20

16 25 Feb 2014 Are junction boxes and other electrical devices provided with covers? Junction boxes were installed without covers. Photograph: Junction boxes have no cover. Provide adequate covers for junction boxes and other electrical devices. Proper junction boxes shall be used wherever conductors are joined or crossover of conductors takes place. Junction boxes shall have covers to prevent lint buildup and reduce the po 15 Aug 2014 Alliance Standard Part 10 Section and Mechanical guards are provided for electrical equipment and wiring where necessary. Mechanical guards are not provided for cables. Location: Substation Photograph: Mechanical guard is not provided for cables. Mechanical guards shall be provided for electrical equipment and wiring where necessary. Rotating parts of electrical equipment and wiring shall have mechanical guards. 15 Aug 2014 Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling, Cables, and 10.7 Main Switch, Switchboards And Metal Clad Switchgear Phase separators are provided between terminals on circuit breakers. Low Phase Separator is not installed on circuit breakers. Location: Every floor. Photograph: Phase Separator is not fixed on circuit breakers. Install phase separators between terminal connections at the noted locations. Phase separators are required for the terminals of circuit breakers to prevent arcing and short circuit between phases. The Alliance for Bangladesh Worker Safety Page 16/20

17 25 Feb 2014 Alliance Standard Part 10 Section Electrical Connections Are electrical insulation mats provided in front of substation, switchboards and/or distribution boards? Low Non-Compliance Level: 1 Electrical insulation mats are not provided in front of substation, switchboards and/or distribution boards Location: DB-P-06, SDB-05/Lab, SDB-07/Lab, SDB- 08/Lab, SDB-09/Office, SDB-10/Office, SDB-11/Office, SDB-01/Comp.Room- 01, SDB-02/Bianca Visual Assessment: Electrical insulation mats are not provided in front of substation, switchboards and/or distribution boards Provide electrical insulation mats in front of distribution boards. Graded insulation/rubber mat shall be provided in front of all switchboards and distribution boxes to prevent electrocution. 15 Aug 2014 Alliance Standard Part 10 Section Inspection of the Installation. Are meters and other electrical devices (Ammeter, Voltmeter, PFI Auto Controller, etc) installed on the main electrical equipment operational? Low Non-Compliance Level: 1 Ammeter, Voltmeter are not working in this factory. These meters are the primary source to see the current status of the system. Location: SDB-03/New Rapid, SDB-01/Comp.Room-01 Photograph: Some of the meters and other electrical devices (Ammeter, Voltmeter, PFI Auto Controller, etc.) installed on the main electrical equipment are not operational Ensure meters and other electrical devices installed on the main electrical equipment are operational. Repair or replace as required. 31 Aug 2014 Alliance Standard Inspection of the Installation Signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Low The Alliance for Bangladesh Worker Safety Page 17/20

18 25 Feb 2014 Non-Compliance Level: 1 No signs are posted prohibiting light fixtures without protective covers. Visual Assessment: No indication of prohibition of light fixtures with protective covers. Light fixtures without protective covers (otherwise known as naked lights) shall not be allowed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Install signs posted in Bengali and Engl 15 Aug 2014 Alliance Standards Part 10 Section Naked Lights Emergency Power System Are cable trenches properly covered? Cable trenches are not properly covered. Photograph: Cable trenches are not properly covered Provide adequate non combustible cover on cable trench. All cable trenches shall have covers of noncombustible material. Underground cables for electrical distribution in the remiss/garden/compound of the building shall be encased in GI or PVC pipes and l 15 Aug 2014 Alliance Standard Part 10 Section Inspection of the Installation Are emergency power switchboards, distribution boards, and circuits properly identified? No identification was evident in any area. Visual Assessment: No identification evident here in all areas. All boxes and enclosures (including transfer switches, generators, and power panels) for emergency circuits shall be permanently marked so they will be readily identified as a component of an emergency circuit or system. All emergency power switchboards, 15 Aug 2014 The Alliance for Bangladesh Worker Safety Page 18/20

19 25 Feb 2014 NFPA 70 Chapter 7 Article Wiring, Emergency System Are life safety loads (fire alarm, fire pump, elevators, emergency lighting, exit signage, etc) connecting to the emergency power system? Life safety loads (fire alarm, fire pump, elevators, emergency lighting, exit signage, etc.) are not connected to the emergency power system. Visual Assessment: Life safety loads are not connected to the emergency power system. Provide emergency power for life safety loads. Life safety loads (fire alarm, fire pump, elevators, emergency lighting, exit signage, etc.) shall be connected to the emergency power system to ensure an uninterrupted power supply to this equipment. Alliance Standard Part 10 Section 10.8 Standby Power Are inspection, maintenance, and testing procedures of the emergency generator being completed and documented? Low Non-Compliance Level: 1 No IMT documents were available. Visual Assessment: Document was not found. Establish a routine maintenance and testing program for the emergency generator. Document inspection, maintenance, and testing procedures of the generator. The program shall be based on all of the following: (1) Manufacturer's recommendations (2) NFPA 110 Chapter 8 Are inspection, maintenance, and testing procedures of the UPS being completed and documented? Low Non-Compliance Level: 1 No ITM records for the UPS were available. The Alliance for Bangladesh Worker Safety Page 19/20

20 25 Feb 2014 Visual Assessment: No record found on inspection, maintenance, and testing procedures of the UPS Inspection, maintenance, and testing procedures of the UPS shall be performed and documented. The routine maintenance and operational testing program shall be based on all of the following: (1) Manufacturer's recommendations (2) Instruction manuals (3) Mi Alliance Standard Part 13 Section NFPA 111 Chapter 8 NFPA 70B Chapter 28 Lightning Protection System Is a lightning protection system installed on the building? Non-Compliance Level: Alliance Standards Part 10 Section Lightning Protection. Calculate Risk Index to determine if required. The Alliance for Bangladesh Worker Safety Page 20/20

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Plot #92 (Partial) DEPZ Extention Area-02 Ganakbari, Ashulia, Savar Uttaron 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17 11 Feb 2015 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/15 19

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/6 Introduction to

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory 81, Kalmessar, "Jalal Shopping Complex" Board Bazar, Gazipur. 20 May 2014 The Alliance for Bangladesh Worker Safety Page 1/21 20 May 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 154 Kamrabad, Atarar Depot Chittagong Chittagong Chittagong The Alliance for Worker Safety Page 1/7 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/10 09 Jun 2014 Introduction to

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory RR Washing Limited (previously Freshtex Pvt Ltd (Washing)) Beximco Industrial Park Sarabo, Kashimpur, Gazipur Gazipur Dhaka 12 Jun 2014 The Alliance

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIKDER APPAREL HOSIERY LTD. Khadun (Dug No. 342/343), Tarabo, Rupgonj, Narayanganj, Bangladesh. Factory List: 1. Sikder Apparel Hosiery Ltd. Inspected by: Pema Wangdi

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIDKO LIMITED PLOT NO. 36, ROAD NO. 46, GULSHAN NORTH C/A, DHAKA. Factory List: 1. N. A. Garments 2. 3. Sidko Apparels 4. Delta Ties Ltd. Inspected on April 17, 2014

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MILLENNIUM TEXTILES (SOUTHERN) LTD., Bara Rangamatia, Ashulia, Savar, Dhaka 1341, Bangladesh Factory List: MILLENNIUM TEXTILES (SOUTHERN) LTD., Inspected on April 8,

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc. Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MUAZUDDIN TEXTILES LTD. Plot # 235/236, East Chandura, Shafipur, Kaliakor, Gazipur, Bangladesh. Factory List: 1. Inspected by: Younten Jamtsho Report Generated by: Stabak

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

Systems of inspecting the existing building and the procedures of auditing engineering plans. M. Mostafa

Systems of inspecting the existing building and the procedures of auditing engineering plans. M. Mostafa Systems of inspecting the existing building and the procedures of auditing engineering plans M. Mostafa 2 Agenda 1. Introduction 2. Why inspection? 3. Initial Verification 4. Periodic verification 5. Reference

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2

Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2 Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2 By: Martin Robinson, CEO of IRISS Group and Level III Thermographer Abstract Every year thousands electrical workers are injured

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

Neil Hewitt Electrical & Air Conditioning P/L

Neil Hewitt Electrical & Air Conditioning P/L VISUAL SAFETY EXAMINATION / INSPECTION CHECKLIST Examination / inspection checklist Customer:... Date:... Address:... Phone:...... Mobile:... Contact:... Inspection Activity Yes No NA General Basic protection

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

Indian Standards On Fire and Electrical Safety. A K Purohit, Scientist E Bureau of Indian Standrds Bhubaneswar

Indian Standards On Fire and Electrical Safety. A K Purohit, Scientist E Bureau of Indian Standrds Bhubaneswar Indian Standards On Fire and Electrical Safety A K Purohit, Scientist E Bureau of Indian Standrds Bhubaneswar Electrical and Fire Safety Why? LIFE SAFETY PROPERTY PROTECTION Electrical Accidents-Statistics

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAGPIE COMPOSITE TEXTILE LTD. 832/833, DEWAN IDRIS ROAD, AMTOLI, ASHULIA, SAVAR, DHAKA OTHER FACTORIES: NONE May 17, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/17/2014

More information

Electrical Management

Electrical Management 5 WHS PROCEDURE P23-01 Page 1 of 9 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment within the mission

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER PRESSIONAL P-16 PRESSIONAL PRESSIONAL PRESSIONAL 1 ONE LINE DIAGRAM 3 EMEGENCY LIGHTING SCHEME 2 FEEDER SCHEDULE PRESSIONAL PRESSIONAL PRESSIONAL PRESSIONAL LOCAL SINGLE POLE SWITCH 3-WAY SWITCH 3-WAY

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671 Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND ADMINISTRATION ADMINISTRATION 301.1.2 LP-Gas installations. Whenever there is a conflict between this code and NFPA 54 and B+NFOA 58 as adopted by the Nevada LP-Gas

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information