INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

Size: px
Start display at page:

Download "INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)"

Transcription

1 INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22

2 27 May 2014 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/22

3 27 May 2014 GENERAL INFORMATION General Information Factory Name: Country: Province: City: Bangladesh Dhaka Rupgonj Zip Code: 1464 Audit Duration: Re-Audit: 2 Days Re-Audit After 0 Months Draft Report Date : Final Report Date : Are all action items from previous assessment complete? : Buildings in Complex : Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : Approximate Building Area (SF) : N/A There are 13 buildings in the factory premises out of which five are main production buildings and eight are ancillary buildings. The buildings are named as: 1) Three story RCC Accessories Building, 2) Single story prefabricated Processing shed, 3) Three story pre-fabricated chemical godown shed, 4) Two story pre-fabricated Weaving Shed Unit-2, 5) Two story RCC utility building with pre-fabricated shed at roof unit-1, 6)Three story RCC office building, 7) Two story pre-fabricated utility shed unit-2, 8) Three story RCC staff quarter, 9) Single story Medical Center, Child Care and pump room pre-fabricated shed, 10) Single story pre-fabricated grey & yarn Shed, 11) Two story pre-fabricated weaving shed unit-1, 12) Two story pre-fabricated warping shed, 13) Two story pre-fabricated towel shed. Owned Information provided below as per following format: est occupied floor level [Height up to roof], Stories above grade, Stories below grade, Occupied levels. 1) Accessories Building: ft [68.88 ft], 3, 0, 3. 2) Processing shed: 1 ft [14.76 ft], 1, 0, 1. 3) Chemical Godown shed: ft [68.88 ft], 3, 0, 3. 4) Weaving Shed Unit-2: ft [29.52 ft], 2, 0, 2. 5) Utility building Unit-1: ft [32.80 ft], 3, 0, 3. 6) Office building: ft [32.80 ft], 3, 0, 3. 7) Utility shed unit-2: ft [29.52 ft], 2, 0, 2. 8) Staff quarter: ft [36.08 ft], 3, 0, 3. 9) Medical Center shed: 1 ft [10.0 ft], 1, 0, 1. 10) Yarn Shed: 1 ft [14.76 ft], 1, 0, 1. 11) Weaving shed unit-1: ft [29.52 ft], 2, 0, 2. 12) Warping shed: ft [29.52 ft], 2, 0, 2. 13) Towel shed with basement: ft [22.96 ft], 2, 1, 3. Total area of buildings in the factory premises: SF. Building wise breakdown as follows: 1) Three story RCC Accessories Building: SF, 2) Single story pre-fabricated Processing shed: SF, 3) Three story pre-fabricated Chemical Godown shed: SF, 4) Two story pre-fabricated Weaving The Alliance for Bangladesh Worker Safety Page 3/22

4 27 May 2014 Shed Unit-2: SF, 5) Two story RCC utility building with pre-fabricated shed at roof unit-1: SF, 6) Three story RCC office building: SF, 7) Two story pre-fabricated utility shed unit-2: SF, 8) Three story RCC staff quarter: SF, 9) Single story Medical Center, Child Care and pump room pre-fabricated shed: SF, 10) Single story pre-fabricated grey & yarn Shed: SF, 11) Two story pre-fabricated weaving shed unit-1: SF, 12) Two story pre-fabricated warping shed: SF, 13) Two story pre-fabricated towel shed with basement: SF. Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Approximate Ancillary Structures Area (SF) : Number of Occupants : Provide brief description of the electrical system for each building.: Physical location of Substation? : What equipment/loads does the UPS serve? : Factory personnel informed the date of construction as follows: 1) Accessories Building: Started in 2006 and finished in 2008, 2) Processing shed: Started in 2005 and finished in 2006, 3) Chemical godown shed: Started in 2007 and finished in 2008, 4) Weaving Shed Unit-2: Finished in 2007, 5) Utility building unit-1: Started in 2005 and finished in 2007, 6) Office building: Started in 2006 and finished in 2007, 7) Utility shed unit-2: Started in 2007 and finished in 2009, 8) Staff quarter: Started in 2007 and finished in 2008, 9) Medical Center shed: Started in 2011 and finished in 2012, 10) Grey & yarn Shed: Started in 2011 and finished in 2012, 11) Weaving shed unit-1: Started in 2005 and finished in 2007, 12) Warping shed: Started in 2006 and finished in 2007, 13) Towel shed with basement: Started in 2009 and finished in No record for date of building renovation or addition was found from factory personnel. 1) Three story RCC Accessories Building, 2) Three story pre-fabricated Chemical Godown shed, 3) Two story RCC utility building with pre-fabricated shed at roof unit-1, 4) Three story RCC office building, 5) Two story pre-fabricated utility shed unit-2, 6) Three story RCC staff quarter, 7) Single story Medical Center, Child Care and pump room pre-fabricated shed, 8) Single story pre-fabricated grey & yarn Shed. 1) Three story RCC Accessories Building: SF (Ground floor: SF, 1st Floor: SF, 2nd Floor: SF), 2) Three story pre-fabricated Chemical Godown shed: SF (Ground floor: SF, 1st Floor: SF, 2nd floor: SF), 3) Two story RCC utility building with prefabricated shed at roof unit-1: SF (Ground floor: SF, 1st floor: SF, 2nd floor area: SF), 4) Three story RCC office building: SF (Ground floor: SF, 1st floor: SF, 2nd floor: SF), 5) Two story pre-fabricated utility shed unit-2: SF (Ground floor: SF, 1st floor: SF), 6) Three story RCC staff quarter: SF (Ground floor: SF, 1st Floor: SF, 2nd floor: SF), 7) Single story Medical Center, Child Care and pump room pre-fabricated shed: SF, 8) Single story pre-fabricated grey & yarn Shed: SF. Total number of occupants: ) Three Story RCC Accessories Building: 45, 2) Single story pre-fabricated Processing shed: 920, 3) Three story pre-fabricated chemical godown shed: 25, 4) Two story pre-fabricated Weaving Shed Unit-2: 1230, 5) Two story RCC utility building with pre-fabricated shed at roof unit-1: 14, 6) Three story storied RCC office building: 135, 7) Two story storied pre-fabricated utility shed unit-2: 7, 8) Three story RCC staff quarter: 79, 9) Single story Medical Center, Child Care and pump room pre-fabricated shed: 16, 10) Single story pre-fabricated grey & yarn Shed: 320, 11) Two story pre-fabricated weaving shed unit-1: 1320, 12) Two story pre-fabricated warping shed: 225, 13) Two story pre-fabricated towel shed with basement: KV REB feed to a 1500 KVA 33 KV / KV Oil type Transformer, Gas Generator 1125 KVA-5, Gas Generator 1175 KVA-1, Gas Generator 1752 KVA-1, Gas Generator 1770 KVA-1, Gas Generator 1330 KVA-3 and Gas Generator 1295 KVA-2 connected with 3-phase 4-wire electrical distribution system and Distribution boards. Substations are located in Utility Building-1, Utility Building-2, Utility Building-3, Ground Floor. Emergency Light, exit signage and fire alarm system. The Alliance for Bangladesh Worker Safety Page 4/22

5 27 May 2014 The Alliance for Bangladesh Worker Safety Page 5/22

6 27 May 2014 ASSESSMENT FINDINGS Electrical System Maintenance Is a periodical Insulation Resistance Measurement Program established and recorded? No periodical Insulation Resistance Measurement Program has been established. Document Review: No periodical Insulation Resistance Measurement Program. Develop an Insulation Resistance Measurement Program that ensures deterioration of insulation resistance will be identified quickly. Testing should be in compliance with International Electrical Testing Association (NETA). All transformers, switchgears etc. shall be subject to an insulation resistance measurement test to ground after installation but before any wiring is connected. Insulation tests shall be made between open contacts of circuit breakers, switches etc. and between each phase and earth. Alliance Standard Part 10 Section Insulation Tests and Electrical Inspections Are thermographic scans of electrical equipment completed at least every three years? Thermographic scans of electrical equipment are not completed. Document Review: No thermographic scans for electrical equipment. Complete thermographic scans at least on a three year cycle. Thermographic scans should be completed in accordance with the Standard for Infrared Inspection of Electrical Systems & Rotating Equipment and NFPA70B or a comparable standard Alliance Standards Part 10 Section Electrical Inspections Transformers do not contain harmful substances such as PCBs. The Alliance for Bangladesh Worker Safety Page 6/22

7 27 May 2014 No documents were found to review, so it cannot be verified if the transformer does not contain harmful substances such as PCBs. Document Review: Oil test report (containing information of harmful substances such as PCBs) was not found. Consider replacing transformer with harmful substances to reduce health hazards. Not Applicable A transformer oil analysis is routinely completed on main service transformers. Low Transformer oil analysis is not routinely completed on main service transformer. Document Review: Transformer oil analysis is not routinely completed. Complete an oil analysis on applicable transformers at appropriate intervals based on voltage and power. Alliance Standard Part 10 Section Electrical Inspections Electrical System Conditions Are all switchboards and/or distribution boards metal enclosed with a dead front construction? Distribution boards are metal enclosed but don't have dead front construction. Location: All distribution boards. Photograph: Metal enclosure with no dead front construction. Ensure distribution boards are metal enclosed with a dead front construction. 28 Jun 2014 The Alliance for Bangladesh Worker Safety Page 7/22

8 27 May 2014 Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Wet type transformers are not leaking and have appropriate levels. Non-Compliance Level: 2 Main incoming transformer is not leaking but the instrument transformer (415 V/575 V) used to supply weaving machine is leaking. Oil level is appropriate. Location: Weaving-1, Ground Floor. Photograph: Transformer is leaking. Ensure that wet type transformer is not leaking and have appropriate oil levels. Alliance Standards Part 10 Section 10.5 Substation Do switchboards and/or distribution boards have a minimum clearance of 1 m (39 in) in front? Distribution boards are not provided with adequate clearance. Location: MDB- Warping-4-GF-Weaving-2, BOX-ETP-2-ETP-2nd Floor, BOX-ETP-1-ETP-2nd Floor, MDB-Towel (Sizing/Warping)-GF-Towel Building, SDB-Towel (Mending)-GF-Towel Building, DB-Towel-Dyeing (LDB-1)-GF-Towel Building, MDB-Towel Dyeing-Electrician Room-GF-Towel Building, MDB-Ingraving Processing-GF-Processing Section, DB-PI (Light)-GF-Processing. Photograph: Inadequate clearance in front of distribution boards. Provide clearance of at least 1 m (39 in) in front of distribution boards. 28 Jun 2014 Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear The Alliance for Bangladesh Worker Safety Page 8/22

9 27 May 2014 Switchboards and/or panelboards are not installed above gas stoves or sinks or within 2.5m of any washing unit in washing rooms or laundries. Switchboards are installed near sinks. Location: General Store-1st Floor- Chemical godown building, Yarn & Fabrics mending. Photograph: Switchboard installed in an improper location. Ensure switchboards and panel boards are not installed above gas stoves or sinks or within 2.5m of any washing unit in washing rooms or laundries. Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear No circuits are drawn for loads without the incorporation of a overcurrent protection device (circuit breaker). Circuits are drawn for panel indicators without the incorporation of an over current protection device (circuit breaker). Location: DB-Lighting-2-GF- Weaving-2, DB-Fan-2 (Ist Floor)-Towel Building, MDB-Towel Stitching-1st Floor-Towel Building, DB-Towel (Stitching) (LDB-1)-1st Floor-Towel Building, MDB-WTP-Thermoboiler Room. Photograph: No protection device. Ensure over an current protection device (circuit breaker) is installed for each and every load. 12 Jul 2014 Alliance Standards Part 10 Section 10.9 Protection of Circuits Indications of overheating, overloading, or signs of burning were not observed. Indications of overheating were observed. Location: LT PANEL 2.1 (lower)- GF-Utility-3 (72.9 C), LT PANEL 2.1 (upper)-gf-utility-3 (76.2 C), MDB-5/3.1- GF-Utility-3 (77.4 C), MDB-Boiler-1-Boiler Room-1-Utility-1 (91.3 C), MDB- GF(8)-GF-Compressor Room-Utility-3 (109.7 C), MDB-GF (6) LEFT-GF-Utility- 2-Pump room-1 (78.2 C), Box-Emergency light-gf Weaving-1 (92.5 C), MDB- Sizing (left) GF-Weaving-2-X-former room (79.8 C). The Alliance for Bangladesh Worker Safety Page 9/22

10 27 May 2014 Photograph: Indications of overheating were observed. Find out the cause of overheating and take proper action. 31 May 2014 Alliance Standard Part 10 Section Is electrical wiring/cables sized according to capacity of circuit breakers (No higher rated circuit breakers with lower rated wiring)? Electrical wiring and cables are not sized according to capacity of circuit breakers. Location: DB-GF-4-Weaving-1, DB-10 (GF)-Weaving-1, DB-14-GF- Weaving-1, DB -16-GF-Weaving-1, MDB-Stitching-2-1st Floor-Stitching-2, DB- Lighting-1-1st Floor-Stitching-2, MDB-Ingraving Processing-GF-Processing Section. Photograph: er rated circuit breakers with lower rated wiring. Consult with a qualified Electrical Engineer and ensure electrical wiring and cables are sized according to capacity of circuit breakers. Alliance Standard Part 10 Section Electrical Connections. No multi looping of wiring/cables observed at circuit breakers within switchboards and/or distribution boards. Multi looping of cables are observed at circuit breakers & busbar within switchboards and distribution boards. Location: DB-Loom-7-GF-Weaving-2, DB-Loom-4-GF-Weaving-2, DB-Loom-3-GF-Weaving-2, DB-Loom-1-GF- Weaving-2, DB-1st-3-Finishing Folder-1st Floor-Stitching-1, BOX-5-1st Floor- Stitching-1, BOX-ETP-3-ETP-2nd Floor, DB Towel Engraving, DB Towel Sewing M/C-2, DB Towel Sewing M/C-1-Towel Building. Photograph: Multi looping of cables at circuit breakers and busbar. Remove multi looping of cables at circuit breakers & busbar within switchboards and distribution boards. Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling The Alliance for Bangladesh Worker Safety Page 10/22

11 27 May 2014 All metal in the building is connected to the building earthing/grounding system such as metal rebar in concrete, metal frame of building, or metal water pipe. Cable tray and MS stair in the building are not connected to the building earthing system. Location: Cable Tray-Thermoboiler Room, Generator Room- Utility-1, MS Stair (Beside Fire control room). Worker Interviews: Cable tray and MS stair in the building are not connected to the building earthing system. Connect Cable trays and MS stairs to the building earthing system. Alliance Standard Part 10 Section Earthing Light fixtures without protective covers are not installed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Light fixtures without protective covers are installed in storage areas. Location: Accessories Store-GF-Weaving-1, Finished Goods Store-1st Floor-Weaving-1. Photograph: Naked light fixtures are installed in storage areas. Ensure light fixtures without protective covers are not installed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. 31 May 2014 Alliance Standards Part 10 Section Naked Lights Wiring systems are selected and erected so that no damage is caused by the ingress of water. Wiring systems are not selected and erected considering the effect of damage caused by ingress of water. Location: Near ETP drain-1st Floor-ETP Building, Roof Top-Foreign Staff Quarter. The Alliance for Bangladesh Worker Safety Page 11/22

12 27 May 2014 Photograph: May damage due to ingress of water. Ensure wiring systems are selected and erected so that no damage is caused by the ingress of water. 12 Jul 2014 Alliance Standards Part 10 Section Presence of Water Do switchboards and/or distribution boards have clear identification markings? Distribution boards do not have clear identification markings. Location: All distribution boards. Photograph: No clear identification markings. Ensure clear and permanent identification marks are painted in all distribution boards, switchboards, sub main boards and switches. 28 Jun 2014 Alliance Standard Part 10 Section 10.7 BNBC Part 8 Section Do switchboards and/or distribution boards have capacity information labels? Distribution boards do not have capacity information labels. Location: All distribution boards. Photograph: No DB capacity information labels. Provide capacity information labels (Maximum current rating, no of circuit breakers etc.) for distribution boards. 12 Jul 2014 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation The Alliance for Bangladesh Worker Safety Page 12/22

13 27 May 2014 Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. Distribution boards are not provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated and listed. Location: All distribution boards. Photograph: No means to prevent the installation of more over current devices. Ensure proper rating for distribution boards and provide physical means to prevent the installation of more over current devices than that number for which the panel board is rated. Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Power and telecommunication or antenna cables are led in separately. Power and telecommunication cables are not led in separately. Location: IT department-2nd Floor, Marketing-1st Floor, Finance department-ground Floor, Office building. Photograph: Power and telecommunication cables are not separated. Lead telecommunication cables separately to the main point of service. Power and telecommunications cables must have separate entrance. Alliance Standards Part 10 Section Service Entry Are all internal components of switchboards and/or distribution boards properly concealed (No missing circuit breaker or knockout covers)? Internal components of switchboards are not properly concealed. Location: Switchboard-1st Floor-Utility-1 Building. Photograph: Internal components are not properly concealed. The Alliance for Bangladesh Worker Safety Page 13/22

14 27 May 2014 Provide covers or blanks to conceal all live internal components of switchboards and distribution boards. 28 Jun 2014 Alliance Standard Part 10 Section Sub-Distribution Boards Are all switchboards and/or distribution boards properly grounded (earthed)? Distribution boards are not grounded. Location: DB-GF-5-Weaving-1, MDB- Warping-4-GF-Weaving-2, BOX-EL-GF-Weaving-2. Photograph: No grounding of distribution boards. Provide grounding for switchboards and distribution boards as per BNBC section Alliance Standard Part 10 Section Circuit and System Earthing Are switchboards and/or distribution boards free of dust and debris? Distribution boards are not clean. Location: SDB-GF (5.1)-Weaving-1, SDB-GF (5.2)-Weaving-1, DB-Overhead-1-AC Plant-GF-Weaving-2, DB-Overhead-2- AC Plant-GF-Weaving-2, BOX-ETP-3-ETP-2nd Floor, BOX-ETP-2-ETP-2nd Floor, BOX-ETP-1-ETP-2nd Floor, MDB-ETP-ETP-2nd Floor. Photograph: Dirt found in distribution boards. Ensure distribution boards free of dirt and debris. 28 Jun 2014 Alliance Standard Part 10 Section Enclosures The Alliance for Bangladesh Worker Safety Page 14/22

15 27 May 2014 Each circuit is provided with a dedicated neutral. Each circuit is not provided with a dedicated neutral. Location: MDB-GF (5)- Weaving-1, DB-GF (22)-Weaving-1, MDB-GF-1-Weaving-1, DB-GF-1- Weaving-1, MDB-GF-3-Weaving-1, DB-GF-2-Weaving-1, DB-GF-8-Weaving- 1, DB-GF-9-Weaving-1, SDB-GF (3)-Weaving-1, DB-GF-13-Weaving-1, DB - 17-GF-Weaving-1, DB-GF-17-Weaving-1, SDB-GF (5.1)-Weaving-1, SDB-GF (5.2)-Weaving-1, MDB-Loom-Tx-Room-GF-weaving-2, DB-1st-2-Finishing Folder-1st Floor-Stitching-1, SDB-1-1st Floor-Stitching-1, SDB-2-1st Floor- Stitching-1, BOX-1-1st Floor-Stitching-1, DB-Lighting-2-1st Floor-Stitching-2, DB-Lighting-3-1st Floor-Stitching-2, DB-Lighting-4-1st Floor-Stitching-2, DB- Machine-1-1st Floor-Stitching-2, DB-Machine-2-1st Floor-Stitching-2, DB- Machine-3-1st Floor-Stitching-2, DB-5-Quilting-1st Floor-Stitching-2, SDB- Quilting-1st Floor-Stitching-2, DB-Towel (Sizing/Warping)-GF-Towel Building, MDB-Towel (Lighting)-GF-Towel Building, DB-Towel (Lighting-1)-GF-Towel Building, DB-Towel (Lighting-2)-GF-Towel Building, MDB-Towel(Loom-1)-GF- Towel Building, MDB-Towel (Loom-2)-GF-Towel Building, SDB-Towel (Mending)-GF-Towel Building, MDB-Towel-Dyeing-Anglada-GF-Towel Blgd, DB-Towel-Dyeing (LDB-2)-GF-Towel Building, DB-Colour Kitchen (LDB)-GF- Towel Building, MDB-Flat Belt-GF-Towel Building, DB-Flat Belt (LDB-1)-GF- Towel Building, DB-Flat Belt (LDB-2)-GF-Towel Building, DB-Towel (Ingraving)-GF-Towel Building, DB-Towel-Stitching-Office-1st Floor-Towel Building, DB-Fan-2 (Ist Floor)-Towel Building, DB-Towel (Stitching)-M/C-3-1st Floor-Towel Building, DB-Processing Ingraving-1-GF-Processing Section. Photograph: No dedicated neutral. Provide dedicated neutral for each circuit. Alliance Standards Part 10 Section 10.3 Electrical Wiring and Cabling Are electrical wiring/cables properly identified? Electrical wiring and cables are not properly identified. Location: DB-11 (GF)- Weaving-1, SDB-Loom-Ground Floor-Weaving-1, MDB-Sizing-Tx Room-GF- Weaving-2, DB-Office-1st Floor-Stitching-2, DB-Towel (Ingraving)-GF-Towel Building, DB-PI (Light)-GF-Processing, SDB-Fabrics Godown-Ground Floor. Photograph: Electrical wiring and cables are not identified. Ensure the means of identification is obtained by separate color coding, marking tape, tagging or other approved means. The Alliance for Bangladesh Worker Safety Page 15/22

16 27 May 2014 Bangladesh Electricity Rules 1937 Rule 51 and 56 Electrical wiring and conduit is properly supported. Electrical wiring and conduit is not properly supported. Location: Roof Top- Weaving-1 Building. Photograph: Inadequate cable support. Provide adequate supports for electrical wiring and conduit. 12 Jul 2014 Alliance Standard Part 10 Section , , and Stranded conductors having a nominal cross-sectional area 6mm2 or greater are provided with cable sockets. Conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. Cable sockets are not provided for stranded conductors. Location: DB-Fire Control Room. Photograph: No cable socket used. Provide cable sockets for stranded conductors having a nominal crosssectional area 6 mm2 or greater. For conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. 12 Jul 2014 Alliance Standards Part 10 Section Cable Ends Cable joints are through porcelain/pvc connectors with PIB tape wound around joint. Improper cable joints were found. Location: Fire Control Room. Photograph: Improper cable joint. The Alliance for Bangladesh Worker Safety Page 16/22

17 27 May 2014 Ensure cable joints are through porcelain or PVC connectors with PIB tape wound around joint. Alliance Standards Part 10 Section Cable Joints Electrical connections at equipment, fixtures, etc are properly secured. Electrical connections at equipment are not properly secured. Location: Grey & Yarn Godown-Mending Section. Photograph: Electrical connections are not secured. Ensure electrical connections at equipment, fixtures etc. are properly secured. 12 Jul 2014 Alliance Standards Part 10 Section Electrical Connections Is all electrical wiring/cable properly terminated at its point of termination (No un-terminated wires, lugs are provided at terminals, etc)? Electrical wire is not properly terminated. Location: DB (Old)-Fire Control Room. Photograph: Un-terminated wire. Ensure all electrical wiring properly terminated at its point of termination. Alliance Standards Part 10 Section Wiring of Sub-distribution Boards Mechanical guards are provided for electrical equipment and wiring where necessary. No mechanical guards are provided for electrical equipment where necessary. The Alliance for Bangladesh Worker Safety Page 17/22

18 27 May 2014 Location: Motor-Ground Floor-Warping-Utility-2 Building, Motor-In Front of Thermo boiler Room, Motor-Ground Floor-Mending Section-Fabrics & Yarn Store. Photograph: No mechanical guards. Provide mechanical guards for electrical equipment where necessary. 28 Jun 2014 Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling, Cables, and 10.7 Main Switch, Switchboards And Metal Clad Switchgear Signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Low No signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Location: Accessories Store-GF-Weaving-1, Finished Goods Store-1st Floor-Weaving-1, Garments accessories Store-2nd Floor-Weaving-1, Yarn Godown-Basement-Towel Bldg, Chemical Store- Basement-Towel Bldg, Chemical Sub Store-Dyeing-GF-Towel Bldg, Wastage Godown-Basement-Towel Bldg. Photograph: No signage indicating the prohibition of installation of naked light fixtures. Ensure signage indicating the prohibition of light fixtures without protective covers is installed at required locations. 28 Jun 2014 Alliance Standards Part 10 Section Naked Lights Are electrical insulation mats provided in front of substation, switchboards and/or distribution boards? Low Electrical insulation mats are not provided in front of switchboards and distribution boards. Location: DB-GF-21-Weaving-1, MDB-AC Plant-AC Plant- GF-Weaving-2, MDB-Warping-4-GF-Weaving-2, DB-Loom-4-GF-Weaving-2, DB-Lighting-1-GF-Weaving-2, BX-Reed Cleaner-GF-Weaving-2, DB-1/7-1st Floor-Stitching-1, MDB-ETP-2nd Floor. Photograph: No mats are provided in front of switchboards and distribution boards. The Alliance for Bangladesh Worker Safety Page 18/22

19 27 May 2014 Provide electrical insulation mats in front of switchboards and distribution boards. 28 Jun 2014 Alliance Standard Part 10 Section Inspection of the Installation. Phase separators are provided between terminals on circuit breakers. Low Phase separators are not provided between terminals on circuit breakers. Location: MDB-GF (5)-Weaving-1, MDB-GF-1-Weaving-1, DB-GF-1-Weaving- 1, DB-GF-2-Weaving-1, DB-GF-5-Weaving-1, DB-11(GF)-Weaving-1, DB-GF- 13-Weaving-1, SDB-Loom-Ground Floor-Weaving-1, MDB-AC Plant-AC Plant- GF-Weaving-2, DB-Overhead-1-AC Plant-GF-Weaving-2, DB-Overhead-2-AC Plant-GF-Weaving-2, MDB-Warping-4-GF-Weaving-2, MDB-Sizing-Tx Room- GF-Weaving-2, MDB-Workshop-Tx Room-GF-Weaving-2, MDB-Workshop-Tx- Room-GF-Weaving-2, DB-Loom-7-GF-Weaving-2, DB-Loom-6-GF-Weaving-2, DB-Loom-5-GF-Weaving-2, DB-Loom-4-GF-Weaving-2, DB-Loom-3-GF- Weaving-2, DB-Loom-1-GF-Weaving-2, SDB-2-1st Floor-Stitching-1, SDB-3-1st Floor-Stitching-1, MDB-Stitching-2-1st Floor-Stitching-2, DB-Lighting-1-1st Floor-Stitching-2, DB-Lighting-2-1st Floor-Stitching-2, DB-Lighting-4-1st Floor- Stitching-2, DB-Machine-1-1st Floor-Stitching-2, DB-Machine-2-1st Floor- Stitching-2, DB-Machine-3-1st Floor-Stitching-2, DB-Office-1st Floor-Stitching- 2, DB-5-Quilting-1st Floor-Stitching-2, MDB-ETP-ETP-2nd Floor, DB-Chemical Store-Basement-Towel Building, MDB-Towel (Sizing/Warping)-GF-Towel Building, MDB-Towel-Dyeing-Anglada-GF-Towel Bldg, DB-Colour Kitchen (LDB)-GF-Towel Building, DB-Towel (Raising)-GF-Towel Building, MDB-Flat Belt-GF-Towel Building, DB-Towel (Ingraving)-GF-Towel Building, MDB-Towel Stitching-1st Floor-Towel Building, DB-Towel (Stitching) (LDB-1)-1st Floor- Towel Building. Photograph: No phase separator. Install phase separators between terminal connections at the noted locations. 12 Jul 2014 Alliance Standard Part 10 Section Electrical Connections Emergency Power System Is the generator room properly rated and physically separated from the remainder of the building? The generator room does not have the required fire rating but is physically separated (approximately 4 m gap between two buildings) from the remainder The Alliance for Bangladesh Worker Safety Page 19/22

20 27 May 2014 of the building. Location: Utility-2 Building, Ground Floor. Photograph: No fire rating for generator room. Provide adequate fire rating for generator room. 12 Jul 2014 Alliance Standards Part 10 Section Generator Room Are cable trenches properly covered? Cable trenches are not covered properly. Location: Cable Trench Utility-2 Building. Photograph: Inadequate cable trench cover Provide adequate cover on cable trench. 28 Jun 2014 Alliance Standard Part 10 Section Inspection of the Installation Are emergency power switchboards, distribution boards, and circuits properly identified? Emergency power distribution boards are not properly identified. Location: All emergency distribution boards. Photograph: Improper identification of emergency distribution boards. Ensure proper identification of all emergency power distribution boards. It may be color paint or metal sticker permanently affixed with door. 28 Jun 2014 NFPA 70 Chapter 7 Article Wiring, Emergency System Are inspection, maintenance, and testing procedures of the UPS being completed and documented? Low The Alliance for Bangladesh Worker Safety Page 20/22

21 27 May 2014 Inspection, maintenance and testing procedures of the IPS are not being completed. Visual Assessment: Inspection, maintenance and testing procedures of the IPS are not being completed. Establish an inspection testing and maintenance program for the Uninterruptible Power Supply (UPS)and/or Instant Power Supply (IPS) associated components. The program must be based on the following: (1) Manufacturer's recommendations (2) Manufacturer's instruction manuals (3) Minimum Requirements of NFPA 111 Chapter 8 (4) Minimum Requirements of NFPA 70B Chapter 28. Alliance Standard Part 13 Section NFPA 111 Chapter 8 NFPA 70B Chapter 28 Are inspection, maintenance, and testing procedures of the emergency generator being completed and documented? Low Inspection, maintenance and testing procedures of the emergency generators are being completed but not documented properly. Photograph: Inspection, maintenance and testing procedures of the emergency generators being completed but not documented properly. Ensure inspection, maintenance, and testing procedures of the emergency generator being completed and properly documented. 25 Jul 2014 NFPA 110 Chapter 8 Lightning Protection System The air termination network vertical and horizontal conductors are appropriately spaced. As built electrical drawing (SLD) for the lightning protection system was not available to review whether the air termination network vertical conductors are appropriately spaced or not. Document Review: No as-built drawing is found. The Alliance for Bangladesh Worker Safety Page 21/22

22 27 May 2014 Consult with an Expert Electrical Engineer and ensure the system is secured against lightning. 12 Jul 2014 Alliance Standards Part 10 Section Lightning Protection The appropriate number of down conductors are installed based on the building size. The as built electrical drawing (SLD) for the lightning protection system was not available to review, so appropriate number of down conductors needed can not be verified. Document Review: No as-built drawing was found. Consult with an Expert Electrical Engineer and ensure your system is secured against lightning. 12 Jul 2014 Alliance Standards Part 10 Section Lightning Protection The Alliance for Bangladesh Worker Safety Page 22/22

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17 11 Feb 2015 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory 81, Kalmessar, "Jalal Shopping Complex" Board Bazar, Gazipur. 20 May 2014 The Alliance for Bangladesh Worker Safety Page 1/21 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Plot #92 (Partial) DEPZ Extention Area-02 Ganakbari, Ashulia, Savar Uttaron 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/15 19

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/6 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 154 Kamrabad, Atarar Depot Chittagong Chittagong Chittagong The Alliance for Worker Safety Page 1/7 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/10 09 Jun 2014 Introduction to

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory RR Washing Limited (previously Freshtex Pvt Ltd (Washing)) Beximco Industrial Park Sarabo, Kashimpur, Gazipur Gazipur Dhaka 12 Jun 2014 The Alliance

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIKDER APPAREL HOSIERY LTD. Khadun (Dug No. 342/343), Tarabo, Rupgonj, Narayanganj, Bangladesh. Factory List: 1. Sikder Apparel Hosiery Ltd. Inspected by: Pema Wangdi

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIDKO LIMITED PLOT NO. 36, ROAD NO. 46, GULSHAN NORTH C/A, DHAKA. Factory List: 1. N. A. Garments 2. 3. Sidko Apparels 4. Delta Ties Ltd. Inspected on April 17, 2014

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MUAZUDDIN TEXTILES LTD. Plot # 235/236, East Chandura, Shafipur, Kaliakor, Gazipur, Bangladesh. Factory List: 1. Inspected by: Younten Jamtsho Report Generated by: Stabak

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

Assessing Your Airfield Electrical Distribution System

Assessing Your Airfield Electrical Distribution System Assessing Your Airfield Electrical Distribution System PRESENTED AT The 2017 Airports Conference March 30, 2017 Hershey, PA PRESENTED BY Samuel Mullen, III - Burns Engineering, Inc. 1 Presentation Objective

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671 Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

El 0. El 0. El El. El El. El 0 TWO FAMILY HOUSING INSPECTINO CHECKLIST

El 0. El 0. El El. El El. El 0 TWO FAMILY HOUSING INSPECTINO CHECKLIST ONE TWO FAMILY HOUSING INSPECTINO CHECKLIST Owner Name Property address Date of Inspection Inspector AREA OF INSPECTION COMPLAINT COMMENTS 1 Fences 2 Dumpsters 3 Trash building materials junk cars branches

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

Electrical Management

Electrical Management 5 WHS PROCEDURE P23-01 Page 1 of 9 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment within the mission

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A Electrical Installation & Test Engineers DETAILS OF THE CLIENT Client / Freshco Food Stores, Kiln Park Business Estate, Milton Keynes, MK3 5FS ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information