1 INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17

2 11 Feb 2015 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/17

3 11 Feb 2015 GENERAL INFORMATION General Information Factory Country: Province: City: Bangladesh Chittagong Chittagong Zip Code: 4204 Audit Duration: Re-Audit: 1 Days Re-Audit After 0 Months Draft Report Date : 15/02/2015 Final Report Date : 26/02/2015 Are all action items from previous assessment complete? : Buildings in Complex : Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : N/A There are eight buildings in the factory premises out of which one is main production building and seven are ancillary buildings. The buildings are named as: 1) Six story main production building, 2) Single story security building, 3) Single story compressor building, 4) Single story compressor and sub-station building, 5) Single story pump shed, 6) Single story hardware materials shed, 7) Single story Dining shed, 8) Single story Wastage shed. Owned 1) Six story main production building: Building height (est occupied floor level): 19.5 m or 64 ft [Height up to roof: m or 75 ft], Stories above grade: 6, Stories below grade: 0, Occupied levels: 6, 2) Single story security building: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 3.05m or 10 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 3) Single story compressor building: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 3.05m or 10 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 4) Single story compressor and sub-station building: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 3.05m or 10 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 5) Single story pump shed: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 2.74 m or 9 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 6) Single story hardware materials shed: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 2.74 m or 9 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 7) Single story Dining shed: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 3.05 m or 10 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. 8) Single story Wastage shed: Building height (est occupied floor level): 15 cm or 0.5 ft above grade [Height up to roof: 3.05 m or 10 ft], Stories above grade: 1, Stories below grade: 0, Occupied levels: 1. The Alliance for Bangladesh Worker Safety Page 3/17

4 11 Feb 2015 Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Approximate Ancillary Structures Area (SF) : Number of Occupants : Provide brief description of the electrical system for each building.: Physical location of Substation? : What equipment/loads does the UPS serve? : Total area of all buildings in the factory premises: SF. Building wise breakdown as follows: 1) Six story main production building: SF (Ground floor: SF, 1st floor: SF, 2nd floor: SF, 3rd floor: SF, 4th floor: SF, 5th floor: SF). 2) Single story security building: 218 SF, 3) Single story compressor building: 136 SF, 4) Single story compressor and sub-station building: 482 SF, 5) Single story pump shed: 197 SF, 6) Single story hardware materials shed: 400 SF, 7) Single story Dining shed: 2215 SF, 8) Single story Wastage shed: 717 SF. Factory personnel informed the date of construction as follows: 1) Six story main production building: Started in November-2010 and finished in September-2014, 2) Single story security building: Started in March-2014 and finished in April-2014, 3) Single story compressor building: Started in January-2015 and finished in February-2015, 4) Single story compressor and sub-station building: Started in November-2013 and finished in December-2013, 5) Single story pump shed: Started in February-2015 and on going, 6) Single story hardware materials shed: Started in January-2014 and finished in February-2014, 7) Single story Dining shed: Started in April-2014 and finished in May-2014, 8) Single story Wastage shed: Started in June-2014 and finished in July Renovations and additions were completed as follows: 1) Six story main production building: Roof is under construction for dining shed, 2) Single story pump shed: Construction started in February-2015 and is on going. 1) Single story security building, 2) Single story compressor building, 3) Single story compressor and substation building, 4) Single story pump shed, 5) Single story hardware materials shed, 6) Single story Dining shed, 7) Single story Wastage shed. 1) Single story security building: 218 SF, 2) Single story compressor building: 136 SF, 3) Single story compressor and sub-station building: 482 SF, 4) Single story pump shed: 197 SF, 5) Single story hardware materials shed: 400 SF, 6) Single story Dining shed: 2215 SF, 7) Single story Wastage shed: 717 SF. Total number of occupants: ) Six story main production building: 1250 (Ground floor: 100, 1st floor: 280, 2nd floor: 280, 3rd floor: 280, 4th floor: 280, 5th floor: 30); 2) Single story security building: 4; 3) Single story compressor building: 0; 4) Single story compressor and sub-station building: 1; 5) Single story pump shed: 0; 6) Single story hardware materials shed: 1; 7) Single story Dining shed: 0 (Capacity-210); 8) Single story Wastage shed: 0. One source of Bangladesh Export Processing Zone Association BEPZA) fed into via 1 No. Tension (HT) Panel to 1 No. 750KVA Oil Type Service Transformer. Electrical power is distributed via 1 No. Low Tension (LT) Panel, 1 No. 415KVAR Power Factor Improvement (PFI) Panel, 6 Nos. Main Distribution Board (MDB) and 12 Nos. Sub Distribution Boards (SDB). Total Captive Power capacity of 28KVA is achieved by 1 No. 28KVA Diesel Generator. The substation is located in the single story compressor and substation building. Instant Power Supply (IPS) provides power to elevator, fire alarm, emergency lighting and exit signage. The Alliance for Bangladesh Worker Safety Page 4/17

5 11 Feb 2015 ASSESSMENT FINDINGS Electrical System Information Are as-built electrical drawings indicating information such as panel and circuit locations throughout the building(s) available for review? Proper as-built single line diagram (SLD) was available on site but electrical layout drawing was not found. Photograph: Electrical Layout diagram is not available. Have a qualified electrical engineer develop an as-built electrical layout diagram detailing the locations of panels and wiring connections throughout the building(s). 08 Apr 2015 Alliance Standard Part 10 Section Electrical System Maintenance Have workers that operate and maintain the electrical system received electrical safety training? Is training documentation on site? Workers that operate and maintain the electrical system have not received electrical safety training. Worker Interviews: Workers that operate and maintain the electrical system have not received electrical safety training. Develop and implement an electrical safety program. Include key topics such as lock out tag out procedures, personal protective equipment requirements, etc. Keep records of completed training available on site. Reference NFPA 70e for example Is a periodical Insulation Resistance Measurement Program established and recorded? The Alliance for Bangladesh Worker Safety Page 5/17

6 11 Feb 2015 Periodical Insulation Resistance Measurement Program has not been established. Worker Interviews: Periodical Insulation Resistance Measurement Program has not been established. Develop an Insulation Resistance Measurement Program that ensures deterioration of insulation resistance will be identified quickly. Testing should be in compliance with International Electrical Testing Association (IETA). All transformers, switchgears etc. shall be subject to an insulation resistance measurement test to ground after installation but before any wiring is connected. Insulation tests shall be made between open contacts of circuit breakers, switches etc. and between each phase and earth. Alliance Standard Part 10 Section Insulation Tests and Electrical Inspections Are thermographic scans of electrical equipment completed at least every three years? Thermographic scans of electrical equipment have not been conducted. Worker Interviews: Thermographic scans of electrical equipment have not been conducted. Complete thermographic scans at least on a three year cycle. Thermographic scans should be completed in accordance with the Standard for Infrared Inspection of Electrical Systems & Rotating Equipment and NFPA70B or a comparable standard. Alliance Standards Part 10 Section Electrical Inspections Transformers do not contain harmful substances such as PCBs. No test result or manufacturer's specification was found to ensure that the transformer is free from harmful substances such as PCBs. Document Review: No test result or manufacturer's specification found. Contact with transformer manufacturer regarding PCB containment report and The Alliance for Bangladesh Worker Safety Page 6/17

7 11 Feb 2015 consider replacing transformers with harmful substances to reduce health hazards. Not Applicable Are periodic safety inspections of the electrical system components completed and documented? Periodic safety inspections of the electrical system components have not been completed. Document Review: Periodic safety inspections of the electrical system components have not been completed. Establish a periodic inspection program to ensure the electrical systems are free from damage, debris, dirt, lint, etc. Maintain records concerning inspections and follow up actions. 08 Apr 2015 Alliance Standard Part 10 Section Inspection and Testing and Part 13 Section 13.6 Housekeeping A transformer oil analysis is routinely completed on main service transformers. Low Transformer oil analysis is not routinely completed on main service transformers. Document Review: Any document regarding transformer oil analysis was not found during audit. Complete an oil analysis on applicable transformers at appropriate intervals based on voltage and power. Alliance Standard Part 10 Section Electrical Inspections Electrical System Conditions All equipment is efficiently earthed and properly connected to the required number of earth electrodes. The Alliance for Bangladesh Worker Safety Page 7/17

8 11 Feb 2015 Door earthing is not provided and an earthing connection is not provided in motor. Location: HT & LT panel, fire pump. Visual Assessment: All electrical equipment is not efficiently earthed. The earth electrodes are not properly identified. Provide earthing of equipment at required locations and connect to required number of electrodes. 08 Apr 2015 Alliance Standard Part 10 Section Inspection of Substation Installations. The substation room has the required fire rating/protection and is physically separated from the remainder of the building. Non-Compliance Level: 2 The substation room does not have required fire rating and is physically separated by less than 3m from the main production building. Photograph: The substation room is separated but not fire rated. Consult with an expert engineer to provide adequate fire rating for the substation room. Alliance Standard Part 3 Section Indications of overheating, overloading, or signs of burning were not observed. Signs of burning were not found but indications of overheating were observed at some locations during thermography. Locations: 1) Compressor Control Unit, Compressor Room (67.9 C); 2) MDB-01, 1st Floor, Sewing Area (99.2 C). Note: Detail therm The Alliance for Bangladesh Worker Safety Page 8/17

9 11 Feb 2015 Photograph: Indications of overheating were observed at some locations during thermography. Find out cause of overheating and take proper action including replacing cables or equipment where necessary. 24 Feb 2015 Alliance Standard Part 10 Section All metal in the building is connected to the building earthing/grounding system such as metal rebar in concrete, metal frame of building, or metal water pipe. Motor body earthing is not provided for the fire pump motor. Location: Fire pump motor. Photograph: Motor body earthing is not provided for the fire pump motor. Connect all metal in the building to the building earthing system such as metal rebar in concrete, metal frame of building, or metal water pipe according to BNBC Part 8 Section 2.8 Earthing requirement. Alliance Standard Part 10 Section Earthing Wiring systems are selected and erected so that no damage is caused by the ingress of water. Panel is located in open space with no protection from ingress of water. Location: Water pump control panel, rear wall of main factory building. Photograph: Possibility of damage due to ingress of water. Ensure wiring systems are selected and erected so that no damage is caused by the ingress of water. 29 Mar 2015 Alliance Standards Part 10 Section Presence of Water The Alliance for Bangladesh Worker Safety Page 9/17

10 11 Feb 2015 Power and telecommunication or antenna cables are led in separately. Power and telecommunication or antenna cables are not routed separately. Location: 4th Floor, Beside the MDB-01. Photograph: Power and telecommunication cables are not separated. Route telecommunication or antenna cables separately to the main point of service. Power and telecommunications cables must have separate entrance. 08 Apr 2015 Alliance Standards Part 10 Section Service Entry Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. Proper capacity information labels of distribution boards are not available and therefore "physical means to prevent the installation of more over current devices" is not known. Location: All distribution boards. Photograph: No means to prevent the installation of more over current devices. Ensure proper DB capacity information labels and ensure distribution boards are provided with the physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed following NFPA 70 section Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear The substation room has adequate ventilation. Non-Compliance Level: 2 Substation room does not have arrangements for cross ventilation. Only one exhaust fan is installed but no supply fan to supply air inside the room or ceiling fans are installed. Photograph: Inadequate ventilation system in substation room. The Alliance for Bangladesh Worker Safety Page 10/17

11 11 Feb 2015 Provide means of proper cross ventilation for the substation room. Consult a qualified electrical engineer to determine the required ventilation rates based on the installed equipment. 29 Mar 2015 Alliance Standard Part 10 Section Inspection of Substation Installations. The substation room has adequate means of security. Non-Compliance Level: 2 There is no fencing provided around the transformer to avoid anyone from accidentally coming into contact with the transformer. The transformer and panels are located within the same room in close proximity. Photograph: There is no fencing provided around the transformer. Ensure proper fencing is around the transformer to avoid accidents by coming into contact with the transformer. 29 Mar 2015 Alliance Standard Part 10 Section Inspection of Substation Installations. Do switchboards and/or distribution boards have capacity information labels? Non-Compliance Level: 2 Inadequate capacity information labels are provided. Only the maximum current rating is provided but number of circuit breakers in use and the number of circuit breakers that can be installed are not provided. Location: All distribution boards. Photograph: Inadequate DB capacity information labels are provided. Provide adequate capacity information labels (Maximum current rating, no of circuit breakers etc.) for distribution boards. 29 Mar 2015 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation The Alliance for Bangladesh Worker Safety Page 11/17

12 11 Feb 2015 Are all internal components of switchboards and/or distribution boards properly concealed (No missing circuit breaker or knockout covers)? Internal components of sockets are not properly concealed. Location: Switchboards, Third Floor Preparation B. Photograph: Sockets are not properly concealed. Provide covers to conceal all live internal components of the socket. 03 Apr 2015 Alliance Standard Part 10 Section Sub-Distribution Boards Electrical wiring and conduit is properly supported. Electrical conduit is not properly supported. Location: Beside the steel frame stair. Photograph: Inadequate cable conduit support. Provide adequate supports for electrical wiring and conduit. 29 Mar 2015 Alliance Standard Part 10 Section , , and Stranded conductors having a nominal cross-sectional area 6mm2 or greater are provided with cable sockets. Conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. Cable sockets are not provided for stranded conductors greater than 6mm2. Location: Low Tension Bushing, Transformer, Substation Room. Photograph: Cable sockets are not provided. Provide cable sockets for stranded conductors having a nominal crosssectional area 6mm2 or greater. The Alliance for Bangladesh Worker Safety Page 12/17

13 11 Feb Mar 2015 Alliance Standards Part 10 Section Cable Ends Cable joints are through porcelain/pvc connectors with PIB tape wound around joint. Improper cable joint was found. Location: 4th Floor, Beside the MDB-01. Photograph: Improper cable joint was found. Ensure cable joints are through porcelain or PVC connectors with PIB tape wound around joint. Alliance Standards Part 10 Section Cable Joints Is all electrical wiring/cable properly terminated at its point of termination (No un-terminated wires, lugs are provided at terminals, etc)? Un-terminated wires were found. Location: 4th Floor, Sewing Line-D. Photograph: Un-terminated wires were found. Ensure all electrical cable is properly terminated at its point of termination. Alliance Standards Part 10 Section Wiring of Sub-distribution Boards Are junction boxes and other electrical devices provided with covers? Junction box is not provided with cover. Location:Ground Floor, Beside the SDB-02. Photograph: No electrical cover. Provide adequate covers for junction boxes and other electrical devices to keep them free from lint & dirt. The Alliance for Bangladesh Worker Safety Page 13/17

14 11 Feb Mar 2015 Alliance Standard Part 10 Section and Required equipment and safety signage is posted within the room. Low Required equipment and safety signage are not posted within the room. Photograph: Equipment and safety signage is not posted. Indoor electrical installations that are accessible to unqualified persons shall be made with metal-enclosed equipment. Switchgear, unit substations, transformers, pull boxes, connection boxes, and other similar associated equipment shall be marked with appropriate caution signs. Entrances to rooms and other guarded locations that contain exposed live parts shall be marked with conspicuous warning signs forbidding unqualified persons to enter. Caution, warning, danger signs or labels should meet the following requirements: (1) The marking shall adequately warn of the hazard using effective words and/or colors and/or symbols. American National Standards Institute ANSI Z , Product Safety Signs and Labels, provides guidelines for suitable font sizes, words, colors, symbols, and location requirements for labels. (2) Shall be permanently affixed to the equipment or wiring method and shall not be hand written. Exception, portions of labels or markings that are variable, or that could be subject to changes, shall be permitted to be hand written and shall be legible. (3) The label shall be of sufficient durability to withstand the environment involved. ANSI Z , Product Safety Signs and Labels, provides guidelines for the design and durability of safety signs and labels for application to electrical equipment. 15 Mar 2015 Alliance Standard Part 10 Section , Section , and , NFPA 70 Chapter 1 Article , and Bangladesh Electricity Rules of 1937 Rule 46 Signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Low No signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Location: Store. Photograph: No signage indicating the prohibition of installation of light fixtures without protective covers. Ensure signage indicating the prohibition of light fixtures without protective covers is posted in Bengali and English at required locations. The Alliance for Bangladesh Worker Safety Page 14/17

15 11 Feb Mar 2015 Alliance Standards Part 10 Section Naked Lights Are electrical insulation mats provided in front of substation, switchboards and/or distribution boards? Low Non graded electrical insulation mat is provided in front of LT Panel. Location: LT panel, Substation Room. Photograph: Non graded Electrical insulation mat is provided. Provide electrically graded insulation mats in front of distribution boards. 15 Mar 2015 Alliance Standard Part 10 Section Inspection of the Installation. Phase separators are provided between terminals on circuit breakers. Low Phase separators are not provided between terminals on circuit breakers. Location: Water Pump Panel, MDB-01 (4th Floor). Photograph: No phase separators are provided between terminals on circuit breakers. Install phase separators between terminal connections at the noted locations. 29 Mar 2015 Alliance Standard Part 10 Section Electrical Connections Emergency Power System Are emergency power switchboards, distribution boards, and circuits properly identified? Emergency power switchboards, distribution boards, and circuits are not identified. Location: All emergency switchboards, distribution boards and The Alliance for Bangladesh Worker Safety Page 15/17

16 11 Feb 2015 circuits. Photograph: Emergency power switchboards, distribution boards, and circuits are not identified. Ensure emergency power switchboards, distribution boards, and circuits are permanently marked so they will be readily identified as a component of an emergency circuit or system. 13 Apr 2015 NFPA 70 Chapter 7 Article Wiring, Emergency System Are cable trenches properly covered? Non-Compliance Level: 2 Cable trenches are not covered. Location: Substation Room. Photograph: No cover on cable trenches. Provide adequate cover on cable trench. 15 Mar 2015 Alliance Standard Part 10 Section Inspection of the Installation Is the generator frame earthing (grounding) provided at two separate points? A small 28kVA generator (which is provided only for fire pump) is not earthed at two separate points. Visual Assessment: Generator is not earthed at two separate points. Provide two separate points earthing for generator. 06 Apr 2015 Alliance Standard Are inspection, maintenance, and testing procedures of the emergency generator being completed and documented? Low The Alliance for Bangladesh Worker Safety Page 16/17

17 11 Feb 2015 Non-Compliance Level: 2 Inspection, maintenance, and testing procedures of the generator was not found. Worker Interviews: Inspection, maintenance, and testing procedures of the generator was not found. Establish a routine maintenance and testing program for the emergency generator. The program shall be based on all of the following: (1) Manufacturer's recommendations (2) Manufacturer's Instruction manuals (3) Requirements of NFPA 110 Chapter Apr 2015 NFPA 110 Chapter 8 Lightning Protection System Is a lightning protection system installed on the building? A lightning protection system is not installed on any of the buildings on the premises. Photograph: Lightning protection system is not installed. Consult with qualified electrical engineer to calculate the risk index of the buildings for confirming the necessity of lightning protection system installation and requirements. 10 May 2015 Alliance Standards Part 10 Section Lightning Protection. Calculate Risk Index to determine if required. The Alliance for Bangladesh Worker Safety Page 17/17

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Plot #92 (Partial) DEPZ Extention Area-02 Ganakbari, Ashulia, Savar Uttaron 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/15 19

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory 81, Kalmessar, "Jalal Shopping Complex" Board Bazar, Gazipur. 20 May 2014 The Alliance for Bangladesh Worker Safety Page 1/21 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/6 Introduction to

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 154 Kamrabad, Atarar Depot Chittagong Chittagong Chittagong The Alliance for Worker Safety Page 1/7 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/10 09 Jun 2014 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory RR Washing Limited (previously Freshtex Pvt Ltd (Washing)) Beximco Industrial Park Sarabo, Kashimpur, Gazipur Gazipur Dhaka 12 Jun 2014 The Alliance

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIKDER APPAREL HOSIERY LTD. Khadun (Dug No. 342/343), Tarabo, Rupgonj, Narayanganj, Bangladesh. Factory List: 1. Sikder Apparel Hosiery Ltd. Inspected by: Pema Wangdi

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS By Thomas Smith, Product Specialist, Brady Corporation Last updated: February, 2015 The Occupational Safety and Health Administration

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIDKO LIMITED PLOT NO. 36, ROAD NO. 46, GULSHAN NORTH C/A, DHAKA. Factory List: 1. N. A. Garments 2. 3. Sidko Apparels 4. Delta Ties Ltd. Inspected on April 17, 2014

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MUAZUDDIN TEXTILES LTD. Plot # 235/236, East Chandura, Shafipur, Kaliakor, Gazipur, Bangladesh. Factory List: 1. Inspected by: Younten Jamtsho Report Generated by: Stabak

More information

CHRISTIAN BROTHERS RISK MANAGEMENT SERVICES Self Inspection Checklist

CHRISTIAN BROTHERS RISK MANAGEMENT SERVICES Self Inspection Checklist CHRISTIAN BROTHERS RISK MAGEMENT SERVICES Self Inspection Checklist Building: Date: Inspected By: Time Began: Time Ended: PARKING LOTS Are gates operable? Condition of striping? Condition of parking lot

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed

More information

Assessing Your Airfield Electrical Distribution System

Assessing Your Airfield Electrical Distribution System Assessing Your Airfield Electrical Distribution System PRESENTED AT The 2017 Airports Conference March 30, 2017 Hershey, PA PRESENTED BY Samuel Mullen, III - Burns Engineering, Inc. 1 Presentation Objective

More information

Apartment Fire & Safety Inspection. City of Guadalupe

Apartment Fire & Safety Inspection. City of Guadalupe Apartment Fire & Safety Inspection City of Guadalupe Intent Provide information and the most common violation. It is NOT the intent to Identify all hazards a building may experience. It is NOT intended

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT Page 1 FIRE SAFETY INSPECTION REPORT Impress Fashion Ltd. ACCORD ID: 12245 Dag No. 2224, Matuial, Konapara, Katherpool, Jatrabari, Dhaka-1362 Other Factories: None Date: August 27, 2015 Sl No. Category

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SOLARPEAK SITE ASSESSMENT FORM. I. Solar Access Assessment

SOLARPEAK SITE ASSESSMENT FORM. I. Solar Access Assessment To be eligible for a SolarPeak solar water heater,the location for a proposed solar water heating system must be assessed for its suitability by the SolarPeak installation assessor. This form must be completed

More information

Substation Signage. Document Number: 1-11-FR-12

Substation Signage. Document Number: 1-11-FR-12 Substation Signage Document Number: 1-11-FR-12 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-12 Substation Signage Asset Class Strategy Intellectual

More information