EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

Size: px
Start display at page:

Download "EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT"

Transcription

1 EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory RR Washing Limited (previously Freshtex Pvt Ltd (Washing)) Beximco Industrial Park Sarabo, Kashimpur, Gazipur Gazipur Dhaka 12 Jun 2014 The Alliance for Worker Safety Page 1/29

2 Factory 12 Jun 2014 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by University of Engineering and Technology (BUET) for the National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which i Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Worker Safety Page 2/29

3 12 Jun 2014 GENERAL INFORMATION General Information Factory Country: Province: City: Dhaka Gazipur Zip Code: 1346 Audit Duration: Re-Audit: Re-Audit After 0 Months Draft Report Date : Final Report Date : Are all action items from previous assessment complete? : Buildings in Complex : Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : N/A There are 31 buildings in the factory premises out of which 10 are main buildings and 21 are ancillary buildings. The buildings are named as: 1) Beximco Woven and Textile shed, 2) Beximco Denim shed, 3) Beximco Knitting shed, 4) Beximco Printing shed, 5) Five story CFDL building, 6) Production shed (Esses), 7) Production shed (IKAL-1), 8) Production shed (IKAL-2), 9) Production shed (NDIL), 10) Production shed (Frestex), 11) Turbine-1 building, 12) Turbine-2 shed, 13) Boiler-1 building, 14) Boiler-2 building, 15) Generator-1 building, 16) Generator-2 shed, 17) Security post-1, 18) Security post-2, 19) Mosque building, 20) Staff residence building, 21) Officer residence building, 22) Foreigner residence building, 23) Guest house building, 24) Corporate office shed, 25) Temporary dining shed (NDIL), 26) Store shed (NDIL), 27) Finished goods store shed (CFDL), 28) Worker dining shed (CFDL), 29) Medical & childcare shed (CFDL), 30) Warehouse shed (Esses), 31) Dining shed (Esses). Owned Information provided below as per following format: est occupied floor level [Height up to roof], Stories above grade, Stories below grade, Occupied level. 1) Beximco Woven & Textile shed: 1 ft [14 ft], 1, 0, 1. 2) Beximco Denim shed: 1 ft [14 ft], 1, 0, 1. 3) Beximco Knitting shed: 1 ft [14 ft], 1, 0, 1. 4) Beximco Printing shed: 1 ft [14 ft], 1, 0, 1. 5) Five story CFDL building: 40 ft [50 ft], 5, 1, 6. 6) Production shed (Esses): 1 ft [14 ft], 1, 0, 1. 7) Production shed (IKAL-1): 1 ft [14 ft], 1, 0, 1. 8) Production shed (IKAL-2): 1 ft [14 ft], 1, 0, 1. 9) Production shed (NDIL): 1 ft [14 ft], 1, 0, 1. 10) Production shed (Frestex): 1 ft [14 ft], 1, 0, 1. 11) Staff residence building: 40 ft [50 ft], 5, 0, 5. 12) Officer residence building: 40 ft [50 ft], 5, 0, 5. 13) Foreigner residence building: 40 ft [50 ft], 5, 0, 5. 14) Guest house building: 20 ft [30 ft], 3, 0, 3. 15) Dining shed (Esses): 10 ft [20 ft], 2, 0, 2, and sixteen single story buildings in the factory premises. The Alliance for Worker Safety Page 3/29

4 12 Jun 2014 Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Approximate Ancillary Structures Area (SF) : Total area of all buildings in the factory premises: sft. Building wise breakdown as follows: 1) Beximco Woven & Textile shed: sft, 2) Beximco Denim shed: sft, 3) Beximco Knitting shed: sft, 4) Beximco Printing shed: sft, 5) Five story CFDL building: sft, 6) Production shed (Esses): sft, 7) Production shed (IKAL-1): sft, 8) Production shed (IKAL- 2): sft, 9) Production shed (NDIL): sft, 10) Production shed (Frestex): sft, 11) Staff residence building: sft, 12) Officer residence building: sft, 13) Foreigner residence building: sft, 14) Guest house building: sft, 15) Dining shed (Esses): sft, and sixteen single story ancillary buildings in the factory premises. Factory personnel informed the date of construction as follows: 1) Beximco Woven & Textile shed: Finished in 2007, 2) Beximco Denim shed: Finished in 1995, 3) Beximco Knitting shed: Finished in 1995, 4) Beximco Printing shed: Finished in 2007, 5) Five story CFDL building: Finished in 2007, 6) Production shed (Esses): Finished in 2013, 7) Production shed (IKAL-1): Finished in 2013, 8) Production shed (IKAL-2): Finished in 2013, 9) Production shed (NDIL): Finished in 2013, 10) Production shed (Frestex): Finished in 2013, 11) Five story RCC staff residence building: Finished in 2010, 12) Five story RCC officer residence building: Finished in ) Five story RCC foreigner residence building: Finished in ) Three story RCC guest house building: Finished in 2012, 15) Two story dining shed (Esses): Finished in 2012, and sixteen single story ancillary buildings in the factory premises. No record for date of renovation or addition was found from factory personnel. However, during audit it was found that, Beximco Industrial Park internal and external road construction work was going on. 1) Single story RCC turbine-1 building, 2) Single story turbine-2 shed, 3) Single story RCC boiler-1 building, 4) Single story RCC boiler-2 building, 5) Single story RCC generator-1 building, 6) Single story generator-2 shed, 7) Single story RCC security post-1, 8) Single story RCC security post-2, 9) Single story RCC mosque building, 10) Five story RCC staff building, 11) Five story RCC officers building, 12) Five story RCC foreigner residence building, 13) Three story RCC guest house building, 14) Single story corporate office shed, 15) Single story temporary dining shed (NDIL), 16) Single story store shed (NDIL), 17) Single story finished goods store shed (CFDL), 18) Single story worker dining shed (CFDL), 19) Single story medical & childcare shed (CFDL), 20) Single story warehouse shed (Esses), 21) Two story dining shed (Esses). 1) Turbine-1 building: sft, 2) Turbine-2 shed: sft, 3) Boiler-1 building: sft, 4) Boiler-2 building: sft, 5) Generator-1 building: sft, 6) Generator-2 shed: sft, 7) Security post- 1: sft, 8) Security post-2: sft, 9) Mosque building: sft, 10) Staff residence building: sft 11) Officer residence building: sft 12) Foreigner residence building: sft 13) Guest house building: sft 14) Corporate office shed: sft, 15) Temporary dining shed (NDIL): sft, 16) Store shed (NDIL): 11, sft, 17) Finished goods store shed (CFDL): 20, sft, 18) Worker dining shed (CFDL): sft, 19) Medical & childcare shed (CFDL): sft, 20) Warehouse shed (Esses): sft, 21) Dining shed (Esses): sft. Number of Occupants : Total number of occupants: ) Beximco Woven & Textile shed: 2014, 2) Beximco Denim shed: 574, 3) Beximco Knitting shed: 480, 4) Beximco Printing shed: 110, 5) Five story CFDL building: 3590, 6) Production shed (Esses): 1334, 7) Production shed (IKAL-1): 1565, 8) Production shed (IKAL-2): 1225, 9) Production shed (NDIL): 2960, 10) Production shed (Frestex): 795, 11) Turbine-1 building: 3, 12) Turbine-2 shed: 3, 13) Boiler-1 building: 5, 14) Boiler-2 building: 5, 15) Generator-1 building: 4, 16) Generator-2 shed: 4, 17) Security post-1: 12, 18) Security post-2: 12, 19) Mosque building: 0, 20) Staff residence: 100, 21) Officer residence: 100, 22) Foreigner residence: 100, 23) Guest house: 0, 24) Corporate office: 252, 25) Dining shed (NDIL): 0, 26) Store shed (NDIL): 12, 27) Finished goods store (CFDL): 6, 28) Worker dining (CFDL): 0, 29) Medical & childcare (CFDL): 4, 30) Warehouse (Esses): 2, 31) Dining shed (Esses): 0. Provide brief description of the electrical system for each building.: Physical location of Substation? : Main source (Gas Turbine), No of Gas Turbine-02 Nos, Gas Turbine-01(4.6MW), Gas Turbine-02(4.2MW), Auxiliary source (Rural Electrification Board,REB-2.9MW), Tranformer-08 Nos, Step up Transformer(1600KVA)-03 Nos, Step up Transformer(5000KVA and 6000KVA)-02 Nos, Step down Transformer(1600KVA, 2000KVA, 2500KVA)-03 Nos, Gas Generator(1MW)-09 Nos, Diesel Generator(635KVA)-02 Nos, Diesel Generator(500KVA, 591KVA)-02 Nos. 2 Substation used For Beximco Textile Ltd- Substation-1(11KV) is located outside of the main building. Substation-2(440V) is located on the ground floor of the main building. 1 Substation used For Beximco knitting The Alliance for Worker Safety Page 4/29

5 12 Jun 2014 Ltd- Substation room is located on the ground floor of the building. 2 Substation used for Beximco Denim Ltd- Substation-01 is located inside the building, Ground floor, East side. Substation-02 is located inside the building, Ground floor. 1 Substation used for Crescent Fashion and Design Ltd- Substation is located attached with the main building, Ground floor. What equipment/loads does the UPS serve? : Fire alarm, emergency lighting, exit signage are connected to IPS and several number of desktop computers are connected to the UPS. The Alliance for Worker Safety Page 5/29

6 12 Jun 2014 ASSESSMENT FINDINGS Electrical System Information Are as-built electrical drawings indicating information such as panel and circuit locations throughout the building(s) available for review? Non-Compliance Level: 2 Electrical diagram of main distribution circuit and floor levels circuits connecting electrical loads (machines, lights, cooling system etc.) are available at site but not as-built. Location: Beximco Textile Ltd. (BLT), Beximco Corporate Office, Beximco International Knitwear and Apparels Unit-1, Beximco International Knitwear and Apparels Unit-2 and Esses Fashions Ltd., Freshtex (Pvt.) Ltd., Beximco Apparels Ltd., Crescent Fashion & Design Ltd., New Dacca Industries Ltd. Document Review: Proper as-built electrical drawing was not found. Have a qualified electrical engineer develop an as-built single line diagram detailing key components and capacity of the electrical system. Alliance Standard Part 10 Section Electrical System Maintenance Is the electrical switchgear and panel boards inspected on an annual basis to ensure that the equipment is installed in accordance with the listed ratings? The electrical switchgear and panel boards are not inspected on an annual basis to ensure that the equipment is installed in accordance with the listed ratings. Location: Beximco Textile Ltd.(BLT), Beximco Knitting Ltd.(BKL), Beximco Corporate Office, Beximco International Knitwear and Apparels Unit- 2 and Esses Fashions Ltd., Beximco Apparels Ltd., Crescent Fashion and Design Ltd., New Dacca Industries Ltd. Document Review: No annual inspection record for electrical switchgear and panel boards. Inspect electrical switchgear and panel boards on an annual basis to ensure that the equipment is in good working condition. The Alliance for Worker Safety Page 6/29

7 12 Jun 2014 Alliance Standards Part 10 Section Electrical Inspections Are thermographic scans of electrical equipment completed at least every three years? Thermographic scans of electrical equipment have not been completed. Location: Beximco Textile Ltd.(BLT), Beximco Denim Ltd.(BDL), Beximco Knitting Ltd. (BKL), Beximco Corporate Office, Beximco International Knitwear and Apparels Unit-1, Beximco International Knitwear and Apparels Unit-2 and Esses Fashions Ltd., Freshtex (Pvt.) Ltd., Beximco Apparels Ltd., Crescent Fashion and Design Ltd., New Dacca Industries Ltd. Document Review: No document on thermographic scans for electrical equipment. Complete thermographic scans at least on a three year cycle. Thermographic scans should be completed in accordance with the Standard for Infrared Inspection of Electrical Systems & Rotating Equipment and NFPA70B or a comparable standard. Alliance Standards Part 10 Section Electrical Inspections Transformers do not contain harmful substances such as PCBs. There was no such document which can prove that transformers don't contain any harmful substance. Location: Beximco Denim Ltd.(BDL), Beximco Knitting Ltd.(BKL), Freshtex (Pvt.) Ltd., Beximco Apparels Ltd., Crescent Fashion and Design Ltd., New Dacca Industries Ltd. Document Review: No document against the absence of harmful substances. Consider replacing transformers that contain harmful substances to reduce health hazards. Not Applicable Are periodic safety inspections of the electrical system components completed and documented? The Alliance for Worker Safety Page 7/29

8 12 Jun 2014 Periodic safety inspections of the electrical system components have not been completed. Location: Beximco Textile Ltd.(BLT), Beximco Denim Ltd.(BDL), Beximco Knitting Ltd.(BKL), Beximco Corporate Office, Beximco International Knitwear and Apparels Unit-1, Beximco International Knitwear and Apparels Unit-2 and Esses Fashions Ltd., Freshtex (Pvt.) Ltd., Beximco Apparels Ltd., Crescent Fashion and Design Ltd., New Dacca Industries Ltd. Document Review: No periodic safety inspections of the electrical system. Establish a periodic inspection program to ensure the electrical systems are free from damage, debris, dirt, lint, etc. Maintain records concerning inspections and follow up actions. Alliance Standard Part 10 Section Inspection and Testing and Part 13 Section 13.6 Housekeeping Is a periodical Insulation Resistance Measurement Program established and recorded? Periodical Insulation Resistance Measurement Program have not been established and recorded. Location: Beximco Denim Ltd.(BDL), Beximco Knitting Ltd.(BKL). Document Review: No periodical Insulation Resistance Measurement Program. Develop an Insulation Resistance Measurement Program that ensures deterioration of insulation resistance will be identified quickly. Testing should be in compliance with InterNational Electrical Testing Association (NETA). All transformers, switchgears et Alliance Standard Part 10 Section Insulation Tests and Electrical Inspections A transformer oil analysis is routinely completed on main service transformers. Low Transformer oil analysis have not been completed on main service transformers. Location: Beximco Denim Ltd.(BDL), Knitting Ltd.(BKL), Freshtex (Pvt.) Ltd., Beximco Apparels Ltd., Crescent Fashions & Design Ltd., New Dacca Industries Ltd. Document Review: No oil test report of main service transformers. The Alliance for Worker Safety Page 8/29

9 12 Jun 2014 Complete an oil analysis on applicable transformers at appropriate intervals based on voltage and power. Alliance Standard Part 10 Section Electrical Inspections Electrical System Conditions The substation room has the required fire rating/protection and is physically separated from the remainder of the building. The substation room is not fire rated but physically separated from the remainder of the building. Location: Beximco Textile Ltd.(BLT)(Substation- 02,Ground floor). Beximco Denim Ltd.(BDL)(Substation room,ground floor). Beximco Knitting Ltd.(BKL)(Substation room,ground floor). Crescent Fashion and Design Ltd.(Substation room,ground floor,main Building). New Dacca Industries Ltd.(Substation room, Ground floor). Photograph: The substation room is not fire rated. Provide adequate fire rating for substation room and make it separated from rest of the building with an expert fire protection engineer and make sure the substation room is fire rated as per Alliance standard. Alliance Standard Part 3 Section Are all switchboards and/or distribution boards metal enclosed with a dead front construction? Distribution boards are metal enclosed without dead front construction. Location: For Beximco Textile Ltd(BLT)-All Distribution Boards. Beximco Denim Ltd(BDL)-All Distribution Boards. Beximco Knitting Ltd(BKL)-All Distribution Boards. Beximco Corporate Office-All Distribution Boards. Crescent Fashion and Design Ltd-All Distribution Boards. Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)-All Distribution Boards (Except LT Panel). Beximco International Knitwear and Apparels Unit-2-All Distribution Boards. Beximco Apparels Ltd-All Distribution Boards. New Dacca Industries Ltd-All Distribution Boards. Photograph: Metal enclosure without dead front construction. Ensure distribution boards are metal enclosed with a dead front construction. The Alliance for Worker Safety Page 9/29

10 12 Jun 2014 Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Is electrical wiring/cables sized according to capacity of circuit breakers (No higher rated circuit breakers with lower rated wiring)? Non-Compliance Level: 2 Electrical cables are not sized according to capacity of circuit breakers. Location: For Beximco Textile Ltd(BLT)- Most of The Distribution Boards such as MDB-2,BL(T),Loom(1); SDB-4,BL(T),Ground Floor; DB,BL(T),Drawing Section; SDB,BL(T),Inspection Section; SDB-1,BL(T),Loom-4; SDB- 6,BL(T),Loom-3; MDB,BL(T),Yand Dyeing,1st Floor; SDB-9,BBT-9,Young Dyeing,1st Floor; DB-2,BBT-9,Young Dyeing,1st Floor. For Beximco Knitting Ltd(BKL)- DB-2(BLK),Ground Floor; MDB-4(BLK),Ground Floor; SDB-2(BLK), Ground Floor; SDB-7(BLK),Ground Floor; SDB-8(BLK),Ground Floor. For Crescent Fashion and Design Ltd- MDB-1-Sewing section-a side-gf-cfdl; DB-3-Finishing section-a side-gf-cfdl; MDB-2-Sewing section-b side- CFDL; DB-5,Cutting section-1st floor-b side-cfdl. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- IKAL-1(MDB- 1,SDB-1,Power Room)(SDB-4 Catting Sec)(Fresh Tex SBD-08B Drayer,SDB- 1 Washing,MDB-1Power Room,SDB-11,MDB-3,SDB-15 Drayer room,sdb- 13,DB-Lafte Random Room. For New Dacca Industries Ltd- SDB-5,Ground Floor,Shed-1; SDB-6,Ground Floor,Shed-1. Photograph: er rated circuit breakers with lower rated wiring. Consult with a qualified Electrical Engineer and ensure electrical cables are sized according to capacity of circuit breakers. Alliance Standard Part 10 Section Electrical Connections. Underground service cables are laid in conformity with the requirements of concealed wiring. Underground service cables are not laid in conformity with the requirements of concealed wiring. Location: Beximco Textile Ltd.(BLT), Crescent Fashion and Design Ltd., New Dacca Industries Ltd. Photograph: Improper wiring of underground service cables. Ensure underground cables for electrical distribution in the premises of the building are encased in GI or PVC pipes and laid in earth trenches of sufficient depth. The Alliance for Worker Safety Page 10/29

11 12 Jun 2014 Alliance Standards Part 10 Section Service Entry No foreign utilities are routed through the substation room (wet pipes). Foreign utilities are routed through the substation room. Location: Beximco Denim Ltd.(BDL)(Substation-02, Ground Floor, Main building). New Dacca Industries Ltd.(Substation room, Ground floor). Photograph: Foreign utilities are found in the substation room. Change direction of such utilities, so that they are not routed through the substation room. Alliance Standard Part 10 Part External Influences Combustible materials are not stored within the substation room. Combustible materials are stored within the substation room. Location: Beximco Textile Ltd.(BLT)(Substation-01,Ground floor); Crescent Fashion and Design Ltd.(Substation room, Ground floor). Photograph: Combustible materials found in the substation room. Remove all combustible materials within the substation room. Not Applicable The Alliance for Worker Safety Page 11/29

12 12 Jun 2014 Do switchboards and/or distribution boards have a minimum clearance of 1 m (39 in) in front? Distribution boards are not provided with adequate clearance. Location: Beximco Textile Ltd. (BLT)- MDB-2,BL(T),Loom(1); SDB-4,BL(T),Ground Floor; DB,BL(T),Drawing Section; SDB,BL(T),Inspection Section; SDB- 1,BL(T),Loom-4; SDB-6,BL(T),Loom-3; MDB,BL(T),Yarn Dyeing,1st Floor; SDB-9,BBT-9,Yarn Dyeing,1st Floor; DB-2,BBT-9,Yarn Dyeing,1st Floor; SDB- 6,BBT-9,Yarn Dyeing,1st Floor; SDB-7,BBT-9,Yarn Dyeing,1st Floor; SDB- 8,BBT-9,Yarn Dyeing,1st Floor. Beximco Denim Ltd.(BDL)- MDB- 5,Compressor Room,Ground Floor. Beximco Knitting Ltd. (BKL) DB-5/BL(K); SDB-6/BL(K); SDB-7/BL(K). Beximco Corporate Office- DB-3-GF-Head Office. Crescent Fashion and Design Ltd.- DB-4-Old fusing area-gf-cfdl. Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt)- SDB-4-Freshtex Wash, DB-Left Random Section. Photograph: Inadequate clearance in front of distribution boards. Provide clearance of at least 1 m (39 in) in front of distribution boards. Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Are switchboards and/or distribution boards installed in compliant locations? Distribution boards are not installed in compliant locations (access limited). Location: For Beximco Denim Ltd(BDL)- SDB-6,BL(D); DB-8,BL(D). For Beximco Knitting Ltd(BKL)- SDB-8,BL(K). For Beximco Corporate Office- DB- 3-Ground Floor-Head office. For Crescent Fashion and Design Ltd- DB-4-Old fusing area-ground Floor-CFDL. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- DB-Left Random Section. For New Dacca Industries Ltd- DB-4, Sewing Section, Shed-1, SDB, Substation Room. Photograph: Distribution boards installed in improper location. Install distribution boards in compliant locations so that operation is not hampered due to limited access. Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear The Alliance for Worker Safety Page 12/29

13 12 Jun 2014 Switchboards and/or panelboards are not installed above gas stoves or sinks or within 2.5m of any washing unit in washing rooms or laundries. Panel boards are installed within 2.5m of washing unit in washing rooms. Location: For Beximco Textile Ltd.(BLT)-MDB,BL(T),Yarn Dyeing,1st Floor; SDB-9,BBT-9,Yarn Dyeing,1st Floor; DB-2,BL(T), Yarn Dyeing,1st Floor; SDB- 6,BL(T),Yarn Dyeing,1st Floor. For Beximco Denim Ltd.(BDL)- MDB- 5(BDL),Ground Floor; DB-9(BDL),Ground Floor. For Beximco Knitting Ltd. (BKL)- MDB-6(BKL),Ground Floor; MDB-4(BKL),Ground Floor. For Freshtex (Pvt.)- SDB-2 Fresh Tex Washing Area. Photograph: Panel boards are installed in improper location. Ensure panel boards are not installed above gas stoves or sinks or within 2.5m of any washing unit in washing rooms or laundries. Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Indications of overheating, overloading, or signs of burning were not observed. Indications of overheating were observed at some locations during thermography. Location: For Beximco Textile Ltd(BLT)- Gas Generator- 4(79.5 C),Substation Room; Gas Generator-5(79.2 C),Substation Room; Gas Generator-6(81.7 C),Substation Room; Gas Generator-9(78.8 C),Substation Room; PFI-2/Right(lower)(80.7 C),Substation Room; LT-2(97.6 C),Substation Room; SDB-3/BL(T)loom-2(73.4 C),Loom1/2; SDB- 1/BL(T)Left(76.5 C),Dyeing Section; SDB-6/BL(T)Lower(73.7 C),Dyeing Section; SDB-6/BL(T)Right(75.7 C),Dyeing Section; DB- 2/BL(T)Right(75.1 C),Dyeing Section; DB-2/BL(T)Upper(73.5 C),Dyeing Section; DB-1/BL(T)LEFT(74.2 C),Dyeing Section; SDB- 10/BL(T)Upper(71.3 C),Dyeing Section; DB-2/BL(T),Inspection(L)(89.7 C), Dyeing Section. For Beximco Denim Ltd(BDL)- LT-1BL(D)Left(lower),Old Station Room(122.9 C); DB-3/BL(D)/GF,Inspection area(76.9 C); DB- 4/BL(D)/GF,Loom Section(unit-1)(71.4 C); DB-5,MDB-1/BL(D)upper(94.4 C); LT-1,BL(D)Right(upper)(105.2 C); Transformer-1(101.7 C). For Beximco Knitting Ltd(BKL)- DB-5,BL(K)lower(91.5 C); LT-2,BL(K),lower(Sub Station Room)(72.7 C); MDB-3,BL(K),Left,Dyeing Section(73.2 C); MDB- 3,BL(K)right(86.2 C); Transformer-1(72.5 C); PFI-1/BL(K)Upper(77.7 C); PFI- 2/BL(K)lower(83.0 C); PFI-2/BL(K)Upper(95.4 C); SDB-2/BL(K)(73.9 C). For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- SDB-Compressor,Fresh Tex (92.2 C); Compressor Cabinet,Fresh Tex(78.3 C); Washing Machine-19,Fresh Tex(76.0 C); PFI,Substation Room,Fresh Tex(76.8 C); Transformer,Substation Room,Fresh Tex(87.7 C); Pump-1,Starter-1,Power Room,Fresh Tex(92.0 C); MDB-1,Power Room,Fresh Tex(107.8 C); MDB-2,Power Room,Fresh Tex(73.3 C); SDB-17,Sample The Alliance for Worker Safety Page 13/29

14 12 Jun 2014 Room,Fresh Tex(75.8 C); SDB-19,Mezzanine Floor,Fresh Tex(92 C); Dryer Machine motor-12,fresh Tex(76.1 C). For Beximco International Knitwear and Apparels Unit-2 & Esses Fashion Ltd- SDB 1,Ground floor,cutting,esses(72.5 C); SDB 2,Ground floor,finishing,esses(72.8 C); MDB 2,Ground floor,finishing,esses(81.3 C); LT-1(Left Side)IKAL- 2,Substation(77.3 C); Transformer,Substation(110.8 C). For Beximco Apparels Ltd- DB 2,2nd floor,sewing B,CFDL-B Side(93.5 C). For New Dacca Industries Ltd- LT-1(Left Side)IKAL-2(NDIL),Substation(77.3 C); DB 7,Ground floor,finishing,ndil(79.0 C). Note: Detail thermography report is uploaded here under General Information section, namely 'Thermography of Beximco Group'. Photograph: Indications of overheating. Find out the cause of overheating and take proper action including replacing cable or equipment where necessary. Alliance Standard Part 10 Section No multi looping of wiring/cables observed at circuit breakers within switchboards and/or distribution boards. Multi looping of cables are observed at circuit breakers within distribution board. Location: For Beximco Textile Ltd(BLT)- SDB-5,BL(T),Loom-3; SDB- 4,BL(T),Loom-3; DB,BL(T),Loom-3. For Beximco Denim Ltd(BDL)- DB- 6,BL(D),Ground Floor; DB-4,BL(D),Ground Floor; DB-5,BL(D),Ground Floor. For Freshtex (Pvt.)- SDB-08B Fresh Tex Dryer Room. Photograph: Multi looping of cables at circuit breakers. Remove multi looping of cables at circuit breakers within distribution boards. Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling All metal in the building is connected to the building earthing/grounding system such as metal rebar in concrete, metal frame of building, or metal water pipe. Not all metal in the building is connected to the building grounding system such as metal rebar in concrete, metal frame of building and metal water pipe. Location: Beximco Denim Ltd.(BDL), Beximco Knitting Ltd.(BKL), Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.). The Alliance for Worker Safety Page 14/29

15 12 Jun 2014 Worker Interviews: As per worker interview all metal is not connected to the building earthing. Connect all metal in the building to the building grounding system such as metal rebar in concrete, metal frame of building and metal water pipe. Alliance Standard Part 10 Section Earthing Light fixtures without protective covers are not installed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Light fixtures without protective covers are installed in storage areas. Location: For Beximco Textile Ltd.(BLT)- Finish Febric Store,Ground Floor. For Beximco Knitting Ltd.(BKL)- Chemical Store,Ground Floor,Knitting Building. For Freshtex (Pvt.)- Freshtex Storage Area Before Wash. Photograph: Light fixtures without protective covers are installed in storage areas. Ensure light fixtures without protective covers are not installed in storage areas or in any area where the Inspector of the Factories Rules disallows these fixtures. Alliance Standards Part 10 Section Naked Lights Wiring systems are selected and erected so that no damage is caused by the ingress of water. Wiring systems are not selected and erected considering the effect of damage caused by ingress of water. Location: For Beximco Denim Ltd.(BDL)- Open area near substation-2. For Beximco Knitting Ltd.(BKL)- Open area North side of the Knitting Building. For Freshtex (Pvt.)- Fresh Tex Washing Area Above of SDB-8; Near SDB-2,Fresh Tex Washing Area. For Beximco Apparels Ltd- Beside the BAL & CFDL Building. Photograph: Damage due to ingress of water. Ensure wiring systems are selected and erected so that no damage is caused by the ingress of water. The Alliance for Worker Safety Page 15/29

16 12 Jun 2014 Alliance Standards Part 10 Section Presence of Water Transformers with large oil content are provided with soak pits. Transformer with large oil content (2100L) are not provided with soak pits. Location: Freshtex (Pvt)(Substation Room,Ground floor). Photograph: No soak pits are provided for Transformer. Provide soak pits for transformer with large oil content as per BNBC. Alliance Standards Part 10 Section 10.5 Substation Do switchboards and/or distribution boards have clear identification markings? Distribution boards have no clear identification markings. Location: For Beximco Textile Ltd(BLT)- All Distribution Boards. For Beximco Denim Ltd(BDL)- All Distribution Boards. For Beximco Knitting Ltd(BKL)- All Distribution Boards. For New Dacca Industries Ltd- LT Panel, Substation Room, SDB, Substation Room, SDB-Compressour, Substation Room,MDB-1, Sewing Section, Shed-1, MDB-2, Sewing Section, Shed-1. For Beximco Apparels Ltd- All Distribution Boards. For Beximco Corporate Office- All Distribution Board. For Crescent Fashion and Design Ltd- All Distribution Boards. For Freshtex (Pvt.)- Fresh Tex (SDB-19,SDB-20,SDB-13) Random Section (DB-Left, DB-Right). Photograph: No clear identification markings. Ensure clear and permanent identification marks are painted in all distribution boards, switchboards, sub main boards and switches. Alliance Standard Part 10 Section 10.7 BNBC Part 8 Section The Alliance for Worker Safety Page 16/29

17 12 Jun 2014 Do switchboards and/or distribution boards have capacity information labels? Distribution boards have no capacity information labels. Location: For Beximco Textile Ltd(BLT)- All Distribution Boards. For Beximco Denim Ltd(BDL)- All Distribution Boards. For Beximco Knitting Ltd(BKL)- All Distribution Boards. For Beximco Corporate Office- All Distribution Boards. For Crescent Fashion and Design Ltd- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-2. All Distribution Boards. For Beximco Apparels Ltd- All Distribution Boards. For New Dacca Industries Ltd- All Distribution Boards. Photograph: No capacity information labels on distribution boards. Provide capacity information labels (maximum current rating, no of circuit breakers etc.) for distribution boards. Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. As there is no capacity information level available on distribution panel board so installation of any means to prevent over current device will not carry any significant meaning. Label the rated capacity information on distribution boards first then follow the given suggestive plan to prevent installation of over current device. Location: For Beximco Textile Ltd(BLT)- All Distribution Boards. For Beximco Denim Ltd(BDL)- All Distribution Boards. For Beximco Knitting Ltd(BKL)- All Distribution Boards. For Beximco Corporate Office- All Distribution Boards. For Crescent Fashion and Design Ltd- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- All Distribution Boards (Except LT Panel). For Beximco International Knitwear and Apparels Unit-2- All Distribution Boards. For Beximco Apparels Ltd- All Distribution Boards. For New Dacca Industries Ltd- All Distribution Boards. Photograph: No means to prevent the installation of more over current devices. Ensure distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated and listed. The Alliance for Worker Safety Page 17/29

18 12 Jun 2014 Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Each circuit is provided with a dedicated neutral. Each circuit is not provided with a dedicated neutral. Location: For Beximco Textile Ltd.(BLT)- All Distriution Boards except (LT-1,440V Substation Room BT(L); SDB-2,BL(T),Loom-4; SDB-4,BL(T),Loom-3). For Beximco Denim Ltd. (BDL)- All Distribution Boards. For Beximco Knitting Ltd.(BKL)- All Distribution Boards. For BeximcoCorporate Office- Most of the Distribution Boards. For Crescent Fashion and Design Ltd- Most of the Distribution Boards such as DB- 1-Sewing Section-A side-gf-cfdl; DB-5-Cutting section-gf-cfdl; DB-6- Sewing section-b side-gf-cfdl. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-2- Most of the Distribution Boards. For Beximco Apparels Ltd- All Distribution Boards. For New Dacca Industries Ltd- Most of the Distribution Boards. Photograph: No dedicated neutral. Provide dedicated neutral for each circuit. Alliance Standards Part 10 Section 10.3 Electrical Wiring and Cabling Are electrical wiring/cables properly identified? Electrical cables are not properly identified. Location: For Beximco Textile Ltd(BLT)- All Distribution Boards. For Beximco Denim Ltd(BDL)- All Distribution Boards. For Beximco Knitting Ltd(BKL)- All Distribution Boards. For Beximco Corporate Office- All Distribution Boards. For Crescent Fashion and Design Ltd- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-2. All Distribution Boards. For Beximco Apparels Ltd- All Distribution Boards. For New Dacca Industries Ltd- All Distribution Boards. Photograph: Electrical cables are not identified. Ensure the means of identification is obtained by separate color coding, marking tape, tagging or other approved means. The Alliance for Worker Safety Page 18/29

19 12 Jun 2014 Electricity Rules 1937 Rule 51 and 56 Stranded conductors having a nominal cross-sectional area 6mm2 or greater are provided with cable sockets. Conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. Cable sockets are not provided for stranded conductors. Location: For Beximco Textile Ltd(BLT)- Most of the Distribution Boards such as MDB- 2,BL(T),Loom(1); SDB-4,BL(T),Ground Floor; DB,BL(T),Drawing Section; SDB,BL(T),Inspection Section; SDB-1,BL(T),Loom-4; SDB-6,BL(T),Loom-3; MDB,BL(T),Yand Dyeing,1st Floor; SDB-9,BBT-9,Young Dyeing,1st Floor; DB- 2,BBT-9,Young Dyeing,1st Floor. For Beximco Denim Ltd.(BDL)- All Distribution Boards. For Beximco Knitting Ltd(BKL)- All Distribution Board. For Beximco Corporate Office- All Distribution Boards. For Crescent Fashion and Design Ltd- All Distribution Boards. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- All Distribution Boards (Except LT Panel). For Beximco International Knitwear and Apparels Unit-2- All Distribution Boards. For Beximco Apparels Ltd- All Distribution Board. For New Dacca Industries Ltd- All Distribution Boards. Photograph: Cable sockets are not provided. Provide cable sockets for stranded conductors having a nominal crosssectional area 6mm2 or greater. Conductors below 6 mm2 without cable sockets, all strands at the exposed ends are soldered together or are crimped using suitable sleeve or ferrules. Alliance Standards Part 10 Section Cable Ends The substation room has adequate ventilation. Non-Compliance Level: 2 The substation room does not have adequate ventilation. Location: Beximco Denim Ltd.(BDL),(Substation-02,Ground floor); Beximco Textile Ltd.(BLT), (Substation room,ground floor); New Dacca Industries Ltd,(Substation room, Ground floor). Photograph: Inadequate ventilation in the substation room. Provide means of ventilation for the substation room. Consult a qualified electrical engineer to determine the required ventilation rates based on the installed equipment. The Alliance for Worker Safety Page 19/29

20 12 Jun 2014 Alliance Standard Part 10 Section Inspection of Substation Installations. Power and telecommunication or antenna cables are led in separately. Power and telecommunication cables are not led in separately. Location: Beximco International Knitwear and Apparels Unit-1, Freshtex (Pvt) Ltd. Visual Assessment: Power and telecommunication cables are not separated. Lead telecommunication or antenna cables separately to the main point of service. Power and telecommunications cables must have separate entrance. Alliance Standards Part 10 Section Service Entry The substation room has adequate means of security. The substation room is not secured properly. Location: Beximco Denim Ltd(BDL)-Substation-2,Ground floor,denim building. Photograph: Improper security in the substation room. Install security measures to ensure access to the substation is restricted. Alliance Standard Part 10 Section Inspection of Substation Installations. Are all switchboards and/or distribution boards properly grounded (earthed)? Distribution boards are not properly grounded due to inadequate size of earth continuity conductor. Location:For Beximco Textile Ltd(BLT)-Most of The Distribution Boards such as MDB-2,BL(T),Loom(1); SDB-4,BL(T),Ground Floor; DB,BL(T),Drawing Section; SDB,BL(T),Inspection Section; SDB- 1,BL(T),Loom-4; SDB-6,BL(T),Loom-3; MDB,BL(T),Yarn Dyeing,1st Floor; SDB-9,BBT-9,Yarn Dyeing,1st Floor; DB-2,BBT-9,Yarn Dyeing,1st Floor; SDB- The Alliance for Worker Safety Page 20/29

21 12 Jun ,BBT-9,Yarn Dyeing,1st Floor; SDB-7,BBT-9,Yarn Dyeing,1st Floor; SDB- 8,BBT-9,Yarn Dyeing,1st Floor. Photograph: Inadequate grounding. Provide grounding for distribution boards as per BNBC. Alliance Standard Part 10 Section Circuit and System Earthing Are switchboards and/or distribution boards free of dust and debris? Distribution boards are not clean and free of dust and debris. Location: Beximco Textile Ltd(BLT)-SDB,BL(T),Generator Room; LDB-2,Generator Room; LDB-3,Generator Room; MDB-1,BL(T),Loom(1); SDB-2,BL(T),Ground Floor; SDB-5,BL(T),Loom-3; SDB-6,BL(T),Loom-3; SDB-7,BL(T),Loom-4; SDB-8,BL(T),Loom -4; SDB-1,BL(T),Winding Section; MDB,BBT-9,Yarn Dyeing,1st Floor; SDB-6,BL(T),BBT-2,Bletching,Solid Dyeing; SDB-5,BL(T),RF Dryer. For Beximco Denim Ltd(BDL)-DB-1,BL(D),Ground Floor; DB- 2,BL(D),Ground Floor; DB-8,BL(D),Ground Floor; MDB-3,BL(D),Ground Floor. For Beximco International Knitwear and Apparels Unit-1 & Freshtex (Pvt.)- Fresh Tex MDB-3,MBD-4,Washing Area Cable Tray. Photograph: Distribution boards are not clean. Disconnect the panel from the electrical service and clean interior components of all dust and debris. Seal all openings within the enclosure to prevent dust and debris from entering. Alliance Standard Part 10 Section Enclosures Are lighting and receptacle (socket) circuits segregated? Lighting and socket circuits were found under same protection or switchgear. Location: For Beximco Textile Ltd(BLT)- DB,BL(T), Drowing Section. Visual Assessment: Lighting and socket circuits are not separated. Lighting and socket circuits must be separated at the noted locations. Have a qualified electrician separate the lighting and sockets into separate circuits. The Alliance for Worker Safety Page 21/29

22 12 Jun 2014 Alliance Standard Part 10 Section Electrical wiring and conduit is properly supported. Electrical wiring and conduit is not properly supported. Location: For Beximco Denim Ltd.(BDL)- Open area south side of the Beximco Denim Building. For Beximco Apparels Ltd- Sweing Section,3rd Floor,BAL. For New Dacca Industries Ltd- Shed-1,Finishing Section,Ground Floor. Photograph: Inadequate cable support. Provide adequate supports for electrical wiring and conduit. Alliance Standard Part 10 Section , , and Cable joints are through porcelain/pvc connectors with PIB tape wound around joint. Cable joint does not meet the standard requirements in respect of conductivity, insulation and mechanical strength. Location: For Beximco Textile Ltd(BLT) Half of the Distribution Boards such as LT-1,BL(T),Switch Room; MDB,BL(T),Switch Room; SDB,BL(T),Generator Room; LDB-3,Generator Room; MDB,BL(T),Loom(1); SDB-1,BL(T),Loom(1); DB,BL(T),Drawing Section; SDB-2,BL(T),Loom-4; SDB-4,BL(T),Loom-3. For Beximco Denim Ltd(BDL)- MDB-4,BL(D),Ground Floor; MDB-6,BL(D),Ground Floor. For New Dacca Industries Ltd- SDB-1,Storage,Shed-2; SDB,Substation Room. Photograph: Improper cable joint. Ensure cable joints through porcelain/pvc connectors with PIB tape wound around joint in respect of conductivity, insulation and mechanical strength. Alliance Standards Part 10 Section Cable Joints The Alliance for Worker Safety Page 22/29

23 12 Jun 2014 Lighting fixtures are supported from the structure and seismic bracing is installed as required. Lighting fixtures are not supported properly from the structure. Location: For Freshtex (Pvt.)-Fresh Tex Sample Section. Photograph: Lighting fixtures are not supported properly. Ensure Lighting fixtures are supported from the structure and seismic bracing is installed as required. Alliance Standards Part 10 Section Lighting Fittings Electrical connections at equipment, fixtures, etc are properly secured. Electrical connections at equipment, fixtures etc are not properly secured. Location: For Beximco Textile Ltd. (BLT)-Dyeing Section. Photograph: Electrical connections are not secured. Ensure electrical connections at equipment, fixtures etc are properly secured. Alliance Standards Part 10 Section Electrical Connections Is all electrical wiring/cable properly terminated at its point of termination (No un-terminated wires, lugs are provided at terminals, etc)? Electrical cables are not properly terminated at its point of termination. Location: For Beximco Textile Ltd.(BLT)- SDB,BL(T),Generator Room; LDB- 3,Generator Room; SDB,BL(T),BBT-3; SDB-1,BL(T),Loom4; SDB- 2,BL(T),Loom-4. For Beximco Denim Ltd.(BDL)- MDB-4,BL(D); Ground Floor near SDB-4. For Crescent Fashion and Design Ltd- Fusing section-gf-cfdl. For Freshtex (Pvt.)- Fresh Tex (SDB-5 Washing Area; SDB-7; SDB-8). Photograph: Un-terminated cables. The Alliance for Worker Safety Page 23/29

24 12 Jun 2014 Ensure all electrical cables properly terminated at its point of termination. Alliance Standards Part 10 Section Wiring of Sub-distribution Boards Mechanical guards are provided for electrical equipment and wiring where necessary. No mechanical guards are provided for electrical equipment where necessary. Location: For Beximco Textile Ltd.(BLT)-Pump Room. For Beximco Knitting Ltd.(BKL)-Dryer machine,ground Floor. For New Dacca Industries Ltd-Sewing Section, Shed-1. Photograph: No mechanical guards. Provide mechanical guards for electrical equipment where necessary. Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling, Cables, and 10.7 Main Switch, Switchboards And Metal Clad Switchgear Signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Low No signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Location: For Beximco Textile Ltd.(BLT)- Finish Febric Store,Ground Floor. For Beximco Knitting Ltd.(BKL)- Chemical Store,Ground Floor, Knitting Building. For Crescent Fashion and Design Ltd- Finished goods store-underground-cfdl. For Beximco International Knitwear and Apparels Unit-2- Store-Esses Fashion Ltd. For Beximco Apparels Ltd- Storage,Ground Floor,BAL. For New Dacca Industries Ltd- Shed-2,Storage. Photograph: No signage indicating the prohibition of installation of without protective covers light fixtures. Light fixtures without protective covers (otherwise known as naked lights) shall not be allowed in storage areas or in any area where the Inspector of the Factories Rules disallows these fixtures. Install signs posted in Bengali and English, indicating th The Alliance for Worker Safety Page 24/29

25 12 Jun 2014 Alliance Standards Part 10 Section Naked Lights Are electrical insulation mats provided in front of substation, switchboards and/or distribution boards? Low Inadequate electrical insulation mats are provided in front of distribution boards. Location: Beximco Textile Ltd.(BLT)- Most of the distribution boards such as SDB-1/Substation Room; SDB BBT-3/DG; MDB-1/Loom-1; MDB- 2/Loom; SDB-7,BL(T),Loom-4; SDB-8,BL(T),Loom-4; SDB-1,BL(T),Winding Section; MDB,BBT-9,Yarn Dyeing,1st Floor; SDB-6,BL(T),BBT- 2,Bletching,Solid Dyeing; SDB-5,BL(T),RF Dryer. Beximco Denim Ltd.(BDL)- MDB-6(BDL),Ground Floor; DB-9(BDL),Ground Floor. Photograph: Inadequate electrical insulation mats are provided. Provide electrical insulation mats in front of distribution boards. Alliance Standard Part 10 Section Inspection of the Installation. Are meters and other electrical devices (Ammeter, Voltmeter, PFI Auto Controller, etc) installed on the main electrical equipment operational? Low Meters and other electrical devices (Ammeter, Voltmeter, Selector switch, Indicator lamp etc) are not installed on the main electrical equipment. Although in some cases meters (Ammeter & Voltmeter) installed on the main electrical equipment are not operational. Location: For Beximco Apparels Ltd- All MDBs except LT Panel. For Beximco Textile Ltd(BLT)- MDB-1/Loom-1, MDB- 2/Loom-1, LT-1/Substation Room. Photograph: Meters and other electrical devices are not installed & operational. Ensure meters and other electrical devices installed on the main electrical equipment are operational. Alliance Standard Inspection of the Installation The Alliance for Worker Safety Page 25/29

26 12 Jun 2014 Phase separators are provided between terminals on circuit breakers. Low Phase separators are not provided between terminals on circuit breakers. Location: For Beximco Textile Ltd(BLT)- SDB,BL(T),Generator Room; MDB- 1,BL(T),Loom(1); MDB-2,BL(T),Loom(1); SDB-2,BL(T),Loom-4; LDB, (OLD),Chiller Room. For Beximco Denim Ltd(BDL)- MDB-6,BL(D),Ground Floor; DB-4,BL(D),Ground Floor; DB-5,BL(D),Ground Floor; DB- 9,BL(D),Ground Floor. For New Dacca Industries Ltd- MDB-2,Sewing Section,Shed-1; SDB-1,Storage,Shed-2. Photograph: No phase separators. Install phase separators between terminal connections. Verify phase separators are installed at all remaining locations. Alliance Standard Part 10 Section Electrical Connections Emergency Power System Is the generator room properly ventilated Generator room is not properly ventilated. Location: For Beximco Textile Ltd. (BLT)-Generator Room-2(BLT), For Beximco Knitting Ltd.(BKL)-Generator Room, Beximco Knitting Building and Central Gas turbine. Photograph: Inadequate ventilation in the generator room. Provide means of ventilation for the generator room. Consult a qualified electrical engineer to determine the required ventilation rates based on the installed equipment. Alliance Standards Part 10 Section Generator Room Are emergency power switchboards, distribution boards, and circuits properly identified? Emergency power switchboards, distribution boards and circuits are not properly identified. Location: All emergency power switchboards, distribution The Alliance for Worker Safety Page 26/29

27 12 Jun 2014 boards and circuits, All factory located in Beximco Group. Visual Assessment: No identification of emergency switchboards, distribution boards and circuits. Ensure proper identification of emergency power switchboards, distribution boards and circuits. NFPA 70 Chapter 7 Article Wiring, Emergency System Is the generator room properly rated and physically separated from the remainder of the building? Generator room is not properly rated but physically separated from the remainder of the building. Location: For Beximco Knitting Ltd.(BKL)-Generator Room, Beximco Knitting Building, Ground floor. Photograph: Generator room is not rated. Consult with an expert fire protection engineer and make sure the generator room is fire rated as per Alliance standard. Alliance Standards Part 10 Section Generator Room Are cable trenches properly covered? Cable trenches are not covered properly. Location: Beximco Textile Ltd(BLT)- Generator Room-2(BLT). Photograph: Inadequate cable trench cover. Provide adequate cover on cable trench. Alliance Standard Part 10 Section Inspection of the Installation Is the generator frame earthing (grounding) provided at two separate points? The Alliance for Worker Safety Page 27/29

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17 11 Feb 2015 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory 81, Kalmessar, "Jalal Shopping Complex" Board Bazar, Gazipur. 20 May 2014 The Alliance for Bangladesh Worker Safety Page 1/21 20 May 2014 Introduction

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/15 19

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Plot #92 (Partial) DEPZ Extention Area-02 Ganakbari, Ashulia, Savar Uttaron 10 Feb 2014 The Alliance for Bangladesh Worker Safety Page

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/6 Introduction to

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 154 Kamrabad, Atarar Depot Chittagong Chittagong Chittagong The Alliance for Worker Safety Page 1/7 Introduction to the Report The following report contains

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/11 30 Oct 2016 Introduction to the Report The following report

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: N. Islam Center, Mazar Road, Dhakkhin Khan Uttara, Dhaka Dhaka Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/10 09 Jun 2014 Introduction to

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Maks Fashion Ltd 1 Kapashgola Road Chawkbazar Chittagong Chittagong Bangladesh 19 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/16 19 Apr 2014 Introduction

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIKDER APPAREL HOSIERY LTD. Khadun (Dug No. 342/343), Tarabo, Rupgonj, Narayanganj, Bangladesh. Factory List: 1. Sikder Apparel Hosiery Ltd. Inspected by: Pema Wangdi

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT SIDKO LIMITED PLOT NO. 36, ROAD NO. 46, GULSHAN NORTH C/A, DHAKA. Factory List: 1. N. A. Garments 2. 3. Sidko Apparels 4. Delta Ties Ltd. Inspected on April 17, 2014

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MUAZUDDIN TEXTILES LTD. Plot # 235/236, East Chandura, Shafipur, Kaliakor, Gazipur, Bangladesh. Factory List: 1. Inspected by: Younten Jamtsho Report Generated by: Stabak

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection

More information

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. (A Wholly Owned Subsidiary of SBI) CIRCLE OFFICE: 4TH FLOOR, SBI LOCAL HEAD OFFICE III/1-PANDIT J N MARG, KHARAVELA NAGAR BHUBANESWAR, ODISHA-751001 Part-II PRICE

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671 Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT COMFORT APPAREL, ( PVT ) LTD. 96, DARUS SALAM, MIRPUR, DHAKA OTHER FACTORIES: SALMA FASHION WEARS LTD, COMFORT KNIT FASHION LTD March 27, 2014 Page 2 SUMMARY was surveyed

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

COMPANY PROFILE Electrical & Instrumentation Contractor

COMPANY PROFILE Electrical & Instrumentation Contractor COMPANY PROFILE Electrical & Instrumentation Contractor Engineering I Supply I Installation I Testing I Commissioning Maintenance I Fabrication I Ship Repairing ABOUT US The year was 2003, where there

More information

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment WALMART SUPPLIER FACTORY SAFETY ASSESSMENT OVERVIEW Wal-Mart Stores, Inc. ( Walmart ) engaged Bureau Veritas to conduct fire, building and electrical safety assessments at factories in Bangladesh designated

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT MILLENNIUM TEXTILES (SOUTHERN) LTD., Bara Rangamatia, Ashulia, Savar, Dhaka 1341, Bangladesh Factory List: MILLENNIUM TEXTILES (SOUTHERN) LTD., Inspected on April 8,

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information