NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL

Size: px
Start display at page:

Download "NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL"

Transcription

1 NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL Stephen J. Jordan Fire Protection Consultant Fire & Risk Alliance, LLC Rockville, MD, USA sjordan@fireriskalliance.com

2 OVERVIEW Motivation Current Spray Details Spray Measurements General overview Notable improvements Spray Tools Developed Sprinkler comparison tool Spray dispersion simulator Example Comparisons Conventional sprinklers ECOH sprinklers ESFR sprinklers Implications Future Work

3 MOTIVATION Sprinklers with same listings generate physically different spray characteristics: Different sprinkler construction = different spray characteristics

4 MOTIVATION Unknown levels of equivalent performance Pass identical testing Only establishes a minimum level of equivalence Residential sprinkler acceptance testing All bins shall have a minimum quantity of water Only a limited number can have less than a secondary threshold Test results are Pass / Fail Pass / Fail Criteria Pass / Unlisted

5 CURRENT LEVEL OF SPRAY DETAIL Listing, pressure, spacing Manufacturer provided ceiling heights General spray angles Spray patterns? No Bucket tests, simulations, etc. Modeling parameters? No FDS, BIM, etc.

6 Instrumentation (flow properties; spray properties; optical configuration) SPRAY MEASUREMENTS 1 Primary Subsystems: (1) Flow Control & Sprinkler Rotation (2) Mechanical Sphere Patternation (3) Optical Sphere Patternation (4) Integral Line Patternation Supported by: Automation & Synchronization Instrumentation Recent measurement upgrades Enhanced flow capacity Extended measurement dynamic range Complete characterization of the discharged spray characteristics GB of data per characterization After data reduction approaches: < 1 MB Automation & Synchronization (measurement location; flow control; measurement time) 2 Data Acquisition (measurement location; raw spray measurements) Analysis (measurement location; probe details; raw measurements) X Z 3 Z 21 X 4

7 SPRINKLER COMPARISON TOOL

8 SPRINKLER COMPARISON TOOL

9 SPRINKLER COMPARISON TOOL

10 DISPERSION SIMULATION TOOL

11 EXAMPLE 1: Sprinkler Type: Conventional k-factor: 5.6 Pressure: 25 psi

12 SPRAY MEASUREMENTS Sprinkler A Sprinkler B

13 SPRINKLER COMPARISONS Sprinkler A Sprinkler B

14 DISPERSION COMPARISONS Sprinkler A Sprinkler B z = -3 m

15 EXAMPLE 2: Sprinkler Type: ECOH k-factor: 11.2 Pressure: 30 psi

16 MANUFACTURER SPECIFICATIONS Sprinkler C Sprinkler D Max Spacing Ordinary Hazard Group 1 Ordinary Hazard Group 2 (ft x ft) Flow (GPM) Pressure (psi) Flow (GPM) Pressure (psi) 12 x x x x x Max Spacing Ordinary Hazard Group 1 Ordinary Hazard Group 2 (ft x ft) Flow (GPM) Pressure (psi) Flow (GPM) Pressure (psi) 12 x x x x x

17 SPRAY MEASUREMENTS Sprinkler C Sprinkler D

18 SPRINKLER COMPARISONS Sprinkler C Sprinkler D

19 DISPERSION COMPARISONS Sprinkler C Sprinkler D z = -3 m

20 EXAMPLE 3: Sprinkler Type: ESFR k-factor: 16.8 Pressure: 35 psi

21 MANUFACTURER SPECIFICATIONS Sprinkler E Sprinkler F Maximum Coverage Area: 100 ft² Minimum Coverage Area: 64 ft² 12 ft for H < 30 ft Maximum Spacing: 10 ft for H < 30 ft Minimum Spacing: 8 ft Minimum Clearance: 36 in Maximum Coverage Area: 100 ft² Minimum Coverage Area: 64 ft² 12 ft for H < 30 ft Maximum Spacing: 10 ft for H < 30 ft Minimum Spacing: 8 ft Minimum Clearance: 36 in

22 SPRAY MEASUREMENTS Sprinkler E Sprinkler F

23 SPRINKLER COMPARISONS Sprinkler E Sprinkler F

24 DISPERSION COMPARISONS Sprinkler E Sprinkler F z = -5 m

25 IMPLICATIONS THE REAL DIFFERENCE ( ) ( GPM/ft Y (ft) 3.50 Y (ft) GPM/ft ) X (ft) X (ft) 3 4

26 FUTURE WORK SPRINKLER COMPARISONS Manufacturer: A k-factor: 16.8 Pressure: 35 psi Manufacturer: B k-factor: 16.8 Pressure: 35 psi Manufacturer: C k-factor: 16.8 Pressure: 35 psi

27 FUTURE WORK BIM INTEGRATION

28 SUMMARY A final case study: Chris Morgen and Dan SanFelice are both track and field athletes Participate in the high jump Both cleared the preliminary qualifying jump Both have comparable heights, weights and years of experience. YOU have to place a bet on one of the two athletes Who do you pick? How do you pick? Athlete Qualified? Chris Morgen Yes Dan SanFelice Yes

29 SUMMARY More information about Chris and Dan: It took Chris one attempt to make the qualifying jump Dan took three attempts Dan touched the grazed the bar on his last attempt Chris cleared the bar with inches to spare The more information you have, the easier it becomes to make an educated choice. The spray measurement, comparison, and visualization tools under development are just a first step in providing much needed information to make an educated engineering judgement.

30 Thank you for your time! Questions?

31 Additional Information Stephen J. Jordan Fire Protection Consultant Fire & Risk Alliance, LLC Rockville, MD, USA

32 THE REAL DIFFERENCE ( ) ( ) 4 GPM/ft2 GPM/ft Y (ft) Y (ft) X (ft) X (ft) 3 4

Early Suppression Fast Response Sprinklers and Obstructions

Early Suppression Fast Response Sprinklers and Obstructions Early Suppression Fast Response Sprinklers and Obstructions Presented at SUPDET 2016 March 1, 2016 San Antonio, Texas Presented by: Garner Palenske, P.E. Senior Vice President Aon Fire Protection Engineering

More information

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

Mud-Motor Characterization

Mud-Motor Characterization Mud-Motor Characterization Joint-Industry Project Proposal September 1 st, 2016 Previous Joint-Industry Projects Conoco Consortium SPE Paper 22735 Objectives Improved Motor Quality Assurance Consistent

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix FINAL REPORT BY: Justin A. Geiman, P.E. Noah L. Ryder, P.E. Fire & Risk Alliance Rockville, MD, USA October 2017 2017 Fire Protection

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying

More information

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Pendent Sprinkler VK537 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0) Sprinkler 83h 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 and Pendent Sprinkler VK572 are thermosensitive glass bulb spray sprinklers

More information

Box-in-Box Cold Storage Fire Protection Options

Box-in-Box Cold Storage Fire Protection Options Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges

More information

The Effect of Large Orifice Sprinklers on High-Challenge Fires

The Effect of Large Orifice Sprinklers on High-Challenge Fires SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application

More information

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based

More information

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91% 210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent

More information

standard/quick response extended coverage light and ordinary hazard elo sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

Exaggerated for Clarity. Residential Pendent, Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

Exaggerated for Clarity. Residential Pendent, Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The Model V3426 residential sprinkler is designed with optimal flow characteristics for use in residential NFPA 13 systems. The larger 6.9 K-Factor will aid

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.)

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.) : new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca

More information

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2) Page 1 of 6 1. DESCRIPTION Viking EC/QREC Pendent Sprinkler VK534 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements.

More information

HYDRAULIC CALCULATIONS. 952 Arapahoe

HYDRAULIC CALCULATIONS. 952 Arapahoe HYDRAULIC CALCULATIONS 952 Arapahoe 952 Arapahoe Ave Boulder, CO 80301 CONTENTS: CALCULATION #1 - CALCULATION METHOD - TWO HEAD CALC HAZEN WILLIAMS Job Job Number Hydraulic Overview CA-11-0531 Job Name:

More information

FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST

FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST AHRI CERTIFICATION PROGRAM FOR AIR-COOLED WATER-CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE ACCL Participant: Date of Test: Witness Test

More information

Fifth Annual Waste Treatment Symposium, September Kelly Brown, BDP Industries, Inc.

Fifth Annual Waste Treatment Symposium, September Kelly Brown, BDP Industries, Inc. Fifth Annual Waste Treatment Symposium, September 2010 Kelly Brown, BDP Industries, Inc. Agenda Description of Operation Advantages / Disadvantages verses Other Options Performance Parameters Capital and

More information

DISCONTINUED PRODUCT

DISCONTINUED PRODUCT SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS These Model V27 residential sprinklers are designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes, depending

More information

STORAGE FIRE PROTECTION SPRINKLERS

STORAGE FIRE PROTECTION SPRINKLERS STORAGE FIRE PROTECTION SPRINKLERS HOW CAN YOU REDUCE YOUR FIRE SPRINKLER INSTALLATION COSTS? Tyco Storage Sprinklers are intended for use in storage applications such as big box retail, extra hazard,

More information

40.49 V27, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Horizontal Sidewall, Recessed Horizontal Sidewall V2744 QUICK RESPONSE

40.49 V27, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Horizontal Sidewall, Recessed Horizontal Sidewall V2744 QUICK RESPONSE SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The residential sprinkler is designed with optimal flow characteristics for use in residential NFPA 13 systems. The larger 5.6 K-Factor will aid in the system

More information

Energy Efficiency Demonstration Residential Ductless Heat Pumps (DHP) Overview. Ammi Amarnath Chris Trueblood

Energy Efficiency Demonstration Residential Ductless Heat Pumps (DHP) Overview. Ammi Amarnath Chris Trueblood Energy Efficiency Demonstration Residential Ductless Heat Pumps (DHP) Overview Ammi Amarnath Chris Trueblood 22 February 2010 Energy Efficiency Demonstration DHP: Overview Research Objectives Assess residential

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014 Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data June 10, 2014 1 Agenda Background / Overview Solution Approach Groupings Criteria Sites Speed Weight

More information

The Worldwide Use of Fire Sprinklers

The Worldwide Use of Fire Sprinklers The Worldwide Use of Fire Sprinklers Russell P. Fleming, P.E. President, National Fire Sprinkler Association (USA) Managing Director, International Fire Sprinkler Association United States Fire Sprinkler

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1 PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY 3/16/2012 Fred Ferrara 1 Typical Hydronic System Problems Low Delta T s resulting in: 1. Chillers operating at higher capacities and/or longer than necessary

More information

PG&E s Applied Technology Services Hot Water Technology Performance Laboratory

PG&E s Applied Technology Services Hot Water Technology Performance Laboratory PG&E s Applied Technology Services Hot Water Technology Performance Laboratory Edwin Huestis, P.E. Senior Mechanical Engineer PG&E Applied Technology Services ACEEE Hot Water Forum February 23, 2016 Presentation

More information

Wildland fire phenomenology experiments:

Wildland fire phenomenology experiments: Wildland fire phenomenology experiments: 2001-2002 RIT: Bob Kremens Stef VanGorden Andy Fordham Bryce Nordgren Dave Pogolarza Adam Cisz RMSC: Dan Latham Colin Hardy Brett Butler We plan to measure unknown

More information

Fire Protection Coffee Break Training August 2016

Fire Protection Coffee Break Training August 2016 Fire Protection Coffee Break Training August 2016 Agenda Introduction - Phelan NFPA 13 versus NFPA 13R systems for Residential Occupancies - Homa NFPA 72 Record of Completion - Homa Questions and Answers

More information

Spray sprinkler system

Spray sprinkler system Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report Spray sprinkler system Recommendations on fire protection in tyre storage facilities using spray

More information

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection

More information

EXAMPLES OF INDIVIDUAL DOWNHOLE HEAT EXCHANGERS SYSTEMS IN KLAMATH FALLS

EXAMPLES OF INDIVIDUAL DOWNHOLE HEAT EXCHANGERS SYSTEMS IN KLAMATH FALLS EXAMPLES OF INDIVIDUAL DOWNHOLE HEAT EXCHANGERS SYSTEMS IN KLAMATH FALLS John W. Lund Geo-Heat Center INTRODUCTION The downhole heat exchanger (DHE), used extensively in Klamath Falls in over 500 installations,

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Improving Dryer Efficiency

Improving Dryer Efficiency Improving Dryer Efficiency Ken Hill Systems Group President Kadant Johnson Inc. What Comprises Dryer Efficiency? Energy Efficiency Steam utilization Drying Efficiency Drying capacity / production Operational

More information

Fiber Optic Cable Qualification Update

Fiber Optic Cable Qualification Update Fiber Optic Cable Qualification Update EQTM 2018 Eric Rasmussen RSCC Wire and Cable LLC Eric.rasmussen@r-scc.com Terry Price Ontario Power Generation Terry.price@opg.com 1 Darlington Nuclear Generating

More information

40.43 V38, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Low Flow Adjustable Concealed Pendent V3806 QUICK RESPONSE

40.43 V38, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Low Flow Adjustable Concealed Pendent V3806 QUICK RESPONSE SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The V3806 concealed, designer style sprinkler allows up to 1/4"/8 mm adjustment to accommodate concealment needs. The separate two-piece mounting cup/cover plate

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com AUGUST 2014 A-15 GLOBE RESIDENTIAL SPRINKLER

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems Abstract In the industry of Fire Protection a large number of Automatic Fire Sprinklers has been developed trying to cover all

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending FireLock LP-46 Low Pressure Storage Sprinkler This storage sprinkler was designed for controlling fires in single, double and multiple row rack storage of up to Cartoned, Unexpanded, Group A plastic commodities

More information

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE March 2, 2007 Sprinkler 147k 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK425 is small a highsensitivity solder link and lever residential sprinkler designed for installation

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

Fire Protection District Business Pre-Plan Form

Fire Protection District Business Pre-Plan Form DATE OF INSPECTION Fire Protection District Business Pre-Plan Form OCCUPANT INFORMATION BUSINESS NAME: BUSINESS ADDRESS: CITY: STATE: ZIP: MAIN CONTACT PERSON: BUSINESS PHONE: BUSINESS FAX: EMAIL ADDRESS:

More information

Leak Detection of Critical Watermains in the City of Hamilton

Leak Detection of Critical Watermains in the City of Hamilton Leak Detection of Critical Watermains in the City of Hamilton Chris Martire, Robinson Consultants Inc. Michael Zantingh, City of Hamilton TRENCHLESS TECHNOLOGY ROADSHOW May 28-29, 2014 Scotiabank Convention

More information

1.1 VTS: number 1 in the world pillars of success

1.1 VTS: number 1 in the world pillars of success Heating Unit 01 VTS GROUP 1.1 VTS: number 1 in the world 1.2 3 pillars of success 02 2.1 water hearers Modernity Innovativeness Energy efficiency 2.2 Assembly 2.3 VR-D destratifier 2.4 Automation 03 TECHNICAL

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved,

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

DCS DSS OSS EIB OBPS OPTS FDS AFSS

DCS DSS OSS EIB OBPS OPTS FDS AFSS www.abdesign.org DCS DSS OSS EIB OBPS OPTS FDS AFSS TOTAL SAFETY ELECTRONIC INCIDENT BOARD ELECTRONIC INCIDENT BOARD AFT ZONE CONTROL POST COMBAT INFORMATION CENTRE ON-BOARD PATROL SYSTEM SHIP CONTROL

More information

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Hai Jiang, Vaidya Sankaran, Med Colket, May Corn United Technologies Research Center Kati Laakkonen Marioff Corporation 14th International

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

Declaration of Conformity

Declaration of Conformity Declaration of Conformity DEMONSTRATION OF CONFORMITY WITH RECOGNIZED STANDARDS TO SATISFY THE SAFETY AND EFFECTIVENESS REQUIREMENTS OF THE CANADIAN MEDICAL DEVICES REGULATIONS Name of the medical device

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems General Description LFII Residential Flush Horizontal Sidewall

More information

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA September 5, 2008 Sprinkler 147u 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK457 is a small highsensitivity solder link and lever residential sprinkler designed for installation

More information

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Aspirating Gas Detection CFD Modelling Predicts Application Performance Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized

More information

ISO/TS TECHNICAL SPECIFICATION

ISO/TS TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION ISO/TS 10811-1 First edition 2000-06-01 Mechanical vibration and shock Vibration and shock in buildings with sensitive equipment Part 1: Measurement and evaluation Vibrations et

More information

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary Sprin klers, Standard

More information

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5 Bulletin 034 Rev. F Model G5 Series Sprinklers Available with Solid, Perforated, or Gasket Standard Coverage, Concealed Pendent K2.8, 4.2, 5.6, & 8.0 (40, 60, 80, & 115 metric) Product Features Model G5

More information

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA October 4, 2007 Sprinkler 149m Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom Residential Pendent Sprinkler VK468

More information

573 Dew Point Mirror. Industrial Chilled Mirror Hygrometer. Typical applications:

573 Dew Point Mirror. Industrial Chilled Mirror Hygrometer. Typical applications: Industrial Chilled Mirror Hygrometer Integral frost/dew point measuring head Internal sample pump Optimal Response Injection System ForceFrost TM function Ice-Test user calibration verification User configurable

More information

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2) Page 1 of 5 1. DESCRIPTION Viking Freedom Residential Horizontal Sidewall Lead Free* Sprinkler VK4840 is a small, thermosensitive, glass-bulb residential sprinkler available in several different finishes

More information

sprinkler vk538 (K11.2)

sprinkler vk538 (K11.2) December 6, 2012 Sprinkler 89h 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems

More information

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart. April 4, 2008 Sprinkler 143g Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom Residential Horizontal Sidewall Sprinkler

More information

ABSTRACT. Title of Document: DEVELOPMENT OF A CYBER PHYSICAL SYSTEM FOR FIRE SAFETY

ABSTRACT. Title of Document: DEVELOPMENT OF A CYBER PHYSICAL SYSTEM FOR FIRE SAFETY ABSTRACT Title of Document: DEVELOPMENT OF A CYBER PHYSICAL SYSTEM FOR FIRE SAFETY Rosalie Faith Wills, Master of Science, 2015 Directed By: André Marshall, Associate Professor, Department of Fire Protection

More information

article continues below

article continues below The NIST Station Nightclub Fire Investigation: Physical Simulation of the Fire By: Daniel Madrzykowski, Nelson Bryner, and Stephen I. Kerber Introduction A fire occurred on the night of February 20, 2003,

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

freedom residential Upright sprinkler vk467 (k4.9)

freedom residential Upright sprinkler vk467 (k4.9) Page 1 of 6 1. DESCRIPTION Viking Freedom Residential Upright Sprinkler VK467 is a small, thermosensitive, glassbulb residential sprinkler available in several different finishes and temperature ratings

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2284) are decorative, fast response, fusible solder sprinklers

More information

Sprinkler Identification Number (SIN)

Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K Horizontal Sidewall Standard Response, Extended Coverage General Description TYCO Series DS-3 Dry-Type Sprinklers, 11.2K Horizontal

More information

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING Paper s No. BUE-FISC2010 154 DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING Hwa Young Shin 1 / Yeunsook Lee 2 / Mi Seon Jang 2 / Ki Hoon Moon 3 / Jeong Tai Kim 1 * 1 Kyung Hee

More information

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems where the appearance

More information

Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory

Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory Amin Delagah Project Engineer Fisher Nickel, a division of Frontier Energy

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis Experience designing cable and network testers has enabled a breakthrough

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) February 27, 2009 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

Visual Alarm Devices. Presented prepared by Chris Orr

Visual Alarm Devices. Presented prepared by Chris Orr Visual Alarm Devices Presented prepared by Chris Orr Visual Alarm Devices The new standard AS7240.23 is based on EN54-23/ISO 7240.23 New Clause 3.22 (b) (xvi)&(xvii) introduces the requirements for VADs

More information