DRAFT BMS SPECIFICATION

Size: px
Start display at page:

Download "DRAFT BMS SPECIFICATION"

Transcription

1 DRAFT BMS SPECIFICATION \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

2 Content 1.0 AUTOMATIC CONTROLS Project outline Extent of work Scope Standards, Codes and Regulations Quality control Responsibilities Design Supply Installation Co-ordination with others Setting to work the automatic controls Setting to work the building services Monthly Return visits Handover Documentation Training Power requirements Services equipment and packaged plant Packaged fan starters Pump starters Fan starters Inverters DX systems Smoke damper control system Smoke dampers Cold water booster sets Sprinkler pumps and tanks Wet riser pumps and tanks Water leak detection Fan coil units Three speed conventional FCU Variable speed FCU Chillers Gas boilers Gas detection system Gas valves and meters Heat meters 16 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

3 Water meters Transformer monitoring Trace Heating Sump pumps Side stream de-aerator System Uvex Lift monitoring Disabled toilet alarm Commissioning and Guarantee General Commissioning Requirements Third party attendance Installation Report Environmental report Approvals and acceptance Test equipment and instruments Test certificates Control and starter panel tests off site Software testing off site User Interface off site testing Pre-commissioning checks Electrical wiring Point to graphic Sensor calibration Identification Local authority demonstrations Commissioning records Standards of Materials and Workmanship Submittals Inspections/approval/requirement Common Control Requirements General Instructions to client Building log book part L compliance Operating and maintenance manual Preparation of Manuals Submission of Operation and Maintenance Manuals Maintenance contract Labelling Cables installed in conduits and trunking 30 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

4 General Control cables Power cables Field mounted equipment Control valve selection Control valves Sensors Flow meters Electrical supply CONTROL PANELS AND CONTROL PANEL General Motor Control Centre (MCC) Mechanical services power board Motor sizes Inverters and Thyristor Outstation panels Off site inspection Outstation UPS Construction Door Interlock Painting and Finishing Painting Galvanising Cable Entries Internal Wiring General Power Wiring (220 Volts and Above) ELV Wiring (Control, Indication or Alarm Circuit) Neutral Bar or Link Arrangement and Installation of Wiring Cable Termination and Terminals Terminals and Terminal Boards and Connections Contactors Power changeover contactor Starters Two speed fans Two speed fans with inverter and DOL starter Multiple speed fans with inverter and fire mode Inverters Relays 46 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

5 2.10 Control Circuits Indicator Lights and Alarms Electrical power meters BMS keypad and display Selector Switches Operation in test position Current Transformers Isolators Fuse Protection Miniature Circuit Breakers Earthing Internal Lighting Panel heating or ventilation Laptop Power Rubber Mat Drawing Holder Ease of Maintenance Component Labelling Name Plates and Labels Safety Interlocks Safety BMS monitoring and action Individual Plant isolation Electric heater batteries AHU frost thermostats Fan isolation dampers Humidifiers Chillers Boilers DESCRIPTION OF PLANT AND SYSTEM OPERATION General Description of operation Standard Ventilation Strategies Standard Pump Strategies System Alarm Handling Fire operation general Plant Demand Optimisers Plant frost protection Tenants demand System set points 56 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

6 3.7 Automatic control valves Ventilation Systems General Office Ventilation AHU/R/1 and AHU/R/ Entrance Hall Office toilet extract Basement plant room ventilation Ventilation loading bay extract Office and Basement smoke extract Boiler house ventilation Basement toilet extract Bin store transfer fan Chilled water cooling systems General CHW distribution pumps Primary cooling pumps P/B/R/1, 2 and Command Fault rotation Pump Duty rotation Operation Fault rotation Pump Duty rotation Chiller R1, R2, Hydraulic pressurisation units Heating Systems Secondary circulation heating pumps Secondary LTHW/DHWS heating pumps CHP Gas boiler B1, B Local cooling and heating systems Fan coil units Switch room cooling Management suite cooling Public Health Services Sump pumps Cold water potable booster set and sterilisation Cold water non potable booster set and sterilisation Residential potable booster set and sterilisation Water Tank Room Leak Detection Sprinkler water system 75 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

7 Water Meters Other plant interfaces Trace Heating Lift monitoring Control panel power monitoring Disabled toilet alarm BUILDING MANAGEMENT SYSTEM Building Management System General Infrastructure Tenants interface Responsibility System Supervisor Central Processor Unit (CPU) Visual Display Unit (VDU) Printer Router Outstations General Capacity Installation Transmission system Analogue inputs Software upgrades Direct digital control (DDC) Logic diagrams Electrical supply Operational Facilities General Software General Access levels Later Development Plant start/stop programme Plant cascade demand programme Head end manual control AHU Hold off programme Optimisation programme Time Control and Holiday Scheduling Frost protection 90 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

8 Historical data programme Event Totalisation Start and power failure restart programme Control point reset programme Sequence Control and Rotation of Plant Fault duty rotation Control loop initiation Load Cycling Control Weather Compensation Control Sensor default control Thermal control Pressure control Control Valve and Actuator Cycling Minimum plant operation Fan coil maintenance strategy Equipment Cycling Protection Alarm programme Energy measurement and metering calculation program Electrical energy Maximum Demand Run time totalisation program Gas and water utility metering Graphics General Movement between the Graphics Data Display Specific graphic displays Installation, Training and Commissioning Scope of Tests 101 \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

9 1.0 AUTOMATIC CONTROLS The Controls Contractor shall read this document in conjunction with all sections of the Contract preliminaries, Technical specifications, Architectural, Structural and Services drawings. The Automatic Control system, or Building Management System (BMS), will provide control and monitoring for the shell and core services. The system will be a Direct Digital Control (DDC) type with fully distributed intelligence. The system shall be configured to allow full access via a web browser and be expandable to other systems by use of BacNet/IP, LonMark/IP or Modbus/IP. The control system will be provided by a single supplier who shall have full responsibility for the works. The system shall comprise of a number of local control instruments and intelligent outstations that can operate independently of other parts of the project. When global information is required, this may be transmitted via the BMS network. However, all safety interlocking and some demand based signals shall be transmitted by hardwired connections between outstations. The Contractor is to note the building is a Section 20 building. Where specialist systems are provided, the installation and engineering shall in all ways reflect the full requirements of this specification. Wherever the term controls contractor is used this shall apply equally to the specialist suppliers. The stair/lobby fire fighting ventilation system is provided by a specialist supplier. The fan coils may be provided with an integral control system. Where this is the case the FCU supplier shall take full responsibility for the interface to the BMS and shall have a full time site presence during the flushing and commissioning of the water and air systems and the BMS associated with the FCUs. The smoke damper control system is provided by a specialist supplier. The system shall operate in the smoke mode as dictated by the smoke control system during any emergency mode. The above ground system shall during normal operation interface to the BMS to allow floor by floor operation of the smoke dampers to provide isolation for unoccupied floors. The below ground installation shall be monitored by the BMS for damper status only. The interfaces shall be software utilising Modbus or BACnet. The installation and engineering shall in all ways reflect the full requirements of this specification. The specialist supplier shall have a full time presence during the commissioning of the BMS associated with the dampers. The specialist supplier shall take full responsibility for the software interface to the BMS. The controls contractor shall include sufficient engineering time and costs to fully integrate these specialist systems within the BMS. The BMS shall provide tenant interfaces on each floor for software and hardwired extension of the base build BMS. 1.1 Project outline The project is an eight story office block located in London. The air conditioning comprises two roof mounted fresh air handling units, these provide conditioned air to the office spaces. The offices are provided with ceiling mounted fan coils. Cooling is provided by roof mounted air cooled chillers with basement circulation pumps. Heating is provided by gas fired boilers and a CHP located in the basement along with the distribution pumps. Local cooling to the electrical rooms is provided by DX units with roof mounted condensers. Support systems such as toilet extract and basement plant room ventilation systems are also provided. Smoke extract is provided for the office and basement spaces. A comprehensive smoke control system is provided by a specialist supplier. This system operates the space smoke isolation dampers and provides signals to the control panels to operate the appropriate life safety fans. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

10 The Building Management System is a direct digital control system with fully distributed intelligence. Each major plant item shall be wired and controlled from the local motor control centre with all drives having inverters. Control panels shall be provided for each fan coil unit. 1.2 Extent of work The controls contractor shall design, supply, install, set to work, test and commission the complete automatic control and building management system required to serve all mechanical services installations specified, in the project specification, unless specifically stated otherwise hereafter. The scope will incorporate all starter panels, mechanical services power distribution boards, control outstations, software, control field devices, valve and damper actuators, inverters, all controls and power wiring, including carrier systems, setting to work, commissioning and all documentation and training necessary to allow the user to operate the installation both reliably and safely. The Controls Contractor will offload, transport to its final location and position all equipment of his supply. He will fit all equipment of his supply other than the valve bodies and pipeline temperature pockets. The Mechanical Contractor will fit all necessary pipework pockets and valves and connect to any pipeline differential pressure switches. If large plant items such as control panels are to be split for delivery, the controls contractor shall include all costs for handling and reassembly and insulation testing of power sections. The power to the fan coil units shall be wired by the electrical contractor with a fused spur. Final termination from the spur to the control unit shall be by the controls contractor. The electrical contractor shall provide power to the plant room Mechanical plant power distribution boards and all remote outstations and network hubs. The controls contractor will size, provide and install all power wiring and carrier system between the Control enclosures, the Mechanical services power boards, the MCCs and the drives including isolators and lockstop circuits. The exception to this is the power and control wiring to the staircase smoke control fans and all motorised smoke dampers, other than those that are directly related to fans. The specialist contractors shall carry out this wiring installation. The controls contractor will size, provide and install all controls wiring and carrier systems between; MCCs and Outstations, and all field mounted controls instruments and actuators and other equipment BMS interfaces. The Automatic Control enclosures shall house all motor starters, hand/off/auto switches, on/off and duty selector switches, electric interlocking and recycling relays, indicator lights, electronic control equipment, control low voltage transformers, time switches, terminal block and power and control fuse gear and isolators. All motors 1.1kW and above shall have inverters. These shall be mounted along side the plant or adjacent to the MCC. All inverters serving essential statutory life safety plant shall generally be located within the associated essential MCC room. Where non essential plant is located remotely from the MCC, the inverter shall be placed local to the plant in an IP 54 enclosure. If the plant is external to the building the inverter shall be located either in the plant housing or in an IP 65 enclosure provided and installed by the controls contractor. Where necessary the controls contractor shall include for heating in the enclosure. The MSPB and control enclosures mounted on the roof shall be complete with weather proof enclosures provided and fitted by the controls contractor. These shall include heaters for condensation protection. The Controls Contractor will take on the responsibility of obtaining from the other Contractors all necessary electrical loads together with wiring and interface diagrams. The Controls Contractor will advise Contractors of the appropriate interfaces to ensure that the BMS can carry out its appropriate functions. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

11 It is the Controls Contractor's responsibility to size and select every item required for the project. The information provided in this document is for tender purposes only. 1.3 Scope The controls system shall interface to and control the building services equipment shall include but is not limited to the following: 1. Controls to office AHU AHU/R/1 and associated extract fans and ran around pump inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor; 2. Controls to office AHU AHU/R/2 and associated extract fans and ran around pump inverters, supplied by controls contractor, fitted and wired to motor by controls contractor.. Set to work by the controls contractor; 3. Controls for the office smoke extract fans. inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor. (The controls contractor shall include at tender stage extra over costs for the motors being star/double star type, including additional power caballing to each motor) 4. Controls for the office toilet extract fans. inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor. 5. Controls to entrance hall AHU inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor. 6. Controls to boiler house ventilation supply and extract fans inverters, supplied by controls contractor, fitted and wired to motor by controls contractor, set to work by the controls contractor. Thyristor and controls for the electric heater supplied and set to work by the controls contractor. 7. Controls to basement AHU and associated extract fan inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor; 8. Controls to loading bay extract fans. inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor. These fans double up as smoke extract, when in smoke control the fan speed is achieved from the fire control panel 9. Controls interface to basement toilet extract fan. Package starter provided by mechanical contractor, fitted and wired by controls contractor. 10. Controls for all chilled water circulation pumps; inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor 11. Control equipment and Interface to the chillers, through hardwired interlocks - chiller controls and starter supplied installed and commissioned by mechanical contractor. The controls contractor shall carry out all chiller package control wiring, of loose items such as the flow switches. Power wiring to crankcase heaters by controls contractor 12. Controls interface to the CHW pressurisations unit; 13. Controls interface to the CHW water treatment systems; 14. Controls for all heating water circulation pumps; inverters, supplied by controls contractor, fitted and wired to motor by controls contractor. Set to work by the controls contractor \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

12 15. Interface to the gas boilers, through hardwired interlocks - boiler controls and starter supplied, and commissioned by mechanical contractor. All interconnecting wiring by boiler supplier; 16. Controls associated with the heating plate heat exchangers; 17. Controls interface to the heating pressurisations units; 18. Controls interface to the heating water treatment systems; 19. Boiler house gas system complete with gas valve, gas safety systems. Monitoring gas meter, meter provided by mechanical contractor. 20. Main gas incomer, monitoring gas meter, meter provided by mechanical contractor 21. Controls interface to the CHP 22. Controls and inverters for the CHP system circulation pumps 23. Controls and inverters for the CHP ventilation fans. Including controls for the heating coils. 24. Controls interface to the heating pressurisations units 25. Controls interface for the thermal stores 26. CHP gas valve and gas safety systems. Monitoring gas meter, meter provided by mechanical contractor 27. Monitor the landlords oil system 28. Controls Interface to the basement smoke system control panel through software connections for monitoring purposes 29. Controls Interface to the lobby ventilation control system. The lobby ventilation control system including panels shall be provided, installed and set to work by the specialist supplier 30. Interface to the smoke system control panel to allow floor by floor zoning. Smoke control system to be provided with Modbus or BACnet connectivity. Dampers to be controlled and monitred for position through the BMS. Fire system shall take precedence in a fire mode 31. Hardwired connections to all smoke ventilation dampers actuators, associated with fans that require to be operated by the BMS. Actuators and dampers to be supplied by the mechanical contractor. Actuators fitted and wired by the controls contractor; 32. All floor dampers and actuators supplied, fitted, wired and set to work by the mechanical contractor. 33. Supply and installation of fan isolation and modulating damper actuators required for normal system operations; 34. Provision and installation including power and controls wiring and commissioning of the heat meters. Meters and associated equipment supplied by controls contractor; pipeline sections installed by mechanical contractor 35. Provision and installation including power and controls wiring of water meters. All RAWS approved. 36. Controls for fan coil units. Free issued to others for off site wiring. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

13 37. Alternatively where FCUs with integral controls are provided, the FCU supplier shall configure all FCU control strategies and provide full engineering interface for software to the BMS. The FCU supplier shall have a full time site presence during flushing and air/water balancing of all FCU systems. The specialist supplier shall have a full time presence during all BMS commissioning associated with the FCUs. 38. Controls for all duct mounted heater/cooler batteries 39. Controls for all space heating zones 40. Controls interfaces and monitoring of LV switchroom cooling systems 41. Controls interfaces and monitoring of management suite cooling systems 42. Power provision and monitoring the trace heating systems 43. Monitoring the potable water storage tanks. All tank high level switches and temperature sensors provided by the controls contractor. 44. Supply and set to work the storage tank motorised isolation valve RAWS approved-. Valve hardwired to tank high level and water leak detection system 45. Monitoring the water sterilisation treatment system; 46. Monitoring the UV water sterilisation system; 47. Monitoring the cold water potable water booster set - Integral controls and starters supplied, installed and commissioned by the mechanical contractor. The controls contractor shall carry out all interconnecting wiring between the tanks and the pump control panel 48. Monitoring the non-potable water storage tanks. Al tank high level switches and temperature sensors provided by the controls contractor. 49. Supply and set to work the storage tank motorised isolation valve RAWS approved-. Valve hardwired to tank high level and water leak detection system 50. Monitoring the water sterilisation treatment system; 51. Monitoring the UV water sterilisation system; 52. Monitoring the cold water non potable water booster set - Integral controls and starters supplied, installed and commissioned by the mechanical contractor. The controls contractor shall carry out all interconnecting wiring between the tanks and the pump control panel 53. Monitoring the recycle water management system. All associated control instruments and actuators supplied, installed and set to work by the specialist supplier 54. Control interface to the HWS system. All HWS calorifier controls and instruments provided and set to work by the specialist supplier. 55. Controls and interface to the HWS circulation pump. 56. Monitoring the sprinkler pump and tanks BMS tank level switches provided by controls contractor. 57. Supply and installation of the water tank room leak detection system \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

14 58. Supply and set to work all water meters RAWS approved, associated with the mains water, the feeds to the pressurisation units and the distribution systems 59. Monitoring the sump pumps. All interconnecting wiring between the floats and the control panel to be carried out by the mechanical contractor 60. Monitoring the lifts; 61. Monitoring the disabled toilet alarm system - alarm system to be supplied, installed and commissioned by the electrical contractor; 62. Monitoring the transformers; 63. Monitoring LV tripping batteries 64. Monitoring the generator. 65. All control valves and actuators. Combined thermal control and differential valves for valves other than the terminal units - to be Tour and Anderson type KT and KTM. The controls contractor shall select all valves in conjunction with the mechanical contractor and TA; 66. All control valves and actuators for the terminal units such as FCUs, perimeter heating remote duct mounted heating/cooling coils.. All valves to be combined thermal control and differential valves - to be Frenger Optima range. The controls contractor shall select all valves in conjunction with the mechanical contractor and Frenga 67. All actuators for ventilation dampers that require to be operated by the BMS; 68. All field instruments that form the automatic controls system 69. Provision and installation of all instruments for two optimisers per floor. Provision and installation of two RH sensors to each floor. 70. All mechanical services power boards and support frames. The roof and basement essential power boards shall be cubicleised form 4 type All control panels and support frames 72. Where panels are located outside the building, the controls contractor shall provide a weatherproof enclosure and ant condensation heaters. MSPB-R-1, CE-R-1/1, 1/2, 1/3. 1/4 73. Installation of all inverters including support frames 74. Monitoring status of MSPB and CE power meters and power status 75. All controls wiring and carrier systems 76. All power wiring, including isolators for all plant items, and carrier systems for equipment connected to and or powered from the motor control centres, mechanical services power boards and control outstations; 77. All wiring power or control associated with life safety system shall be FP All power wiring to the fan coil units from local spur \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

15 79. All networks, inclusive of outstations, routers, switches, panel mounted UPS and the like 80. All main plant controllers to have UPS. All routers and switches to have UPS. UPS to maintain communications from plant controllers to head end for a minimum of 60 minutes. 81. Tenants Interface outstations on each floor for hardwired and software interface for tenant complete with spare and addressed RJ45 socket, for future tenants network. 82. Interface on each floor for future connection to heat/coolth meter. Lon or M-bus. 83. All operating software, firmware and licences; 84. Complete BMS engineering and configuration; 85. Energy monitoring and management package; 86. BMS head end supervisor, inclusive of all operating software and server, complete with web browser and SMS functions. The controls contractor shall provide a 30 minute UPS for the head end workstation; 87. Line printer for alarm and general messages; 88. A3 colour laser jet printer for reports; 89. Keypad and display screen on the MCC fascia in both the roof AHU compound and the boiler house; 90. Fully integrated BMS/controls and plant testing, setting to work and commissioning; 91. Return visits to retune the system operations; 92. Full commissioning of all inverters irrespective if these are provided by the controls contractor or not 93. Detailed trend logging and installation report of complete system; 94. Operating and maintenance manuals 95. Assistance with production of the building log book 96. Training of operators 97. All necessary consumables for the project. At project completion provide new printer cartridges and paper. 1.4 Standards, Codes and Regulations The Automatic Controls will be designed, installed, tested and commissioned in accordance with the following: Statutory Acts; Local Standards and Standard Codes of Practice; Local Authority Building Regulations; Health & Safety at Work Act; The requirements of the relevant Local Authority; The requirements of the relevant Water Authority; The requirements of the relevant Fire Authority; The fire officers committees/the loss prevention councils rules and recommendations; The Factories Act; \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

16 Current Institute of Plumbing Standards; The current Electrical Regulations with amendments; The Environmental Health and Safety Office; and Manufacturers Recommendations for Installation Testing Commissioning and The Landlord s Regulations and Approvals. Materials and installation will conform to the relevant current Local Standards where applicable. Where no such standards exist, the equipment will include for the known factors and requirements and will be installed to suit the manufactures recommendation. All equipment furnished for the project will be suitable for their location and suitable for purpose. Reference will be made to BS 6204, BS 5850, BS 6527, BS 6667, BS 800, BS 5486, CIBSE Guides and Commissioning Code C, BS 5750 and the Controls Group Publications. 1.5 Quality control The contract will be carried out under following the principles of the Contractor's Quality Assurance documentation. All equipment supplied will receive commercial tests to comply with IEE Regulations. All equipment will be CE marked. 1.6 Responsibilities Design The Controls Contractor will examine all drawings and documentation and will produce for approval the basis of design. The design will be carried out by competent engineers and will be suitable for the intended purpose. The design will incorporate any necessary statutory requirements with respect to Health and Safety. The Controls contractor shall produce the system description of operations. These shall clearly show the system operation, hardwired and software interlocks, the operation during fault conditions, alarm handling, head end adjustments. The Controls Contractor will advise the Engineer of any changes that the Controls Contractor considers would be beneficial to the system. These modifications will not involve additional costs to the Engineer unless the Controls Contractor demonstrates, at tender stage, that the documentation issued by the Engineer is unworkable Supply The Controls Contractor will supply all materials and equipment necessary to be installed for the complete control and monitoring system. All materials and equipment will be suitable for purpose and location. All materials and equipment either manufactured by the Controls Contractor or bought from an outside source will conform to all relevant Local Standards. The equipment supplied will all be of a standard type and readily available for replacement in the event of damage or malfunction. The Controls Contractor will provide schedules of all equipment indicating the site reference, manufacturer, type and serial numbers two weeks following the placing of the order. The Controls Contractor will keep on site a detailed record of all equipment received. Where it is necessary that others install equipment, e.g. pipeline probes pockets, then the Controls Contractor will hand this equipment to the appropriate Contractor. All equipment delivered will be boxed and wrapped to prevent damage either in transit or in storage. All equipment will be stored in a clean, dry store protected from fumes, dirt and general site activities. The Controls Contractor will provide a robust and lockable storage facility for all equipment supplied by \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

17 themselves. The Controls Contractor will off-load, position in its final location and fix all equipment of their supply Installation The Controls Contractor will install and wire all equipment necessary for the complete operation of the building management system. The control system will be installed by competent engineers regularly employed by the Controls Contractor. The complete system will be installed under the supervision of an experienced field supervisor familiar with all parts of the control system. He will ensure that the work is of the highest standard and will carry out the daily co-ordination and system interface as required to ensure the completion of the project within the agreed programme of works. The installation shall include all necessary carrier systems and supporting steel work for control panels and inverters Co-ordination with others The Controls Contractor will liaise closely with all other Contractors to ensure that the installation works proceed in an orderly and co-ordinated manner. They will, for instance, provide within 14 days of receipt of an instruction to precede a panel schedule. This will identify the size and location of every panel to be installed. The schedule will also show all electrical requirements. With regards to main wiring routes, the Controls Contractor will provide their desired routes to others in the form of drawings. The Controls Contractor will appreciate that they will not always be able to route their cables in whatever direction they demand. The single conduit runs may be site co-ordinated and will be installed in a neat and orderly manner. It is a requirement of this document that the Controls Contractor provides floor plans showing the location of any control device that is to be mounted in the occupied space. These are to be provided to the architect two weeks after receipt of the instruction to proceed Setting to work the automatic controls The controls contractor shall be responsible for setting to work the system of his supply. The controls contractor shall recognise that the BMS is an integral part of the building services and as such the operation of the major plant requires close co-operation with the M & E contractors and their appointed representatives. The controls contractor shall allow in the contract costs for the standalone commissioning of his system, i.e. the BMS from the head end to the field interface with a third party and his own equipment. In addition the controls contractor shall allow for the integrated testing required to set the building services plant to full operation. The controls contractor shall not assume a continuous commissioning operation for either his plant or the third parties. The integrated testing shall include low level operation such as running fans and pumps, through to full integrated testing of the building services to include loop tuning of heating, cooling and ventilation systems and integrated building tests covering such activates as : fire cause and effect, power failures and black building tests Setting to work the building services It is the responsibility of all contractors to set the building services to work and to leave the systems operating as described in the project specifications. The mechanical and electrical contractors shall provide full attendance to the controls contractor to allow integrated testing of packaged plant and equipment with the BMS. Testing of the BMS shall include full end to end tests such as forcing faults in chillers and DX systems and reviewing the actions of the BMS. The electrical contractor shall ensure that full attendance and co-operation is provided when testing of the \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

18 electrical interfaces such as breaker positions and power meters are to be carried out by the controls contractor Monthly Return visits The controls contractor shall include in the contract costs three return visits after contract completion. These shall be at four monthly intervals and have a duration of at least one month at each visit. During this time the controls contractor shall review the operating parameters of the plant to ensure efficiency of use, provide enhanced training to the user, modify head end displays as appropriate, verify the remote interfaces such as SMS and web browsers, review the maintenance and management reports. The cooling systems shall be inspected in the cooling periods and the heating in the heating period. The time shall not be spent correcting contract defects, nor carrying out maintenance Handover The controls contractor shall work in conjunction with all other contractors to enable the complete project to be handed over as set out in the contract documents. The controls contractor shall recognise that the Automatic Controls is likely to be the last system completed and therefore sufficient engineering staff shall be available throughout the hand over process Documentation The controls contractor shall provide all documentation necessary to allow the user to operate the plant both efficiently and safely. The controls contractor shall provide sufficient information to and co-operate with the mechanical contractor for the production of the building log book Training The controls contractor shall train the user s staff in all aspects of the automatic controls and BMS Power requirements The controls contractor shall carry out all power wiring of equipment connected to the motor control centres and the controls outstations. Inclusive of cabling between the spurs the LCMs and the outstations. The controls contractor shall make all final power connections, including the provision of any required cabling between the local fused spur and the terminal equipment. This shall include but not be limited to: Fan coil units All free standing outstations The power cables shall be installed within a flexible steel conduit and fixed to the building structure. Where control circuits control life safety equipment such as dampers and fan commands the cables shall be fire rated FP600 or equivalent. All power cables to life safety equipment shall be FP600 or equivalent 1.7 Services equipment and packaged plant Where other contractors or suppliers provide controls and starter gear for packaged plant or equipment, the standard of design and construction shall not be less than that described in the Controls section of this document. The following describe the minimum requirements for packaged plant over and above that set out in the package plant section of this specification and the minimum BMS interfaces required. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

19 The packaged plant shall be delivered to site complete with all starters and hardwired control systems. The package controls shall allow the plant to operate without the external influence of the BMS. The extent of packaged plant shall be developed, but shall include the following: Chillers Gas fire boilers Electric heaters Sump pumps Water pressurisation units Twin fan units Split DX systems Trace heating Domestic hot water system Cold water booster sets, including all, starters and interconnecting wiring between the tank high and low level switches and the booster set panel; and Smoke damper control system Fire fighting staircase ventilation system Packaged fan starters Where packaged fan starters are provided, these shall be installed and commissioned by the mechanical Contractor. The IP65 control panel shall include duty change over and duty sharing timers for twin fan sets and all motor protection and speed controllers. The starters shall be interfaced to the BMS through an extra low voltage interface and be complete with a local/remote selector switch. The panel shall include fan run indicator and fault lamps. The interface to the BMS shall include: 1. Single Fan set Unit enable; Fan 1 running; Fan 1 fault 2. For dual fans Unit enable; Fan 1 running; Fan 2 running; Fan 1 fault; Fan 2 fault Where duplicate fan sets are provided, the controls contractor shall also install a separate DP switch across the fan set. These shall not be required where the fan serves less than two cubicles Pump starters Each pump shall be provided with a matched inverter wired to the motor. The power wiring shall be to the recommendation of the inverter manufacturer and shall be not less than 4-core with an earthed screen. An isolator shall be provided up stream of the inverter. The isolator shall have early brake late make auxiliary \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

20 contacts that shall be wired to the inverter enable circuit. The plant supplier shall configure the inverter such that manual operation is only possible once all external safety interlocks are satisfied. It shall be unacceptable that any inverter can be run from the key pad without the safety interlocks being healthy. All pumps greater than 1.1kW shall have inverters Fan starters Each fan shall be provided with a matched inverter wired to the motor. The power wiring shall be to the recommendation of the inverter manufacturer and shall be not less than 4-core with an earthed screen. An isolator shall be provided up stream of the inverter. The isolator shall have early brake late make auxiliary contacts that shall be wired to the inverter enable circuit. The plant supplier shall configure the inverter such that manual operation is only possible once all external safety interlocks are satisfied. It shall be unacceptable that any inverter can be run from the key pad without the safety interlocks being healthy. All fans greater than 1.1kW shall have inverters Inverters The inverters shall be provided by the controls contractor. The inverters forming part of the staircase smoke ventilation system shall be provided by the specialist supplier. The contractor supplying the inverter shall set to work and commission the units to match the BMS operations. The inverter supplier shall be responsible for all technical aspects of the inverters as described both in the mechanical specification and in clause 2.8 of this specification. The controls contractor shall however provide management of all inverters and shall provide support during commissioning to establish the operation of all inverters. Where critical systems fans are provided with inverters they shall be set to operate in the fire mode utilising the fire jog commands. If other speeds are required during a fire mode these shall be set using combination of relays wired direct to the inverter jog command. All inverters shall be IP 54 and complete with a keypad and connected to the BMS through hardwired and software connections DX systems The mechanical contractor shall supply and install all works for the DX cooling systems. The equipment shall include the internal and external units along with all controllers. The mechanical contractor shall include all interconnecting wiring and carrier systems for the power and controls between the external and internal units and the room controllers. The BMS shall enable the units and monitor for fault, the controllers shall communicate to the internal and external units. All interfaces to the BMS shall be either volt free contacts or 24VAC. If necessary the DX vendor shall provide and fit the interposing relays and contacts Smoke damper control system The smoke damper control system shall be provided, installed and commissioned by the mechanical contractor or his specialist supplier. The BMS shall interface to the panel through a Modbus or BACnet link for general monitoring and normal damper positioning. The smoke damper panel shall provide hardwired volt free outputs to the automatic control system that shall be wired, by the controls contractor FP600, directly to the MCC panels to enable the necessary fans and at the required speed. These terminal points shall be within 1M of the controls contractors control panels. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

21 The BMS shall provide software signals to the smoke damper control system to allow each floor ground and above to operate independently of any other. The software and necessary hardware shall be developed and supplied by the controls contractor. The smoke control system supplier shall provide engineering services at no cost to the controls contractor for this work Smoke dampers The dampers complete with suitable actuators and decoders shall be supplied and fitted by the mechanical contractor. They shall be motor open/motor closed and spring closed/open on power failure. The fail safe position shall be determined to suit the life safety operation. The actuators and decoders shall be located out of the smoke extract compartment, or enclosed in a suitably fire rated enclosure. The actuator shall have separate end switches indicating closed and open positions, these shall be adjustable between 90 o and 70 o. The actuators that are required to be driven by the BMS for normal operation, interlocked directly with ventilation fans, shall be 24VAC type and be complete with open position end switches. The actuators that are controlled by the smoke control system and powered directly from the essential power circuits shall be 240V. The actuators shall be located out of the fire zone or provided by the mechanical contractor with a fire rated enclosure. All wiring associated with the control of the dampers shall be carried out in fire rated cable FP600. Where the damper is directly associated with a ventilation fan the wiring between the MCC/outstation and the damper shall be by the controls contractor. All 'remote' dampers shall be wired by the damper specialists Smoke make up ventilation The air make up to the offices and basement areas shall be provided from the opening shafts and the main office ventilation fans as appropriate. When required to operate the smoke control system shall set the isolation dampers to the appropriate position either open or closed and open the appropriate air make up routes. The appropriate fans shall be set to run using hardwired strategy in the control panels. This is initiated by the local fire/smoke system interface units Office smoke extract ventilation The roof mounted smoke extract fans provide extract from the office floors via the normal extract duct route. When required to operate the smoke damper control system sets the floor isolation dampers to the appropriate position. The two duty extract fans are enabled via hardwired signals from the fire detection OR smoke damper control system as appropriate. The controls contractor supplied control enclosure isolates the AHU normal extract systems, opens the two duty fans isolation dampers and sets the fans to work once all interlocks are proven. If a duty fan fails the standby fan is enabled. The availability of the system to run and the running status of the system is monitored by the fire/smoke damper system through hardwired interlocks Fire fighting staircase lobby ventilation The basement fire fighting core extract system provides ventilation to the cores. The specialist supplier shall provide all equipment and services to the standards described in this specification in addition to that required to provide the smoke control strategy. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

22 The system shall be provided and to set work by the mechanical contractor or the specialist supplier. The specialist supplier shall provide all control panels, fan inverters, actuators, controllers, controls and power wiring including carrier systems for the complete system Cold water booster sets The cold water booster sets, shall be provided with integral controls and interconnecting wiring by the mechanical contractor. The BMS shall interface for monitoring. The controls contractor shall provide and install a water board approved motorised shut off valve for the incoming water system. The actuator shall be suitable for the BMS operation and operated through hardwired control from a controls contractor supplied and installed panel. The valve shall close if the tank high level alarm is or the water leak detection is active. The valve shall remain closed for minimum of (30) minutes after the alarm has cleared. The controls contractor shall carry out all interconnecting wiring between the pumps and the tanks. The tank low level switches shall be hardwired interlocked with the pumps to prevent pumps running dry. The cold water booster set supplier shall provide the tank1/tank2/tank1&2 selector switches on the cold water booster set control panel Sprinkler pumps and tanks The sprinkler system shall be a self contained package with interface monitoring provided by the fire detection system. The BMS shall monitor the system for status Wet riser pumps and tanks The sprinkler system shall be a self contained package with interface monitoring provided by the fire detection system. The BMS shall monitor the system for status Water leak detection The tank room water leak detection system shall be supplied and installed by the controls contractor. The BMS shall interface for monitoring and activation of shut off valves through hardwired interlocks. The system shall be zoned such that major tank areas are separately monitored Fan coil units The fan coil units shall be provided by the mechanical contractor. The controls contractor shall free issue all control items to the FCU supplier, including the valves actuators and temperature sensors. If the FCUs are provided with integral controllers that are not part of the BMS package, the FCU supplier shall provide all works to the standards as detailed in this specification. The FCU supplier shall provide all hardware and software, as described in this document and as necessary to operate the FCUs. The FCU supplier shall have a full time site presence during the air and water flushing and balancing of system associated with the FCUs. The FCU supplier shall have a full site presence during the commissioning of the BMS associated with the fan coil units. The FCU shall provide all address registers to the controls contractor and shall assist in the construction of all engineering data such as graphics that are provided at the BMS head end supervisor. Irrespective of the supplier of the FCU controls the controls contractor shall wire and connect the BMS network and shall provide the cable and make the final power connections from a local spur to the FCU. \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

BMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT:

BMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT: BMS Commissionability Review October 2009 PROJECT: Four Seasons Hotel Park Lane Summary This report details our review of the BMS specification produced by i.d.a. Building Services Consulting Engineers,

More information

University of Brighton

University of Brighton University of Brighton S t a n d a r d S p e c i f i c a t i o n f o r B M S R e q u i r e d C o n t r o l s S t r a t e g y Version 1.0 October 2017 Document Control Published document name: University

More information

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System August 2016 Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Safegard V4 Bespoke Intelligent Damper Control and Monitoring System Devices

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

Fire and Smoke Control Systems

Fire and Smoke Control Systems Control Systems Electrical Mechanical Standard Panel Modular design for control and monitoring Premier Panel Customised design for control and monitoring Fully Addressable Fully programmable data wired

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

DCS-100. intelligent damper control & monitoring system

DCS-100. intelligent damper control & monitoring system DCS-100 intelligent damper control & monitoring system 02 //DCS-100 Introduction The Disys Technologies DCS-100 is a revolutionary new control system designed specifically for the fire/smoke damper controls

More information

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS CONTENTS 100 PERFORMANCE OBJECTIVES 200 DESIGN PARAMETERS 300 SYSTEM DESIGN 310 Design Guidance 320 Outstation Choice 330 Outstation Position 340 Documentation 400 SYSTEM COMPONENTS 410 Master Handsets

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

Smoke Vent Control Panel PCB4 V4 Installation Manual

Smoke Vent Control Panel PCB4 V4 Installation Manual Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel www.besafedirect.com Page 1 Contents Page 3) Important Regulations, Safety, Maintenance,

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION Page 1 of 7 25 00 00 25 10 00 NETWORK EQUIPMENT Standby Power 1. Consider whether the controls system should be on standby/emergency power, or UPS when central applications are controlled or the equipment

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

Specification Data. General:

Specification Data. General: Specification Data General: Zone Units (ACU s) will be draw through vertical type having double skin construction. All Zone Units will have all necessary components such as control valves and motors to

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Actionpac LNS3 Intelligent Damper Control and Monitoring System

Actionpac LNS3 Intelligent Damper Control and Monitoring System November 2005 Actionpac LNS 3 NEW AND ENHANCED Intelligent Damper Control and Monitoring System Range and Features Panel PC Driven system. User friendly, no need for operating and maintenance manual. Full

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

The integral solution for. Air Handling Units. Technology & Evolution

The integral solution for. Air Handling Units. Technology & Evolution The integral solution for Air Handling Units Technology & Evolution For over 25 years Carel has been dealing with the design and production of electronic controllers and supervision systems for Air-Conditioning

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Operating Performance

Operating Performance INFORMATION SHEET 1 Jackson Engineering Advisers are specialist Building Services Engineers. This information sheet is offered as an aid to Building Owners and Managers as a guide to plant life expectancies.

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

October 2013 Bespoke Intelligent Damper Control and Monitoring System

October 2013 Bespoke Intelligent Damper Control and Monitoring System October 2013 Actionpac LNS4 Bespoke Intelligent Damper Control and Monitoring System l All system wide activity is logged and viewable for diagnostics and preventative maintenance l Devices powered by

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

Actionpac 60/120 (LNS Standard)

Actionpac 60/120 (LNS Standard) July 2006 Actionpac 60/120 (LNS Standard) Actionpac 60/120 (LNS Standard) Cost Competitive Intelligent Damper Control and Monitoring System Range and Features Panel system, utilising solid state technology.

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

V3 Intelligent Damper Control and Monitoring System

V3 Intelligent Damper Control and Monitoring System March 2011 V3 Intelligent Damper Control and Monitoring System Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Devices powered by closest

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500 Unvented Calorifier Range. Operating and Maintenance Manual. For Models 125 300 & 500 Telephone 08456 448802 Fax 08456 448803 Emial info@mhgheating.co.uk Web www.mhgheating.co.uk TABLE OF CONTENTS. Section

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN Brown University Department of Facilities Management Design & Construction Standards 26 09 01 Campus Central Metering System Design SECTION 26 09 01: CAMPUS CENTRAL METERING SYSTEM DESIGN 1. GENERAL A.

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

BULLETIN. Temperature Controls (Chilled / Hot Water)

BULLETIN. Temperature Controls (Chilled / Hot Water) BULLETIN Temperature Controls (Chilled / Hot Water) (05-07-2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant Responsibility:

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions ISSUE A, MAY 2008 Hard Wired Damper Control Panels Systems 10, 11, & 12 Hard-Wired Systems Bespoke Systems Available Value Engineered Solutions Overview The Hard-Wired Control Panels On a number of projects

More information

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range PRODUCT SELECTION DATA Plug & play unit (built-in control) Class A+ across entire range Classic/Vertical/ceiling-mounted dualflow units High-efficiency heat recovery unit High performance plug fan High-efficiency

More information

Pressurisation units & expansion vessels

Pressurisation units & expansion vessels Pressurisation units & expansion vessels Pressurisation units The new generation of microprocessor controlled pressurisation units Standard Unit/Advanced Unit These microprocessor controlled pressurisation

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Instruction Manual WARNINGS

Instruction Manual WARNINGS Instruction Manual LARGE COMMERCIAL RECESSED AIR CURTAIN HSACR9000, 12000 & 18000 ELECTRICALLY HEATED RECESSED AIR CURTAINS WITH ENERGY SAVING CONTROLS INSTALLATION AND OPERATING MANUAL INDEX Section General

More information

Project Briefing Document. Section 3 Electrical Services design guide and specifications

Project Briefing Document. Section 3 Electrical Services design guide and specifications ESTATES SUPPORT SERVICE Project Briefing Document Section 3 Electrical Services design guide and specifications Issue 1.1 June 2014 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor...

More information

Millfield Schools Fire Risk Prevention Policy

Millfield Schools Fire Risk Prevention Policy Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school

More information

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH. THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH www.thermomax-group.com CONTENTS SECTION 1 - INTRODUCTION... 2 SECTION 2 - INSTALLATION... 3 2.1 - RCX 100 UNIT... 4 2.2 -

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Odyssey. issue 01c. system manual

Odyssey. issue 01c. system manual dyssey issue 01c system manual SYSTEM MANUAL Table of Contents Technical Specification 1 Summary of Features 2 General Description 3 Control ptions 4 Description of Main Features 5 Control Schemes 6 Installation

More information

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE Installation instructions For the heating engineer Installation instructions timeswitch VTS 160 GB, IE Table of contents Table of contents 1 Notes on the installation instructions...4 1.1 Observing other

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Vigilant MX4428 Fire Alarm System

Vigilant MX4428 Fire Alarm System Vigilant MX4428 Fire Alarm System The Vigilant MX4428 is an intelligent fire alarm system, incorporating Tyco MX TECHNOLOGY to provide advanced, analogue addressable fire detection. It features support

More information

TopVent Design Handbook

TopVent Design Handbook TopVent Design Handbook Recirculation Units and Supply Air Units for Heating and Cooling High Spaces TopVent Content TopVent DHV Recirculation unit for heating high spaces TopVent NHV Recirculation unit

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System.

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System. Catalogue ActionpacEMSStandard Electro Mechanical Control & Monitoring System www.actionair.co.uk sales@actionair.co.uk Actionair Actionpac EMS Standard Electro- Mechanical Control and Monitoring System

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

ECONOBOOST EB II & EB III Compact Water Booster

ECONOBOOST EB II & EB III Compact Water Booster ECONOBOOST EB II & EB III Compact Water Booster The Stokvis EB II twin pump & EB III triple pump cold water booster units meet today s need for compact, reliable, high performance equipment with modest

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

At Coster we manufacture a comprehensive range of pre confi gured modular controllers which are both easy to install and simple to programme by use

At Coster we manufacture a comprehensive range of pre confi gured modular controllers which are both easy to install and simple to programme by use At Coster we manufacture a comprehensive range of pre confi gured modular controllers which are both easy to install and simple to programme by use of 4 operating keys and an alphanumeric display. When

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

NEW. Innovative heating controls. Commercial boiler control systems. Control 8000 & MX25

NEW. Innovative heating controls. Commercial boiler control systems. Control 8000 & MX25 Innovative heating controls NEW Commercial boiler control systems Control 8000 & MX25 2 Everything perfectly under control About the Bosch Group Leading global supplier The Bosch Group is active in the

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3 DUCT AIR HEATER WITH BUILT-IN CONTROLS Installation & User Instructions Stock Ref. 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 105 31 250 T1 105 31 315 T1 Stock Ref. 105 31 315 T3 105 31 400

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

LZA High efficiency air to water heat pumps with HP compressor

LZA High efficiency air to water heat pumps with HP compressor High efficiency air to water heat pumps with HP compressor -10 C +43 C +60 C HP C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information