BMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT:

Size: px
Start display at page:

Download "BMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT:"

Transcription

1 BMS Commissionability Review October 2009 PROJECT: Four Seasons Hotel Park Lane

2 Summary This report details our review of the BMS specification produced by i.d.a. Building Services Consulting Engineers, and related documents, issued through the contract for the Four Seasons Hotel refurbishment project. The review considers concepts and schematics from a commissioning perspective and focus s on the commissionability and robustness of the design information currently available. At this stage we have also reviewed the design panel drawings submitted by the contractor for MCC10. These are to be updated for final approved status to be given, prior to production of the panel. Page 2 of 5

3 Contents 1 Introduction 2 BMS Specification, Ref: 07/105 Jan 09 Rev B 2.1 General Comments 2.2 Software 2.3 Motor Control Centres 3 MCC 10 drawings Issued by Ashford Controls 3.1 General Comments 3.2 Specific Items Page 3 of 5

4 1 Introduction The specification produced by i.d.a. Building Services Consulting Engineers, which details the schemes for plant and building control, has been reviewed for ease of Commissionability. Associated design drawings and plant schematics have also been reviewed. Our report details observations for the benefit of, but not limited to, the testing and commissioning of the BMS control system for the mechanical and electrical services. 2 BMS Specification, Ref: 07/105 Jan 09 Rev B 2.1 General Comments 1. Alarm handling: we would recommend the additional early specification of particular requirements for alarm handling, such as priority level for defining the alarm action. This may be a client or user driven activity. With the early issue of these details then initial software can be produced to include the required information and this can be verified during the commissioning stage. Some examples are given in the Four Seasons Design Standards document. 2. The required graphic structure, including the use of Engineering Pages, should be reviewed at the earliest opportunity, again to benefit from initial engineering and review on site. 3. All of the plant references and software labelling should have been reconciled prior to the commencement of any project activities. 2.2 Software 1. Pump change over: The specification requests pump duty changeover to occur at start up (eg. Section 3.6.2). However there may well be plant operating 24 hours per day due to the nature of the building. Consideration should be made for these systems, as to whether changeover should occur during low priority night hours, or during day time priority hours when maintenance staff may be more available to follow up a changeover problem. 2. Section HWS circulation pumps proof of running is required from flow and return temperature detection this may benefit from additional contactor status monitoring. 3. Section Variable volume AHU01 (apply comment to all variable volume plant) we would recommend an additional pressure control failure alarm be generated as a general warning. 2.3 Motor Control Centres 1. Section Emergency Operation. This details control of the CHP for emergency building backup / essential power supply, as it is enabled by the BMS. As safety interlocks at the MCC are generally fail safe, then ensure the relevant MCC that controls the CHP has back up power to maintain control during power failure Cubicle sections 1. Within the Form 4 cubicle sections, the specification states Each control circuit shall be arranged to permit emergency de-energising of the starter from a remote lock-stop or the Firemans switch MCC10 drawings do not indicate this, as the 24Vac control circuit from the control section is interlocked with the emergency lockstop, which will only stop the starter if it is switched to auto, and not if it is switched to operate in hand. Advice required as to emergency operation when starters in Hand mode Control Section The following could not be located within the issued MCC10 drawings hence are raised by the author as requiring confirmation of their full requirements: Page 4 of 5

5 1. Continuous/Off/Auto Time switch selector is required within the specification with Time switch On/Off lamps for each switch. 2. Blinking alarm indication and buzzer, complete with mute audible alarm push button and also Reset button for when alarm condition clears, on each MCC. 3. A switch to control power to control section (not door interlocked), with appropriate shrouds and warning. 4. Each MCC to have a common alarm generated by hard wiring, for connection to the Central Heat Pump Alarm Panel and also the Main Fire Alarm Panel. 3 MCC 10 drawings Issued by Ashford Controls The drawings issued by the BMS contractor for MCC10 have been reviewed with consideration to the issued specification and also with regard to general good practice. The following items do not appear to meet the BMS specification (as well as the points previously highlighted in section 2.3.2), though a relaxation may have been made though the contract and unknown by the author of this report. 3.1 General Comments 1. Cubicle terminals for connection cables to control section should be numbered. 2. Power to control section to be identified and installed as per specification, page Panel facia label details not included in drawings issued. 3.2 Specific Items 1. The two MCBs feeding transformers Tx1 and Tx2, and the two secondary MCBs have the same pair of reference numbers and the primarys have the same cable number. 2. Page 20: identify 24Vac control line interlocked with safety conditions. 3. The dampers on several fans are opened by hardwiring when that fan is switched to hand but the endswitch is not interlocked with the fan enable under a damper failed to open condition, the hand overridden fan will still attempt to run against the closed damper. 4. There appears to be no BMS monitoring of the Firemans switch status, so consequential alarms may occur. 5. Smoke extract fan SEF501 how is this controlled as no details of the exhaust damper are shown on the MCC drawings or on the vent schematic, as mentioned in the Spec, and electrical schematic shows essential power to fan via the MCC, though no wiring for this shown in MCC10. Has this been changed under design development? Also the fire schematic and 11 th floor layout show no direct interface with a local fan control panel, but only a fire interface at MCC Three inputs are shown for monitoring the open status of Spa smoke dampers we assume this has been consolidated with the mechanical package and is for alarm indication only, on failure to open in a Fire condition. 7. Toilet Extract EF505 is specified to have an Extended Working pushbutton this is not shown within the panel drawings so we assume it is a software button? 8. The MCC shows a power feed to CSP2 Window Cleaning pump package, but not power to CSP1 Spa & Drench Shower pump package is this is specified elsewhere? Page 5 of 5

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System August 2016 Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Safegard V4 Bespoke Intelligent Damper Control and Monitoring System Devices

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Fire and Smoke Control Systems

Fire and Smoke Control Systems Control Systems Electrical Mechanical Standard Panel Modular design for control and monitoring Premier Panel Customised design for control and monitoring Fully Addressable Fully programmable data wired

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

DRAFT BMS SPECIFICATION

DRAFT BMS SPECIFICATION DRAFT BMS SPECIFICATION \\JONES-PC\Fairlawn Controls\Honeywell\Draft BMS spec.docx Content 1.0 AUTOMATIC CONTROLS... 1 1.1 Project outline 1 1.2 Extent of work 2 1.3 Scope 3 1.4 Standards, Codes and Regulations

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright

More information

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System.

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System. Catalogue ActionpacEMSStandard Electro Mechanical Control & Monitoring System www.actionair.co.uk sales@actionair.co.uk Actionair Actionpac EMS Standard Electro- Mechanical Control and Monitoring System

More information

October 2013 Bespoke Intelligent Damper Control and Monitoring System

October 2013 Bespoke Intelligent Damper Control and Monitoring System October 2013 Actionpac LNS4 Bespoke Intelligent Damper Control and Monitoring System l All system wide activity is logged and viewable for diagnostics and preventative maintenance l Devices powered by

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

V3 Intelligent Damper Control and Monitoring System

V3 Intelligent Damper Control and Monitoring System March 2011 V3 Intelligent Damper Control and Monitoring System Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Devices powered by closest

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

Actionpac LNS3 Intelligent Damper Control and Monitoring System

Actionpac LNS3 Intelligent Damper Control and Monitoring System November 2005 Actionpac LNS 3 NEW AND ENHANCED Intelligent Damper Control and Monitoring System Range and Features Panel PC Driven system. User friendly, no need for operating and maintenance manual. Full

More information

Actionpac 60/120 (LNS Standard)

Actionpac 60/120 (LNS Standard) July 2006 Actionpac 60/120 (LNS Standard) Actionpac 60/120 (LNS Standard) Cost Competitive Intelligent Damper Control and Monitoring System Range and Features Panel system, utilising solid state technology.

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

DENVER INTERNATIONAL AIRPORT MAIN AND NORTH TERMINALS 2016

DENVER INTERNATIONAL AIRPORT MAIN AND NORTH TERMINALS 2016 IMPACT ENGINEERING, INC. MAIN AND NORTH TERMINALS Smoke Control System Testing Procedures Manual September 24, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected

More information

University of Brighton

University of Brighton University of Brighton S t a n d a r d S p e c i f i c a t i o n f o r B M S R e q u i r e d C o n t r o l s S t r a t e g y Version 1.0 October 2017 Document Control Published document name: University

More information

DCS-100. intelligent damper control & monitoring system

DCS-100. intelligent damper control & monitoring system DCS-100 intelligent damper control & monitoring system 02 //DCS-100 Introduction The Disys Technologies DCS-100 is a revolutionary new control system designed specifically for the fire/smoke damper controls

More information

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016 Gas Safety Products Installation, operating and maintenance 05/10/2016 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Mains Supply...

More information

Prescriptive Requirement for Smoke Control

Prescriptive Requirement for Smoke Control HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date: Gas Safety Products Merlin 1500S Gas Interlock System Installation, operating and maintenance Rev: 03 Date: 08-01-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting....

More information

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System Gas Safety Products Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System Installation, operating and maintenance Read these instructions carefully before operating or servicing

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions ISSUE A, MAY 2008 Hard Wired Damper Control Panels Systems 10, 11, & 12 Hard-Wired Systems Bespoke Systems Available Value Engineered Solutions Overview The Hard-Wired Control Panels On a number of projects

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Exhaust Duct Design Page 1 of (C)

Exhaust Duct Design Page 1 of (C) Exhaust Duct Design Page 1 of 16 2016-10-07 (C) Oven Exhaust Guide Version: R5 Exhaust Duct Design The following section is for your guidance in establishing a design to suit your Exhaust duct design requirements.

More information

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date: Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

THX-DL Data Logger USER & INSTALLATION MANUAL V

THX-DL Data Logger USER & INSTALLATION MANUAL V THX-DL Data Logger USER & INSTALLATION MANUAL V1.2012 www.thermomax-refrigeration.com Contents PRESENTATION Summary of Features 2 INSTALLATION Safety Precautions 4 THX Unit 4 Sensors 4 Alarm Relay 4 Power

More information

SIMPLEX WEATHERPROOF CONTROL PANELS

SIMPLEX WEATHERPROOF CONTROL PANELS TECHNICAL BROCHURE BCP3 R10 FEATURES Rugged, NEMA 4X construction withstands even the most severe weather con ditions and prevents corrosion. Solid-state control board displays float status for ease of

More information

SAS6000UTK-7 UNIVERSAL THERMOSTAT

SAS6000UTK-7 UNIVERSAL THERMOSTAT SAS6000UTK-7 UNIVERSAL THERMOSTAT Used with Single Stage, Multi-Stage, Heat pump Installation and operation instructions SPECIFICATION: Power Supply Dual Power 24VAC (18-30VAC,50/60Hz) or Battery Powered

More information

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS TYPE C STANDARD & NIGHT SETBACK S Specifications and Owner s Manual PLASTEC VENTILATION, INC. TYPE C STANDARD & NIGHT SETBACK General Description BENEFITS Safety: air flow is maintained at required speed

More information

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property... Interactive Fire Alarm System Release 3 Operator's Handbook Information Panel, BV-320 Protecting life, environment and property... ASAFE-IN/FE Rev. A, 010531 COPYRIGHT This publication, or parts thereof,

More information

Hands On: Introduction to Safety Workshop Presented by Robert Jones Manufacturing in America March 14-15, 2018

Hands On: Introduction to Safety Workshop Presented by Robert Jones Manufacturing in America March 14-15, 2018 Hands On: Introduction to Safety Workshop Presented by Robert Jones Manufacturing in America March 14-15, 2018 Before we start A Penny for Your Thoughts At the end of the session, share your feedback via

More information

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016 IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United

More information

NATURAL VENTILATION CONTROL SYSTEMS

NATURAL VENTILATION CONTROL SYSTEMS ...... CI/SfB (57.9) Uniclass L755 September 2005 NATURAL VENTILATION CONTROL SYSTEMS... . 2 ...... Passivent ventilation control systems have been have been specially developed to meet the requirements

More information

Loadstar AC/DC Systems

Loadstar AC/DC Systems WARRANTY W A R R A N T Y YEAR The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

I P. Tough Starters for Tough Environments. Explosion Proof Starter. Ready to Install, Completely Wired and Assembled

I P. Tough Starters for Tough Environments. Explosion Proof Starter. Ready to Install, Completely Wired and Assembled I P Explosion Proof Starter 1Ø & 3Ø, 115~600VAC, 1 75HP START/STOP AND RESET PUSHBUTTONS ELECTRONIC MOTOR PROTECTION Tough Starters for Tough Environments Ready to Install, Completely Wired and Assembled

More information

intelligent fire alarm ID60series panels

intelligent fire alarm ID60series panels intelligent fire alarm ID60series panels features LPCB approved to EN54 Parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports advanced detection such as

More information

ID50series. intelligent fire alarm panels

ID50series. intelligent fire alarm panels ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of

More information

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT Islenska Français Deutsch Nederlands Svenska EN54-8 Zone Conventional Fire Control Panel User Manual 997-493-00, Issue 0 November 003 Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs

More information

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH. THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH www.thermomax-group.com CONTENTS SECTION 1 - INTRODUCTION... 2 SECTION 2 - INSTALLATION... 3 2.1 - RCX 100 UNIT... 4 2.2 -

More information

08/17/2011 Rev. 4 PULL STATION EXHAUST HOOD 10 TO 20 FEET FROM HOOD LOCATE ONE NEAR EVERY POINT OF EGRESS FROM HOOD

08/17/2011 Rev. 4 PULL STATION EXHAUST HOOD 10 TO 20 FEET FROM HOOD LOCATE ONE NEAR EVERY POINT OF EGRESS FROM HOOD 24V CORE TOTAL FLOOD PROTECTION INSTALLATION SUMMARY CORE WATER LINE- 30 TO 70 PSI OPERATING PRESSURE, 90 PSI MAX STATIC PRESSURE, 1.5 GPM PER FOOT OF HOOD 3/4 INCH NPT FITTING, CONNECTED TO SUPERVISED,

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Chapter 10. HVAC System

Chapter 10. HVAC System Standardized Technical Specification Bi-Level Passenger Rail Cars for Intercity Corridor Service Chapter 10 HVAC System Revision C Table of Contents 10-1 Table of Contents 10.0 HVAC System... 10-3 10.1

More information

Control Panel Checklist

Control Panel Checklist Control Panel Checklist Versatronik -C Panel Checklist Option Selection for Control Panel Quotes Checklist Control Panel Checklist Section 1 General Information Customer name Phone number Fax number Email

More information

ID2000. operating manual

ID2000. operating manual ID2000 operating manual 997-434-000-2, Issue 2 Contents ID2000 Series Operating Manual Contents 1 Introduction 1 1.1 Associated Documents 1 1.2 The ID2000 Panels 1 1.3 Cleaning 2 2 Panel Controls and Indicators

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design Basis of Design University of Washington Specific Controls Features The following items are specific to the University of Washington: The goal is to move from pneumatic to DDC controls. This goal shall

More information

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47) DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4

More information

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1 Gas Safety Products Merlin CT1650+ Gas Interlock System Installation, operating and maintenance 09/05/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

Mechanical Smoke Extract Shaft Systems

Mechanical Smoke Extract Shaft Systems Mechanical Smoke Extract Shaft Systems Presented by Mechanical Smoke Extract Shaft Systems Why Choose Crossflow? Crossflow is a family run company with over 45 years technical expertise. We are a solutions

More information

Smoke Control Manual

Smoke Control Manual Smoke Control Manual For BACnet Systems ON BAC-5800 Controller OFF ON BAC-5800 Controller Pressurized Third Floor Stairwell Fan ON OFF BAC-5800 Controller Exhausted Second Floor OFF BAC-5800 Controller

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

MANUFACTURER OF LT PANELS

MANUFACTURER OF LT PANELS MANUFACTURER OF LT PANELS POWER CONTROL CENTRE PANEL(PCC): Power Control Centre is used for distribution & control of various power source used in industry. Normally PCC is installed near power source.

More information

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual Installation and Operation Manual Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control Pump-Lead-Lag Warning This Heat-Timer control is strictly an operating control; it should

More information

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670 Bulletin AV-670 Series 670 Hood Monitor Specifications - Installation and Operating Instructions DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Phone: 219/879-8000 Fax: 219/872-9057

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

Indoor Swimming Pools:

Indoor Swimming Pools: Indoor Swimming Pools: The Technologies 20 th November 2017 Amnon Holland BE Eng, M.AIRAH www.esbsconsult.com.au 1 Agenda The driver Code Compliance of Ventilation The Technologies - Heat exchange and

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Broag Pressurisation equipment

Broag Pressurisation equipment Broag Pressurisation equipment Compact wall mounted and free standing pressurisation units, utilising the latest microprocessor control. For use on sealed heating and cooling systems, offering accurate

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

Capacity: 1.5 to 6.0 Ton

Capacity: 1.5 to 6.0 Ton VACPB1 Series Wall Mount Explosion Proof Air Conditioner and Room Pressurization System Hazardous Location N.E.C. and I.E.C. Approved 50 Hertz Models 60 Hertz, High Ambient, & Custom Designs Available

More information

SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series

SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series Instruction Manual Read and retain carefully for as long as the product is being used. It contains

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL INSTALLATION & OPERATION MANUAL Model TME- * * Balance of model number is determined by customer specifi ed limits and Setbacks. AUTOMATIC SETBACK THERMOSTAT LIGHT SENSING OR CONTACT CLOSURE FOR LOW VOLTAGE

More information

Marlin Filament Monitoring October 2014

Marlin Filament Monitoring October 2014 Why is Filament Monitoring Useful? Marlin Filament Monitoring October 2014 There are a number of filament monitors and filament break detectors available which will generate an alarm if the filament runs

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

DESIGN GUIDELINE SBA 5.11

DESIGN GUIDELINE SBA 5.11 GeneralScope DESIGN GUIDELINE SBA 5.11 FIRE COMMAND CENTER This design guideline clarifies how certain Michigan Building Code (MBC) requirements for Fire Command Centers are to be applied on University

More information

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, mechanical, by photocopying, recording or in any other manner

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

Please read this sheet as it contains important information

Please read this sheet as it contains important information Important Please read this sheet as it contains important information Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions.

More information

Capacity: 1.5 to 6.0 Ton

Capacity: 1.5 to 6.0 Ton VACPB1 Series Wall Mount Explosion Proof Air Conditioner and Room Pressurization System CSA Certified for Use in Division 2 Locations 60 Hertz Models 50 Hertz, High Ambient, & Custom Designs Available

More information

TESTING, ADJUSTING AND BALANCING

TESTING, ADJUSTING AND BALANCING PART 1 GENERAL 1.01 DESCRIPTION A. Work Included: After completion of the work of installation, owner is responsible for procuring an air balancing and testing agency to test and regulate all components

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

BUILDING MANAGEMENT SYSTEMS. Introduction to Building Management Systems

BUILDING MANAGEMENT SYSTEMS. Introduction to Building Management Systems BUILDING MANAGEMENT SYSTEMS Introduction to Building Management Systems The Building Management System is used for all the functions carried out by the building including energy services security monitoring,

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Tender Document. MR 193/ Design, Supply & Commission New Control Panel for Ruston 16RK270 Generator

Tender Document. MR 193/ Design, Supply & Commission New Control Panel for Ruston 16RK270 Generator Tender Document MR 193/2017 - Design, Supply & Commission New Control Panel for Ruston 16RK270 Fiji Electricity Authority Generation 17-Jul-17 Tender Submission - Instruction to bidders It is mandatory

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

03.03.mmm REV.2 09/01

03.03.mmm REV.2 09/01 03.03.mmm REV.2 09/01 Via del Lavoro, 80-40056 CRESPELLANO (Bologna) ITALY - ( +39 051/733.383 - Fax. +39 051/733.620 P.O. BOX, 150-40011 ANZOLA EMILIA (Bologna) - ITALY Power Factor Regulator cosφ V A

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3 DUCT AIR HEATER WITH BUILT-IN CONTROLS Installation & User Instructions Stock Ref. 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 105 31 250 T1 105 31 315 T1 Stock Ref. 105 31 315 T3 105 31 400

More information

ID2000. intelligent fire alarm panel

ID2000. intelligent fire alarm panel ID2000 6pp A4 10-01 3/8/06 22:57 Page 1 ID2000 intelligent fire alarm panel features Certified to EN54 Parts 2 and 4 Expandable from 2 to 8 loop capacity Up to 198 devices per loop (99 sensor and 99 modules)

More information

Operating Guidelines for Your Roof and Gutter Ice Dam Prevention System

Operating Guidelines for Your Roof and Gutter Ice Dam Prevention System 1. Your heat cable system is designed to be preventative. This means it needs to be energized several hours prior to snow fall and should remain on while there is substantial snow on the roof. We will

More information