Installation Instructions for Honeywell ALL-SPEC Air Sampling Smoke Detection System
|
|
- Shanna Hodge
- 6 years ago
- Views:
Transcription
1 Installation Instructions for Honeywell ALL-SPEC Air Sampling Smoke Detection System Operating indicator light Alarm indicator light for detector module II Alarm indicator light for detector module I Indicator light for common fault Pre-punched cable entries for connection to the central fire panel or power supply (input/output) Connection pipe system I Connection pipe system II Connection for air return ALL-SPEC_Unit_HON.doc 0/0 /
2 S F O 0 Installation of the Detector Module Please note: Only the detector modules of the type ASD-TP-0, ASD-TP-0 and ASD-TP-00 that have been approved by the VdS-certification authority with the approval number G 00 may be used.. Carry out the following works only if the device is powered down.. Open the device by carefully unlocking the housing snap-in closures by means of a screwdriver. Then lift the housing lid a little bit.. Carefully pull the connection cable of the display board off and remove the housing lid. Note: Shall the device only be provided with one detector module, please skip to point. Shall the device however be provided with two modules please follow the following instructions.. If you want to install a second detector module you have to recover carefully the ventilator cover for the second air sampling duct (self-adhesive plastic cover). Take for this if necessary a screwdriver.. Break carefully the clasp for the connection of the second pipe system (predetermined breaking point, marked by II ) with a screwdriver from the housing. Note: The knocked clasp is to removed completely from the device.. Make the required settings at the detector module by setting the contacts of switch S accordingly (see also Settings of the detector module ).. Carefully spread a bit the support clamps used to fix the detector module in the corresponding mounting position.. Carefully place the detector module in between them until it audibly snaps in and thus is fixed by the support clamps. Note: Make sure that the inserted detection module is fixed tight and save by the brackets by pressing the brackets additional by hand.. Connect the detector module via the ribbon cable with the connection Head (detector module I) or Head (detector module II) to the base board. Note the labelling of the base board. 0. Reconnect the display board to the base board. Note the connections and labelling of the base board. ALL-SPEC_Unit_HON.doc 0/0 /
3 Detector Module Settings In the following tables the switch S has two positions: on off The standard settings have a grey background. Setting the response sensitivity detector module DM-TP- 0 DM-TP- 0 DM-TP- 0 S. S. 0, %/m 0, %/m on on 0, %/m 0,0 %/m off on,0 %/m 0, %/m 0,0 %/m on off 0, %/m 0, %/m 0,0%/m off off Setting the alarm delay S. S. 0 seconds off off 0 seconds on off 0 seconds off on 0 seconds on on Setting the activating threshold air flow fault S. S. I on off II off on III off off IV on on Setting the delay air flow fault S. S. 0. minutes off on minutes on off minutes on on 0 minutes off off Setting the fault signal S. non-latched latched off on Setting LOGIC SENS S.0 off on off on ALL-SPEC_Unit_HON.doc 0/0 /
4 JU JU JU JU HEAD HEAD X X X X DIAG DISPLAY X JU JU JU JU JU JU JU JU Choose number of the detector modules The number of fitted detector modules are chosen with the jumper JU. The following table shows, whether the jumper must be put or not: X = pin pair bridge O = pin pair open The standard settings have a grey background. Choose number of the detector modules Jumper Pin No. JU, + detector module X detector module O Setting the ventilator voltage Jumper JU allows to set the ventilator voltage on the base board. The following table shows whether the jumper is set or not: X = pin pair bridged O = pin pair open The standard setting has a grey background. Setting the ventilator voltage Jumper Pin No. JU, +, V X V O ALL-SPEC_Unit_HON.doc 0/0 /
5 Setting the function of the fault contact The contact type (break contact or make contact) of the collective fault is set using the jumper JU and JU. Fault contact detector module I = Jumper JU Fault contact detector module II = Jumper JU The following table shows the positioning of the jumpers: X = pin pair bridge O = pin pair open The standard settings have a grey background. Setting the collective fault contact Jumper Pin No. JU/ + JU/ + break contact X O make contact O X A B Device Supports A B Support type MT- horizontal installation Support type MT- vertical installation ALL-SPEC_Unit_HON.doc 0/0 /
6 Installation of the device General information: - When choosing the installation location make sure the displays of the device are clearly visible. - Screw the air sampling smoke detection system either directly to the wall with its bottom casing or mount it by means of a special support (type MT-). This support allows to mount the device also to racks for example. - The air outlet of the device must not be blocked. (The distance between the air outlet and adjacent objects (e.g. wall) is to be at least 0 cm.) - The air sampling smoke detection system can be mounted with the air sampling pipe connector(s) pointing upwards or downwards (If necessary, turn the housing-lid by 0 ). If the air sampling pipe connector(s) point downwards make sure no impurities enter the air outlet which then points upwards. Procedure:. First, clearly mark the fixing points for mounting the device. If necessary, use the provided drilling jig. Fix the device using four screws (max. of mm for wall mounting and max. of mm for mounting by means of the device support MT-) in order to guarantee a safe fixing and to limit vibrations which occur.. Fix the device by means of four screws in accordance with the mounting type to the wall or the device support. Make sure the device is not fixed under mechanical tension or the screws are not tightened too much. Otherwise the device might be damaged, or unintended. secondary noise may arise. Note: To balance unevenness and/or to avoid vibrations vibration dampers need to be installed.. Carefully break out of the housing the required cable entries (max. x M0 und x M). If required, use a screwdriver.. Carefully equip the cable entrie(s) according to requirements with M0 or M glands (x M, x M0 included in the delivery) by inserting them into the corresponding cable entry/entries.. Pass the connection cable(s) (max.. mm²) required to wire the device through the suitable cable entry/entries into the device and cut it to the required length within the device.. Wire the device according to the following connection diagram. ALL-SPEC_Unit_HON.doc 0/0 /
7 internal connection base board X 0V +V 0V +V connection to central fire panel DJ or DJ _ + _ + _ + V connection to central fire panel connection to central fire panel connection to central fire panel DJ or DJ X _ + X, X, X, X, X, X, X, X, X, X, X, X, X, X, Connection contact of the first alarm relay (make contact) centre tap of first alarm relay contact of the first alarm relay (break contact) + external response indicator for first detector module external response indicator for first detector module + V reset input 0 V reset input + V supply voltage 0 V supply voltage fault contact nd detector module (connection ) fault contact nd detector module (connection ) contact of the nd alarm relay (make contact) centre tap of nd alarm relay contact of the nd alarm relay X, X, X, X, + external response indicator for nd detector module external response indicator for nd detector module fault contact first detector module (connection ) fault contact first detector module (connection ) ALL-SPEC_Unit_HON.doc 0/0 /
8 S Flow-Init Commissioning. Make sure first that the device has been in operation for at least 0 minutes prior to the air flow initialization in order to reach the operating temperature.. In order to initialize the connected pipe system, press the Flow-Init-button S (see figure) of the corresponding detector module until the green operating indicator light of the device starts flashing. The initialization is terminated after approx. seconds. After a successful initialization the operating indicator light is lit permanently.. During and after initialization the pipe system must no longer be changed. Even the ventilator voltage of the device must no longer be modified after initialization. Otherwise the initialization must be carried out again: ALL-SPEC_Unit_HON.doc 0/0 /
9 Conformity certification pursuant to EU Construction Products Directive /0/EEC The conformity of the air sampling smoke detector for fire detection and fire alarm systems in buildings according to DIN EN -0 has been established by a test at the VdS laboratory. The EC certificate of conformity has been issued by notified product certification body (ID no. 0, VdS). The CE designation according to DIN EN -0 has been carried out. 0 WAGNER Group GmbH Schleswigstrasse - 0 Langenhagen EN -0: 00 Air sampling smoke detector for fire detection and fire alarm systems in buildings 0 Nr. 0 CPD 0 0,0 % light obscuration/m Class: A, B and C 0, % light obscuration/m Class: A, B and C 0, % light obscuration/m Class: A, B and C Honeywell Life Safety Systems 0 Waterside Road Hamilton Industrial Park Leicester LE TN Tel (+) 000 ALL-SPEC_Unit_HON.doc 0/0 /
Air Sampling Smoke Detection
Air Sampling Smoke Detection Notifier by Honeywell: Data Sheet Air Sampling Smoke Detection Data Sheet The Notifier by Honeywell range of air sampling smoke detection systems (ASSD) comprises smoke detectors
More informationSiemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation
Sinteso Cerberus PRO FDA241, FDA221 ASD Aspirating smoke detector Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Patented technology Early
More informationDUAL MONITORED INPUT/OUTPUT UNIT BN-305
DUAL MONITORED INPUT/OUTPUT UNIT BN-30 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection
More informationInterface Modules for SENTRI
EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface
More informationSensepoint XCL Fixed Gas Detector
Gas Detec on Sensepoint XCL Fixed Gas Detector Quick Start Guide Sensepoint XCL Fixed Gas Detector Quick Start Guide Read and understand the Sensepoint XCL Operating Instructions before installing, operating
More informationFAS-420 Aspirating Smoke Detector LSN "improved version" FAS-420. Operation Guide
FAS-40 Aspirating Smoke Detector LSN FAS-40 en Operation Guide FAS-40 Aspirating Smoke Detector LSN Table of Contents en 3 Table of Contents General 6. Introduction 6. Safety Instructions 6.3 Warranty
More informationInterface and EOL Modules 8
Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface
More informationHoneywell Air Sampling Devices Data Sheet
Honeywell Air Sampling Devices Data Sheet Smoke detection with high sensitivity and false alarm immunity Product Overview Honeywell Air Sampling Devices (ASDs) are smoke detectors that actively take air
More informationHoneywell Air Sampling Devices Data Sheet
Honeywell Air Sampling Devices Data Sheet Smoke detection with high sensitivity and false alarm immunity Product Overview Honeywell Air Sampling Devices (ASDs) are smoke detectors that actively take air
More informationDUAL MONITORED INPUT/OUTPUT UNIT BN-305-2
DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection
More informationSMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS
SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH
More informationWD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.
Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction
More informationALARM OUTPUT MODULE. Product #7736
ALARM OUTPUT MODULE The Alarm Output Module (AOM) enables you to use weather station alarms or commands from your computer to automatically start or stop external devices such as indicator lights, audio
More informationSnifter. User Manual. Distributor
Snifter User Manual Distributor Version 1.3 08/09/2009 1 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2. INSTALLATION... 4 2.1 Selecting the
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS The SensorNet I/O Module provides attachment for up to 32 alarms and up to 16 switched devices. An RS-232 or RS-422 communications port is also provided for receiving serial alarms.
More informationone Operating instructions SenTRI ONE panel-based Fire detection and alarm system
SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -
More informationEnd To End Optical Beam Smoke Detector. Additional Information
End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important
More informationInstallation Instruction Venturi-Air Duct Kit. (Part No. S )
Installation Instruction Venturi-Air Duct Kit (Part No. S4-34760) Intended purpose This product is designed for installation on a loop circuit of a Vigilon system. Warning In order to ensure correct and
More informationK00364 Electronic Bin Thermostat
K00364 Electronic Bin Thermostat Installation Instructions This kit reduces overfill and condensation issues and can be used on any Manitowoc ice machine installed on an ice dispenser. Order kit number
More informationAZSG10000/AZSG10005/AZSG10010 ABUS Wired Outdoor Siren
AZSG10000/AZSG10005/AZSG10010 ABUS Wired Outdoor Siren EN Installation instructions and user guide Version 1.0 Contents Introduction... 3 Safety information... 4 Scope of delivery... 5 Technical data...
More informationOperating Manual. English. Refrigerators for chemicals KRC 50 KRC 180
English Operating Manual Refrigerators for chemicals KRC 50 KRC 180 1.951.6610-V1 12/12 JULABO GmbH 77960 Seelbach / Germany Tel. +49 (0) 7823 / 51-0 Fax +49 (0) 7823 / 24 91 info@julabo.de www.julabo.de
More informationFDA241, FDA221 Siemens ASD
FDA241, FDA221 Siemens ASD Patented Technology Sinteso TM Cerberus PRO Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red)
More informationSmoke Detector and Siren. Manual
Smoke Detector and Siren Manual 004001 Smoke Detector and Siren Manual Quick Start... 2 Product Description... 2 Installation Guidelines... 3 Behavior within the Z-Wave Network... 3 Operating the Device...
More informationLASER ASPIRATED SMOKE DETECTOR
LASER ASPIRATED SMOKE DETECTOR LASD1 (Single Channel) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE) 1 INTRODUCTION The LASD1 utilises one or two high-sensitivity laser point detectors in an aspirated
More informationInstallation instructions
Installation instructions Hold-open system For non VdS fire doors Version: 51171560 -en- Stand: c / 12.2015 0000000 0000 51171560 XXXXX 2 GfA ELEKTROMATEN GmbH & Co. KG Wiesenstraße 81 40549 Düsseldorf
More informationFDA241, FDA221 Siemens ASD
FDA241, FDA221 Siemens ASD Patented Technology Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red) Configurable as a Standalone
More informationFireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds
Fireray 2000 pplication and FETURES Installation Guide Range 10-100 metres 12V to 24V dc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or automatic reset
More informationSnifter ATEX22 VERSION. User Manual. Distributor
Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5
More informationLASER ASPIRATED SMOKE DETECTOR
LASER ASPIRATED SMOKE DETECTOR LASD2 (Dual Channel) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE) 1 INTRODUCTION The LASD2 utilises two, high-sensitivity laser point detectors in an aspirated
More informationFLAME AMPLIFIER MODULE 3001D
SYSTEM 000 / 000 FLAME AMPLIFIER MODULE 00D TECHNICAL DESCRIPTION EDITION TB 00D-SZ Dipl.-Ing. K.-H. Mindermann GmbH, Eggerscheidter Str. 7, D-088 Ratingen Phone +9 (0) 0 9 8 0, Fax +9 (0) 0 98 EMail:
More informationTECHNICAL INFORMATION Touchtronic Clothes Dryers
TECHNICAL INFORMATION Touchtronic Clothes Dryers Includes: T1302, T1303, T1322, T1329ci T1403 & T1405 2004 Miele This page intentionally left blank. Table of Contents GENERAL INFORMATION A. Warning and
More informationFCS-320-TM Series Conventional Aspirating Smoke Detectors
Fire Alarm Systems FCS-320-TM Series Conventional Aspirating Smoke Detectors FCS-320-TM Series Conventional Aspirating Smoke Detectors For connecting to conventional fire panels High deceptive alarm immunity
More informationModels NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring
More informationCellarSafe. Carbon Dioxide and Oxygen Safety Monitor
CellarSafe Carbon Dioxide and Oxygen Safety Monitor Installation and operating instructions for the CellarSafe Monitor and the CellarSafe Calibration Unit M07234 May 2008 Issue 6 Warning Please take care
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationUSER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -
USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...
More informationKey-Operated Switch GMA 41 / GMA 44 SW. Operation Manual
Key-Operated witch GMA 41 / GMA 44 W Operation Manual Table of contents Page Introduction... 4 Key function... 4 Distinction of GMA 41/44 W models... 4 Relays... 5 P.C. boards of GMA 41/44 W... 7 Terminal
More informationFire control panel detect 3004 plus and accessories
Fire control panel detect 3004 and accessories The modular fire alarm panel detect 3004 is the basic version of a broad product portfolio of the system detect 3000. Up to 20 fire control panels can be
More informationTTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.
TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.
More informationThe EN54 Part 2 and 4 Fire System
Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire
More informationInstallation and maintenance instructions for cabin units type vertical IDAC (V50)
GB Installation and maintenance instructions for cabin units type vertical IDAC (V50). Application. Bundled parts. Handling. Marking. Weight. Transport. Storage 5. Installation 5. Mounting 5. Water trap
More informationCat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE
Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product
More informationE N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.
E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration
More informationLOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division
7 8 ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or twostage oil burners with an oil throughput of up to 0 kg/h in intermittent
More informationAT-G-DETECT Gas Sensing System
AT-G-DETECT Gas Sensing System CHECK / CALIBRATION PROCEDURE* *Technician use only This procedure must be carried out by a suitably qualified technician in accordance with these instructions and the standards
More informationPerformance Specifications LSF LIFT-SMOKE-FREE
Performance Specifications LSF LIFT-SMOKE-FREE Lift shafts and machinery rooms must be ventilated and equipped with a smoke and heat exhaust ventilation (SHEV) system in accordance with the currently valid
More informationOn the job around the clock 24/7: Fire detection systems
On the job around the clock 24/7: Fire detection systems Version 02.2010 Version: 02.2010 Product catalogue Fire detection systems This product catalogue is intended for sales purposes only. For planning,
More informationFIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module
FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required
More informationDISPLAY ALARM SYSTEMS
DISPLAY ALARM SYSTEMS ROVIS Co is the MYRIAD partner and distributor in Romania Tel: 021 224 03 35 Fax: 021 225 00 04 Email: valentin.iosif@rovisco.ro; office@rovisco.ro Adresa: Str. Garlei nr. 190A, sector
More informationENGLISH INSTALLATION AND USER S MANUAL FRENCH NOTICE D INSTALLATION ET D UTILISATION ITALIAN MANUALE D ISTRUZIONE
ENGLISH INSTALLATION AND USER S MANUAL FRENCH NOTICE D INSTALLATION ET D UTILISATION ITALIAN MANUALE D ISTRUZIONE 1 INSTALLATION AND USER S MANUAL CONTENT INTRODUCTION 03 SAFETY PRECAUTION 03 SPECIFICATION
More informationRoom Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature
1 858 1858P01 1858P02 1859P02 Symaro Room Sensors for relative humidity (high accuracy) and temperature AQF3150 QFA31 Use Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for r h and
More informationISIS SAFETY SYSTEM Installation guide
ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly
More informationOverpressure Leak Detector
Overpressure Leak Detector Installation and User Manual Model LD-UPP-3 Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
More informationVisit for more technical information and downloads.
Visit for more technical information and downloads. Vehicle Heaters Technical Documentation Installation instructions EasyStart Timer EN Operating instructions Quick start guide Installation instructions
More informationWater Detection Controllers
Page 1 of 5 Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation or erosion
More informationE N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI
E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm
More informationMGD Murco Gas Detector. Check / Calibration Procedure* 10 ASH (1)
MGD Murco Gas Detector Check / Calibration Procedure* Content Page 1- Introduction 2 2- Electrical Set-Up 2 3- Bump Test 2 4- Calibration 3 4.1 Exchange Sensor board 3 4.2 Gas Calibration 3 5- Additional
More informationGL-CO-RFG Channel Gas Leak Alarm System
Four Elms Road Edenbridge Kent TN8 6AB UK Features & Benefits Remote sensors for natural gas, LPG and CO 1 x SPST relay outputs DIN-rail as standard, panel mounting kit available Adjustable alarm thresholds
More information(68.52) X. June 2000 supersedes February vigilon ADVANCED FIRE DETECTION & ALARM SYSTEMS
(68.52) X June 2000 supersedes February 2000 vigilon ADVANCED FIRE DETECTION & ALARM SYSTEMS VIGILON SYSTEM ARCHITECTURE Repeat Panel Spur Manual Call Point T-breaker Alarm Sounder Max loop length 1000m
More informationEngineering Specification Guide VESDA-E VEP
Guide VESDA-E VEP 29712_07 November 2018 Contents 1 GENERAL 3 1.1... Scope 3 1.2... ASD System Information 3 1.3... Approvals and Standards 3 1.4... Codes, Standards or Regulations 3 1.5... Quality Assurance
More informationXGUARD-10/-5. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more
EN XGUARD-0/-5 LASER SCANNERS for industrial doors XGUARD-0: max. detection range of 9.9 m x 9.9 m XGUARD-5: max. detection range of 5.0 m x 5.0 m User s Guide for product version 0600 and more SAFETY
More informationOriginal operating instructions Safety switch with guard locking AC901S AC902S
Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5
More informationSection 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.
CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions 1 PACKAGE CONTENTS Wiring Harness 6 Wire Nuts #6 x 3/4 Screws s BP7175 3/16 Wall Plugs Section 1: General Description Camden CM-RQE-70 Request-to-Exit
More informationHydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)
Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front
More informationLZR -FLATSCAN SW SAFETY SENSOR FOR FULL- AND LOW-ENERGY AUTOMATIC SWING DOORS
EN LZR -FLATSCAN SW SAFETY SENSOR FOR FULL- AND LOW-ENERGY AUTOMATIC SWING DOORS 75.5947.01 LZR-FLATSCAN SW 20180627 Page 1 of 16 DESCRIPTION 1 2 3 4 5 6 7 8 11 12 13 14 15 16 9 10 17 18 1. cover 2. push
More informationCM-RQE70 PIR REQUEST TO EXIT DETECTOR
Door Activation Devices CM-RQE70 PIR REQUEST TO EXIT DETECTOR THIS PACKAGE INCLUDES (1) Wiring Harness (2) #6 x 3/4" Screws (2) 3/16" Wall Plugs (6) Wire Nuts (2) 's BP7175 1. GENERAL DESCRIPTION Camden
More informationAO Annunciator Module
General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,
More informationINLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL
INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data
More informationDMFPM-2R MULTIFUNCTIONAL
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND
More informationInstallation and user manual for the BiWire / Conventional Repeater Panel
Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....
More informationHEAT PUMP PROGRAMMABLE THERMOSTAT
HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15
More informationLOGIC MODULE EX-22 For lighting control with automatic regulation of light level
LOGI MODULE For lighting control with automatic regulation of light level Order no: 366. Description is a logic module for controlling two lighting groups in one area, orintwo areas with one lighting group
More informationPremier Hazard STC Instructions
PREMIER HAZARD Ltd Bessingby Industrial Estate Bridlington YO16 4SJ Tel: +44 (0) 113 239 1111 Fax: +44 (0) 113 239 1131 www.premierhazard.co.uk info@premierhazard.co.uk Premier Hazard STC Instructions
More informationBetriebsanleitung / Operation manual. Druckwächtereinheit QUINGUARD / Pressurization Controller QUINGUARD
Betriebsanleitung / Operation manual Druckwächtereinheit QUINGUARD / Pressurization Controller QUINGUARD 12 V Version 07/2014 Manufacturer... 28 Description... 28 Installation of the QUINGUARD unit...
More informationQXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.
QXA2100 Condensation monitor QXA2100 Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power. Application Monitors condensation build up in buildings
More informationPublic Safety DAS Annunciator Panel
Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This
More informationInstructions for the fan motor control system with integrated wiring terminals SILVER C
Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.
More informationTYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER
Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke
More informationInput module, input/output module
Sinteso / Cerberus PRO Input module, input/output module FDCI221, FDCIO221 Input module and input/output module for the automatically addressed detector line Input module FDCI221: Monitorable contact input
More informationABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual
ABLOY DA460 SWING DOOR OPERATOR Installation and commissioning manual APPROVALS / STANDARDS 73/23/EEC (Low Voltage directive) 93/68/EEC (Low Voltage directive) 89/336/EEC (EMC directive) Statement of fire
More informationFCS-320-TM Aspirating Smoke Detector FCS-320-TM FCS-320-TM-R. Operation Guide
FCS-320-TM Aspirating Smoke Detector FCS-320-TM FCS-320-TM-R en Operation Guide FCS-320-TM Aspirating Smoke Detector Table of Contents en 3 Table of Contents 1 General 6 1.1 Introduction 6 1.2 Safety
More informationASD 535 Aspirating smoke detector
ASD 535 Aspirating smoke detector From production number 3072 and FW version 0.06.00 The ASD 535 aspirating smoke detector performs the task of taking continuous air samples via one or two sampling pipe
More informationDEB71. Earth Leakage Monitoring Relay. Benefits. Description
Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional
More informationCertificate: / 29 April 2014
Test report: 936/21217455/A of 10 September 2013 Initial certification: 01 April 2014 Expiry date: 31 March 2019 Publication: BAnz AT 01 April 2014 B12, chapter I, No. 1.1 Approved application The tested
More informationINSTALLATION MANUAL. Decoration Panel Provided with Filter Auto Cleaning Function Self Cleaning decoration panel BYCQ140D7GW1 BYCQ140D7GFW1
INSTALLATION MANUAL Decoration Provided with Filter Auto Cleaning Function Self Cleaning decoration panel BYCQ0D7GW BYCQ0D7GFW BYCQ0D7GW BYCQ0D7GFW Installation manual Contents. SAFETY PRECAUTIONS....
More informationAx60+ Multi-Gas, Quick Connect Option
Ax60+ Multi-Gas, Quick Connect Option Analox Limited 15 Ellerbeck Court, Stokesley Business Park, North Yorkshire, TS9 5PT, UK UK/RoW T: +44 (0)1642 711400 F: +44 (0)1642 713900 US T: (714) 891-4478 W:
More informationMatrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1
Matrix2000 User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 s Version: 2.0 Revision: 1 IMPORTANT INFORMATION Limitation of liability It is mandatory, Matrix2000 panel to be installed in accordance
More informationFIELD-INSTALLED MOTION ACTIVATED LED DIMMER CONTROL
FIELD-INSTALLED MOTION ACTIVATED LED DIMMER CONTROL FOR REACH-IN GLASS DOORS AND MULTI-DECK MERCHANDISERS INSTALLATION AND OPERATION MANUAL P/N 05035_A December 008 LED Dimmer Control Installation and
More informationD7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector
D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex
More informationOperation and Installation Instruction
Operation and Installation Instruction Extinguishing Control Computer 8010 19-Inch Design (Series 2 and Series 3) 798955.GB0 09.2007 G 200090 G 205064 GB Technical changes reserved! Intended purpose This
More informationDec Wirsbo CoSy Radio. Installation and Operating Instructions
Dec. 2002 Wirsbo CoSy Radio Installation and Operating Instructions Contents 1. Overview... 3 2. Room thermostat... 3 2.1 Thermostat models... 3 2.2 Function... 4 2.3 Positioning... 4 2.4 Setting and limiting
More informationAccessories for Alarm Systems in the Protect Series. Instruction Manual en/en
Accessories for Alarm Systems in the Protect Series Instruction Manual 02.07.2014 en/en Contents Contents General Information... 2 Water Leak Detector... 11 Guarantee... 2 Intended Use... 12 Regular Maintenance
More informationOperating Instructions
Operating Instructions System 57 Module Kit (05701-A-0309) Alarm Update Panel (05701-A-0339) Helping to make a safer world Ensure that you read and understand these instructions BEFORE operating the equipment.
More informationLZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12
EN LZR -I30 LASER SCANNERS FOR INDUSTRIAL DOORS max. detection range of 30 ft x 30 ft 75.5667.07 LZR-I30 0509 Page of SAFETY The device contains IR and visible laser diodes. IR laser: wavelength 905nm;
More informationSecure the other corner. bracket using the remaining screw,
Mount the E-FENCE1 directly to the fabric of the chain link or wire mesh, on the interior side of the protected area as shown in the illustrated examples, at a height of 4 5 feet and 1 foot from a post.
More informationCO2 Gas Warning System Assembly and Operating Instructions
CO2 Gas Warning System Assembly and Operating Instructions EURO-GAS MANAGEMENT SERVICES LTD CHURSTON HOUSE, BASCOMBE ROAD, CHURSTON FERRERS, DEVON, TQ5 0JJ, UK : +44 (0)1803 844414 Fax: +44 (0)1803 844224
More informationtcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual
tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual This manual covers operation of the tcm100 and tcm101 Series Temperature Control Modules.
More informationFrost Protection Thermostat
1 203 Frost Protection Thermostat Electromechanical thermal reset limit thermostat RAK-TW.5..H RAK-TW.5..H.. Use Monitoring of frost protection temperature, with single-pole changeover microswitch Switching
More informationPROFIBUS-PA Display RID 261 PROFIBUS-PA
Technical Information TI 071R/09/en Mat.-Nr.: 510 01194 PROFIBUS-PA Display RID 261 PROFIBUS-PA Display of process values and set point alarms on PROFIBUS-PA systems R Applications Direct connection to
More informationDigital Distributing Frame (DDF) Wall-Mount Panel Assembly Installation and Cabling
Digital Distributing Frame (DDF) Wall-Mount Panel Assembly Installation and Cabling CommScope 365-301-136-2 Instruction Sheet Issue 4, February 2004 Material ID 847 532 421 General This instruction sheet
More information