Monitoring of Electrical Equipment Failure Indicators and Alarming

Size: px
Start display at page:

Download "Monitoring of Electrical Equipment Failure Indicators and Alarming"

Transcription

1 Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE Cell #

2 PAST: TIME BASED MAINTENANCE Past maintenance practices were based on original equipment manufacturers or industry standard guidelines. While some of these guidelines were based on the number of equipment operations, the majority resulted in a time-based maintenance program. 2

3 PAST: TIME BASED MAINTENANCE EXAMPLE TIME-BASED PREVENTATIVE MAINTENANCE (Minimum) Equipment Type Mechanical Operation Check Visual Inspection Energized Infrared Inspection and/or Oil Testing Outage Preventive Main.& Testing Cables Terminations & Connections 1 year 1 year 3 year Liquid filled transformers 1 year 1 year 3 years Dry type transformers 1 year 1 year 3 years Metal-clad switchgear Monthly 1 year 3 years MV Circuit Breakers 1 year 1 year 1 year 3 years Buses and Bus ducts 1 year 1 year 3 years Protective relays 1 year 1 year Automatic Transfer Equipment 1 year 6 months 1 year 3 years Low Voltage Equipment 1 year 1 year 3 years Dry type transformers 1 year 1 year 3 years Switchgear 6 months 1 year 3 years LV Circuit Breakers 1 year 1 year 1 year 3 years Panel boards 1 year 1 year 3 years Direct-Current Systems: Batteries 3 months 1 year 1 year Direct-Current Systems: Chargers 3 months 1 year 6 months Electrical Safety Equipment Per OSHA Per OSHA Per OSHA Ground-Fault Protection Systems 1 year Motor Control Centers 1 year 1 year 1 year 3 years Rotating Machinery: AC Motors 1 year 1 year 1 year 1 year Rotating Motors & Generators 1 year 1 year 1 year 1 year Metering 1 year 1 year 3 years 3 Outdoor Bus Structures 1 year 1 year 3 years

4 PAST: TIME BASED MAINTENANCE ISSUES Circuit breaker guidelines would recommend detailed inspections following a fault interruption, but when a fault occurs most of the resources are diverted to identifying and correcting the down steam fault, and restoring power as soon as possible, therefore the circuit breaker was usually neglected Past Time-Based Maintenance is VERY DIFFICULT to properly implement 4

5 PRESENT: MAINTENANCE NEEDS Present maintenance has been driven by a reduction in maintenance budgets, while the need for electrical uptime has become even more critical. Resources reduced, expectations the same When the equipment is available for maintenance, there is no funding to perform the maintenance, and when the funding is available, the equipment is not accessible to perform the required maintenance. 5

6 PRESENT: MAINTENANCE ISSUES 100% 80% 60% 40% 20% 100% 0% % 60% 40% 20% Resources Resources Expectations Uptime Catastrophic Risk Expectations Uptime Catastrophic Risk 0% PAST Reduced Resources Uptime may be reduced Potential Failure Risks increase Management Expectations expect continuous Uptime FUTURE Unique Solutions Technology 6

7 PRESENT: NEW MAINTENANCE APPROACHES Review past maintenance records and observe equipment operating conditions and determine the level of maintenance required based on this historical data. Maintenance work scopes would also be adapted to Full-Maintenance which involved the traditional maintenance practices and a lesser level of maintenance, referred to as Operational Maintenance. 7

8 PRESENT: NEW MAINTENANCE APPROACHES The equipment would be rated and ranked based on the past maintenance records and ongoing visual inspections. Low-resistance (Doctor) measurement across a circuit breaker contacts Insulation resistance of electrical distribution equipment, as well as gas-in-oil testing results for transformers. 8

9 PRESENT: FULL VS. OPERATIONAL MAINT. LV BREAKERS LV BREAKERS FULL MAINTENANCE OPERATIONAL MAINTENANCE INSPECT AND OPERATE INSPECT AND OPERATE CHECK RACKING CHECK RACKING LUBRICATE LUBRICATE MEGGER (INS RESISTANCE) MEGGER (INS RESISTANCE) HIGH-CURRENT TESTING - ALL PHASES LOW-CURRENT TESTING - ONE PHASE CLEAN CONTACT RESISTANCE TESTING INSPECT ARC CHUTES, CONTACTS CHECK AUXILIARY DEVICES CHECK MECHANISM MAN-HOURS MAN-HOURS Savings exceed 30% during a typical scheduled outage. In a case study involving 390 low voltage circuit breakers, 52.8% of the circuit breakers were candidates for a reduced scope of maintenance (Operational Maintenance).

10 FUTURE: MAINTENANCE REQUIREMENTS End-User Needs Fewer Outages Possible Lower Capital & Maintenance Budgets Higher reliability required Unknowns of the current state of the electrical system My current budget is limited Let me know that I must do maintenance and when. 10 Let me know that I must investigate a potential problem now.

11 FUTURE: CONTINUOUS MONITORING Continuous monitoring of critical failure modes, while performing this monitoring in a cost effective manner What to monitor? (IEEE Gold Book) 11 Parameter IEEE Standard Failure Contributing Causes App E, Table XVIII, (Ins & Bare Bus Gear) IEEE Failure Causes Humidity 23.1% Dust Sensors 14.9% Temperature 9.0% Relay Outputs 7.2% Motion 4.9% Water 3.6% Smoke 3.4% Total 66.1% Gold Book data from 1970 s on old electrical equipment.

12 IEEE Failure Data (e.g. Switchgear Bus) Switchgear Bus Failure Contributing Causes (%) From IEEE Std Ins. Bare Pro-Rated Monitoring Options Appendix E - Table XVIII Bus Bus Total to 100% Expected Application 5/15kv 480volt Thermocycling 6.6% 6.6% 3.4% Temperature 3.4% Mechanical Structure Failure 3.0% 8.0% 11.0% 5.6% Mechanical Damage From Foreign Source 6.6% 6.6% 3.4% Motion 3.4% Shorting by Tools or Metal Objects 0.0% 15.0% 15.0% 7.7% Shorting by Snakes, Birds, Rodents, etc. 3.0% 3.0% 1.5% Motion 1.5% Malfunction of Protective Relays 10.0% 4.0% 14.0% 7.2% Relay Trouble Contacts 7.2% Improper Setting of Protective Device 0.0% 4.0% 4.0% 2.1% Above Normal Ambient Temperature 3.0% 3.0% 1.5% Temperature 1.5% Exposure to Chemical or Solvents 3.0% 15.0% 18.0% 9.2% Exposure to Moisture 30.0% 15.0% 45.0% 23.1% Humidity 23.1% Exposure to Dust or Other Contaminants 10.0% 19.0% 29.0% 14.9% Special Airborne Sensors 14.9% Exposure to Non-Electrical Fire or Burning 6.6% 6.6% 3.4% Smoke 3.4% Obstruction of Ventilation 0.0% 8.0% 8.0% 4.1% Temperature 4.1% Normal Deterioration from Age 10.0% 4.0% 14.0% 7.2% (Temp is some benefit) Severe Weather Condition 3.0% 4.0% 7.0% 3.6% Humidity/Temperature/Wate 3.6% Testing Error 0.0% 4.0% 4.0% 2.1% Total 94.8% 100.0% 194.8% 100.0% 66.1% Other Relay Outputs; Surges, Sags, High Loads 12 Patent Pending

13 IEEE Failure Data (e.g. Switchgear Bus) Switchgear Bus Failure Contributing Causes (%) From IEEE Std Ins. Bare Pro-Rated Monitoring Options Appendix E - Table XVIII Bus Bus Total to 100% Expected Application 5/15kv 480volt Thermocycling 6.6% 6.6% 3.4% Temperature 3.4% Mechanical Structure Failure 3.0% 8.0% 11.0% 5.6% Mechanical Damage From Foreign Source 6.6% 6.6% 3.4% Motion 3.4% Shorting by Tools or Metal Objects 0.0% 15.0% 15.0% 7.7% Shorting by Snakes, Birds, Rodents, etc. 3.0% 3.0% 1.5% Motion 1.5% Malfunction of Protective Relays 10.0% 4.0% 14.0% 7.2% Relay Trouble Contacts 7.2% Improper Setting of Protective Device 0.0% 4.0% 4.0% 2.1% Above Normal Ambient Temperature 3.0% 3.0% 1.5% Temperature 1.5% Exposure to Chemical or Solvents 3.0% 15.0% 18.0% 9.2% Exposure to Moisture 30.0% 15.0% 45.0% 23.1% Humidity 23.1% Exposure to Dust or Other Contaminants 10.0% 19.0% 29.0% 14.9% Special Airborne Sensors 14.9% Exposure to Non-Electrical Fire or Burning 6.6% 6.6% 3.4% Smoke 3.4% Obstruction of Ventilation 0.0% 8.0% 8.0% 4.1% Temperature 4.1% Normal Deterioration from Age 10.0% 4.0% 14.0% 7.2% (Temp is some benefit) Severe Weather Condition 3.0% 4.0% 7.0% 3.6% Humidity/Temperature/Wate 3.6% Testing Error 0.0% 4.0% 4.0% 2.1% Total 94.8% 100.0% 194.8% 100.0% 66.1% Other Relay Outputs; Surges, Sags, High Loads 13 Moisture & Dust: 38% Patent Pending

14 FUTURE: FAILURE CONTRIBUTING CAUSES IEEE Standard Failure Contributing Causes App E, Table XVIII, (Ins & Bare Bus Gear) Parameter IEEE Failure Causes IEEE Failure Causes Failure Contributing Causes End-User Feedback (April, '08) Humidity 23.1% Humidity (LV), Discharges (MV) Humidity (LV), Discharges (MV) Dust Sensors 14.9% 26.7% 24.9% Temperature 9.0% Dust, Smoke Dust, Smoke Relay Outputs 7.2% 18.3% 16.6% Motion 4.9% Heat, Fire Heat, Fire Water 3.6% 9.0% 12.5% Smoke 3.4% Total Total Total 66.1% 54.0% 54.0% 14 IEEE data was then grouped into sub-sets in three categories: Humidity/Water-Discharges, Dust-Smoke and Heat-Fire and correlated against end-user surveys which were conducted at random IEEE regional meetings

15 FUTURE: FAILURE CONTRIBUTING CAUSES IEEE Standard Failure Contributing Causes App E, Table XVIII, (Ins & Bare Bus Gear) Parameter IEEE Failure Causes IEEE Failure Causes Failure Contributing Causes End-User Feedback (April, '08) Humidity 23.1% Humidity (LV), Discharges (MV) Humidity (LV), Discharges (MV) Dust Sensors 14.9% 26.7% 24.9% Temperature 9.0% Dust, Smoke Dust, Smoke Relay Outputs 7.2% 18.3% 16.6% Motion 4.9% Heat, Fire Heat, Fire Water 3.6% 9.0% 12.5% Smoke 3.4% Total Total Total 66.1% 54.0% 54.0% 15 IEEE data was then grouped into sub-sets in three categories: Humidity/Water-Discharges, Dust-Smoke and Heat-Fire and correlated against end-user surveys which were conducted at random IEEE regional meetings

16 FUTURE: MONITORING REQUIREMENTS Approximately 50% of potential failure contributing causes of electrical distribution equipment can be monitored, trended and alarmed to provide the desired future maintenance mode of operation. Humidity and the presence of water Partial Discharges (MV Equipment) Dust Trending and Smoke Detection Temperature trending of cubicles, bus-duct, critical cable joints and/or bus connections Bus / Cable Connection Point-Temperature sensors Load Current, Heater and Fan Circuit Currents Intrusion or motion 16 Additional Options for rotating apparatus: Vibration of rotating apparatus Exert herm IR sensors

17 FUTURE: MAINTENANCE REQUIREMENTS Internal Copper Bus Internal Void Bus Insulating Sleeve Internal Void Cubicle Barrier MV Partial Discharge Detection in MV Gear (13.8 / 34.5kv+) Partial discharges emit high-frequency radiation and the application of specifically designed sensors, with filtering and data analysis equipment allows for the continuous monitoring of these partial discharges which will lead to eventual equipment failure 17

18 FUTURE: MONITORING REQUIREMENTS Partial discharge detection and temperature sensors, when combined with sensing options such as humidity, floor water, dust, smoke, load/heater/fan currents, cubicle or bus-duct temperatures provides a robust predictive monitoring package for both low voltage and medium voltage equipment. By adding available vibration sensors to the above, this is adapted to rotating equipment. Patented Algorithms, based on historical and designedbased operating conditions, which will alarm when a parameter is considered out of the normal operating range and provide maintenance recommendations. 18

19 FUTURE: SAFETY & SMART GRID FACTORS Safety: Thermographic surveys require direct viewing of energized connections, requiring removal of panels and exposing of energized equipment. With the Arc-Flash protection requirements, difficult to safely implement. One safety solution: infra-red viewing windows Surveys must still be scheduled and therefore do not provide continuous monitoring Solution is remote continuous cubicle temperatures trending with algorithms Smart Grid: Being notified of a potential pending failure, before it occurs, provides us with a smarter grid. 19

20 Characteristics of Air: With increased temperature - air changes from an insulator to a conductor - Flashover becomes self-conducting Ionized Air Ref: W. Rieder, Circuit Breakers: Physical and Engineering Problems, IEEE Spectrum, July

21 PREVENTABLE FAILURE CASE STUDIES 21 Monitor Humidity, PD, Dust & Contamination (Moisture) Life Ext: Vacuum Replacements ANSI Tested Monitor Cubicle and/or Point Temperatures (Overheated finger cluster) Monitor Cubicle Humidity & Heater Current (Heater Failure)

22 PREVENTABLE FAILURE CASE STUDIES 22 Monitor Floor Water (Overhead water & upstream breaker failure Life Ext: ArcFlash Reduction Switch, Arc Res MCC s Monitor Cubicle and/or Point Temperatures (Improper Maintenance) Monitor Cubicle Temperature (Finger Cluster Failure)

23 FUTURE: MONITORING CASE STUDY Case Study: Monitoring of the above parameters would have warned of a pending major equipment failure due to severe weather conditions and the subject equipment could have been de-energized and isolated from the electrical grid. Since the monitored environmental parameters where not available to the remote operator, the equipment was re-energized in an attempt to clear an anticipated minor fault and resulted in the completed melt-down of the medium voltage circuit breaker and the associated enclosure. 23

24 Diagnostic Remote Monitoring Automatic Report Example Red Light = Alarm Yellow Light = Inspect soon Green Light = Good

25 Customized Automatic Reporting Red Light = Alarm Yellow Light = Inspect soon Green Light = Good

26 Temperature Sensor Alarm Level: Text Message Voice Message Text Message: High Temp Cub XX Bus B

27 Alarms - Blogs Global Coverage Iridium Satellites

28 SUMMARY The future of maintenance is here today Economic swings are preventing past maintenance practices Review available IEEE failure contributing causes Combined with recent end-user surveyed data Identify parameters to be continuous monitored, trended and alarmed Application of new technologies (PD, temperature, algorithms) IT-independent or integrated into a facility monitoring and alarming Smart-grid systems that can self-predict a pending failure and also provide for ongoing maintenance recommendations Technological solutions exist today to support this future maintenance mode. Tell me when I need to do maintenance & what maintenance to do. Tell me that I have a problem now and what I should do about it. 28

29 Questions? Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE Cell #

Risk Mitigation of Aging Electrical Infrastructure

Risk Mitigation of Aging Electrical Infrastructure Risk Mitigation of Aging Electrical Infrastructure 2014 WWOA Annual Conference 10:55am Thursday October 9 th, 2014 Presented by and Authored by Jeff M. Miller, PE, ENV SP About the Presenter Jeff M. Miller,

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-0 Tab Schedule Page of 0 DISTRIBUTION OPERATIONS AND MAINTENANCE PREDICTIVE MAINTENANCE Predictive maintenance expenditures fund work that is required to test and audit distribution system assets.

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

Safety Meeting Topic #37 NFPA 70E What is it?

Safety Meeting Topic #37 NFPA 70E What is it? Safety Meeting Topic #37 NFPA 70E What is it? The National Fire Protection Association (NFPA) 70E is the standard for Electrical Safety Requirements for Employee Workplaces and is a supplement to the NFPA70

More information

Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk

Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk Unrestricted Siemens Industry, Inc. 2015 All rights reserved. usa.siemens.com/arc-flash Everyone is concerned about the risk of Arc

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

Case Study. A Geothermal Energy Generation Facility Embraces Infrared. Polymer Window Inspections. Overview: iriss.com

Case Study. A Geothermal Energy Generation Facility Embraces Infrared. Polymer Window Inspections. Overview: iriss.com A Geothermal Energy Generation Facility Embraces Infrared Polymer Window Inspections By Dominique Capili, Spectrum Scientific Corporation (An IRISS Distributor) Overview: A prominent geothermal energy

More information

Technical News. Solutions to prevent overheating of critical switchgear. Specialists in electrical and automation products, systems and solutions

Technical News. Solutions to prevent overheating of critical switchgear. Specialists in electrical and automation products, systems and solutions Issue #77 - Spring 2017 Technical News Specialists in electrical and automation products, systems and solutions Solutions to prevent overheating of critical switchgear Written By George Matta Product Marketing

More information

AT10.1 Series Microprocessor-Controlled Float Battery Charger (single phase input)

AT10.1 Series Microprocessor-Controlled Float Battery Charger (single phase input) STANDARD SAMPLE SPECIFICATION AT10.1 Series Microprocessor-Controlled Float Battery Charger (single phase input) A battery charger shall be furnished in accordance with the following specification: 1.0

More information

White Paper. Reducing Arc Flash Risks with Electrical Maintenance. Safety Devices. Abstract: iriss.com

White Paper. Reducing Arc Flash Risks with Electrical Maintenance. Safety Devices. Abstract: iriss.com Reducing Arc Flash Risks with Electrical Maintenance By Martin Robinson, CMRP Level III Thermographer President, IRISS Inc. Abstract: Electrical accidents, such as arc flashes, happen daily; however, there

More information

ULD-40. Ultrasonic Leakage Detection, Accoustic emission & Corona detection

ULD-40. Ultrasonic Leakage Detection, Accoustic emission & Corona detection ULD-40 Ultrasonic Leakage Detection, Accoustic emission & Corona detection Common events leading to Metalclad and Breaker Failures Moisture Dust Rodents Animals Poor conductivity do to high resistance

More information

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB.  Paul Lee 17 TH APRIL Switch Board Monitoring Protecting Switchboard Courtesy of ABB. www.fengshengelectric.com.sg Paul Lee Agenda 1. Introduction 2. IEC 61439 3. Why Switchboard Monitoring 4. Switchboard Monitoring

More information

Case Study. Custom Solutions for High Arc Flash Incident Energy and. Interlocked Electrical Enclosures. Overview: iriss.com

Case Study. Custom Solutions for High Arc Flash Incident Energy and. Interlocked Electrical Enclosures. Overview: iriss.com Custom Solutions for High Arc Flash Incident Energy and Interlocked Electrical Enclosures By Mark Bowling, Level II Thermographer, IRISS Inc. & Rick Miner, Level III Thermographer, Thermal Techniques Overview:

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

CONTINUOUS MONITORING IS ON THE RISE:

CONTINUOUS MONITORING IS ON THE RISE: CONTINUOUS MONITORING IS ON THE RISE: CAN YOU ADAPT? BY WILLIAM HIGINBOTHAM, EA Technology LLC Electrical testing companies have traditionally built their businesses by periodically running tests on electrical

More information

Enhancing Current Maintenance Practices 04. Managing the Risk 06. Constant Monitoring of Electrical Enclosures 08

Enhancing Current Maintenance Practices 04. Managing the Risk 06. Constant Monitoring of Electrical Enclosures 08 2 Table of Contents Enhancing Current Maintenance Practices 04 Managing the Risk 06 Constant Monitoring of Electrical Enclosures 08 Delta T Alert A Simple Device with Staggering Results 10 An Easy Way

More information

A Powerful Case for Infrared Windows

A Powerful Case for Infrared Windows ROI A Powerful Case for Infrared Windows By Martin Robinson, CMRP Level III Thermographer CEO, IRISS, Inc. Overview: A regional Facility had been tasked by their insurance carrier to perform regular preventive

More information

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In?

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Electrical Distribution How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not only

More information

Continuous, real-time detection, alarming and analysis of partial discharge events

Continuous, real-time detection, alarming and analysis of partial discharge events DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation

More information

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE Switchgear is a general term used for any devices that breaks and makes the electrical circuit and covers right from a typical piano switch used

More information

Engineering Design & Testing Corp./EDT Engineers, P.C.

Engineering Design & Testing Corp./EDT Engineers, P.C. ENGINEER: ELECTRICAL ALBERT M. ROSE, P.E. Engineering Design & Testing Corp. Post Office Box 940520 Maitland, Florida 32794 Telephone: (407) 865-9900 amrose@edtengineers.com EDUCATION: 1981 Bachelor of

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers on September 6, 2011. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Utility with

More information

Machinery Room Electrical Best Practices

Machinery Room Electrical Best Practices Machinery Room Electrical Best Practices Brad Heeres Angus-Young Associates February 8, 2007 Understand and comply with applicable codes and standards The National Electrical Code requirements for a safe

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Reliable solutions for electrified railway systems

Reliable solutions for electrified railway systems Reliable solutions for electrified railway systems 1 2 3 Insulation Enhancement System Insulation Enhancement System 1. Raychem MVLC: (Medium Voltage Line Cover) Provides insulation for catenary, droppers

More information

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

Introduction Consultant shall incorporate the material in the DSS into the project specifications. DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

Electrical Safety Compliance: NFPA 70E

Electrical Safety Compliance: NFPA 70E Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat

More information

BGH Series Hot Surface Ignition Control

BGH Series Hot Surface Ignition Control Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor

More information

SONOCHEK The ultrasonic testing device

SONOCHEK The ultrasonic testing device SONOCHEK The ultrasonic testing device Listen to the asset, it s got stories to tell! Imagine... When water is boiling in your teapot the steam will make sound as soon as the pressure exceeds a certain

More information

WARNING Important Safety Information

WARNING Important Safety Information 1 Specifications Premier Series Non-Programmable Thermostats MODEL 3000 MODEL 3200 1 2 3 4 Specifications Installation Testing Your New Thermostat Programming User Settings WARNING Important Safety Information

More information

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

IEEE Transformer Committee PC Distribution Transformer Monitoring - User IEEE Transformer Committee PC57.167 Distribution Transformer Monitoring - User Mark Scarborough Electrical Engineering Consultant DuPont January 9, 2019 Transformer Types in DuPont Control power Dry-type

More information

NFPA 70B and the Importance of Electrical Predictive Maintenance

NFPA 70B and the Importance of Electrical Predictive Maintenance NFPA 70B and the Importance of Electrical Predictive Maintenance PRESENTED BY Bhanu Srilla Director of Product Marke0ng Grace Engineered Products, Inc. Learning Objectives 1. Review NFPA 70B Maintenance

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

TABLE OF CONTENTS Flow Detect 1000 Specifications 3 Description 4 Principle of Operation 4 Detection Through Walls 4 Sensing Beam Shape 4 Installation

TABLE OF CONTENTS Flow Detect 1000 Specifications 3 Description 4 Principle of Operation 4 Detection Through Walls 4 Sensing Beam Shape 4 Installation DETECT 1000 DOPPLER DETECTION INSTALLATION AND OPERATING INSTRUCTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT TABLE OF CONTENTS Flow Detect 1000 Specifications 3 Description 4 Principle of Operation

More information

IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows

IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows Abstract There exists a dangerous misconception regarding the Arc Rating of IR viewing windows or viewing panes.

More information

Standards for MV switchgear rated for arc flash protection

Standards for MV switchgear rated for arc flash protection Standards for MV switchgear rated for arc flash protection by Bryan Johnson, ABB Switchgear standards historically considered the electrical capability of switchgear with little regard to the effects of

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Supplement Manual Title: 4180, 4181 Technical Guide Supplement Issue: 3 Part Number: Web-Only Issue Date: 4/18 Print Date: March 2013 Page Count: 4 Revision/Date: This supplement contains information

More information

Predictive Maintenance Training

Predictive Maintenance Training Predictive Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This predictive maintenance

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage Summary of Event: The Golden Eagle Refinery (Refinery) experienced a partial electrical outage December 10, 2010 at 10:12 hrs when a transformer at Switching Station #7 failed. A CWS Level 1 report was

More information

WARNING Important Safety Information

WARNING Important Safety Information 1 Specifications Premier Series Non-Programmable Thermostats MODEL 3000 MODEL 3200 1 2 3 4 5 Specifications Installation Testing Your New Thermostat Programming User Settings Temperature Adjustment WARNING

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date:

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date: Energy Report EDR-5391 Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49 Qualification Testing of Nuclear High Voltage Splice (NHVS) Enclosures: Report Number: Date: EDR-5391

More information

Advantage Services Capabilities

Advantage Services Capabilities Advantage Capabilities Achieve optimal results for the life of your facility. www.usa.siemens.com/service Building Automation Ensures automation systems and controls are performing at optimal levels, maintaining

More information

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation Implementing an Energized Electrical Work Program SESHA Hill Country Chapter May 22, 2009 Brett Jay Davis, PE Zephyr Environmental Corporation bdavis@zephyrenv.com, 512 879-6628 Presentation Outline 1.

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

Emerson s Pervasive Sensing strategies enable plants to realize full potential of Industrial IoT

Emerson s Pervasive Sensing strategies enable plants to realize full potential of Industrial IoT October 25, 2016 Media contact: Grace Capwell O 1 (512) 834-7214 M 1 (512) 840-8209 Grace.Capwell@Emerson.com Emerson s Pervasive Sensing strategies enable plants to realize full potential of Industrial

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Maintenance Best Practices & Intervals for Substation Equipment. Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc.

Maintenance Best Practices & Intervals for Substation Equipment. Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc. Maintenance Best Practices & Intervals for Substation Equipment Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc. Background - 40 Years in the Industry Education NWTC (Northeast

More information

ELECTRICAL POWER SYSTEMS

ELECTRICAL POWER SYSTEMS Scope The various Codes applicable to the University's electrical power system are mainly based upon a model of a single utility service, connected to a single premise. The University s electrical system,

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014 Contents 1. INTRODUCTION... 3 1.1. Design Criteria and Specification...

More information

Dual Column Dehydrating Breather Manual

Dual Column Dehydrating Breather Manual Dual Column Dehydrating Breather Manual DCB-MANUAL 1.6 Read and understand this manual prior to operating or servicing the products. SPX Transformer Solutions, Inc., Service & Components Division U.S.

More information

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

NECA. Standard for Electrical Safety in the Workplace

NECA. Standard for Electrical Safety in the Workplace 4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace

More information

Infrared Portable Space Heater

Infrared Portable Space Heater Infrared Portable Space Heater 1500 Watts with Two Heat Settings Automatic Thermostat Tip-Over Switch Room Temperature LED Display Precision Temperature Control Easy Push-Button Controls Remote Control

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima page 1 Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima No-idle auxiliary battery operated air con PICCOLO SPLITTER Model PS3000 MY2012

More information

Arc Flash Protection Training - NFPA 70e Electrical Safety

Arc Flash Protection Training - NFPA 70e Electrical Safety Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq

More information

Guide to Transmission Equipment Maintenance

Guide to Transmission Equipment Maintenance Guide to Transmission Equipment Maintenance March 2018 Revision History Issue Date Update 1 September 2013 First Issue 2 March 2016 Updated in response to SEM-15-071 Decision Paper Outturn Availability.

More information

NFPA 70E Electrical Safety in the Workplace

NFPA 70E Electrical Safety in the Workplace NFPA 70E Electrical Safety in the Workplace Objectives What NFPA 70E covers Understand Arc Flash, Incident Energy, & Flash Protection Boundary Standards, Enforcement, & Safe Practices Arc Flash Hazard

More information

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities. i-con Switchgear Condition HV Switchgear Integrated Substation Condition ISCM Answers for Infrastructure & Cities. The challenge: Reliable energy supply is the key to success for every enterprise in a

More information

STEPHEN W. COLLINGS, MSEE, PE, Post Office Box CFEI, CVFI, CESCP Franklin, TN Telephone: (615)

STEPHEN W. COLLINGS, MSEE, PE, Post Office Box CFEI, CVFI, CESCP Franklin, TN Telephone: (615) ENGINEER: ELECTRICAL Engineering Design & Testing Corp. STEPHEN W. COLLINGS, MSEE, PE, Post Office Box 682425 CFEI, CVFI, CESCP Franklin, TN 37068-2425 Telephone: (615) 915-5255 scollings@edtengineers.com

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf Training presentation for: 2015 Florida AHCA Conference NFPA 110 Updates for 2016 David Stymiest, CHFM, CHSP, FASHE, (PE in LA MS MA) DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2015, Smith Seckman

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK ISO/IEC 17065:2012 to provide product conformity certification Presley Way Crownhill Milton Keynes MK8 0ES Contact: Tracie Hunter Tel: +44 (0)1908 267300 Fax: +44 (0)1908 267255 E-Mail: mail@basec.org.uk

More information

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death.

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death. Please Read: Safety Precautions DC AC In order to ensure that this product is used safely, be sure that you read and understand the following precautions fully and use the product only as directed. Be

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100 Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training

More information

Early Warning Fire Detection Engineering

Early Warning Fire Detection Engineering Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful

More information

2008 MS Electrical Engineering Vanderbilt University, Nashville, Tennessee

2008 MS Electrical Engineering Vanderbilt University, Nashville, Tennessee ENGINEER: ELECTRICAL STEPHEN W. COLLINGS, MSEE, PE, CFEI Post Office Box 682425 Franklin, TN 37068-2425 Telephone: (615) 915-5255 scollings@edtengineers.com EDUCATION: 2008 MS Electrical Engineering Vanderbilt

More information

WARNING Important Safety Information

WARNING Important Safety Information Builder Series Non-Programmable Thermostats MODEL 1000 MODEL 0 1 2 3 4 Single Stage Heat / Cool Conventional and Heat Pump Multi-Stage 2 Heat / 1 Cool Conventional and Heat Pump Before Installing, Programming

More information

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions NFPA 70E Electrical Safety in the Workplace KTR Associates Engineering Solutions Joseph Deane, PE Goal for Today Better understanding of NFPA 70E Raise the awareness of Electrical Hazards Why the sudden

More information

PROTECTING AGAINST ARC FLASH HAZARDS

PROTECTING AGAINST ARC FLASH HAZARDS PROTECTING AGAINST ARC FLASH HAZARDS Presented by: Andrew J. Fitzpatrick, P.E. Electricity Simply stated electricity is the flow of electrons Electricity is governed by laws: Ohms Law : V=IR Kirchoff s

More information

DANGERS AND HAZARDS OF ENTERING LIVE SUBSTATIONS AND ENCLOSURES Barry Gass Actom Protection and Control

DANGERS AND HAZARDS OF ENTERING LIVE SUBSTATIONS AND ENCLOSURES Barry Gass Actom Protection and Control DANGERS AND HAZARDS OF ENTERING LIVE SUBSTATIONS AND ENCLOSURES Barry Gass Actom Protection and Control INTRODUCTION There are many dangers and hazards which have to be taken into account when entering

More information

US Navy Leading the Way in Switchboard Protection

US Navy Leading the Way in Switchboard Protection US Navy Leading the Way in Switchboard Protection Rick Kurek Naval Sea Systems Command (NAVSEA) 2341 Jefferson Davis Highway Arlington, VA 22202 Ph: 202-781-1274 rick.kurek@navy.mil Abstract According

More information

Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows

Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows Tim Rohrer, VP of Sales & Marketing Martin Robinson, President and IRISS, Inc. 4914 Lena Road, Suite 105 Bradenton, FL

More information

Infrared Inspection Reference Letters Commercial & Residential

Infrared Inspection Reference Letters Commercial & Residential Infrared Inspection Reference Letters Commercial & Residential Cascade Thermal Imaging, Inc. P.O. Box 2131 Redmond, WA 98073-2131 425-861-3887 www.cascadethermal.com ~ Infrared Inspection The Non-Invasive

More information

NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS

NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS January, 2013 Infrared Inspection Report NLR Electric Murray Hydro Plant Company Contact James Bray Project: 09170113 2605 CHARTER OAK DRIVE,

More information

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides

More information

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut Electrical Safety Through Design Mersen EP formerly Ferraz Shawmut Agenda Who is Mersen? Selective Coordination Code Requirements Coordination Made Easy Mitigating Arc Flash Energy on Transformer Secondary

More information

FALCON SERIES 12 METAL CLAD

FALCON SERIES 12 METAL CLAD We engineer, we assure. FALCON SERIES 12 METAL CLAD Until 11kV - 31,5 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel Saudi Cable Company REF: EMCF-EN-16-03 2 www.elimsan.com FALCON

More information

KSD-35 DR11 KUE-35 DVN11

KSD-35 DR11 KUE-35 DVN11 FLOOR-STANDING TYPE AIR CONDITIONER Owner s Manual Floor-Standing Type KSD-35 DR11 KUE-35 DVN11 IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit.

More information

STRATEGIES FOR RELIABLE ARC FLASH DETECTION IN LOW- VOLTAGE SWITCHGEAR

STRATEGIES FOR RELIABLE ARC FLASH DETECTION IN LOW- VOLTAGE SWITCHGEAR STRATEGIES FOR RELIABLE ARC FLASH DETECTION IN LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC-2018-14 Robert J. Burns, P.E. Member, IEEE Eaton Corporation 221 Heywood Rd. Arden, NC 28704

More information