BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING

Size: px
Start display at page:

Download "BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING"

Transcription

1 GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014

2 Contents 1. INTRODUCTION Design Criteria and Specification Scope of the Services Scheme Report PROJECT SUMMARY Project Description ELECTRICAL SYSTEMS MV Network Switchgear and Cabling Transformers Main Low Voltage Panel Emergency Power Stand-by Generator Change-over Panel Un-interrupted Power Supply LV Distribution Boards/Floor DBs Lighting Small Power Solar System Building Earthing Bonding and Lightning Protection Power Factor Correction and Harmonic Filter RECOMMENDATIONS Imbuba House/75 Fox Energy Efficiency considerations

3 1. INTRODUCTION Imbuba House is located on 75 Fox Street, Johannesburg, Gauteng (see Locality Map): Figure 1 - Locality Map The project brief, as issued by Gauteng Funding Agency (GFA), was to conduct an initial assessment of the building electrical infrastructural condition and to provide recommendations regarding the repairs and renovations of the buildings electrical infrastructure of Imbuba House/75Fox Street Design Criteria and Specification This project will be implemented in compliance with all the requirements of the National Building Regulations and SANS Scope of the Services Scheme Report This report deals with the condition of existing electrical services and recommendations on electrical services to be implemented based on the existing systems and proposed architectural changes to the building. Remedial work to be carried on the services and equipment affected. It also deals with proposed new works as per the new layouts from the Architects. 3

4 2. PROJECT SUMMARY 2.1. Project Description The building is currently occupied on all the floors. The electrical installation is still intact, and it s in a good state except for the plant room where there are signs pointing out that there was theft copper earthing cables which now puts the entire electrical installation under danger because it unknown on where exactly this took place; However it was seen that a replacement of copper with anti-theft earthing cable took place. The due diligence involved inspecting the following: MV Network Transformers Main LV Panels Emergency Power and UPS Low Voltage DBs/Floor DBS Lighting and Small power Solar system installed on the roof. Building bonding and Lightning protection Power Factor Correction 4

5 3. ELECTRICAL SYSTEMS 3.1. MV Network Switchgear and Cabling The switchgear and its cabling are in the basement in the transformer room. The switchgears are intact but quiet old. Visually they are well maintained in a good condition. The transformer room is well ventilated and clean. Figure 2 11KV Switchgear Figure 3 11KV Switchgear Figure 4 11KV Metering Cubicle Figure 5 MV Network 5

6 Figure 6 MV Network We recommend that the MV Network (Switchgears and Metering Unit) be replaced with modern equipment because after so many years (above 25years) of existence, the protection ability of the switchgears cannot be relied up on in next coming years Transformers There are four 1000KVA transformers in the basement transformer room. All of the transformers are intact and visually they are well maintained in a good condition. The transformer room is well ventilated and clean. Figure 7 11\0.4KV Transformer 1 - Figure 8 11\0.4KV Transformer 2 - Operational Operational 6

7 Figure 9 Transformer 3&4 Operational Figure 10 Cooling Fans Figure 11 Transformer Feeder Panel (TRF 3&4) We recommend that the transformers undergo maintenance tests; otherwise they are in a good condition Main Low Voltage Panel The Main low voltage panel is in the basement in the LT room. The room was neat and clean. The distribution boards for the main LV panel and its components are very old, however they are intact, well maintained and are in a good working condition. 7

8 Figure 12 Main LT Room and Panels Figure 13 Main Supply Transformer 1 Figure 14 Main Supply Transformer 2 We recommend that the Main LT equipment be upgraded to modern equipment Emergency Power Stand-by Generator The building has 2 Generator rooms in the basement, Generator room 1 has 2 of 750kVA generator sets and Generator room 2 has 1 of 1000kVA generator set. All of these generator sets are in a good working condition and do not need replacement or upgrade. 8

9 Figure 15 Two Generator Sets (750kVA) in Generator Room1 Figure 16 Generator Set (100kVA) in Generator Room2 Figure 17 Generator-A Log Book Figure 18 Generator-B Log Book Change-over Panel The generator change-over panels are well maintained, in a good condition and they are working. 9

10 Figure 19 C/O Panel Generator-A Figure 20 C/O Panel Generator-B Figure 21 Generator Controller A Figure 22 Generator Controller-B Figure 23 C/O Panel and Generator DB (100kVA Gen-Set) We recommend that the Generator and Change-Over panels be tested and commissioned Un-interrupted Power Supply The UPS System is in the UPS room, it is intact, the condition of the system is good and compliant except for the clumsy cables and earthing cables which are not labelled. 10

11 Figure 24 UPS Units 1&2 (300kVA) Figure 25 UPS Units 1&2 (630kVA) Figure 26 UPS Return 1&2 (630kVA) Figure 27 UPS Outgoing Supplies to Various DB s Figure 28 UPS Battery Store/Room Figure 29 UPS Room Cable Reticulation (Clumsy) 11

12 Figure 30 UPS Room Earth Cables (no labels) We recommend that all the cables be contained together, labeled for compliance and the UPS be tested and commissioned LV Distribution Boards/Floor DBs The DBs on most floors are in good working condition; however there are few things to be sorted such as; Containment of wires in the DBs Upgrade the some of the DBs and Panels components to modern technology Remove/clean the DB spaces Label all the cables Figure 31 DB-E14 in the Lifts control room Figure 32 Lift DB 12

13 Figure 33 Installed Floor DB-XEL14 Figure 34 Installed Bus-bar riser Figure 35 Typical Floor DBs Figure 36 Bus-bar riser (old fuser switch) We recommend that the above mentioned issues be sorted 3.5. Lighting Small Power Most of the building floors have under floor plug points with normal and emergency power. The condition of the plugs is good. The building lighting is good in areas such as the basements, plant rooms, etc, however in the floors there are issues with the lighting and below they are stated; Light fittings are old and some are not working Insufficient light levels in the office areas due the old lights, results to lux levels not meeting minimum office requirements Very Bad connection/ wiring for the lights( connection non-compliant) On fire escapes, it s dark, emergency lights (bulkheads) to be upgraded. 13

14 Figure 37 Dark office space with some Lights not working Figure 38 Office space (insufficient light levels) Figure 39 Bad and non-compliant connection Figure 40 Office space (insufficient light levels) Figure 41 Parameter lighting 3302/E&E/H/001 14

15 We recommend that the old light fittings be replaced with new energy efficient lights to achieve minimum requirements lux levels and parameter lighting be sorted out Solar System 20 solar panels were installed on the roof. Total power calculated is about 2.2kw. It could not be ascertained what the system supports since there is no drawing or information on site. The system consists of panels and inverter but no batteries. We recommend that information be made available and the system be maintained in line with energy efficiency. Figure 42 Installed solar panels (east) Figure 43 Installed solar panels (west) 15

16 Figure 44 Solar PV Array Controller (West) Figure 45 Solar PV Array Controller (East) 3.7. Building Earthing Bonding and Lightning Protection It was seen that the building bonding and lightning protection is not intact and compliant, which in turn pose danger to the building and people in it when there is lightning. Figure 46 Building Earth Figure 47 Clumsy Earth Cables 16

17 Figure 48 Loose Lightning rod and conductor Figure 49 Lightning rod with no conductor Figure 50 Lightning rod wit h no conductor Figure 51 Lightning Conductor with Intact We recommend that the building bonding and lightning protection should undergo repairs to achieve compliance Power Factor Correction and Harmonic Filter The building has Power Factor Correction Equipment both for normal power and emergency power and Harmonic Filter Equipment in the LT Room. The PFC equipment and Harmonic are intact and in a good working condition. We recommend that these equipments be tested and commissioned, otherwise they seem good. 17

18 Figure 52 PFC Equipment (normal power) Figure 53 PFC Equipment (emergency power) Figure 54 PFC Equipment (normal power) Figure 55 Harmonic Filter We recommend that these equipments be tested and commissioned, otherwise they seem good. 18

19 4. RECOMMENDATIONS The remedial work required to meet the minimum national standard and reinstate the building s electrical system and infrastructure is recommended above on each equipment and a high level budgetary cost for the remedial work is presented below Imbuba House/75 Fox All the electrical works to be designed and re-done in accordance to SANS and SANS Below is a brief summary of the remedial work to be done. 1. Install 4 new 11KV Switchgears and Ring Main Unit 2. Main Low Voltage Board and all its associated equipment be upgraded 3. It is recommended that further examination and testing of transformers is conducted 4. Generator, Change-Over panels and UPS Systems be tested and commissioned 5. Repairing of existing floor DBs 6. Rewire the building (small power and lighting) according to current building and floor layouts 7. Building Bonding and Lighting Protection be repaired 8. We recommend that the PFC and Harmonic Filter equipments be tested and commissioned 4.2. Energy Efficiency considerations The following initiatives will be implemented. 1. Occupancy sensors in storerooms, kitchens, offices and open plan areas. 2. Introducing daylight saving in public areas and offices. 3. Installation of a BMS to control and monitor Air conditioning and lighting. 4. Installation of smart meters on all floors and this will be linked to the BMS. 5. Installation of geyser control systems where water heating is installed. 6. Use of T5 Lamps and LEDs. 7. Use of DALI controlled lights for controlling light fittings. 8. Maintaining the solar system installed and use it on energy lighting 19

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR LIBRARY HOTEL OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: Library

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT VERTICAL TRANSPORT FOR ABSA BUILDING OCTOBER 2014 Report for Gauteng Department of Infrastructure Development Vertical Transport

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. #

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. # ELECTRICAL ELECTRIC SERVICE EVALUATIONS / BOILER REPLACEMENTS Clarkstown Central School District June 2015 CSArch Arch Proj. # 151-1501.00 151 Table of Contents SECTION 1 Executive Summary... 1 SECTION

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction

More information

SECTION 1.02 DETAILED SCOPE OF WORK

SECTION 1.02 DETAILED SCOPE OF WORK SECTION 1.02 DETAILED SCOPE OF WORK 1.02.1 General 1.02.1.1 Introduction... 3 1.02.1.2 General description of the works... 4 1.02.1.3 Design criteria... 5 1.02.2 Public Health Services 1.02.2.1 Mains cold

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 169-171 Tetulzhora Union, Hemayetpur, Savar Savar Dhaka 24 May 2014 The Alliance for Worker Safety Page 1/20 24 May 2014 Introduction to the Report

More information

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE)

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE) Palak Parikh, Lalit Lopez GE Digital Energy Acknowledgment: Scottish and Southern Energy(SSE) Outline Why LV network monitoring? Challenges and Opportunities LV Monitoring Node Architecture Advance LV

More information

Technical Report 2: Electrical Systems Criteria and Existing Conditions

Technical Report 2: Electrical Systems Criteria and Existing Conditions Technical Report 2: Electrical Systems Criteria and Existing Conditions Princeton Theological Seminary Library Princeton, NJ Stephanie Deckard Lighting Electrical Faculty Advisor Dr. Kevin Houser 10/12/2012

More information

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth Corbin Building Technical Assignment 2 Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth 10/26/2011 Technical Report II 1 Executive Summary The following report is an overview

More information

Telecity. Table of Contents. Page. Section 3.2

Telecity. Table of Contents. Page. Section 3.2 1 3.2 System Descriptions Table of Contents 3.2 SYSTEM DESCRIPTIONS... 3 3.2.1 General Notes... 3 3.3 Power Distribution MV... 4 3.3.1 Incoming Supply... 4 3.3.2 MV Switch room... 4 3.4 Power Distribution

More information

Power Plants with Webel Solar Modules

Power Plants with Webel Solar Modules Power Plants with Webel Solar Modules Power Plants with Webel Solar Modules 17W Nautilus Water Pump imported fm Australia X 2 80Wp Solar Panel X 1 Charge controller X 1 Galvanised Steel Pole (3 meters)

More information

ELECTRICAL AND COMMUNICATION INSTALLATION DESIGN IN AN OFFICE COMPLEX

ELECTRICAL AND COMMUNICATION INSTALLATION DESIGN IN AN OFFICE COMPLEX ELECTRICAL AND COMMUNICATION INSTALLATION DESIGN IN AN OFFICE COMPLEX PROJECT INDEX: PRJ017 BY F17/1765/2006 MUTUMA WALTER MURIMI SUPERVISOR: PROF. E. MWANGI EXAMINER: DR. J. MBUTHIA DATE: 27 th MAY 2011

More information

COMPANY PROFILE Electrical & Instrumentation Contractor

COMPANY PROFILE Electrical & Instrumentation Contractor COMPANY PROFILE Electrical & Instrumentation Contractor Engineering I Supply I Installation I Testing I Commissioning Maintenance I Fabrication I Ship Repairing ABOUT US The year was 2003, where there

More information

Monitoring of Electrical Equipment Failure Indicators and Alarming

Monitoring of Electrical Equipment Failure Indicators and Alarming Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE gabrieljpaoletti@eaton.com

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Kunia, K.B.Bazar, Joy Bangla Road, Barabari, Gazipur Gazipur Dhaka 12 May 2014 The Alliance for Worker Safety Page 1/14 Factory 12 May 2014 Introduction

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2 Lindsay Frederick Lighting + Electrical Ron Dodson Faculty Advisor Native American Cultural Center Arizona Technical Report 2 Native American Cultural Center Technical Report 2 p. 2 Executive Summary The

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory SFB 2 Adamjee EPZ, Siddergonj, Narayangonj, Siddhirgonj Dhaka 22 Feb 2017 The Alliance for Worker Safety Page 1/18 Factory 22 Feb 2017 Introduction to

More information

DOMESTIC INSTALLATIONS COMMERCIAL INSTALLATIONS LIGHTING SOLAR PV REPAIRS LANDLORDS SWITCH ON TO SWH ELECTRICAL SOLUTIONS

DOMESTIC INSTALLATIONS COMMERCIAL INSTALLATIONS LIGHTING SOLAR PV REPAIRS LANDLORDS SWITCH ON TO SWH ELECTRICAL SOLUTIONS DOMESTIC INSTALLATIONS COMMERCIAL INSTALLATIONS LIGHTING SOLAR PV REPAIRS LANDLORDS SWITCH ON TO SWH ELECTRICAL SOLUTIONS SWH ELECTRICAL SOLUTIONS Domestic INSTALLATIONS Expert and reliable electrical

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Plot 33-35, Dhaka (EPZ), Savar Savar Dhaka Bangladesh 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 06 Jul 2014 Introduction to

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/18

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Plot No. 60&61, Sector-3, KEPZ, North Patenga, Chittagong Chittagong 11 Feb 2015 The Alliance for Bangladesh Worker Safety Page 1/17 11 Feb 2015 Introduction

More information

2009 ELECTRICAL CODE REQUIREMENTS

2009 ELECTRICAL CODE REQUIREMENTS 2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements

More information

GeyserWise MAX. Thermostat instruction manual. SANS 181 compliant. All in one hot water management

GeyserWise MAX. Thermostat instruction manual. SANS 181 compliant. All in one hot water management GeyserWise MAX Thermostat instruction manual SANS 181 compliant All in one hot water management Before operating and installation, carefully read all instructions. Do not discard this manual. Index Warranty

More information

GeyserWise MAX. Instruction manual. All in one hot water management

GeyserWise MAX. Instruction manual. All in one hot water management GeyserWise MAX All in one hot water management Before operating and installation, carefully read all instructions. Do not discard this manual. DISPLAY The display is the feedback mechanism to the user

More information

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT CITY ELECTRIC TRANSPORT 2 MODULAR TRACTION SUBSTATION Modular traction substation produced by PrJSC Pluton is an integrated solution for reliable power supply of electric transport catenary. Modular traction

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38 BR 54/ NATIONAL OCCUPATIONAL CERTIFICATION ACT 2004 2004 :38 The National Training Board, with the approval of the Minister responsible for the National Training Board, in exercise of the powers conferred

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

Project Briefing Document. Section 3 Electrical Services design guide and specifications

Project Briefing Document. Section 3 Electrical Services design guide and specifications ESTATES SUPPORT SERVICE Project Briefing Document Section 3 Electrical Services design guide and specifications Issue 1.1 June 2014 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor...

More information

Section 8 Electrical.

Section 8 Electrical. Design Guidelines Section 8 Electrical. www.canterbury.ac.nz/learningresources Standards in the Design Guidelines Suite Design Standard Guidelines Index: 01 General 02 Architecture 03 Audio Visual 04 Civil

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

How to light a small storage space rabdesign.ca 1

How to light a small storage space rabdesign.ca 1 How to light a small storage space rabdesign.ca 1 SUMMARY Storage lighting for smaller spaces in the home or workplace is often ignored, forgotten or given minimal attention. Builders and homeowners typically

More information

Comprehensive Inspection Agency (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE

Comprehensive Inspection Agency (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE Phone: 570-573-28251 Fax: 570-385-3010 Page 1 of 7 Phone: 570-573-2825 CIA Fax: 570-385-3010 RESIDENTIAL FEES BUILDING / MISCELLANEOUS Plan Review $ 0 New Construction,

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Photovoltaic (Solar) Array Installation Guide

Photovoltaic (Solar) Array Installation Guide Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL t Thank you for choosing Aqua inverter heat pump. This manual provides you necessary information for optimal use and maintenance, please read it carefully and keep it for subsequent

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL Thank you for choosing inverter heat pump. This manual provides you necessary information for optimal use and maintenance, please read it carefully and keep it for subsequent

More information

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets 2 X 1996 Wartsila 18V26 5.125mw Each 50hz HFO Generator Sets The responsibility for any and all additional charges is the purchasers. 2 x WARTSILA 5 MW Power plant 2 Units of Wartsila 18V26 @ 5 MW each,

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required. Executive Summary The current electrical system is functional but requires some understanding in order to avoid overloading circuits. Certain outlets can be used for space heaters while others cannot and

More information

A student investigated how much energy from the Sun was incident on the Earth s surface at her location.

A student investigated how much energy from the Sun was incident on the Earth s surface at her location. A student investigated how much energy from the Sun was incident on the Earth s surface at her location. She put an insulated pan of water in direct sunlight and measured the time it took for the temperature

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

Home Energy Management (Device Control): Immersion Heater Controller Use Cases, Application Note

Home Energy Management (Device Control): Immersion Heater Controller Use Cases, Application Note Home Energy Management (Device Control): Immersion Heater Controller Use Cases, Application te Revision History Version 1.0, v. 2017 Initial release V1.0, v. 2017 Introduction Overview The SolarEdge Home

More information

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH

ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH ELECTRICAL SAFETY INSPECTION REPORT ANLIMA TEXTILE LTD, DHAKA, BANGLADESH January 14, 2014 Anlima Textile Ltd. PAGE 1 SUMMARY The Anlima compound located in Dhaka, Bangladesh was surveyed for Electrical

More information

PART 1. Executive Summary. The Frederick College of Cardiology

PART 1. Executive Summary. The Frederick College of Cardiology Executive Summary This report will summarize the electrical system of the Frederick College of Cardiology. First, an estimation of the possible building electrical loads will be performed. The actual loads

More information

ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES

ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES ABOUT US Quality products, exceptional service and quick delivery of a diverse product line are the foundation of our company. By leveraging the portfolio

More information

Installation and Maintenance Manual for Dimako NERM Panels REV 4. NERM Reference Manual NERM Panels 1 of 7

Installation and Maintenance Manual for Dimako NERM Panels REV 4. NERM Reference Manual NERM Panels 1 of 7 NERM Panels 1 of 7 Installation and Maintenance Manual for Dimako NERM Panels REV 4 Dimako Transformers Release VER 4 F:\Master Docs\Manuals\NERM.docx Page 1 of 7 NERM Panels 2 of 7 Table Of Contents Page

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Address: Assessor: 1Plot # 4 (half) 8, 12 (half)-16, DEPZ (Old), Dhaka EPZ, Ganakbari, Ashulia, Savar Ashulia, Savar Dhaka Bangladesh Uttaron 25

More information

Work involving High Voltage (HV) Systems and Maintenance of Plant.

Work involving High Voltage (HV) Systems and Maintenance of Plant. University of Strathclyde Estates Services Electrical Procedure No E001 Procedure No: ELE 001 Procedure Title: Work involving High Voltage (HV) Systems and Maintenance of Plant. Visual check and operational

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Address: Plot 61-64 & 70-73, Sector 02, KEPZ Karnafully, North Patenga, Chittagong Chittagong Chittagong Bangladesh The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: AJ Super Garments Ltd (Woven) Aj Garden, Goshbagh Zirabo Zirabo, Savar Savar Dhaka Bangladesh 23 Mar 2014 The Alliance for Bangladesh Worker Safety

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory C-13, South Badda, Gulshan-1, Badda, Dhaka Dhaka Dhaka 22 May 2014 The Alliance for Worker Safety Page 1/21 22 May 2014 Introduction to the Report The

More information

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson M.A.E./B.A.E. Integrated Degree Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson Renzo Museum of American Art Executive Summary This report provides an analysis of the electrical

More information

Ground Fault Protection Improvement Study

Ground Fault Protection Improvement Study Ground Fault Protection Improvement Study Greg Ball DNV KEMA Solar ABCs Stakeholder Meeting July 11, 2013 San Francisco, CA Study Authors 2 Bill Brooks Brooks Engineering Andy Rosenthal New Mexico State

More information

ENTSO-E response to GB compliance understanding

ENTSO-E response to GB compliance understanding ENTSO-E response to GB compliance External Project Team / WG CNC 29 May 2017 1. Contents 1. Contents... 2 2. Response to GB compliance... 3 GB of LVFRT...3...3 No need for changes in current practice...3...3

More information

PROFILE. industrial services rental trading

PROFILE. industrial services rental trading PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field

More information

Comprehensive Inspection. (CIA) RESDENTAL & COMMERCIAL

Comprehensive Inspection. (CIA) RESDENTAL & COMMERCIAL Comprehensive Inspection. (CIA) Agency RESDENTAL & COMMERCIAL FEE SCHEDULE Phone: 570-573-2825 I Fax: 570-385-3010 Page 1 of 7 RESIDENTIAL FEES BUILDING'I NI!'S,OELLANEO.. Plan Review $0 New. Construction,

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection Bryan Johnson ABB South Africa Shaping the world

More information

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

Introduction Consultant shall incorporate the material in the DSS into the project specifications. DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding

More information

COSINE DEVELOPMENTS Reg. No. IT 1637/97

COSINE DEVELOPMENTS Reg. No. IT 1637/97 COSINE DEVELOPMENTS Reg. No. IT 1637/97 LEADERS IN LIGHTING TECHNOLOGY P O Box 10177 Tel. : +27 (31) 5793090/4 24 Ashfield Avenue Marine Parade Int. Fax. : +27 (31) 5793021 Springfield Park 4056 Local

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction

More information

TIME KNITWEAR (PVT) LTD.

TIME KNITWEAR (PVT) LTD. ELECTRICAL SAFETY INSPECTION REPORT TIME KNITWEAR (PVT) LTD. Baribogh, Enayetnagar, Fatullah, Narayangonj-1400, Bangladesh Factory List: 1. Time Knitwear (Pvt) Ltd. Inspected by: Dawa Report Generated

More information

Annexure - D. Station Interface Matrix Power Supply, S&T, AFC,Lift & Escallators,Rolling stock and Track work. Station Civil and E & M Contractor

Annexure - D. Station Interface Matrix Power Supply, S&T, AFC,Lift & Escallators,Rolling stock and Track work. Station Civil and E & M Contractor Item No A Item Description Power Supply contractor Connection between Secondary of Auxillary Transfomer and the LowVoltage Switch Board Station Interface Matrix Power Supply, S&T, AFC,Lift & Escallators,Rolling

More information

KTDC HOTELS & RESORTS LIMITED MASCOT SQUARE, TRIVANDRUM - 33

KTDC HOTELS & RESORTS LIMITED MASCOT SQUARE, TRIVANDRUM - 33 EMPANELMENT OF ARCHITECTS / LANDSCAPING CONSULTANT / INTERIOR DESIGNER / EVENT MANAGERS / TOURISM CONSULTANT SCOPE OF WORKS 1. Introduction It is essential to have plan for development of Tourism Destinations

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

NEW ENERGY IN THE BATTERY INFRASTRUCTURE

NEW ENERGY IN THE BATTERY INFRASTRUCTURE NEW ENERGY IN THE BATTERY INFRASTRUCTURE Maurice H. Johnson Business Development Engineer UL LLC Northbrook, IL Paper Overview Over the past several years, there has been a significant effort to address

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global

More information

ABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear

ABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear ABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear Technical session Title of presentation Speaker name Speaker title Company name Location Martin Kropf Head of Local Product

More information

TONY ESPOSITO LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY

TONY ESPOSITO LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY 1 1A. POWER DISTRIBUTION SYSTEMS a. EXECUTIVE SUMMARY b. SUMMARY DESCRIPTION

More information

ESTIMATE SET-UP PACKAGE BID SCHEDULE ENTRY AND MAINTENANCE

ESTIMATE SET-UP PACKAGE BID SCHEDULE ENTRY AND MAINTENANCE BIDDING INFORMATION BID DATE: PROJECT NAME: ADDRESS: ESTIMATE SET-UP PACKAGE BID SCHEDULE ENTRY AND MAINTENANCE ESTIMATE NO.: CITY: STATE: ZIP: PRIME: PROJECT MANAGER: PROJECT TYPE: SUB: $ SIZE: BID TIME:

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

ILLUMINATOR EM. CENTRAL LIGHTING INVERTER 1000 VA/W through 2800 VA/W 98% Efficiency!

ILLUMINATOR EM. CENTRAL LIGHTING INVERTER 1000 VA/W through 2800 VA/W 98% Efficiency! ILLUMINATOR EM CENTRAL LIGHTING INVERTER 1000 VA/W through 2800 VA/W 98% Efficiency! THE ILLUMINATOR SERIES EM The Illuminator Series EM is a fast transfer Emergency Lighting Inverter utilizing Myers Power

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: 33/1, Darail, Shataish Tongi, Gazipur Tongi, Gazipur Dhaka Emkay Enterprises 26 Feb 2014 The Alliance for Worker Safety Page 1/12 26 Feb

More information

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE Checklist items A - L may receive a result of Pass or Fail A. Railing is present for interior and exterior steps with more

More information

Teesside University upgrades its emergency lighting system with Hochiki Europe

Teesside University upgrades its emergency lighting system with Hochiki Europe Teesside University upgrades its emergency lighting system with Hochiki Europe Published on 11 Jun 2012 The luminaires are also equipped with battery back-up, making sure they will function in every situ

More information

Consumer unit replacement in domestic and similar premises

Consumer unit replacement in domestic and similar premises Consumer unit replacement in domestic and similar premises 6 Issue 2 The Electrical Safety Council is indebted to the following organisations for their contribution and/or support to the development of

More information

NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies

NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies Version:- 2.0 Date of Issue:- May 2015 Page 1 of 17 NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies 1. Purpose The purpose of this

More information

ELECTRICAL POWER SYSTEMS

ELECTRICAL POWER SYSTEMS Scope The various Codes applicable to the University's electrical power system are mainly based upon a model of a single utility service, connected to a single premise. The University s electrical system,

More information

Substation Signage. Document Number: 1-11-FR-12

Substation Signage. Document Number: 1-11-FR-12 Substation Signage Document Number: 1-11-FR-12 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-12 Substation Signage Asset Class Strategy Intellectual

More information

Photovoltaic Specialists: Job Task Analysis

Photovoltaic Specialists: Job Task Analysis Photovoltaic Specialists: Job Task Analysis Photovoltaic Design, Photovoltaic Installer, Photovoltaic Commissioning & Maintenance September 2017 V. 09.17 www.nabcep.org Raising Standards. Promoting Confidence.

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Assessor: Thakurbari TEAC, Masumabad, Bhulta, Rupganj, Narayangonj Rupgonj Uttaron 18 Nov 2013 The Alliance for Bangladesh Worker Safety Page 1/12

More information

Guided Learning Hours (GLH) 8 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 10

Guided Learning Hours (GLH) 8 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 10 Qualification: Date Completed: 02 Feb 17 Unit: FIA AO Level 3 Fire Detection and Alarm Advanced Installer Development Group: FD&A Development Group Guided Learning Hours (GLH) 8 Invigilated Assessment

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY)

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY) V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY) ACN 114 572 084 "Driving Sustainability through Teamwork" e: pcthomas@teamcatalyst.com.au m: 0417 405 478 CALCULATING COOL USER GUIDE V4 15JUNE2016 Page

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

ELECTRICAL DESIGN BRIEF

ELECTRICAL DESIGN BRIEF 4211 Yonge Street Suite 500 Toronto Ontario M2P 2A9 416 487 8151 f 416 487 9104 smithandandersen.com ELECTRICAL DESIGN BRIEF FOR 128 HAZLETON AVENUE RESIDENTIAL CONDOMINIUM BUILDING TORONTO, ONTARIO OUR

More information

Riverdale NetZero Project Summary of Costs and Expected Performance

Riverdale NetZero Project Summary of Costs and Expected Performance Riverdale NetZero Project Summary of Costs and Expected Performance Natural Resources Canada Sustainable Buildings and Communities Edmonton, Ottawa 2009 January 07 Gordon Howell, P.Eng. 2008-2009 Progressively

More information