1 GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT VERTICAL TRANSPORT FOR ABSA BUILDING OCTOBER 2014

2 Report for Gauteng Department of Infrastructure Development Vertical Transport Services Preliminary Report: ABSA Building October 2014 Table of Contents 1. INTRODUCTION Design Criteria and Specifications Scope of the Services Scheme Report PROJECT SUMMARY Project Description INSPECTION Albertina Sisulu Road Entrance Lifts Cars Motor Room Motor Room Ventilation and Fire Fraser Street Entrance Lifts Cars Motor Room Motor Room Ventilation and Fire RECOMMENDATIONS Lifts i P a g e

3 1. INTRODUCTION ABSA Building is a multistory building located at the corner of Fraser Street and Albertina Sisulu Road in Johannesburg, Gauteng (see Locality Map). The development comprises three buildings linked and accessible to each other on certain floors. Figure 1 - Locality Map The project brief, as issued by GFA, was to conduct an initial assessment of the building vertical transport infrastructure and systems and to provide recommendations regarding the repairs and renovations of the building. 1.1 Design Criteria and Specifications This project will be implemented in compliance with all the requirements of the National Building Regulations and SANS (All Parts). SANS 1543: Escalators and passenger conveyors SANS 1545: Safety rules for the construction and installation of lifts (All Parts). SANS 10360: The maintenance and repair of electric and hydraulic powered lifts, escalators and passenger conveyors 1.2 Scope of the Services Scheme Report This report deals with the vertical transport services to be implemented based on the existing systems and proposed architectural changes to the building. This report is based on a visual inspection only of the applicable service installation.

4 2. PROJECT SUMMARY 2.1 Project Description ABSA Building is a multistory building located at the corner of Fraser Street and Albertina Sisulu Road in Johannesburg, Gauteng. The development comprises three buildings linked and accessible to each other on certain floors. The building is currently mostly in use, with some of the higher levels not currently occupied. 3. INSPECTION The lift installation serving ABSA building comprises the following: Core 1: Albertina Sisulu Road Entrance: 1 off 10 Stop Basement -2 to 8 th Floor Passenger Lift 2 off 8 Stop Ground to 8 th Floor Passenger Lift These lifts were originally installed in 1949 and were modernised in The 10 stop lift was not operational at the time of our inspection. Core 2: Fraser Street Entrance: 1 off 9 Stop Basement -2 to 5 th Floor (including Mezzanine) Passenger Lift 2 off 7 Stop Ground to 5 th Floor (including Mezzanine) Passenger Lift The lifts were installed in 1986 and appear to be original (i.e. not modernised or upgraded). The lifts were not operational at the time of our inspection. 3.1 Albertina Sisulu Road Entrance Lifts Cars The lift cars appeared to be in fair condition though showing their age. The car ride was bumpy indicating misaligned / worn guide rails.

5 Figure 2 Car Interior: Albertina Sisulu Entrance Figure 3 Car Exterior: Albertina Sisulu Entrance The lift car doors in one lift were badly scoured from misalignment. Figure 4 Scoured Car Doors Figure 5 Car Control Panel The call stations appeared to be operational on the lower floors but were not operational on 8 th floor.

6 Figure 7 8 th Floor Indicator Figure 6 8 th Floor Call Station Motor Room The lift motor room is messy and dirty and does not appear to be well maintained. A spares cupboard house spare parts and old parts kept for reuse but also appeared to be disorganized. The work desk was littered with old drawings and schematics not filed away or stored neatly. Figure 8 Lift Motor Room Desk Figure 9 Spares Cupboard

7 The lift registration certificates appeared to all be present in the motor room. The Otis service records were in the room and indicate fairly regular servicing. According to the records a service was carried out on 16 October Figure 11 Lift Service Book Figure 10 Lift Registration Certificate The control panels were all unlocked and open. The panels were dirty and dusty with messy and unsafe wiring. The panels did not appear to comply with the regulations. Figure 12 Control Panel Figure 13 Unsafe Control Panel Wiring

8 3.1.3 Motor Room Ventilation and Fire The motor room is mechanically ventilated though the fan was not operational. Figure 14 Lift Motor Room Split Units - Indoor Figure 15 Lift Motor Room Fire Extinguisher The single motor room extinguisher had not been serviced since Fraser Street Entrance Lifts Cars The lifts at the Fraser Street entrance were not operational at the time of our inspection. The cars were not accessible as a result.

9 Figure 16 Fraser Street Lifts Fire Control Figure 17 Car Exterior: Fraser Street Entrance Motor Room The lift motor is located at roof level. The door was broken and offered minimal protection to the room. The lift motor room is messy and dirty and does not appear to be well maintained. Spares and removed parts were littered across the floor making access dangerous. Figure 18 Lift Motor Room Figure 19 Removed Motor on Floor

10 Machine drums and cables were unprotected. Figure 20 Lift B Drive Figure 21 Lift A Drive without Motor The lift registration certificates appeared to all be present in the motor room. Figure 22 Lift A Registration Certificate Figure 23 Service Records Service records for 2014 could not be located. The last service on record was 12 December 2014.

11 The control panels were all unlocked and open. The panels appeared to mostly original. The panels were dirty and dusty with messy and unsafe wiring. The panels did not appear to comply with the regulations. Figure 24 Lift A Control Panel Figure 25 Lift B Control Panel The lift A motor had been removed and was lying on the motor room floor. Figure 26 Lift A Drive Without Motor Figure 27 Lift A Motor

12 3.2.3 Motor Room Ventilation and Fire The motor room is mechanically ventilated though the fan was not operational. Figure 28 Lift Motor Room Fan Figure 29 Lift Motor Room Fire Extinguisher A single extinguisher was installed but the service date could not be ascertained.

13 4 RECOMMENDATIONS The remedial work required to the vertical transport systems is recommended and a high level budgetary cost for the remedial work is presented. 4.1 Lifts Remove and scrap existing lifts (in excess of 30 years old). Replace all lifts with new. Upgrade lift motor rooms and infrastructure.

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR LIBRARY HOTEL OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: Library

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69

More information

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014 Contents 1. INTRODUCTION... 3 1.1. Design Criteria and Specification...

More information

Branch Capital Projects Feasibility Study

Branch Capital Projects Feasibility Study Mission Branch Library Chinatown Him Mark Lai Branch Ocean View Branch Library 1 Outline: Feasibility Study Guiding Principles Potential Concepts Preliminary Budget Findings Recommendations Next Steps

More information

Common Area Cleaning Guide

Common Area Cleaning Guide 1 P a g e Common Area Cleaning Guide It is the responsibility of every occupant, owner, tenant, contractor, employee & visitor and ALL users of this facility to ensure they take all reasonably practical

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. #

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. # ELECTRICAL ELECTRIC SERVICE EVALUATIONS / BOILER REPLACEMENTS Clarkstown Central School District June 2015 CSArch Arch Proj. # 151-1501.00 151 Table of Contents SECTION 1 Executive Summary... 1 SECTION

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

LE ROI DANIELS SCHOOL CALGARY, ALBERTA

LE ROI DANIELS SCHOOL CALGARY, ALBERTA LE ROI DANIELS SCHOOL CALGARY, ALBERTA School Facility Evaluation Project Calgary School Board, District 19 Prepared For Alberta Infrastructure March 2000 Prepared By Bernbaum Architect Ltd. Rae Mclean

More information

Fire Risk Assessment Borough High Street

Fire Risk Assessment Borough High Street Fire Risk Assessment Borough High Street Page 1 of 8 / BHS Fire Risk Assessment / 07/2017 / V4.0 / ES Premises Details Occupier Premises Address Premises Description FIRE RISK ASSESSMENT Report of Audit

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

Proposed Student Accommodation Development

Proposed Student Accommodation Development Statement of Response to the Notice of Pre- Application Consultation Opinion Former "Matts of Cabra" public house and lands to the rear, Fassaugh Avenue, Cabra, Dublin 7 Proposed Student Accommodation

More information

the Two WeekEND Organizing Tweak Checklist get your whole home back in order!

the Two WeekEND Organizing Tweak Checklist get your whole home back in order! the Two WeekEND Organizing Tweak Checklist get your whole home back in order! Weekend Day 1: Command Center / Paper Clutter Go through built-up paperwork and mail and sort (trash, act, file, or store)

More information

PUBLIC WORKSHOP. Re-use of the Josiah Smith Tavern and Old Library. December 14, 2010

PUBLIC WORKSHOP. Re-use of the Josiah Smith Tavern and Old Library. December 14, 2010 PUBLIC WORKSHOP Re-use of the Josiah Smith Tavern and Old Library Professional Team: The Cecil Group, Inc Peter W. Smith, Inc. Howard/Stein-Hudson Associates December 14, 2010 AGENDA Introductions The

More information

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012) Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085

More information

Contents HEALTH AND SAFETY MANAGEMENT SYSTEMS FIRE PREVENTION AND EVACUATION PROCEDURE. 1. Introduction. 2. Warning in the event of fire

Contents HEALTH AND SAFETY MANAGEMENT SYSTEMS FIRE PREVENTION AND EVACUATION PROCEDURE. 1. Introduction. 2. Warning in the event of fire Contents 1. Introduction 2. Warning in the event of fire 3. Action in the event of fire 4. Assembly point 5. Key escape routes 6. Firefighting equipment 7. Roles and responsibilities 8. Arrangements for

More information

1

1 1 2 3 4 north N. Square S. Square Main Street Salisbury Ave Melville St. S Imperial Lane Byng Ave George St. South Hood St. River St. Warnock St. St. Andrews St. Bruce St. Fraser St Gilholm St Cant Ave

More information

DMTF: Specific Building Recommendations

DMTF: Specific Building Recommendations DMTF: Specific Building Recommendations Asset Name Project Title Total Cost BLOCKER BUILDING 22,503,303 Capital Renewal 7,640,013 DOMESTIC WATER HEATER REPLACEMENT 16,374 EXTERIOR DOOR REPLACEMENT 133,623

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

DATE OF BIRTH : 23 October 1971 YEARS EXPERIENCE : 21

DATE OF BIRTH : 23 October 1971 YEARS EXPERIENCE : 21 POSITION NAME OF FIRM SPECIALISATION : Director : UrbanEQ Consulting Engineers (Pty) Ltd : Transportation Engineer DATE OF BIRTH : 23 October 1971 NATIONALITY : South African YEARS EXPERIENCE : 21 Andrew

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PIMKIE APPARELS LTD. PLOT # 328, BLOCK # F, TONGI, INDUSTRAL AREA OTHER FACTORIES: NONE May 25, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/25/2014 by Hughes Associates,

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

Dudley Branch Library Renovations

Dudley Branch Library Renovations Dudley Branch Library Renovations Martin J. Walsh, Mayor Project #7084 City of Boston Public Facilities Department Utile, Inc. Architecture and Planning February 7, 2017 Meeting Agenda Introductions Project

More information

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

Selection of air conditioning systems

Selection of air conditioning systems Selection of air conditioning systems Prof. M. Ramgopal Department of Mechanical Engineering IIT Kharagpur Objectives 1. List the criteria used in the selection of air conditioning systems 2. List typical

More information

GENERAL POLICY NO.1 - HEALTH & SAFETY: RISK ASSESSMENT/MANAGEMENT

GENERAL POLICY NO.1 - HEALTH & SAFETY: RISK ASSESSMENT/MANAGEMENT GENERAL POLICY NO.1 - HEALTH & SAFETY: RISK ASSESSMENT/MANAGEMENT 1. GENERAL NOV. 1996 AUG. 1997 JAN. 2003 SEP. 2004 JULY 2006 ONGOING The Manager was appointed as the competent person to advise the Council.

More information

ITALIAN STANDARD UNI 11565

ITALIAN STANDARD UNI 11565 ITALIAN STANDARD UNI 11565 Consequences on Designing, Testing and Maintaining of Fire Protection Systems in Italy Dr. Markus Mueller WAGNER Bayern GmbH railsystems@wagner.de Agenda 1. Introduction About

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT ABA FASHIONS LTD. SENA KALYAN COMMERCIAL COMPLEX (2ND FLOOR), PLOT # 9, BLOCK # F, TONGI, GAZIPUR March 16, 2014 Accord - Bangladesh RMG Fire Safety Inspection ABA Fashions

More information

Call to Artists Public Art for Los Angeles Metro Stations

Call to Artists Public Art for Los Angeles Metro Stations Conceptual Design for Call to Artists Public Art for Los Angeles Metro Stations Artesia Transit Center Union Station/Patsaouras Transit Plaza Los Angeles County Metropolitan Transportation Authority February

More information

BeltLine Corridor Environmental Study

BeltLine Corridor Environmental Study BeltLine Corridor Environmental Study Joint TAC and SAC Meeting December 8, 2008 What We Will Discuss Today Outreach and Agency Coordination Scoping Results Existing Conditions Historical and Archeological

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information

SECTION : FIRE PROTECTION SYSTEMS

SECTION : FIRE PROTECTION SYSTEMS SECTION 21 00 10: FIRE PROTECTION SYSTEMS 1. GENERAL A. This section applies to the design and performance information for fire protection and suppression systems. B. All fire protection materials and

More information

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16

2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16 1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated

More information

General Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin

General Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin The purpose of a monthly self-inspection program is to identify unsafe conditions in the work environment and unsafe employee actions. Management can then correct these safety hazards, reducing the potential

More information

Croxley Rail Link - Cassiobridge Station, Ascot Road Reference Number :

Croxley Rail Link - Cassiobridge Station, Ascot Road Reference Number : PART A Report of: Development Management Section Head Date of Committee 3 rd April 2014 Site address: Croxley Rail Link - Cassiobridge Station, Ascot Road Reference Number : 14/00097/DISCON Description

More information

KTDC HOTELS & RESORTS LIMITED MASCOT SQUARE, TRIVANDRUM - 33

KTDC HOTELS & RESORTS LIMITED MASCOT SQUARE, TRIVANDRUM - 33 EMPANELMENT OF ARCHITECTS / LANDSCAPING CONSULTANT / INTERIOR DESIGNER / EVENT MANAGERS / TOURISM CONSULTANT SCOPE OF WORKS 1. Introduction It is essential to have plan for development of Tourism Destinations

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

COUNCIL HEALTH, SAFETY AND WELLBEING COMMITTEE. Projects Update

COUNCIL HEALTH, SAFETY AND WELLBEING COMMITTEE. Projects Update COUNCIL HEALTH, SAFETY AND WELLBEING COMMITTEE September 2017 Projects Update Executive Summary: The purpose of this report is to provide the HS & W Committee an update of completed projects undertaken

More information

1071 King Street West Zoning Amendment Application - Preliminary Report

1071 King Street West Zoning Amendment Application - Preliminary Report STAFF REPORT ACTION REQUIRED 1071 King Street West Zoning Amendment Application - Preliminary Report Date: August 9, 2012 To: From: Wards: Reference Number: Toronto and East York Community Council Director,

More information

Fire Safety and Evacuation Plan

Fire Safety and Evacuation Plan AUDIT OF BUILDING RESOURCES The following pages provide a description of the fire safety equipment installed in the building including: Fire Alarm and Detection Systems Central Station (Fire Alarm System

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection

More information

MAY 2016 Elevator QEI & Maintenance Performance Report

MAY 2016 Elevator QEI & Maintenance Performance Report MAY 2016 Elevator QEI & Maintenance Performance Report SOUTH PASSENGER ELEVATORS 4 & 5 JUNEAU SQUARE 809 E WISCONSIN AVENUE MILWAUKEE, WISCONSIN BY: ELEVATOR CONSULTING SERVICES, INC. Equipment Inventory

More information

Design Review of Facility Improvement Projects

Design Review of Facility Improvement Projects Design Review of Facility Improvement Projects Agenda Board Meeting Schedule Scope of Work Summary Overall Building Plans and Scope Summary Update on Areas of Design Development Programming and Space planning

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY)

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY) V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY) ACN 114 572 084 "Driving Sustainability through Teamwork" e: pcthomas@teamcatalyst.com.au m: 0417 405 478 CALCULATING COOL USER GUIDE V4 15JUNE2016 Page

More information

At the end of this study topic, you will be able to discuss the legal requirements of the Fire Safety Manager Scheme, and list the statutory duties

At the end of this study topic, you will be able to discuss the legal requirements of the Fire Safety Manager Scheme, and list the statutory duties Hi everybody, Welcome back again. This topic discusses the Fire Safety Managers Scheme of Work implemented under the Fire Safety Act and the Fire Safety Managers Regulations. This is one topic closest

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PADMA SWEATERS LTD. 1/B DARUS SALAM ROAD, SECTION 1. MIRPUR OTHER FACTORIES: NONE. July 9, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/9/2014 by Hughes Associates,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

Authentic Art Deco apartment complex. Bespoke lifts bring easy access. 30s style + 21st-century action = smoother circulation for all.

Authentic Art Deco apartment complex. Bespoke lifts bring easy access. 30s style + 21st-century action = smoother circulation for all. Authentic Art Deco apartment complex. Bespoke lifts bring easy access. 30s style + 21st-century action = smoother circulation for all. Find out what 3 bespoke passenger lifts did for Gunnersbury Court,

More information

Bangkok Expressway and Metro Public Company Limited Form General Information and Other Significant Information

Bangkok Expressway and Metro Public Company Limited Form General Information and Other Significant Information 6. General Information and Other Significant Information 6.1 General Information (1) General information of the Company Company Issuing Securities : Bangkok Expressway and Metro Public Company Limited

More information

ASME A17.1/CSA B44 Handbook

ASME A17.1/CSA B44 Handbook 2016 Edition ASME A17.1/CSA B44 Handbook ASME A17.1-2016, Safety Code for Elevators and Escalators CSA B44-16, Safety Code for Elevators Kevin L. Brinkman, PE 2016 Edition ASME A17.1/CSA B44 Handbook ASME

More information

Cambridge. West Cambridge site. What is a Shared Facilities Hub? Welcome

Cambridge. West Cambridge site. What is a Shared Facilities Hub? Welcome Cambridge West Cambridge site What is a Shared Facilities Hub? Welcome Thank you for taking the time to attend our public exhibition on proposals for the Shared Facilities This will be a landmark building

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT HAN A HATS & CAPS LTD. ACCORD ID: 12339 DAG NO. CS &SA-115/117, RS-188/181, KHOTION NO. CS-128, SA-274, BAIPAIL, ASHULIA, SAVAR, DHAKA. OTHER FACTORIES: TEXTSTREAM FASHION

More information

HELENA PUBLIC SCHOOLS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT. May 2013

HELENA PUBLIC SCHOOLS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT. May 2013 HELENA PUBLIC SCHOOLS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT May 2013 HPS FRONT STREET LEARNING CENTER CLEANING OUTCOMES ASSESSMENT PURPOSE During the week of May 20th, 2013 BRUCO INC.

More information

Barking Riverside Gateways Housing Zone. Development Opportunity for 3,000 homes & modern commercial space

Barking Riverside Gateways Housing Zone. Development Opportunity for 3,000 homes & modern commercial space Barking Riverside Gateways Housing Zone Development Opportunity for 3,000 homes & modern commercial space Executive Summary Barking Riverside is one of London s largest housing development sites with

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout

Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout I. About the Agency StopWaste helps Alameda County s businesses, residents and schools waste less, recycle more and use

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on

More information

Philip A. Ginsburg, General Manager Toks Ajike, Acting Planning and Capital Program Director

Philip A. Ginsburg, General Manager Toks Ajike, Acting Planning and Capital Program Director Date: March 7, 2018 To: Through: From: Subject: Recreation and Park Commission Capital Committee Philip A. Ginsburg, General Manager Toks Ajike, Acting Planning and Capital Program Director Dan Mauer,

More information

ENVIRONMENTAL IMPACT ASSESSMENT

ENVIRONMENTAL IMPACT ASSESSMENT ENVIRONMENTAL IMPACT ASSESSMENT NOTICE OF APPLICATION FOR AMENDMENT OF AN ENVIRONMENTAL AUTHORISATION FOR THE HAASENDAL DEVELOPMENT ON PORTIONS 1, 11, 26, 30, 34, 58, AND 87 OF FARM HAASENDAL NO. 222,

More information

Planning and Growth Management Committee. Chief Planner and Executive Director, City Planning Division. Pg12013 (File No NNY 34 OZ)

Planning and Growth Management Committee. Chief Planner and Executive Director, City Planning Division. Pg12013 (File No NNY 34 OZ) 865 York Mills Road Official Plan Amendment Application Preliminary Report STAFF REPORT ACTION REQUIRED Date: February 28, 2012 To: From: Wards: Reference Number: Planning and Growth Management Committee

More information

Project Scenario Summary Report http://fusion.deltacollege.edu/code/planning/project/editfpu/scenariorpt.asp?id=2629&ce... Page 1 of 1 11/7/2017 California Community Colleges Project Scenario Summary 2019

More information

The meeting house is of low-key design typical of the inter-war period. It has an attractive appearance with a spacious interior and good amenities.

The meeting house is of low-key design typical of the inter-war period. It has an attractive appearance with a spacious interior and good amenities. Friends Meeting House, Preston 189 St George s Road, Preston, PR1 6NQ National Grid Reference: SD 54314 30558 Statement of Significance The meeting house is of low-key design typical of the inter-war period.

More information

Hudson Group North America LLC

Hudson Group North America LLC Hudson Group North America LLC Mr. John Palmieri, Director Boston Redevelopment Authority One City Hall Square Boston, MA 02201 August 30, 2010 RE: 120 Kingston Street Development, Notice of Project Change

More information

MASTER PLAN DIAGRAMS DISTRICT CAMPUS OVERVIEW

MASTER PLAN DIAGRAMS DISTRICT CAMPUS OVERVIEW DISTRICT CAMPUS OVERVIEW Classrooms, CR Special Education Computer Lab INTERSTATE 5 FW - Faculty Work, FL - Faculty Physical Education / Athletics Support Spaces S - Storage, T - Toilets, U - Utility,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT YOUNG INTERNATIONAL PLOT NO. 32-36, SECTOR 5-CEPZ, CHITTAGONG OTHER FACTORIES: NONE July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by Hughes Associates,

More information

Applications of California Historical Building Code in Fire Safety Upgrades

Applications of California Historical Building Code in Fire Safety Upgrades Applications of California Historical Building Code in Fire Safety Upgrades California Preservation Foundation 37 th Annual Conference May 3-6, 2012 Presented by: Cheryl L. Domnitch, P.E. Hughes Associates,

More information

Visitor & Intruder Security Policy

Visitor & Intruder Security Policy Visitor & Intruder Security Policy Reviewed: October 2019 GENERAL The Management responsibility for school security is shared between the local authority, Spie, the governing body and the Headteacher.

More information

Building Consent Application Compliance Schedule Information

Building Consent Application Compliance Schedule Information Private Bag 9023 Whangarei 0148 New Zealand T: 09 430 4200 0800 WDC INFO 0800 932 463 F: 09 438 7632 W: www.wdc.govt.nz E: mailroom@wdc.govt.nz Building Consent Application Compliance Schedule Information

More information

Today We re Talking About:

Today We re Talking About: Today We re Talking About: Lynnwood/Millican 160 AVENUE N Station to Shepard 144 AVENUE N Station NORTH POINTE (At Grade Stations) TUSCANY 96 AVENUE N BEDDINGTON SADDLETOWNE Lynnwood/Millican at Ogden

More information

FLORA-TEC GROUNDS MAINTENANCE CAPABILITY STATEMENT

FLORA-TEC GROUNDS MAINTENANCE CAPABILITY STATEMENT FLORA-TEC GROUNDS MAINTENANCE CAPABILITY STATEMENT 2015 Flora-tec. Head Office, Unit 1, Unwins Farms, Cottenham Road, Histon, Cambridge, CB24 9ESFlora-tec Limited, Registered Office at Head Office, Registration

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

Guide to the Emmet Mercury Boiler Records

Guide to the Emmet Mercury Boiler Records Guide to the Sara Wheeler 2017 Archives Center, National Museum of American History P.O. Box 37012 Suite 1100, MRC 601 Washington, D.C. 20013-7012 archivescenter@si.edu http://americanhistory.si.edu/archives

More information

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIVISION OF ADULT FOSTER CARE LICENSING ADULT FOSTER CARE FACILITIES

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIVISION OF ADULT FOSTER CARE LICENSING ADULT FOSTER CARE FACILITIES DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIVISION OF ADULT FOSTER CARE LICENSING ADULT FOSTER CARE FACILITIES (By authority conferred on the department of social services by section 9 of Act No. 380

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

The Riverview Condominium

The Riverview Condominium The Riverview Condominium Frequently Asked Questions and Answers MARCH 2016 Page # 1 of 5 Q1: What are my voting rights in the condominium association? A1: One vote for each apartment owned. Q2: What restrictions

More information

The Maryland-National Capital Park and Planning Commission Prince George s County Planning Department Development Review Division

The Maryland-National Capital Park and Planning Commission Prince George s County Planning Department Development Review Division The Maryland-National Capital Park and Planning Commission Prince George s County Planning Department Development Review Division 301-952-3530 Note: Staff reports can be accessed at www.mncppc.org/pgco/planning/plan.htm.

More information

c. DTAH Toronto Complete Streets Guidelines

c. DTAH Toronto Complete Streets Guidelines c. DTAH Toronto Complete Streets Guidelines 164 166 C.1 Project Delivery Process 168 C.5 This section provides a summary of the overarching process for delivering street projects in Toronto. The conclusion

More information

OSHA Subpart F Fire Protection and Prevention

OSHA Subpart F Fire Protection and Prevention OSHA Subpart F Fire Protection and Prevention The Employer shall: Develop the fire protection program. Provide fire fighting equipment. Periodically inspect fire fighting equipment. Firefighting Equipment

More information

Old Jail HVAC Replacement Feasibility Report

Old Jail HVAC Replacement Feasibility Report Old Jail HVAC Replacement Feasibility Report Madera, CA Prepared by Kitchell for the County of Madera, California Job No. 6168A3 Executive Summary On October 21, 2016, Kitchell conducted a Feasibility

More information

Bridgedale, Bridgetown Request for Expressions of Interest to Lease and/ or Develop

Bridgedale, Bridgetown Request for Expressions of Interest to Lease and/ or Develop Bridgedale, Bridgetown Request for Expressions of Interest to Lease and/ or Develop 1 Are you interested in leasing Bridgetown s oldest building and/or redeveloping an iconic site on the banks of the Blackwood

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

SECTION HYDRAULIC PASSENGER ELEVATOR

SECTION HYDRAULIC PASSENGER ELEVATOR SECTION 14200 HYDRAULIC PASSENGER ELEVATOR PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 05500 - Metal Fabrications. 2. Division 15 - Mechanical. 3. 16721 - Fire Alarm Detection System 4. Division

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

Renovation Project Presentation Public Meetings

Renovation Project Presentation Public Meetings Renovation Project Presentation Public Meetings SWBR Architects and Tappé Associates made a formal presentation to both the Board and Public in early February of a conceptual design of a proposed renovation

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TUBA GARMENTS LTD. PLOT # 1682, ANANDA NAGAR, MERUL BADDA, BADDA, DHAKA OTHER FACTORIES: NONE July 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/5/2014 by Hughes

More information

City of Farmington. Downtown Plan. Amendment to the 1998 Master Plan Adopted October 11, 2004

City of Farmington. Downtown Plan. Amendment to the 1998 Master Plan Adopted October 11, 2004 City of Farmington Amendment to the 1998 Master Plan Adopted October 11, 2004 Introduction Planning Background 1 Scope and Components of the Plan Amendment 2 Concept Introduction 3 Plan Concepts 3 Conceptual

More information

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position

More information

Riverview West Side Elementary 160 Isabel Avenue East

Riverview West Side Elementary 160 Isabel Avenue East 160 Isabel Avenue East Project Summary: At the center of Hispanic culture in St. Paul is Riverview Elementary - and it s truly the center of the West Side community. Our newly renovated location offers

More information

University of Michigan Guidelines for Emergency Evacuation Maps/Plans

University of Michigan Guidelines for Emergency Evacuation Maps/Plans University of Michigan Guidelines for Emergency Evacuation Maps/Plans Emergency evacuation maps/plans are signs with maps that are posted inside campus buildings that indicate the evacuation routes/exits

More information