Telecity. Table of Contents. Page. Section 3.2

Size: px
Start display at page:

Download "Telecity. Table of Contents. Page. Section 3.2"

Transcription

1 1 3.2 System Descriptions Table of Contents 3.2 SYSTEM DESCRIPTIONS General Notes Power Distribution MV Incoming Supply MV Switch room Power Distribution LV Incoming Supply Main Switchroom UPS System Distribution Boards Cabling Containment GENERAL PURPOSE POWER Sockets/Commando Outlets & Fused Connection Units Equipment Connections Roller Shutter Doors Lift Installation LIGHTING/ESCAPE LIGHTING & EXTERIOR LIGHTING General Emergency Lighting Lighting Control FIRE ALARM Fire Alarm System COMMUNICATIONS & IT Security/Door Access & CCTV Installation Data Cabling Telephone Cabling Disabled Alarm System... 14

2 2 3.9 MECHANICAL SERVICES SMCC Cabling Earthing, Bonding & Lightning Protection System Lightning Protection... 16

3 3 3.2 SYSTEM DESCRIPTIONS General Notes The following text describes the electrical service installation by each electrical system: - Power Distribution MV Power Distribution LV UPS System General Purpose Power Lighting/Lighting Control/Escape Lighting & Exterior Lighting Fire Alarm System Security Communications & IT Mechanical Services Earthing, Bonding & Lightning Protection Disabled Alarm

4 4 3.3 Power Distribution MV Incoming Supply AMS 06 main MV incoming supply is fed from 2 no Liander 10kV A & B supplies fed locally from the AMS 04 site. The A supply feeds customer room A and the B supply feeds customer room B. The equipment is provided to allow for the MV supply to be upgraded to 20kV in the future. The MV cabling is installed as per the MV schematic drawing which can be seen in the as-built section of the manuals MV Switch room The main MV Switchgear has been supplied by Schneider electric and is situated in customer room A, customer room B, Trafo room A, Trafo room B & Trafo room C. The type of switchgear is Schneider PIX type and details of the switchgear are shown in the materials of the manuals. Supplies emanate from customer room A & customer room B to MV switchgear located in Trafo room A, Trafo room B & Trafo room C. Within Trafo room B & Trafo room C there is 1 no Schneider transformer located in each room. The details of the transformer can be seen in the materials section of the manuals. The MV switchgear controls are backed up by 110V DC UPS units within MV customer room A, MV customer room B, Trafo room B and Trafo room C. Each of the transformer are protected by transformer protection relay units. For more details on the 100V DC UPS units and the transformer protection relay units please refer to the materials section of this manual. 3.4 Power Distribution LV Incoming Supply The main incoming LV supply comes from TX-B a n d TX-C a n d f e e d s to MDP-B & MDP-C respectively, located in the MDP 400/230V 50Hz. This service utilizes 1

5 5 no 4000A rated busbar fed from the transformer TX-B to a 4000 Amp Main ACB within MDP-B and 1 no 4000A rated busbar fed from the transformer TX-C to a 4000 Amp Main ACB within MDB-C Main Switchroom The main LV Switchgear has been supplied by Siemens and is situated in rooms MDP-A, MDP-B, MDP-C & MDP-E. The main distribution arrangement, energy per section configuration, is composed of two parts, to know: - MDP-distributor for the data zones (IT load); - MCC distributor for the mechanic and building installations. Supplies emanate from ACB s within the MDP panels to a distribution system via busbar through electrical containment and risers comprising of the following MDP-B TX-B Incomer 4000A GEN-B Incomer 4000A Loadbank Incomer 4000A MCC-B outgoing 1250A Outgoing UPS B1 1000A Outgoing UPS B2 1000A Outgoing UPS B3 1000A Outgoing UPS B4 1000A Incoming UPS B1 1000A Incoming UPS B2 1000A Incoming UPS B3 1000A Incoming UPS B4 1000A Maintenance by-pass 4000A Data Hall 2 A-Side 1250A Data Hall 3 A-Side 1250A MDP-C

6 6 TX-C Incomer 4000A GEN-C Incomer 4000A Loadbank Incomer 4000A MCC-C outgoing 1250A Outgoing UPS C1 1000A Outgoing UPS C2 1000A Outgoing UPS C3 1000A Outgoing UPS C4 1000A Incoming UPS C1 1000A Incoming UPS C2 1000A Incoming UPS C3 1000A Incoming UPS C4 1000A Maintenance by-pass 4000A Data Hall 2 B-Side 1250A Data Hall 3 B-Side 1250A MCC-C, MCC-B, MCC-C & MCC-D The MCC panels have a critical section and a non-critical section within each of the panels. The Non-critical section is made up of non-critical equipment such as lifts & non-critical mechanical equipment. The critical equipment is made up of Lighting and Power distribution boards and critical mechanical equipment. Supplies emanate from MCCB s within the MCC panels to a distribution system via cabling through electrical containment and risers to their final locations. For additional information regarding the MV Switchgear, LV Switchgear and Transformers, please refer to manufacturer s literature in the materials used section of this manual UPS System The UPS units have been supplied on the project by Eatons. There are 4 no IT UPS units installed per UPS room which power the IT systems in the event of a power failure. There is 1 no mechanical UPS unit installed in each of the UPS rooms which power the critical side of the MCC panels in the event of a power failure.

7 7 For additional information regarding the UPS units please refer to the manufacturer s literature located within the materials used section of this manual.

8 Distribution Boards Endenburg have supplied the LDP panels & SMCC panels distribution panels. There are 14 no LDP panels and 21 no SMCC panels. They are Rittal type and are fitted with Siemens double pole & four pole MCB protective devices for lighting circuits and small power circuits. The socket circuits are fitted complete with RCBO protective devices with 30mAmp protection. Blanking plates for all spare ways and detailed distribution charts are securely fixed, indicating all outgoing and spare ways Cabling All Sub-mains distribution cabling are Draka Hult & Hultflex mbzh 0,6/1kV gy. The UPS cabling is Hultflex XS mbzh 0,6/1kV gy Containment Schneider c a b l e tray & ladder rack have been installed for all electrical sub circuit wiring with separate trays for LV & ELV cabling. The ELV cable trays have been split up into 3 compartments, Data/Fire-Security/BMS. All conduit has been installed using Hostalit pipe with the exception of steel conduit been installed in various locations throughout the plantroom. For further details refer to containment drawings within the As Built drawings section of this manual.

9 9 3.5 GENERAL PURPOSE POWER Sockets/Commando Outlets & Fused Connection Units New general purpose socket outlets have been installed throughout the project and all general services layouts can be found in the relevant drawings contained within the materials used section of this manual. All socket outlets are from the Jung electrical range. Generally they are wired on 20 Amp radial circuits with 30mAmp protection or as detailed on the distribution board schedules. All associated cabling has been carried out in 2.5mm 2 & 4mm 2 Draka hult 0,6/1kV gy cabling contained within galvanized tray and plastic Hostalit conduit Equipment Connections All equipment regardless of whether it is supplied under contract or by others, shall be tested, connected and commissioned Roller Shutter Doors Roller shutter doors have been installed at the Delivery area and Entrance area. Please refer to the Main contractor s literature for the specific details on the shutters Lift Installation There are 2 no lifts located in the building. Please refer to the Main contractor s literature for the specific details on the Lifts.

10 LIGHTING/ESCAPE LIGHTING & EXTERIOR LIGHTING General All lighting on the project is split up on A & B supplies and backed up through the critical side of the MCC panels. Within the office areas, data halls, external Pole lighting and surrounding areas there is LED type luminaires installed. Throughout the remainder of the project all luminaires installed are fluorescent types. All final positions o f l u m i n a i r e s can be found on the relevant drawings contained within the as builts section of this manual and associated information regarding the lighting literature within the materials used section of this manual Emergency Lighting The lighting in all areas is divided 50% from power supply A and 50% from power supply B. The power supplies A and B are connected behind the no-break power supply supplemented by power generator. As a result, it is not necessary to provide separate emergency lighting. Emergency exit signs have be applied in accordance with the BS EN1838 using luminaires with icons. The emergency exit signs have been provided with LED lamps. There have been areas such as the technical rooms & E-tech rooms where emergency luminaires have been installed with 60 minutes runtime. All final positions o f e m e r g e n c y l u m i n a i r e s can be found on the relevant drawings contained within the as builts section of this manual and associated information regarding the emergency lighting literature within the materials used section of this manual.

11 Lighting Control The lighting control system has been supplied by Endenburg and is a KNX system. The switches and KNX equipment is by Jung. The PIR s are by Steinel. All information regarding the lighting control switching can be seen in the lighting control matrix within the As-Built drawings section of the manual. The times for the KNX clock function 1 and 2 are set as follows: - Clock 1: to % to % - Clock 2: to % to % The data hall entry points are provided with 4hr override switches. The lighting control panel is located at the reception desk. 3.7 FIRE ALARM Fire Alarm System A complete addressable fire alarm system is installed throughout the building. The system is by Fire Technology and reference to the components can be found on the fire alarm drawings in the as-builts section of this manual. The system is wired with 1x2x1,5 + 0,8 JH(st)HmbZH Red fire rated cable into the relevant zones contained in accordance with Dutch regulations. There is a Vesda system installed below the ground floor raised floor, in the trafo rooms, in the UPS rooms, in the plantroom and in the Crac corridors. The main fire alarm panel is located behind the main reception beside the reception area and the fire alarm repeater panels are located throughout the project as can be seen on the As-Built drawings. There are I/O units interfacing the fire alarm system with the lifts, fire dampers, BMS panels and security systems. All final positions o f f i r e d e t e c t i o n e q u i p m e n t can be found on the relevant drawings contained within the as builts section of this manual and associated information regarding the fire detection literature within the materials used section of this manual.

12 12 The Pve document and all other relevant fire detection information can also be found within the O&M manuals. Separate Operations & Maintenance manuals have been issued by the specialist contractor. Fire Technology: Fire Detection system

13 COMMUNICATIONS & IT Security/Door Access & CCTV Installation A full Intruder Alarm, Intercom, Clocks, Door Access and CCTV system has been installed throughout the Facility by specialist contractors - Beveco. All final positions and associated information regarding these systems can be found on the relevant drawings & materials section contained within this manual. Separate Operations & Maintenance manuals have been issued by the specialist contractor. Beveco: Intruder Alarm, Intercom, Clocks, Door Access and CCTV Data Cabling The CAT5 cabling has been installed and runs from the XMS cabinets located throughout the building to data outlets, wifi points & Dect points. All XMS cabinets are connected together via Fibre Optic Cabling for the IT Network. All final positions and associated information regarding the XMS system system can be found on the relevant drawings contained within this manual Telephone Cabling Telecity have installed new incoming lines to both the Lifts on the 2 nd floor. Please refer to the Main contractor s literature for the specific details on the shutters.

14 Disabled Alarm System There is 1 no disabled alarm system installed on the project that consists of a power pack insert, alarm signaling insert, single push button insert with pull cord and cancel button insert. The power packs require a 230V power supply. The disabled alarm system has been provided and installed by another party. The disabled alarm system is located in the disabled WC.

15 MECHANICAL SERVICES SMCC Cabling The SMCC cabling can be seen by referring to the SMCC distribution board schedules and the layout drawings which can be seen within the relevant sections of these manuals.

16 Earthing, Bonding & Lightning Protection System A complete earthing and bonding system is provided for the buildings electrical and mechanical installation. All exposed conductive parts and all extraneous conductive parts of the electrical installation are bonded and connected to earth so that in the event of a fault of negligible impedance, disconnection will take place in a manner, and in such time, as to ensure no danger exists. Earth protective conductors interconnect all items of major electrical equipment and incoming services to the main earth bar located in the main corridor. All mechanical and public health installations throughout the Telecity project have been bonded Lightning Protection There has been 2 no lighting spikes installed on the roof next the weather stations. Locations and layouts of the system can be found on the as built drawings contained within the O&M manuals.

GOLDFIELDS PRIMARY SCHOOL. TENDER SPECIFICATION For ELECTRICAL SERVICES MECHANICAL ENGINEER:

GOLDFIELDS PRIMARY SCHOOL. TENDER SPECIFICATION For ELECTRICAL SERVICES MECHANICAL ENGINEER: GOLDFIELDS PRIMARY SCHOOL TENDER SPECIFICATION For ELECTRICAL SERVICES PROJECT MANAGER: School Support Dunedin ARCHITECTURAL DESIGNER: Katipo Design ELECTRICAL ENGINEER: Pedersen Read Dunedin MECHANICAL

More information

SECTION 1.02 DETAILED SCOPE OF WORK

SECTION 1.02 DETAILED SCOPE OF WORK SECTION 1.02 DETAILED SCOPE OF WORK 1.02.1 General 1.02.1.1 Introduction... 3 1.02.1.2 General description of the works... 4 1.02.1.3 Design criteria... 5 1.02.2 Public Health Services 1.02.2.1 Mains cold

More information

The works comprise the complete supply and installation of new Electrical Engineering Services to the site comprising:-

The works comprise the complete supply and installation of new Electrical Engineering Services to the site comprising:- 3.0 ELECTRICAL SPECIFICATION 3.1 SCHEDULE OF WORKS 3.1.1 Introduction The works comprise the supply and installation of new Electrical Services within the refurbishment of an existing warehouse to form

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

IEEE Transformer Committee PC Distribution Transformer Monitoring - User IEEE Transformer Committee PC57.167 Distribution Transformer Monitoring - User Mark Scarborough Electrical Engineering Consultant DuPont January 9, 2019 Transformer Types in DuPont Control power Dry-type

More information

Product Guide Low Voltage Switchboard & Switchgear

Product Guide Low Voltage Switchboard & Switchgear Product Guide 2018 Low Voltage Switchboard & Switchgear General INESING low voltage switchgear is completely designed and engineered by INESING using circuit breakers from a leader manufacturers like ABB,

More information

Brochure. Security Designed, Installed by Experts

Brochure. Security Designed, Installed by Experts Brochure Security Designed, Installed by Experts 02 03 Introduction Working in Partnership with our Customers. At b2b Secure IT our commitment to our customer is simple; we will provide an unrivalled end

More information

Guide to: 17 th Edition Consumer Units

Guide to: 17 th Edition Consumer Units Guide to: 17 th Edition Consumer Units Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.

More information

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING

BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014 Contents 1. INTRODUCTION... 3 1.1. Design Criteria and Specification...

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. (A Wholly Owned Subsidiary of SBI) CIRCLE OFFICE: 4TH FLOOR, SBI LOCAL HEAD OFFICE III/1-PANDIT J N MARG, KHARAVELA NAGAR BHUBANESWAR, ODISHA-751001 Part-II PRICE

More information

soaring high. scoring high. Trading Co. LLC

soaring high. scoring high. Trading Co. LLC soaring high. scoring high. Trading Co. LLC SWITCHING GEARS TO GREATER SUCCESS Skyway tells a tale of electric growth that began in 1992. Coming a long way in its core business of electrical panel boards

More information

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. #

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. # ELECTRICAL ELECTRIC SERVICE EVALUATIONS / BOILER REPLACEMENTS Clarkstown Central School District June 2015 CSArch Arch Proj. # 151-1501.00 151 Table of Contents SECTION 1 Executive Summary... 1 SECTION

More information

EDS SUBSTATION ELECTRICAL SERVICES

EDS SUBSTATION ELECTRICAL SERVICES Document Number: EDS 07-1119 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 07-1119 SUBSTATION ELECTRICAL SERVICES EPN, LPN, SPN This standard specifies the electrical services requirements including

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

DC POWER DISTRIBUTION BOARD

DC POWER DISTRIBUTION BOARD DC POWER DISTRIBUTION BOARD February 2016 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

Newport County Council Bettws High School Electrical Particular Specification and Data Sheets. Contract

Newport County Council Bettws High School Electrical Particular Specification and Data Sheets. Contract Electrical Particular Specification and Data Sheets Contract Electrical Particular Specification and Data Sheets August 2008 4 Pierhead Street, Capital Waterside, Cardiff CF10 4QP Tel +44 (0)29 2047 3727

More information

INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2

INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2 FINANCE, RISK AND BUSINESS PLANNING GROUP Supply Chain Management November 4, 2015 INVITATION TO TENDER ITT NO. PS20151058 KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2 RE: Insert attached Section

More information

Ackrediteringens omfattning / Scope of accreditation Components and installation

Ackrediteringens omfattning / Scope of accreditation Components and installation Standard designation Mini-Couplers for the interconnection of electrical mains supplied equipment in road vehicles Flat non-wirable two-pole plugs 2,5A 250V for class II-equipment Conversion adapters for

More information

Silent Alert Fire Safe System

Silent Alert Fire Safe System Silent Alert Fire Safe System Technical Manual This manual covers the FSTX-2225-EU Fire alarm interface PG3A-2204-EU Pager FSCH-2226-IN Fire Safe Charger or CH3A-2205-IN Alarm clock charger SW3A-2208-EU

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Product Test Centre 15 Progress Road Eastwood Leigh-on-Sea Essex SS9 5JA Contact: Mr S Bailey Tel: +44 (0)1702 425738 E-Mail: stuart.bailey@honeywell.com

More information

3. RCCB (residual current operated circuit-breaker without integral overcurrent protection)

3. RCCB (residual current operated circuit-breaker without integral overcurrent protection) RESIDUAL CURRENT DEVICE (RCD) - Contents 1. Introduction 2. General 3. RCCB (residual current operated circuit-breaker without integral overcurrent 4. RCBO (residual current operated circuit-breaker with

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

DCS-100. intelligent damper control & monitoring system

DCS-100. intelligent damper control & monitoring system DCS-100 intelligent damper control & monitoring system 02 //DCS-100 Introduction The Disys Technologies DCS-100 is a revolutionary new control system designed specifically for the fire/smoke damper controls

More information

ORION Mini-Rep INSTALLATION MANUAL

ORION Mini-Rep INSTALLATION MANUAL ORION Mini-Rep INSTALLATION MANUAL Orion Mini-Rep - INSTALLATION MANUAL - REVISION 1.0-04/007 The Orion Mini-Rep will provide remote control and system display status from multiple locations to an Orion

More information

650-EL-C-E-1995 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian Birth Date : 06/01/1969 Marital Status : Married

650-EL-C-E-1995 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian Birth Date : 06/01/1969 Marital Status : Married 650-EL-C-E-1995 Senior Electrical Engineer Holds a B. Sc. in Electrical Engineering and has about 16 years experience in the field of electrical construction, pre-commissioning and follow up activities

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: DIV. COMPUTER INFO-DATA CENTER-K, 2 METROTECH CENTER, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

LoadCentre KQ Distribution boards

LoadCentre KQ Distribution boards > LoadCentre KQ Distribution boards 4 LoadCentre KQ - single phase A distribution boards - 125A Single phase A distribution boards - 125A Manufactured and tested to BS EN 61439-3 Maximum busbar 125A Voltage

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule

Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule HBS-SH-MEP-803 May 2017 For Peterborough City Council ver. author date checked comment P1 DH 19-05-17 TJC TENDER ISSUE 1 Ref

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

ELECTRICAL DESIGN BRIEF

ELECTRICAL DESIGN BRIEF 4211 Yonge Street Suite 500 Toronto Ontario M2P 2A9 416 487 8151 f 416 487 9104 smithandandersen.com ELECTRICAL DESIGN BRIEF FOR 128 HAZLETON AVENUE RESIDENTIAL CONDOMINIUM BUILDING TORONTO, ONTARIO OUR

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS CONTENTS 100 PERFORMANCE OBJECTIVES 200 DESIGN PARAMETERS 300 SYSTEM DESIGN 310 Design Guidance 320 Outstation Choice 330 Outstation Position 340 Documentation 400 SYSTEM COMPONENTS 410 Master Handsets

More information

Proposed Mechanical, Plumbing, and Electrical Systems For the LEDYARD POLICE DEPARTMENT LEDYARD, CT

Proposed Mechanical, Plumbing, and Electrical Systems For the LEDYARD POLICE DEPARTMENT LEDYARD, CT DESIGN ASSOCIATES INC MECH/ELEC DESIGN & CONSULTING 422 Highland Ave, Cheshire, CT. 06410 (203) 271-3787, fax (203) 271-2886 Proposed Mechanical, Plumbing, and Electrical Systems For the LEDYARD POLICE

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Related Sections: TBD. Effective Date: January 1, 2016

Related Sections: TBD. Effective Date: January 1, 2016 Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:

More information

INNOVATIVE TRAINING SYSTEMS FOR FUTURE ENGINEERS

INNOVATIVE TRAINING SYSTEMS FOR FUTURE ENGINEERS INNOVATIVE TRAINING SYSTEMS FOR FUTURE ENGINEERS CHAPTER 15: TRAINING SYSTEMS FOR ELECTRICAL INSTALLATIONS 527 Training Panel to Electrical Protective Measures 528 Training Panel to Installation Tests

More information

DSCR Communications Room Standards

DSCR Communications Room Standards Document number: 0203 Status: Classifications: Published Project Restricted New Builds Deep Refurbishments Design Performance Standard Date: April 2010 Version: 1.3 Issue number Date Description 0.1 July

More information

Connections, displays and operating elements C D E G H. Installing the control unit

Connections, displays and operating elements C D E G H. Installing the control unit 1 2 3 GB Control unit 0-10 V REG-K/3-gang with manual mode Operating instructions Art. no. MTN646991 ¼ DANGER Risk of fatal injury from electrical current. All work on the device should only be carried

More information

Technical II Report Electrical Systems

Technical II Report Electrical Systems Technical II Report Electrical Systems Kelly Chan Consultant: Prof T. Dannerth, P.E. Part A Drawings Drawings needed for single-line diagram EE1.01 title sheet (electrical drawings) EE2.09 penthouse/roof

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

Amendment 3 Metal Cased Skeleton Consumer units for use in Meter Cabinets. Starbreaker

Amendment 3 Metal Cased Skeleton Consumer units for use in Meter Cabinets. Starbreaker Starbreaker mendment 3 Metal Cased Skeleton Consumer units for use in Meter Cabinets SKELETON CONSUMER UNITS FOR USE IN METER CBINETS 17th Edition Wiring Regulations Incorporating mendment No. 3: 2015

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14

More information

Electronic 7 Installation Instructions

Electronic 7 Installation Instructions Electronic 7 Installation Instructions The Horstmann Electronic 7 is an advanced water heating control, which can be programmed to take advantage of cheap night-rate electricity, so that there is a tank

More information

An overview of the main proposals in BS th Edition. Electrical Contractors Association

An overview of the main proposals in BS th Edition. Electrical Contractors Association An overview of the main proposals in BS 7671 17 th Edition Electrical Contractors Association Why have Regulations Behold the electrician standing there. Soot, soil & verdigris defile his greasy hair.

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61892-6 First edition 1999-02 Mobile and fixed offshore units Electrical installations Part 6: Installation Unités mobiles et fixes en mer Installations électriques Partie 6:

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

Proposed Development at Likoni Road, Nairobi for NTSA - Electrical Installations Bills of Quantities. DESCRIPTION QTY UNIT RATE AMOUNT KSh. 28 No.

Proposed Development at Likoni Road, Nairobi for NTSA - Electrical Installations Bills of Quantities. DESCRIPTION QTY UNIT RATE AMOUNT KSh. 28 No. BILL 1 GROUND FLOOR Supply, Deliver, Install, Set to Work and Commission the Following: 1.01 Lighting point completely wired in 3x1.5mm² single core PVC insulated copper cables drawn in 20mm diameter HG

More information

Subject Description Form

Subject Description Form Subject Description Form Subject Code Subject Title Credit Value IC259 IC Training for BSE II 8 Training Credits Level 2 Pre-requisite / Co-requisite/ Exclusion Objectives Nil 1) To provide trainees with

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1 Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping

More information

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets 2 X 1996 Wartsila 18V26 5.125mw Each 50hz HFO Generator Sets The responsibility for any and all additional charges is the purchasers. 2 x WARTSILA 5 MW Power plant 2 Units of Wartsila 18V26 @ 5 MW each,

More information

Installation Guide. Disabled Persons Emergency Alarm Kit. Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering

Installation Guide. Disabled Persons Emergency Alarm Kit. Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering Installation Guide Disabled Persons Emergency Alarm Kit Contents: Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering Remote Reset Unit c/w Sounder & call Answered

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

Working in Partnership with our Customers.

Working in Partnership with our Customers. 02 03 Introduction Working in Partnership with our Customers. At McElwaine Security our commitment to our customer is simple; we will provide an unrivalled end to end electronic security service and solutions,

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT CITY ELECTRIC TRANSPORT 2 MODULAR TRACTION SUBSTATION Modular traction substation produced by PrJSC Pluton is an integrated solution for reliable power supply of electric transport catenary. Modular traction

More information

Division 26 ELECTRICAL TABLE OF CONTENTS

Division 26 ELECTRICAL TABLE OF CONTENTS Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

C-Bus Application Note. Function Rooms and Ballrooms. Overview

C-Bus Application Note. Function Rooms and Ballrooms. Overview C-Bus Application Note Function Rooms and Ballrooms Overview A function venue or hotel will generally include large spaces purpose designed and built for holding functions. Function rooms and Ballrooms

More information

Smoke Vent Control Panel PCB4 V4 Installation Manual

Smoke Vent Control Panel PCB4 V4 Installation Manual Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel www.besafedirect.com Page 1 Contents Page 3) Important Regulations, Safety, Maintenance,

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels B. Wire and cable markers C. Conduit markers 1.2 REFERENCES A. NFPA 70 - National Electrical

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department SOUTH DUBLIN COUNTY COUNCIL Roads (Traffic and Transportation) Department TECHNICAL SPECIFICATION 4 SDCC-TS-04 SIGNAL INSTALLATION REQUIREMENTS REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF TRAFFIC CONTROL

More information

SCHEDULE OF RATES SHEET PRELIMINARIES

SCHEDULE OF RATES SHEET PRELIMINARIES Page : 1 PRELIMINARIES 1 CONTAINER BUDGET ALLOWANCE 1,100.00 1,100.00 1 SUPERVISION 3,900.00 3,900.00 1 ACCOMMODATION 5,390.00 5,390.00 1 TRAVEL ALLOWANCE 7,800.00 7,800.00 Sub- 18,190.00 18,190.00 Page

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

13. ELECTRICAL - TECHNICAL

13. ELECTRICAL - TECHNICAL 13. ELECTRICAL - TECHNICAL 13.1 GENERAL REQUIREMENTS 1. Base the electrical design on providing the following features at the most economical cost, considering both investment and operating expenditures:

More information

SIVACON Partner Program and MVC Juergen Loeschberger, Siemens EM LP Partners. 21, 2017 I Berlin

SIVACON Partner Program and MVC Juergen Loeschberger, Siemens EM LP Partners. 21, 2017 I Berlin SIVACON Partner Program and MVC Juergen Loeschberger, Siemens EM LP Partners VAR Partner Day September 20-21, 21, 2017 I Berlin SIVACON Partner Program and Medium Voltage Components Table of Contents Business

More information

FPC-02 Series. Installation and Operating manual

FPC-02 Series. Installation and Operating manual Installation and Operating manual Index Introduction.... 3 FPC-02 Installation notes......... 4 Wiring the FPC-02-120V, FPC-02-120V-MDB. 5 Wiring the FPC-02-240V, FPC-02-240V-MDB. 6 Operating instructions.

More information

Oakdale Primary School Expansion Project Appendix A - MEP Schedule of Works

Oakdale Primary School Expansion Project Appendix A - MEP Schedule of Works Oakdale Primary School Expansion Project Appendix A - MEP Schedule of Works HBS-SH-MEP-801 May 2017 For Peterborough City Council ver. author date checked comment P1 KA 19-05-17 TC TENDER ISSUE 1 1. Mechanical

More information

Heimdall Radar Traffic Detector

Heimdall Radar Traffic Detector Heimdall Radar Traffic Detector Traffic Data Detector Installation Guide Document Authorisation Role Name Function Signed Prepared by: R. Martin Project Support Manager Reviewed by: A. Rhodes Lead Product

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth Corbin Building Technical Assignment 2 Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth 10/26/2011 Technical Report II 1 Executive Summary The following report is an overview

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

PROFILE. industrial services rental trading

PROFILE. industrial services rental trading PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field

More information

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3 DUCT AIR HEATER WITH BUILT-IN CONTROLS Installation & User Instructions Stock Ref. 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 105 31 250 T1 105 31 315 T1 Stock Ref. 105 31 315 T3 105 31 400

More information

Independent, accredited testing station Member laboratory of STL and LOVAG

Independent, accredited testing station Member laboratory of STL and LOVAG Independent, accredited testing station Member laboratory of STL and LOVAG TYPE TEST REPORT NO. 3096.2081034.859 GSAB Elektrotechnik GmbH Lindenstraße 23 99718 Greußen GERMANY GSAB Elektrotechnik GmbH

More information

LexCom 19" patch panels. Put your hands on innovation

LexCom 19 patch panels. Put your hands on innovation LexCom 19" patch panels Put your hands on innovation 1 P111564 2 Finally IT is simple! As you know, there are several products and systems available for installation of IT infrastructure. Some of them

More information

GENERAL ELECTRICAL TECHNICAL SPECIFICATION

GENERAL ELECTRICAL TECHNICAL SPECIFICATION SECTION D GENERAL ELECTRICAL TECHNICAL SPECIFICATION Project: 15-106 Page D.1 Revision T Table of Contents Element 60 - General... 4 60.1 Standards and Regulations... 5 60.2 Materials... 12 60.3 Installations...

More information

Electrical Equipment & Systems

Electrical Equipment & Systems ELECTRA has been associated with world renowned electrical equipment and systems manufacturers since 1965. Our international manufacturers and suppliers are known for their quality, creativity, unique

More information

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) Fire Safety Technical Guide FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) UCL Fire Alarm Standards & Specific

More information

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements. Issued 2005/06/01 Section 13704 Video Surveillance Page 1 of 10 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Video cameras..2 Video handling..3 Recording devices..4 Transmission methods. 1.2 RELATED SECTIONS.1

More information

A guide to consumer unit and wiring accessory solutions to meet the demands of general housing installations.

A guide to consumer unit and wiring accessory solutions to meet the demands of general housing installations. MEM Memera Consumer Units and Wiring Accessories Specification for general housing installations A guide to consumer unit and wiring accessory solutions to meet the demands of general housing installations.

More information

Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site.

Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site. Indoor Infrascan Passive Infrared Motion Sensor 751 Series Installation Instructions Please leave these instructions at the installation site. Table of Contents 1.0 Product Range...3 2.0 Description...3

More information

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26 SHRISTI MEP CAREER DEVELOPMENT CENTRE Trichy-26 MEP Syllabus Contact : dhinesh.shristimep@gmail.com / sangeetha.shristimep@gmail.com +91-80984 49847, 97158 67493 ELECTRICAL DESIGNING AND DRAUGHTING FUNDAMENTALS

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Heimdall Radar Traffic Detector

Heimdall Radar Traffic Detector Heimdall Radar Traffic Detector Selectable Speed Detector Installation Guide Document Authorisation Role Name Function Signed Prepared by: R. Martin Project Support Manager Reviewed by: A. Rhodes Lead

More information

Heimdall Radar Traffic Detector

Heimdall Radar Traffic Detector Heimdall Radar Traffic Detector Single Lane VA Detector Installation Guide Document Authorisation Role Name Function Signed Prepared by: R. Martin Project Support Manager Reviewed by: A. Rhodes Lead Product

More information