IEEE Transformer Committee PC Distribution Transformer Monitoring - User

Size: px
Start display at page:

Download "IEEE Transformer Committee PC Distribution Transformer Monitoring - User"

Transcription

1 IEEE Transformer Committee PC Distribution Transformer Monitoring - User Mark Scarborough Electrical Engineering Consultant DuPont January 9, 2019

2 Transformer Types in DuPont Control power Dry-type in MCCs and control panels Small dry-type Lighting, receptacle, instrument power panel type 5kVA 330kVA (1 phase and 3 phase) Specialty Dry-type and fluid filled for rectifier and ASD applications Pole top Small power Some 20 45MVA main substation transformers Distribution (substation) dry-type VPI conventional wound and cast coil 750kVA 3000kVA Distribution (substation) fluid filled Mineral oil, natural ester, silicone insulation fluids 750kVA 5000kVA (some 10MVA and 30MVA) Pad-mounted Mineral oil and natural ester fluids 100kVA 3000kVA

3 Typical Distribution System Incoming power Purchased power substations Mostly all owned by Utilities 230kV down to 12.47kV Internal plant distribution Typically medium voltage (1 35kV) but mostly 2.4kV to 13.8KV. Few 34.5kV system. Utilization 480V and 575V for most applications 2.4kV and 4.16kV for motor applications about 250HP and above 120V / 230V for small loads Grounding B-Phase HGR LRG Soild

4 Transformer Monitoring Techniques Control power, small dry-type, pole top Usually don t do anything. Investigate when something doesn t work or power goes out. Some pole tops and small dry-types may get an infrared inspection. Visual Probably the most common but questionable as to what people know what to look for. Some plants require an operator or maintenance technician to walk the main electrical system from substation to substation daily, weekly, or monthly. Looking for abnormal sounds and or smells, leaks, broken gages, deterioration in paint system. Infrared Inspection Typically on an annual basis for most facilities. Good way to see if cooling system is working or if low fluid level.

5 Transformer Monitoring Techniques If transformers are fluid filled, then very good at taking samples for oil screen and DGA on an annual basis. Typical issues with sample methods and labs and reporting and interpretation. Need to realize that you have to put some oil back in occasionally. If critical application, will shut down on a 2 or 4 year interval to do inspection, testing, and cleaning. Planned shutdowns sometimes are impossible until the system shuts down automatically.

6 Transformer Monitoring Techniques Internal Specification Three (3) internal standards / guidelines Fluid Filled 300kVA to 10MVA, 3 Ph, primary voltage 2,400 to 46,000V Dry-Type 300 to 7.5MVA, 3 Ph, primary voltage 2,400 to 34,500V Pad Mount 2500kVA and below, primary voltage of 34,500V and below and a secondary voltage of 600V and below Each standard describes the feature sets required on each transformer type. User can add or take away as necessary for their application.

7 Transformer Monitoring Techniques Fluid Filled Standard Field Dial thermometer with alarm and control contacts. Pressure / vacuum gage. Pressure relief valve. Large pressure relief device with alarm contacts (sometimes directional shield). Magnetic liquid level gauge with alarm contacts. Optional / Custom Push to test circuit and/or current monitoring (4-20mA signal) of space heater circuit in ATCs or control box. Space heater control? Thermostat or no thermostat? Fan controls and aux contacts off of fan starter and/or control switch. N2 bottle monitoring system with alarms. Sudden or fault pressure relay with trip and alarm contacts. Winding hot-spot temperature indicator relay with alarm contacts. Add alarm contacts to pressure / vacuum gage. Infrared view ports on ATC.

8 Transformer Monitoring Techniques Dry- Type Standard Winding temperature with 3- phase hot spot temperature indication with peak indicator, contacts for alarm, trip and fan control and fan exerciser. (Typically this is a self contained package from the vendor.) Infrared view ports. Cooling fans w/ running status Optional / Custom Push to test circuit and/or current monitoring (4-20mA signal) of space heater circuit in ATCs or control box. Space heater control? Thermostat or no thermostat? Infrared view ports on ATC.

9 Transformer Monitoring Techniques Pad- Mounted Standard Liquid level gauge on 500kVA and above. Dial type thermometer with peak indicator on 500kVA and above. Vacuum / pressure gage on 500kVA and above. Pressure relief device. Large pressure relief device with alarm contacts on 1000kVA and above. Optional / Custom Require that sample valve be accessible outside of the HV and LV compartments. Require that all gages be accessible outside of the HV and LV compartments. Infrared view ports on HV and LV compartments. Alarm contacts on liquid level gage, liquid thermometer, and vacuum / pressure gages.

10 Alarm and Trip Contacts? In most cases, these transformers are located in an industrial facility and feed a substation or electrical room that has local DCS / PLC (control system) I/O. Historically, some or all of the alarm contacts would be hard wired to local DCS / PLC I/O cabinets. If it didn t exist, then it basically didn t get wired any where. More recently

11 Alarm and Trip Contacts?. we have been using the I/O capabilities on microprocessor based protective relaying and even expansion I/O modules for such devices.

12 Example #1 13.8kV Metal Clad Switchgear Radial feed to 2500kVA transformer but looped to additional substations. Switched breaker local to each substation. Microprocessor relay local to substation not capable of handling I/O from transformer so wired to DCS local I/O.

13 Construction Interconnection Dwg

14 Example # kV Metal Clad Switchgear Radial feed to 1000kVA substation transformer near by. SEL-787 protective relay for transformer with differential.

15 Construction Interconnection Dwg

16 MV Switchgear Vendor Schematic

17 Transformer Vendor Drawing

18 Example #3

19 Signals and What Action? So now we have gotten the signals to the plant DCS or PLC system. A DCS screen or HMI screen is developed with the alarm points. DCS / PLC system is monitored by Operation / Operations. Sometimes they don t know how to respond. Started developing action / resolution matrix. Call the on call maintenance electrician? Go to field and look at the equipment? System automatically send Text message to on call maintenance electrician response? Shutdown the process so the transformer can be shutdown? Alarms can go into a PI Data Historian system but not aware of active trending.

20 Misc. Topics / Considerations Confusion as to what to do with an alarm comes in. What action is required? Firewalls and cyber security. Not all sites have a centralized DCS or PLC to connect to. Typically do not monitor of pad mounted transformer but we have some that are in critical applications. Been some interest in: On line monitoring for moisture. (On line moisture removal systems in service.) On line monitoring for DGA monitoring. Better monitoring of dry-type transformers. Have had some sudden failures. Starting to experiment with wireless communications technology for instruments. Thinking may be able to use for transformers because not part of process control. Trending / data collection.

21 Thank You. Questions / Discussion

A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM

A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM by B.S.RAJPUROHIT, GAURAV SAVLA, NAUSHAD ALI, P.K.PANDA, S.K.KAUL, H.MISHRA* ENGINEERING SERVICES GROUP, BHABHA ATOMIC RESEARCH CENTRE

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

What Utility Analytics means to Exelon

What Utility Analytics means to Exelon What Utility Analytics means to Exelon Presented by Bart Enright IT Director Smart Grid Initiatives at ComEd Exelon s Analytic Journey Exelon Utilities Overview T&D Grids Data Visualization Data Analytics/Notifications

More information

NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS

NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS January, 2013 Infrared Inspection Report NLR Electric Murray Hydro Plant Company Contact James Bray Project: 09170113 2605 CHARTER OAK DRIVE,

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

SIDEWINDER DRILLING RIG 107 HOUSTON, TEXAS

SIDEWINDER DRILLING RIG 107 HOUSTON, TEXAS SIDEWINDER DRILLING RIG 107 HOUSTON, TEXAS January, 2017 Infrared Inspection Report Sidewinder Drilling Rig 107 Lufkin, Texas Company Contact: Jesse Russell Project: 06050117 2605 CHARTER OAK DRIVE, LITTLE

More information

Maintenance Best Practices & Intervals for Substation Equipment. Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc.

Maintenance Best Practices & Intervals for Substation Equipment. Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc. Maintenance Best Practices & Intervals for Substation Equipment Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc. Background - 40 Years in the Industry Education NWTC (Northeast

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

Gas ventilation monitoring and control system

Gas ventilation monitoring and control system Gas ventilation monitoring and control system A case study Regulations and customer requirements surrounding the operation and maintenance of gas and ventilation monitoring and control systems in underground

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

CIRCUIT BREAKER - GAS

CIRCUIT BREAKER - GAS CIRCUIT BREAKER - GAS Capabilities: In a large substation, circuit breakers are used to interrupt any short-circuits or overload currents that may occur on the network. A 345 kv, high voltage, three position/phase

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply   - Tel: Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical

More information

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability

More information

Control Panel For Water Wash Hoods AM2

Control Panel For Water Wash Hoods AM2 Control Panel For Water Wash Hoods AM2 For further information Call: (919) 554-1025 Or Fax: (919)554-1525 Aqua-Matic 117 Franklin Park Ave. Youngsville, NC 27506 TABLE OF CONTENTS AQUA-MATIC LIMITED WARRANTY

More information

CONTINUOUS MONITORING IS ON THE RISE:

CONTINUOUS MONITORING IS ON THE RISE: CONTINUOUS MONITORING IS ON THE RISE: CAN YOU ADAPT? BY WILLIAM HIGINBOTHAM, EA Technology LLC Electrical testing companies have traditionally built their businesses by periodically running tests on electrical

More information

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In?

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7 SCR Battery Charger Product Specifications Description The is RIC Electronics premiere SCR battery charger/rectifier. The provides power to critical DC loads through a wide range of outputs and is engineered

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

EE034: Electrical Maintenance for Engineers & Technicians

EE034: Electrical Maintenance for Engineers & Technicians EE034: Electrical Maintenance for Engineers & Technicians EE034 Rev.001 CMCT COURSE OUTLINE Page 1 of 6 Training Description: We have taken all the latest techniques and know-how relating to electrical

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT CITY ELECTRIC TRANSPORT 2 MODULAR TRACTION SUBSTATION Modular traction substation produced by PrJSC Pluton is an integrated solution for reliable power supply of electric transport catenary. Modular traction

More information

Guide To Troubleshooting INEFFICIENT COOLING FANS

Guide To Troubleshooting INEFFICIENT COOLING FANS Guide To Troubleshooting INEFFICIENT COOLING FANS TABLE OF CONTENTS Introduction Enclosure Cooling Basics Key Attributes of Enclosure Cooling Symptoms of Poor Enclosure Cooling Typical Cooling Fan Problems

More information

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers BULLETIN 92046 APPLICATION INFORMATION NOVEMBER 2002 SUPERSEDES August 2002 CONTENTS

More information

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

Arc Fault Detection Devices (AFDDs) Protecting People and Property

Arc Fault Detection Devices (AFDDs) Protecting People and Property Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS

More information

Telecity. Table of Contents. Page. Section 3.2

Telecity. Table of Contents. Page. Section 3.2 1 3.2 System Descriptions Table of Contents 3.2 SYSTEM DESCRIPTIONS... 3 3.2.1 General Notes... 3 3.3 Power Distribution MV... 4 3.3.1 Incoming Supply... 4 3.3.2 MV Switch room... 4 3.4 Power Distribution

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

Factory Equipment Testing of Single Lift Substation

Factory Equipment Testing of Single Lift Substation Factory Equipment Testing of Single Lift Substation Presented by: Kurt Vosburg & Ronak Goswami IEEE CED Houston Chapter November 17-18, 2015 Objective This technical presentation will discuss various aspects

More information

Monitoring of Electrical Equipment Failure Indicators and Alarming

Monitoring of Electrical Equipment Failure Indicators and Alarming Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE gabrieljpaoletti@eaton.com

More information

Product Guide Low Voltage Switchboard & Switchgear

Product Guide Low Voltage Switchboard & Switchgear Product Guide 2018 Low Voltage Switchboard & Switchgear General INESING low voltage switchgear is completely designed and engineered by INESING using circuit breakers from a leader manufacturers like ABB,

More information

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7 Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic

More information

650-EL-C-E-1995 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian Birth Date : 06/01/1969 Marital Status : Married

650-EL-C-E-1995 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian Birth Date : 06/01/1969 Marital Status : Married 650-EL-C-E-1995 Senior Electrical Engineer Holds a B. Sc. in Electrical Engineering and has about 16 years experience in the field of electrical construction, pre-commissioning and follow up activities

More information

C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART)

C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART) C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART) Suneel kumar P I Shravan Kumar Seema Deo Bhanu Kumar Raine Dy.General Manager, Dy.Manager Sr.Manager Manager NTPC RSTPS NTPC

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities. i-con Switchgear Condition HV Switchgear Integrated Substation Condition ISCM Answers for Infrastructure & Cities. The challenge: Reliable energy supply is the key to success for every enterprise in a

More information

800 MHz US 2 NMR system

800 MHz US 2 NMR system 800 MHz US 2 NMR system To achieve ultra-high-fields (>700 MHz), the magnet must be cooled to below (ambient pressure) liquid He temperature. The He cryostat is divided into two sections. The upper section

More information

This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).

This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS). Introduction This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS). The Purpose of the ETS is to deliver chilled

More information

Risk Mitigation of Aging Electrical Infrastructure

Risk Mitigation of Aging Electrical Infrastructure Risk Mitigation of Aging Electrical Infrastructure 2014 WWOA Annual Conference 10:55am Thursday October 9 th, 2014 Presented by and Authored by Jeff M. Miller, PE, ENV SP About the Presenter Jeff M. Miller,

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

Operation Manual. Programmable Logic Controller

Operation Manual. Programmable Logic Controller Operation Manual Programmable Logic Controller Part No. 9983-0000-E01 / January 2018 OPERATION MANUAL TABLE OF CONTENTS CUSTOMER SERVICE 3 CONTACT INFORMATION 3 ORDER INFORMATION 3 INTRODUCTION 4 THE PROCESS

More information

FB10000 Error Messages Troubleshooting

FB10000 Error Messages Troubleshooting Error ID: 66300 - UV UV System Active Alarm (UV will shut down). 66300 UV System Active Alarm (UV will shut down). Tap Get Ready. For more details open the Troubleshooting guide This UV error

More information

Predictive Maintenance Training

Predictive Maintenance Training Predictive Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This predictive maintenance

More information

Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER

Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER For Operating Instructions or Technical Support Call 1-507-886-6666 Last Revision: 1/31/12 Starting

More information

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance A. Introduction 1. Title: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance 2. Number: PRC-005-6 3. Purpose: To document and implement programs for the maintenance of all

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability

More information

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits 01 VAMP 120 & 121 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during work

More information

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB.  Paul Lee 17 TH APRIL Switch Board Monitoring Protecting Switchboard Courtesy of ABB. www.fengshengelectric.com.sg Paul Lee Agenda 1. Introduction 2. IEC 61439 3. Why Switchboard Monitoring 4. Switchboard Monitoring

More information

Continuous, real-time detection, alarming and analysis of partial discharge events

Continuous, real-time detection, alarming and analysis of partial discharge events DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation

More information

EVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson

EVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson EVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson INTRODUCTION The WIDAR correlator being developed for the EVLA project will

More information

Multi-Zone Wireless Control Training Systems ( )

Multi-Zone Wireless Control Training Systems ( ) Multi-Zone Wireless Control Training Systems 593306 (3467-00) LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 11/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 3 List

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Open Source Home Security System

Open Source Home Security System Open Source Home Security System Final Report ECE 410: Senior Project By: Allen Chu March 28, 2012 Project Advisor: Dr. John Ventura, PE Table of Contents Title 1 Table of Contents 2 1. Abstract 3 2. Customer

More information

Relay Performance Index for a Sustainable Relay Replacement Program

Relay Performance Index for a Sustainable Relay Replacement Program Relay Performance Index for a Sustainable Relay Replacement Program Aaron Feathers, Abesh Mubaraki, Nai Paz, Anna Nungo Pacific Gas & Electric Company San Francisco, CA Western Protective Relay Conference

More information

HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics

HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...5 5. PROTECTION...6 6. PARAMETER

More information

FLUID BED EQUIPMENT. Drying

FLUID BED EQUIPMENT. Drying Drying FLUID BED EQUIPMENT Tapasya s Fluid Bed Equipment (FBE) is specially designed unit for agglomeration and simultaneous drying for top spray granulation conforming to the international quality norms

More information

PROFILE. industrial services rental trading

PROFILE. industrial services rental trading PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field

More information

Executive Summary. CNBC Global Headquarters Christine Cajilig

Executive Summary. CNBC Global Headquarters Christine Cajilig Executive Summary This report contains an analysis and description of the existing electrical distribution of the including the distribution type, emergency power, uninterruptible power system, over current

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C) Models 51, 51-S and 53 Boiler Water Feeders Models 51-2, 51-S-2 and 53-2 Feeder Cut-Off Combinations McDonnell & Miller Installation & Maintenance Instructions MM-315(C) OPERATION Maximum Water Supply

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

Heating Cable. Description

Heating Cable. Description ITLS Base Panel 10 VGA Touch Screen HMI 40 Amps/Loop @ 100 480 VAC 6 Loops to 72 Loops NEMA 4 or NEMA 4X Enclosure SCR Control Integral Circuit Panel with Circuit Breakers Optional Main Disconnect Soft

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

4. Applicability: 4.1. Functional Entities: 4.2. Facilities:

4. Applicability: 4.1. Functional Entities: 4.2. Facilities: Standard PRC-005-2(i) Protection System A. Introduction 1. Title: Protection System 2. Number: PRC-005-2(i) 3. Purpose: To document and implement programs for the maintenance of all Protection Systems

More information

Life Cycle Considerations for Microprocessor Relays

Life Cycle Considerations for Microprocessor Relays 2017 Texas A&M Conference for Protective Relay Engineers Life Cycle Considerations for Microprocessor Relays Michael Kleman, Regional Technical Manager ABB Coral Springs, FL - USA Todd Moyer P.E., Distribution

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.

More information

Proservo NMS5- / NMS7-

Proservo NMS5- / NMS7- Functional Safety Manual Proservo NMS5- / NMS7- Tank gauge for Liquid level measurement with 4 to 20mA Output or with Alarm Relay Contact Output Application Operating minimum (e.g. dry run protection),

More information

Distribution Control Center Operator Training

Distribution Control Center Operator Training Distribution Control Center Operator Training OnlineTraining 15-Hour Course COURSE I BASIC DISTRIBUTION 1. Introduction to Distribution Systems a. Terminology b. Basic electricity and Ohm s Law c. BES

More information

Mission Critical. Fuel Supply Systems

Mission Critical. Fuel Supply Systems Fuel Supply Systems Insight Onsite Fuel Supply Systems Page 2 Simplex Mission Critical Fuel Supply Systems are comprehensive, integrated, project-matched fuel management systems for diesel and turbine

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

Flexible Air-sampling Smoke Detection

Flexible Air-sampling Smoke Detection Flexible Air-sampling Smoke Detection BY Technology Pioneers in Highsensitivity Air-sampling Smoke Detection Systems Providing Solutions Beyond Traditional Smoke and Fire Detection Hochiki, a world-leader

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

White Paper. Maintenance Inspection Windows on Transformers. Maintenance Inspection Windows on Transformers. Abstract: iriss.com

White Paper. Maintenance Inspection Windows on Transformers. Maintenance Inspection Windows on Transformers. Abstract: iriss.com Maintenance Inspection Windows on Transformers By Rudy Wodrich, P.Eng., MBA, CRL, VP Engineering Services, IRISS Inc. Abstract: Everyone knows that Thomas Alva Edison invented the lightbulb but who invented

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

Part: I TECHNICAL SPECIFICATION

Part: I TECHNICAL SPECIFICATION Part: I TECHNICAL SPECIFICATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR THE WORK OF DESIGN, SUPPLY, ERECTION AND COMMISSIONING INCLUDING CIVIL WORK OF NITROGEN INJECTION

More information

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards LIN ZHOU M Eng, MIEAust RIZNER Australia YANG YIJUN B. Eng, Senior Engineer State Grid, Zhejiang

More information

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576

More information

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam

More information

ADVANCED MONITORING AND DIAGNOSTIC SYSTEMS FOR INDUSTRIAL GAS TURBINES

ADVANCED MONITORING AND DIAGNOSTIC SYSTEMS FOR INDUSTRIAL GAS TURBINES ADVANCED MONITORING AND DIAGNOSTIC SYSTEMS FOR INDUSTRIAL GAS TURBINES Jon Aylett BSc Senior Diagnostic Systems Engineer jaylett@chromalloy.com CHROMALLOY TURBINE SERVICES Venture Building Kelvin Campus

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Electrical Energy department

Electrical Energy department Al-Balqa Applied University Power systems Protection course Dr Audih al-faoury Electrical Energy department 2018-2019 Department of Electrical Energy Engineering 1 Part 1 Power System protection Introduction

More information

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2 FEATURES: Closed Loop Design (Class A Wiring) Microprocessor Based System Intelligent Distributed System Structure Quick Response Time Fire Alarm in

More information

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water. Temperature Control Units Water & Oil 30-500 F Portable Chillers Air & Water-Cooled 20-70 F Central Chillers Air & Water-Cooled Packages & Modules 20-70 F Pump Tank Stations Chilled or Tower Water 200-3600

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

Introduction Consultant shall incorporate the material in the DSS into the project specifications. DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding

More information

AS950 ALL-WEATHER REFRIGERATED SAMPLERS

AS950 ALL-WEATHER REFRIGERATED SAMPLERS AS950 ALL-WEATHER REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 All-Weather Refrigerated

More information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall

More information

SYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996

SYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996 User responsibility SYSTEM 3400 (with 34000 Devices) Control and indicating equipment Quick reference Emergency conditions ANALOGUE ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Other controls Site labels

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Standard PRC-005-5 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Standard Development Timeline This section is maintained by the drafting team during the development

More information

Arc Flash Protection Training - NFPA 70e Electrical Safety

Arc Flash Protection Training - NFPA 70e Electrical Safety Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq

More information

STCP 02-1 Issue 005 Alarm & Event Management

STCP 02-1 Issue 005 Alarm & Event Management STCP 02-1 Issue 005 Alarm & Event Management STC Procedure Document Authorisation Party Name of Party Representative Signature Date National Grid Electricity Transmission plc SP Transmission plc Scottish

More information