Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems (DRY-AAA)

Size: px
Start display at page:

Download "Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems (DRY-AAA)"

Transcription

1 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () M E M O R A N D U M TO: FROM: and Alternate Members of the Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems (DRY- AAA) Sandra Stanek, NFPA Staff Liaison DATE : March 26, 2012 SUBJECT: AGENDA NFPA 17 & 17A ROC (Fall 2012 revision cycle) for the 2013 edition Enclosed is the agenda for the Report on Comments (ROC) for NFPA 17 & 17A Dry & Wet Chemical Fire Extinguishing Systems which will be held on Wednesday, April 18th and Thursday, April 19 th in Nashville, TX. Please review the meeting notice, sent to your address of record, for pertinent information concerning hotels, etc. As your new staff liaison, I welcome any questions you may have & look forward to working with all of you. Office: (617) sstanek@nfpa.org For administrative questions, please contact Elena Carroll at (617)

2 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () ROC (F2012) Agenda April 18-19, 2012 Hilton Garden Inn Nashville Vanderbilt 1715 Broadway Nashville, TN Wednesday, April 18, 2012: 8:00 A.M. -5:00 P.M. or at the discretion of the Chairman 1. Call to Order 8:00 A.M. MST 2. Introductions & Attendance 3. Committee member status & Update of membership Roaster 4. Review Agenda 5. Approval of Previous Meeting minutes (see attachments) 6. NFPA Staff Liaison presentation, review of key dates within current cycle. 7. Chairman Comments 8. Task Group reports 9. Process Public Comments & generate Committee Comments for NFPA 17 & 17A revision cycles F2012 (see attachments) 10. Adjourn 5:00 P.M. CST or at the discretion of the Chairman

3 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () Thursday, April 19,2012: 8:00 A.M. -5:00 P.M. or at the discretion of the Chairman 1. Call to Order 8:00 A.M. CST 2. Process Public Comments & generate Committee Comments for NFPA 17 & 17A revision cycles F2012 (see attachments) 3. Adjourn 5:00 P.M. CST or at the discretion of the Chairman Please submit requests for additional agenda items to the chair at least seven days prior to the meeting. Key Dates: for the Fall 2012 Revision Cycle (NFPA 17 & 17A 2013 edition) Comment Closing date March 2, 2012 Final date for ROC Meeting May 4, 2012 Final Date for mailing TC ballots May 18, 2012 Receipt of ballots returned by June 8, 2012 ROC Published & Posted Aug. 24, 2012 Closing Date for Notice of Intent to Make a Motion (NITMAM) Oct. 5, 2012 Issuance of Consent Document (No NITMAMs) Nov. 27, 2012 NFPA Annual Meeting June 2013 Issuance of Document with NITMAM Aug. 1, 2013 Technical Committee deadlines are in bold.

4 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () General Procedures for Meetings Use of tape recorders or other means capable of producing verbatim transcriptions of any NFPA Committee Meeting is not permitted. Attendance at all NFPA Committee Meetings is open. All guests must sign in and identify their affiliation. Participation in NFPA Committee Meetings is generally limited to committee members and NFPA staff. Participation by guests is limited to individuals, who have received prior approval from the chair to address the committee on a particular item, or who wish to speak regarding public proposals or comments that they submitted. The chairman reserves the right to limit the amount of time available for any presentation. No interviews will be allowed in the meeting room at any time, including breaks. All attendees are reminded that formal votes of committee members will be secured by letter ballot. Voting at this meeting is used to establish a sense of agreement, but only the results of the formal letter ballot will determine the official action of the committee. Note to Special Experts: Particular attention is called to Section 3.3(e) of the NFPA Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process in the NFPA Directory. This section requires committee members to declare any interest they may represent, other than their official designation as shown on the committee roster. This typically occurs when a special expert is retained by and represents another interest category on a particular subject. If such a situation exists on a specific issue or issues, the committee member shall declare those interests to the committee and refrain from voting on any action relating to those issues. Smoking is not permitted at NFPA Committee Meetings.

5 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () Attachment #1: Previous Meeting Minutes

6 Page 1 Members & Alternates Present: Report on Proposals Meeting (F2012) Minutes July 13 th, 14 th & 15 th, 2011 UL Laboratories Inc. Main Bldg. #8 333 Pfingsten Rd. Northbrook, IL :00 A.M. to 6:30 P.M. David de Vries Firetech Engineering Inc. Committee Chairman Thomas Brown RJA Group, Inc. Jack Dick Heiser Logistics Thomas Kelly Zurich Serices Corp. Doug Kline Fire Suppression Systems Assoc. William Klingenmaier, Tyco Fire Suppression & Building Products Michael McGreal Firedyne Engineering, PC Thomas McVerry III, DunnWell, LLC J.R. Nerat UTC/Badger Fire Protection Erik Olsen Chubb Group of Insurance Companies Blake Shugarman UL Laboratories Inc. William Vegso Fire Equipment Manufacturers Assoc. J. Voelkert Amerex Corporation Mark Conroy Tyco Fire Suppression & Building Products Robert Kaisiki FM Global Richard Lupien UTC/Kidde-Fenwal Edward Leedy retired (member emeritus) Guests Present: Sheryl Lemire Tyco Fire Suppression & Building Products Guy Jones Amerex Corporation Joseph Ciesiel NAFED ( National Association of Fire Extinguisher Distributors) Larry Engle M. Jacks Fire & Safety Scott Plumer Liberty Mutual Insurance Fred Sanford Liberty Mutual Insurance NFPA Staff: Sandra Stanek NFPA Staff Liaison Jonathan Hart NFPA Staff Meeting Minutes: The meeting was called to order by Chairman de Vries at 8:00 AM CST. Chairman de Vries welcomed Committee s, Alternates and Guest attendees and noted the 179 proposals to discuss & vote upon. He introduced new NFPA staff liaison Sandra Stanek, and she reviewed a presentation on meeting protocols, etc. for the benefit of attendees. The minutes from the past ROC web conference meeting on April 11, 2007 were reviewed and approved. A motion was made & seconded to accept the minutes of the ROC meeting in April 2011.

7 Page 2 Chairman de Vries discussed the agenda inclusion of the NFPA paper, U.S. Experience with Non-Water-Based Automatic Fire Extinguishing Equipment, as well as a short review of NFPA 17/17A proposals. It was decided that the following Task Groups would break into their respective groups & work from 8:30-10:30. The groups were assigned to undertake the proposal review for the following areas: System Design/Layout Tom Brown Chair Larry Engle Bill Klingenmaier Mike McGreal Tom McVerry Richard Wood (not in attendance) Training/Qualifications Doug Kline Chair Andrew Blum (not in attendance) Paul Buchh0fer (not in attendance) Sam Dannaway Jack Dick J.R. Nerat Sheryl Lemire Joe Ciesiel System Acceptance Erik Olsen Chair Mark Conroy Ed Kaminske (not in attendance) Mike Luna (not in attendance) Rich Lupien Mike Mitchell (not in attendance) Scott Plumer Robert Scholes (not in attendance) Blake Shugarman Laurie Szumla (not in attendance) Inspection, Testing & Maintenance Bill Vegso Chair Bradley Howard (not in attendance) Bill Isemann (not in attendance) Guy Jones Tom Kelly Robert Popa (not in attendance) Fred Sanford Raymond Stacy (not in attendance) Bob Kasinski Craig Voelkert Steve Wright (not in attendance) Mobile Equipment Mike McGreal Chair Bill Isemann (not in attendance) Bob Kasiski Bill Klingenmaier Mike Luna (not inattendance) Mike Mitchell (not in attendance) J.R. Nerat Craig Voelkert The above Task Groups were formed prior to the ROP meeting, including members who were not in attendance and will be retained for the duration of this

8 Page 3 development cycle to review comments on proposals in the assigned subject areas. The Task Groups on System Acceptance & Mobile Equipment will develop committee comments and welcome any public input. Meeting participants voted upon Proposals and generated Committee proposals. Any & all Formal Interpretations were retired. The Committee discussed the future ROC meeting location of Washington, DC or surrounding area for April A Task Group was formed & continues to work on alternatives to full discharge testing protocols prior to the ROC meeting. Any and all public input is welcome. The meeting adjourned at 3:00 PM on Friday, July 15, 2011 Respectfully Submitted, Sandra Stanek Staff Liaison for NFPA 17/17A sstanek@nfpa.org

9 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () Attachment #2: Committee Member Information

10 Address List No Phone Dry and Wet Chemical Extinguishing Systems 03/26/2012 Sandra Stanek David A. de Vries Chair Firetech Engineering Inc Harrison Street Evanston, IL SE 1/10/2008 Larry Angle M. Jacks Fire & Safety 538 Sandau Road San Antonio, TX National Association of Fire Equipment Distributors Alternate: Norbert W. Makowka IM 8/9/2011 Art Black Carmel Fire Protection Associates PO Box 7168 Carmel-by-the-Sea, CA E 10/18/2011 Andrew Blum Exponent, Inc Forest Grove Drive Silver Spring, MD Alternate: Richard T. Long, Jr. SE 10/28/2008 Thomas C. Brown The RJA Group, Inc. Rolf Jensen & Associates, Inc Greenview Drive, Suite 500 Laurel, MD Alternate: Stephen M. Hill SE 11/2/2006 Samuel S. Dannaway S. S. Dannaway Associates, Inc. 720 Iwilei Road, Suite 412 Honolulu, HI SE 7/1/1996 Jack K. Dick Heiser Logistics, Inc Fire Hall Road PO Box 730 Canadaigua, NY Alternate: Mark T. Conroy M 1/1/1992 Bradley T. Howard Koorsen Fire & Security 727 Manor Park Drive Columbus, OH IM 8/5/2009 Bill Isemann Guardian Fire Protection Services LLC 7668 Standish Place Rockville, MD IM 10/28/2008 Edward J. Kaminski Clark County Fire Department 575 East Flamingo Las Vegas, NV E 1/1/1991 Thomas H. Kelly Zurich Services Corporation 1333 Richwood Drive, SE Grand Rapids, MI I 8/5/2009 Doug Kline Nowak Supply Fire Systems 302 West Superior Street Fort Wayne, IN Fire Suppression Systems Association IM 1/10/2008 William Klingenmaier Tyco Fire Protection Products One Stanton Street Marinette, WI Alternate: Richard J. Biehl M 4/4/1997 Michael E. Luna Intertek Testing Services Shady Falls Road Elmendorf, TX RT 8/5/2009 1

11 Address List No Phone Dry and Wet Chemical Extinguishing Systems 03/26/2012 Sandra Stanek Michael P. McGreal Firedyne Engineering, PC Cork Road Tinley Park, IL SE 7/1/1996 Thomas L. McVerry III DunnWell, LLC 4601 Creekstone Drive, Suite 200 Durham, NC IM 10/28/2008 Stephen M. Micke Fireman's Fund Insurance Company 2744 Bonnard Street Davis, CA Alternate: Robert V. Scholes I 10/20/2010 Michael S. Mitchell Boulder Fire Rescue Department rd Street Boulder, CO E 7/23/2008 J. R. Nerat UTC/Badger Fire Protection W-6615 Number 11.5 Road Wallace, MI NFPA Industrial Fire Protection Section Alternate: Richard L. Lupien M 10/1/1996 Erik G. Olsen Chubb Group of Insurance Companies 132 Naughright Road Long Valley, NJ I 3/2/2010 Robert B. Popa Farmington Fire Department Fire Marshal s Office 850 Municipal Drive Farmington, NM E 10/28/2008 Neal G. Pulvermacher West Bend Mutual Insurance NSI Division 8401 Greenway Blvd., Suite 1100 Middleton, WI I 10/18/2011 Frederick Sanford Liberty Mutual Insurance Company 9 Riverside Road Weston, MA Alternate: Scott M. Plumer I 8/9/2011 Blake M. Shugarman Underwriters Laboratories Inc. 333 Pfingsten Road Northbrook, IL Alternate: Kevin Holly, Jr. RT 11/2/2006 Raymond A. Stacy FM Approvals 1151 Boston-Providence Turnpike PO Box 9102 Norwood, MA FM Global Alternate: Robert Kasiski I 8/5/2009 Laurie K. Szumla All State Fire Equipment of WNY 4804 Transit Road Depew, NY IM 7/23/2008 2

12 Address List No Phone Dry and Wet Chemical Extinguishing Systems 03/26/2012 Sandra Stanek William Vegso Buckeye Fire Equipment Company 110 Kings Road Kings Mountain, NC Fire Equipment Manufacturers' Association Alternate: Bruce J. Euler M 7/23/2008 J. Craig Voelkert Amerex Corporation 7595 Gadsden Highway PO Box 81 Trussville, AL Alternate: Guy L. Jones, Jr. M 4/1/1996 Richard W. Wood City of Nashua Fire Rescue Department 177 Lake Street Nashua, NH E 3/2/2010 Thomas Steven Wright Fisher Engineering, Inc South Copper Key Court Gilbert, AZ Alternate: Steven A. Sheldon SE 7/23/2008 Richard J. Biehl Alternate Tyco Suppression Systems One Stanton Street Marinette, WI : William Klingenmaier M 4/16/1999 Mark T. Conroy Alternate Brooks Equipment Company 20 Hampden Drive, Suite 2 South Easton, MA : Jack K. Dick M 3/1/2011 Bruce J. Euler Alternate Buckeye Fire Equipment Company 110 Kings Road PO Box 428 Kings Mountain, NC Fire Equipment Manufacturers' Association : William Vegso M 8/9/2011 Stephen M. Hill Alternate The RJA Group, Inc. Rolf Jensen & Associates, Inc Greenview Drive, Suite 500 Laurel, MD : Thomas C. Brown SE 8/9/2011 Kevin Holly,Jr. Alternate Underwriters Laboratories Inc. 333 Pfingsten Road Northbrook, IL : Blake M. Shugarman RT 10/20/2010 Guy L. Jones, Jr. Alternate Amerex Corporation 7595 Gadsden Highway PO Box 81 Trussville, AL : J. Craig Voelkert M 10/18/2011 Robert Kasiski Alternate FM Global 1151 Boston Providence Turnpike PO Box 9102 Norwood, MA : Raymond A. Stacy I 7/23/2008 Richard T. Long, Jr. Alternate Exponent, Inc Science Drive, Suite 200 Bowie, MD : Andrew Blum SE 8/5/2009 3

13 Address List No Phone Dry and Wet Chemical Extinguishing Systems 03/26/2012 Sandra Stanek Richard L. Lupien Alternate UTC/Kidde-Fenwal, Inc. 400 Main Street Ashland, MA NFPA Industrial Fire Protection Section : J. R. Nerat M 10/4/2001 Norbert W. Makowka Alternate National Association of Fire Equipment Distributors 122 South Michigan Avenue, Suite 1040 Chicago, IL : Larry Angle IM 1/1/1992 Scott M. Plumer Alternate Liberty Mutual 20 Riverside Road Weston, MA : Frederick Sanford I 8/9/2011 Robert V. Scholes Alternate Fireman's Fund Insurance Company 1711 Baywood Drive Concord, CA : Stephen M. Micke I 8/5/2009 Steven A. Sheldon Alternate Fisher Engineering, Inc East Southern Avenue Mesa, AZ : Thomas Steven Wright SE 3/4/2008 Edward D. Leedy Member Emeritus 2033 Butterfly Lane, CC304 Naperville, IL /1/1990 Sandra Stanek Staff Liaison National Fire Protection Association 1 Batterymarch Park Quincy, MA /6/2011 4

14 Technical Committee on NFPA 17 & 17A Dry & Wet Chemical Extinguishing Systems () Attachment #3: Report on Comments

15 Report on Comments November 2012 NFPA Log #2 John F. Bender, Underwriters Laboratories Inc Revise text to read as follows: Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 300,, 2005, Revised ANSI/UL 1254,, Update reference to ANSI/UL 300 to indicate and clarify that the date of the UL standard is 2005 with revisions adopted through Log #4 Marcelo M. Hirschler, GBH International Revise text to read as follows: Those having predetermined flow rates, nozzle pressures, and quantities of extinguishing agent. These systems have the specific pipe size, maximum and minimum pipe lengths, flexible hose specifications, number of fittings, and number and types of nozzles prescribed by a testing laboratory. The maximum and minimum pipe lengths and the number of fittings shall be permitted to be expressed in equivalent feet of pipe. The hazards protected by these systems are specifically limited as to type and size by a testing laboratory, based on actual fire tests. Limitations on hazards that are permitted to be protected by these systems and piping and nozzle configurations are contained in the manufacturer s listed installation and maintenance manual, which is part of the listing of the system. A These systems have the specific pipe size, maximum and minimum pipe lengths, flexible hose specifications, number of fittings, and number and types of nozzles prescribed by a testing laboratory. The maximum and minimum pipe lengths and the number of fittings shall be permitted to be expressed in equivalent feet of pipe. The hazards protected by these systems are specifically limited as to type and size by a testing laboratory, based on actual fire tests. Limitations on hazards that are permitted to be protected by these systems and piping and nozzle configurations are contained in the manufacturer s listed installation and maintenance manual, which is part of the listing of the system. Definitions are supposed to be in single sentences. The balance of this definition is additional information that should be in the annex or in an alternate section of the document. Printed on 3/26/2012 1

16 Report on Comments November 2012 NFPA Log #9 Mark T. Conroy, Brooks Equipment Company Add text to read as follows: During assembly, the piping system shall be examined internally to detect the possibility of contaminants or other foreign materials. Contaminants and foreign materials could affect the extinguishing agent distribution due to a reduction in the effective nozzle orifice area. All extinguishing agent storage containers shall be examined to assure that they are fastened securely to their mounting brackets. The proposed new text provides reasonable minimum requirements for examination during assembly and installation approval to assure safety of these systems and provide a reasonable assurance that the systems will work as intended. 17- Log #7 Arthur Londensky, Northeastern Regional Fire Code Development Committee Revise text to read as follows: Revise section as follows: Expellant gas that is used to pneumatically operate shutoff devices shall be taken prior to its entry into the dry chemical tank containers. Currently 4.9 refer to the tanks as containers. The proposed text correlates with the rest of the document. 17- Log #5 Doug Hohbein, Northcentral Regional Fire Code Development Committee Revise to read: An audible and visual indicator shall be provided to show that the system has operated, that personnel response is needed, and that the system is in need of recharge. The audible and visible indicator shall be placed within 10 feet of the protected equipment. Many times the fire-extinguishing system is located in a remote location from the cooking equipment being protected, such as an adjacent room or above a ceiling. There have been instances where, due to the clean agent being utilized, it is difficult to see that the system has triggered and the audible/visual notification cannot be heard/seen due to the remote or inaccessible location of the system. Printed on 3/26/2012 2

17 Report on Comments November 2012 NFPA Log #10 Mark T. Conroy, Brooks Equipment Company Revise text to read as follows: The completed system shall be tested by a service technician as outlined in The tests shall determine that the system has been properly installed and will function as intended. Only listed equipment and devices shall be used in these systems. The installer shall certify that the installation has been made in accordance with the approved plans and the system listing of a testing laboratory. Verify that nozzles and pipe sizes are in accordance with approved plans and the system listing. Verify that piping supports are securely fastened. Acceptance tests shall include a discharge of dry chemical in sufficient amounts to verify that the system is properly installed and functional. Prior to the test required by , piping shall be physically checked for tightness. A test using nitrogen or dry air shall be performed on the piping network at a pressure not to exceed the normal operating pressure of the extinguishing system and verify that nitrogen or dry air has discharged out of each nozzle in the system. The test is intended to verify that flow is continuous and that the piping and nozzles are reasonably unobstructed. The nitrogen or dry air should be introduced into the piping network at the extinguishing agent container connection. The quantity of nitrogen or dry air used for this test should be sufficient to verify that each nozzle is unobstructed. Nozzle flow should be verified by the installation of balloons or similar devices on discharge nozzles. The method of verification shall be acceptable to the authority having jurisdiction. Piping shall not be hydrostatically tested. Where pressure testing is required, it shall be by means of a dry gas. The labeling of devices with proper designations and instructions shall be checked. The use of dry chemical for the approval test shall be permitted to be waived by the authority having jurisdiction. After any discharge of dry chemical, all piping and nozzles shall be blown clean using compressed dry air or nitrogen. Where the system is connected to a building alarm system, verify that alarm-sounding or displaying devices and remote annunciation devices are functional. Verify that all manual release devices (manual pull stations) are readily accessible and accurately identified. Where a control panel is provided, verify that it is connected to a dedicated circuit and labeled properly. Where a control panel is provided, verify that it is readily accessible and restricted from unauthorized personnel. System operational tests shall be performed and include functional tests of the automatic detection system and the manual release devices. The system shall be properly charged and placed in the normal set condition. Verify that each extinguishing agent storage container is reconnected and the system has been returned to its fully operational condition. After completion of functional testing, if system is connected to an alarm receiving office, the alarm-receiving office and all concerned personnel at the end-user s facility shall be notified that the fire system test is complete and that the system has been returned to full service operational condition. The proposed new text provides reasonable minimum requirements for examination during assembly and installation approval to assure safety of these systems and provide a reasonable assurance that the systems will work as intended. Printed on 3/26/2012 3

18 Report on Comments November 2012 NFPA Log #6 Doug Hohbein, Northcentral Regional Fire Code Development Committee Revise text to read as follows: Where pressure testing or purge testing is required, it shall be by means of a dry gas. We would like the committee to reconsider the original proposal. One purpose for discharging dry powder is to ensure the piping is not obstructed. By adding purge testing as permitted in Annex A, this gives the AHJ an option beyond waiving the dry powder discharge as permitted in Log #1 David R. Hague, Liberty Mutual Property Risk Engineering Add new text to read as follows: The installing contractor shall complete and sign the acceptance test form in Figure ******Insert Figure Dry Chemical System Acceptance Test Report Here****** Currently there is no form for documenting the test results for a dry chemical system acceptance test. The proposed form is consistent with the required tests in the installation standard. This form has been changed from that proposed (and rejected) in the ROP to document the basic common elements that need to be evaluated in all dry chemical systems to document proper operation at the time of acceptance. 17- Log #3 R. T. Leicht, Delaware State Fire Marshal s Office Revise text to read as follows: A service technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online test that is in a manner acceptable to the authority having jurisdiction. Contrary to the Committee Statement to ROP 17-62; Log #11, the wording cannot be too specific since different AHJ s will have different requirements. The AHJ, by definition is the organization, office, or individual responsible for enforcing the requirements of the standard and for approving procedures. There is nothing in the definition that states that this responsibility excludes the responsibility of promulgating rules for his jurisdiction. Committee makes the assumption, without substantiation, that the task of determining competency causes some undue pressure and no substantiation had been provided that shows that this particular portion of the AHJ s responsibility causes any significant burden. If the Committee feels that a sample program, such as written testing, needs to be provided as an option for what the AHJ should establish to confirm the level of competency, that material can be included as guidance in an Annex section. That way, and AHJ may choose that option or may choose to use any combination of other options to determine who is and who isn t qualified in his jurisdiction. Printed on 3/26/2012 4

19 Dry Chemical System Acceptance Test Report Property Information Building Name: Address: Building Owner: Address: Phone/Fax/ Designer / Installer Information Company Name: Address: Contact Person: Phone/Fax/ System Check or Test Installation in accordance with approved plans and listing laboratory. Piping Integrity Test (where required) Operational Test (where required) Detection System Manual release Device(s) Gas Shutoff Electrical Power Shutoff System properly charged and left in normal set condition. One copy of installation and maintenance manual left with owner. Date System left in Service: Results Test Witnessed By: Owner/authorized agent Title Date Installing Contractor Title Date Additional comments: Page 1 of 1 17_F2012_ROC_Log #1_Figure _Rec

20 Report on Comments November 2012 NFPA Log #8 Arthur Londensky, Northeastern Regional Fire Code Development Committee Revise to read: A service technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online test that is acceptable to the authority having jurisdiction. Persons performing maintenance and recharging of extinguishing system shall meet one of the following criteria: (1) Factory training and certification for the specific type and brand of fire extinguishing system being serviced (2) Certification by an organization acceptable to the authority having jurisdiction (3) Registration, licensure, or certification by a state or a local authority having jurisdiction. As currently worded certification if personnel performing work on fire extinguishing systems is a state or local issue. The proposed wording provides better guidance to the user, ahj etc. for what constitutes an approved certification program instead of stating a certification program that may not be acceptable to the ahj. The proposed wording is consistent with other NFPA Standards. Printed on 3/26/2012 5

21 Report on Comments November A- Log #6 Mark T. Conroy, Brooks Equipment Company 17A-4 Incorporate proposal 17A-4 into proposals 17A-2, 17A-3, and 17A-70. Editorial. NFPA 17A Printed on 3/26/2012 1

22 Report on Comments November A- Log #15 NFPA 17A Richard L. Lupien, UTC/Kidde-Fenwal, Inc. 17A-5 I request that the committee reconsider the action taken in the ROP for this log. The following text contains changes from the original log proposal with some renumbering and an additional section added for consideration. 1.3 Minimum requirements are specified for restaurant, commercial and institutional hoods, plenums, ducts and associated cooking appliances. Minimum requirements are also specified for mobile equipment UL Publications Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 300, Fire testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, ANSI/UL 1254, Pre-Engineered Dry Chemical Extinguishing System Units, ASME Publications American Society of Mechanical Engineers, Three Park Avenue, New York, NY Boiler and Pressure Vessel Code, ANSI/ASME B31.1. Power Piping 1998 edition (including B31.1a 1999 Addenda and B31.1b 2000 Addenda) Discharge nozzles utilized for restaurant applications shall be provided with an internal strainer or a separate listed located immediately upstream of the nozzle. 4.9 Storage Containers The wet chemical containers used in these systems shall be designed to meet the requirements of the U.S. Department of Transportation (DOT) or Transport Canada (TC) is used as shipping containers under pressure If not shipping containers under pressure, the wet chemical containers shall be designed, fabricated, inspected, certified, and stamped in accordance with ASME Boiler and Pressure Vessel Code, Rules for Construction of Pressure Vehicles Wet chemical fire extinguishing systems intended to protect restaurants, commercial and institutional hoods, plenums, ducts and associated cooking appliances shall comply with ANSI/UL (6) Mobile equipment Pneumatic actuation piping, hose and tubing that is not normally pressurized shall not require supervision. 5.7 Systems for Protection of Mobile Equipment Only pre-engineered wet chemical systems, including detection systems that have been listed for such use, shall be installed on mobile equipment Compartments or areas that could be subject to fire shall be protected in accordance with the manufacturer s listed installation and maintenance manual Each protected compartment or area shall be provided with a listed fire detection device specified in the manufacturer s listed installation and maintenance manual to automatically actuate the extinguishing system Manual actuation only shall be permitted to be provided if acceptable to the authority having jurisdiction Only the flexible hose and hose fittings specified in the manufacturer s listed installation and maintenance manual shall be used All discharge nozzles shall be located to minimize the likelihood of damage or misalignment and within the limitations and constraints of the manufacturer s listed installation and maintenance manual Location of agent containers, expellant gas cartridges or cylinders, and a manual actuator station(s) shall be appropriate to each application, protected against physical damage and accessible At least one easily accessible manual actuator or operating device shall be provided for use by the equipment operator An additional manual actuator or operating device shall be located so that it is in the path of egress and operable from the ground level If the system is provided with a discharge delay device, both audible and visual alarms shall be provided to warn of the impending system discharge In the event of system discharge, the vehicle being protected shall not be returned to service until the system is recharged and operational. Current applications of wet chemical systems are being utilized on mobile machinery equipment without an applicable standard. This change seeks to ensure that guidance is given to these systems utilizing similar information from the pertinent mobile machinery text in NFPA 17 (Dry chemical extinguishing systems). The existing text Printed on 3/26/2012 2

23 Report on Comments November 2012 NFPA 17A in 17A is primarily focused on commercial restaurant applications but the standard has a broad scope of wet chemical extinguishing systems. 17A- Log #2 John F. Bender, Underwriters Laboratories Inc. 17A-2 Revise text to read as follows: Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 300,, 2005, Revised ANSI/UL 1254,, 2005, Revised Update reference to ANSI/UL 300 to indicate that the date of the UL standard is 2005, with revisions adopted through Add reference to ANSI/UL 1254 in support of TC action on 17A-5 Log #CP1. 17A- Log #7 Mark T. Conroy, Brooks Equipment Company 17A-10 Add a reference to NFPA 72 as the source of the definition. Conformance to the NFPA Manual of Style. 17A- Log #4 Arthur Londensky, Northeastern Regional Fire Code Development Committee 17A-69 Revise to read: A service technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online test that is acceptable to the authority having jurisdiction. Persons performing maintenance and recharging of extinguishing system shall meet one of the following criteria: (1) Factory training and certification for the specific type and brand of fire extinguishing system being serviced (2) Certification by an organization acceptable to the authority having jurisdiction (3) Registration, licensure, or certification by a state or a local authority having jurisdiction. As currently worded, certification if personnel performing work on fire extinguishers are a state or local issue. The proposed wording provides better guidance to the user, ahj etc. for what constitutes an approved certification program instead of stating a certification program that may not be acceptable to the ahj. The proposed wording is consistent with other NFPA Standards. Printed on 3/26/2012 3

24 Report on Comments November A- Log #8 NFPA 17A Mark T. Conroy, Brooks Equipment Company 17A-21 Revise text to read as follows: All remote readily accessible manual operating devices shall be identify identified to the hazard(s) they protect. (See ). From a safety standpoint, all manual operating devices should be identified to the hazard(s) they protect. It would seem odd and would be unsafe to have a manual operating device which is not readily accessible. 17A- Log #9 Mark T. Conroy, Brooks Equipment Company 17A-53 Add the following new text: During assembly, the piping system shall be examined internally to detect the possibility of contaminants or other foreign materials. Contaminants and foreign materials could affect the extinguishing agent distribution due to a reduction in the effective nozzle orifice area. All extinguishing agent storage containers shall be examined to assure that they are fastened securely to their mounting brackets. The proposed new text provides reasonable minimum requirements for examination during assembly and installation approval to assure safety of these systems and provide a reasonable assurance that the systems will work as intended. 17A- Log #10 Mark T. Conroy, Brooks Equipment Company 17A-30 Delete the proposed new text. The requirement is currently in the latest edition of NFPA 96. This type of requirement should be in an occupancy standard such as NFPA 96, which covers all automatic extinguishing systems. It should not be in NFPA 17A which covers the installation requirements. Copying part of the requirement and placing it in NFPA 17A is not only inappropriate, but creates an unnecessary conflict between the two documents. Printed on 3/26/2012 4

25 Report on Comments November A- Log #11 NFPA 17A Mark T. Conroy, Brooks Equipment Company 17A-38 Delete the proposed new text. The requirements for manual actuation devices are appropriately located in the occupancy standard, NFPA 96 and modifications should not be introduced in the installation standards such as NFPA 17A. Recommendations for proposed changes should be submitted to the committee responsible for updating NFPA 96 (refer to of the NFPA Regulations and section V, subsection F of the NFPA Officers Guide). 17A- Log #12 Mark T. Conroy, Brooks Equipment Company 17A-48, 17A-49 Revise text to read as follows: Either a common extinguishing system shall be provided to protect both the ignition source(s) contained within an exhaust system as well as the exhaust system itself, or separate extinguishing systems protecting shall be provided to protect the exhaust system and the ignition sources which shall be arranged for simultaneous automatic operation upon actuation of any one of the those systems. Proposal 17A-48 and proposal 17A-49 were both accepted and they contain different wording. The recommended text provides a clarification of the proposed requirement. 17A- Log #13 Mark T. Conroy, Brooks Equipment Company 17A-50 Delete the proposed new text. Proposal 17A-50 sets up an awkward precedent. A provision addressing all types of automatic fire suppression systems is currently in the occupancy standard, NFPA 96 (paragraph 9.3.3). A conflict has now been created by adding a modified version of the NFPA 96 occupancy requirement. The NFPA Regulations Governing Committee Projects, section covers this topic and the Committee Officers Guide section V, subsection F provides guidance for inter-committee coordination. A modified version of NFPA 96, paragraph should not be added to NFPA 17A. Rather, a committee proposal should be submitted to the NFPA 96 and followed through the process. Printed on 3/26/2012 5

26 Report on Comments November A- Log #9a Mark T. Conroy, Brooks Equipment Company 17A-53 Add the following new text: NFPA 17A Verify that the appliances, hoods, and ducts are properly protected with nozzles and positioned in accordance with the manufacturer s design, installation, and maintenance manual. Verify that nozzles and pipe sizes are in accordance with the manufacturer s design, installation, and maintenance manual. Verify that piping supports are securely fastened. Verify that the installed appliances are the same and in the same locations as the approved system design. Prior to the test required by , piping shall be physically checked for tightness. A test using nitrogen or dry air shall be performed on the piping network at a pressure not to exceed the normal operating pressure of the extinguishing system and verify that nitrogen or dry air has discharged out of each nozzle in the system. The test is intended to verify that flow is continuous and that the piping and nozzles are reasonably unobstructed. The nitrogen or dry air should be introduced into the piping network at the extinguishing agent container connection. The quantity of nitrogen or dry air used for this test should be sufficient to verify that each nozzle is unobstructed. Nozzle flow should be verified by the installation of balloons or similar devices on discharge nozzles. Where the system is connected to a building alarm system, verify that alarm-sounding or displaying devices and remote annunciation devices are functional. Verify that all manual release devices (manual pull stations) are readily accessible and accurately identified. System operational tests shall be performed in accordance with the manufacturer s design, installation, and maintenance manual and include functional tests of the automatic detection system, the manual release devices, the gas shutoff, and to verify that the electrical power shutdown operates. Where a control panel is provided, verify that it is connected to a dedicated circuit and labeled properly. Where a control panel is provided, verify that it is readily accessible and restricted from unauthorized personnel. Verify that each extinguishing agent storage container is reconnected and the system has been returned to its fully operational condition. After completion of functional testing, if system is connected to an alarm receiving office, the alarm-receiving office and all concerned personnel at the end-user s facility shall be notified that the fire system test is complete and that the system has been returned to full service operational condition. The proposed new text provides reasonable minimum requirements for examination during assembly and installation approval to assure safety of these systems and provide a reasonable assurance that the systems will work as intended. Printed on 3/26/2012 6

27 Report on Comments November A- Log #1 David R. Hague, Liberty Mutual Property Risk Engineering 17A-60 Add new text to read as follows: The installing contractor shall complete and sign the acceptance test form in Figure NFPA 17A ******Insert Figure Wet Chemical System Acceptance Test Report Here****** Currently there is no form for documenting the test results for a dry chemical system acceptance test. The proposed form is consistent with the required tests in the installation standard. This form has been changed from that proposed (and rejected) in the ROP to document the basic common elements that need to be evaluated in all dry chemical systems to document proper operation at the time of acceptance. 17A- Log #3 R. T. Leicht, Delaware State Fire Marshal s Office 17A-69 Revise text to read as follows: A service technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online test that is to a level and in a manner acceptable to the authority having jurisdiction. Where required by the authority having jurisdiction the The service technician shall possess a certification document acceptable to the authority having jurisdiction confirming the requirements in Section and issued by the manufacturer or testing organization that is acceptable to the authority having jurisdiction. Contrary to the Committee Statement to ROP 17A-69; Log #8, the wording cannot be too specific since different AHJ s will have different requirements. The AHJ, by definition is the organization, office, or individual responsible for enforcing the requirements of the standard and for approving procedures. There is nothing in the definition that states that this responsibility excludes the responsibility of promulgating rules for his jurisdiction. Committee makes the assumption, without substantiation, that the task of determining competency causes some undue pressure and no substantiation had been provided that shows that this particular portion of the AHJ s responsibility causes any significant burden. If the Committee feels that a sample program, such as written or on-line testing, needs to be provided as an option for what the AHJ should establish to confirm the level of competency, that material can be included as guidance in an Annex section. That way, and AHJ may choose that option or may choose to use any combination of other options to determine who is and who isn t qualified in his jurisdiction. Printed on 3/26/2012 7

28 Wet Chemical System Acceptance Test Report Property Information Building Name: Address: Building Owner: Address: Phone/Fax/ Designer / Installer Information Company Name: Address: Contact Person: Phone/Fax/ System Check or Test Installation in accordance with approved plans and listing laboratory. Piping Integrity Test (where required) Operational Test (where required) Detection System Manual release Device(s) Gas Shutoff Electrical Power Shutoff System properly charged and left in normal set condition. One copy of installation and maintenance manual left with owner. Date System left in Service: Results Test Witnessed By: Owner/authorized agent Title Date Installing Contractor Title Date Additional comments: Page 1 of 1 17A_F2012_ROC_Log #1_Figure 6.4.3_Rec

29 Report on Comments November A- Log #14 NFPA 17A Mark T. Conroy, Brooks Equipment Company 17A-76 Revise to read as follows: Where maintenance of any wet chemical containers reveals conditions such as, but not limited to, corrosion or pitting in excess of the manufacturer s limits; structural damage; fire damage; or repairs by soldering, welding, or brazing, the affected container shall be replaced or hydrostatically tested or replaced in accordance with the recommendations instructions of the manufacturer or the listing agency. The hydrostatic testing of wet chemical containers shall be in accordance with Section 7.5. Recommendations do not belong in the body of the standard. 17A- Log #5 Bill Galloway, Southern Regional Fire Code Development Committee 17A-81 Revise to read: Until such repairs are accomplished, the systems shall be tagged as noncompliant impaired, and the owner or owner s representative responsible for the system shall be notified and where required, the authority having jurisdiction shall be notified of the impairment. The decision and enforcement should remain with the AHJ, not the vendor. The section talks about impaired systems and the correct term that should be used when tagging the system is impaired not non compliant. There are many items that may impair the system such as a fusible link not replaced that does not make the system noncompliant which appears to be the intent of this section. Printed on 3/26/2012 8

Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum

Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum DATE: Tuesday, April 12, 2016 TO: Principal and Alternate Members of the Technical Committee on Dry and Wet Chemical

More information

NFPA 17A. Standard for Wet Chemical Extinguishing Systems Edition {016E4141-A B736-7D }

NFPA 17A. Standard for Wet Chemical Extinguishing Systems Edition {016E4141-A B736-7D } NFPA 17A Standard for Wet Chemical Extinguishing Systems Customer ID 63459974 NFPA, 1 Batterymarch Park, Quincy, MA 02169-7471 An International Codes and Standards Organization IMPORTANT NOTICES AND DISCLAIMERS

More information

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems Report of the Committee on Dry and Wet Chemical Extinguishing Systems Edward J. Kaminski, Chair Schirmer Engineering Corporation, NV [I] Paul E. Buchhofer, Building Inspection Underwriters, Inc., PA [E]

More information

Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum

Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum DATE: May 7, 2015-May 8, 2015 TO: Principal and Alternate Members of the Technical Committee on Dry and Wet Chemical

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

2016 Annual Revision Cycle Consent Document NFPA 75

2016 Annual Revision Cycle Consent Document NFPA 75 2016 Annual Revision Cycle Consent Document NFPA 75 The Committee on Electronic Computer Systems produced a Technical Committee Report that received at least one Notice of Intent to Make a Motion (NITMAM)

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS FIREFIGHTING home smoke alarms REGULATIONS GOVERNING THE NFPA EDUCATIONAL MESSAGES DESK REFERENCE FOR THE FIRE SERVICE AND FIRE AND LIFE SAFETY EDUCATORS MATCHES & LIGHTERS medical oxygen cooking FIRE

More information

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems San Antonio, TX October 12-14, 2016 The following are the meeting minutes from the third meeting of the Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems held in San Antonio,

More information

Introductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation.

Introductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation. NFPA Technical Committee On Fire Hose NFPA 1961 Minutes Task Group Update Underwriters Laboratory November 15 th - 16 th 2016 Tuesday, November 15 th, 2016 Meeting called to order at 8:07 AM by Chairman

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached)

1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached) TECHNICAL COMMITTEE ON WATER-COOLING TOWERS NFPA 214 (F2015) Second Draft Meeting Agenda February 17, 2014 10:00 AM - 1:00 PM EST Web/Teleconference Meeting 1. Welcome. Robert Smith, Chair 2. Introductions

More information

NFPA 550 ROP Meeting Minutes

NFPA 550 ROP Meeting Minutes NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,

More information

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT BLD/SAF-FIR 24-25 September 2009 ROP Meeting Minutes ROP MEETING MINUTES Building Code Life Safety Technical Committee on Fire Protection Features Thursday-Friday, September 24-25, 2009 Meeting Embassy

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

Standards and Safety Update

Standards and Safety Update Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical

More information

Agenda. If you are participating via Microsoft Live Meeting, here is the web address to join the Live Meeting:

Agenda. If you are participating via Microsoft Live Meeting, here is the web address to join the Live Meeting: Agenda NFPA Technical Committee on Manufactured Housing Fall 2012 Report on Comments Tuesday, April 10, 2012 from Noon to 5:00 PM Wednesday, April 11, 2012 from 8:00 AM to 5:00 PM (CDT) Hilton Garden Inn

More information

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.

More information

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

NFPA Technical Committee on Building Systems. NFPA 900 First Draft Teleconference/Web Meeting AGENDA. Thursday, February 13, :00 a.m.

NFPA Technical Committee on Building Systems. NFPA 900 First Draft Teleconference/Web Meeting AGENDA. Thursday, February 13, :00 a.m. 1. Call to Order: NFPA Technical Committee on Building Systems NFPA 900 First Draft Teleconference/Web Meeting AGENDA Thursday, February 13, 2014 11:00 a.m. Noon EDT Online meeting link: http://nfpa.adobeconnect.com/r366m2eaxx6/

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped

More information

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Nonvoting Industrial and Medical Gases Michael W. St. Clair, Chair Ostrander, OH [U] Rep. NFPA Industrial Fire Protection Section

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks R. P. Benedetti DATE: September 16, 2010 SUBJECT:

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET)

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) Item No. Subject 10-10-1 Call to Order (10:00 A.M.) 10-10-2 Roll Call 10-10-3 Staff Remarks 10-10-4

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017.

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017. NFPA 72 SIG-PRO Meeting Minutes NFPA Technical Committee on Protected Premises Fire Alarm Systems (SIG-PRO) Second Draft Meeting, July 17 19, 2017 Charlotte, North Carolina 17-7-1 Call to Order Chair Jack

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

NFPA s Standards Development Process

NFPA s Standards Development Process NFPA s Standards Development Process Revision Cycle 104 weeks or 141 weeks Guiding Principles Due process Openness Lack of dominance Seek society s balance between: Acceptable risk Commitment of resources

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

MEETING AGENDA High Rise Building Safety Advisory Committee

MEETING AGENDA High Rise Building Safety Advisory Committee MEETING AGENDA High Rise Building Safety Advisory Committee Renaissance Blackstone Chicago 636 South Michigan Avenue, Chicago, IL 60605 May 13-14, 2014 Chicago, IL 1. Call to Order. Call the meeting to

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL Fire-CAC Members in Attendance Anthony Apfelbeck (Vice-Chairman) Daniel Finnegan Howard Hopper, P.E. Andrew King Kelly Nicolello

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda]) FINAL MINUTES Healthcare Interpretations Task Force Tuesday, June 15, 2016 Mandalay Bay Convention Center South Convention Center, Level 2 Room Surf F Las Vegas, NV 1. Call to Order. The meeting was called

More information

Technical Committee on Water Mist Fire Suppression Systems

Technical Committee on Water Mist Fire Suppression Systems Date: January 29, 2013 1. Call to Order. Meeting was called to order by Chair Larry Owen at 8:00 AM. 2. Building Safety Message. Building safety was discussed and exits identified by Chair Larry Owen.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX 1. Call to Order. The meeting of the Technical Committee on Fire Tests

More information

2013 Annual Revision Cycle. Report on Comments. A compilation of NFPA Technical Committee Reports on Comments for the 2013 Annual Revision Cycle.

2013 Annual Revision Cycle. Report on Comments. A compilation of NFPA Technical Committee Reports on Comments for the 2013 Annual Revision Cycle. 2013 Annual Revision Cycle Report on Comments A compilation of NFPA Technical Committee Reports on Comments for the 2013 Annual Revision Cycle. Notice of Intent to Make a Motion (NITMAM) deadline: April

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

Correlating Committee on Automatic Sprinklers

Correlating Committee on Automatic Sprinklers Correlating Committee on Automatic Sprinklers First Draft Correlating Committee Meeting December 6, 2016 MEETING MINUTES 1. Call to Order. CC Chair Ken Linder called the meeting to order at 8AM. 2. Self-Introductions

More information

National Fire Protection Association (NFPA) Fire Service Occupational Safety and Health Technical Committee Meeting. October 10 12, 2011 Baltimore, MD

National Fire Protection Association (NFPA) Fire Service Occupational Safety and Health Technical Committee Meeting. October 10 12, 2011 Baltimore, MD National Fire Protection Association (NFPA) Fire Service Occupational Safety and Health Technical Committee Meeting October 10 12, 2011 Baltimore, MD Chairman Glenn Benarick called the meeting to order

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

FINAL* REPORT OF THE MOTIONS COMMITTEE

FINAL* REPORT OF THE MOTIONS COMMITTEE FINAL* REPORT OF THE MOTIONS COMMITTEE ON CERTIFIED AMENDING MOTIONS FOR PRESENTATION AT THE 2012 ASSOCIATION TECHNICAL MEETING JUNE 13-14, 2012 LAS VEGAS, NEVADA I. Introduction. This is the second and

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333 Paul Cabot Administrator National Fuel Gas Ms. Gabriella Davis Recording Secretary, IAPMO Standards Council International Association of Plumbing and Mechanical Officials (IAPMO) IAPMO Group World Headquarters

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122

Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122 Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122 Zurich Hosted 1400 America Lane Schaumburg, Illinois May 22 23, 2013 AGENDA 1. Chair Matt Bujewski calls meeting to order

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Technical Committee on Portable Fire Extinguishers (PFE-AAA)

Technical Committee on Portable Fire Extinguishers (PFE-AAA) Technical Committee on Portable Fire Extinguishers (PFE-AAA) M E M O R A N D U M DATE: July 22, 2011 TO: FROM: Principal and Alternate Members of the Technical Committee on Portable Fire Extinguishers

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI

Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI Technical Committee on Electrical Equipment Evaluation ROC Meeting Agenda September 28-29, 2010 Providence, RI Item 10-09-1 Call to Order Item 10-09-2 Introductions Item 10-09-3 Staff Remarks Item 10-09-4

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

3M Personal Safety Division. Standards Update. NFPA 1981/1982, 2018 Edition. March 30, 2018

3M Personal Safety Division. Standards Update. NFPA 1981/1982, 2018 Edition. March 30, 2018 3M Personal Safety Division Standards Update NFPA 1981/1982, 2018 Edition March 30, 2018 Standards Update NFPA 1981/1982, 2018 Edition The purpose of this presentation is to provide an update on the status

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL RULES AND REGULATIONS CONCERNING 8 CCR 1507-57 BUILDING AND FIRE CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR LIMITED GAMING

More information

NIFAD CONFERENCE 2018

NIFAD CONFERENCE 2018 NIFAD CONFERENCE 2018 LUXOR Las Vegas, NV June 9-11, 2018 AGENDA AND REGISTRATION FEATURED SPEAKERS Richard Roberts, Honeywell Security and Fire Richard Roberts is Industry Affairs Manager at Honeywell

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Technical Committee on Aircraft Fuel Servicing (AIF-AAA)

Technical Committee on Aircraft Fuel Servicing (AIF-AAA) Technical Committee on Aircraft Fuel Servicing () DATE: February 13, 2014 TO: FROM: M E M O R A N D U M and Alternate Members of the Technical Committee on Aircraft Fuel Servicing () Barry Chase, NFPA

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to comprehensively update Section 3004-01 of Title

More information