BUILDING FIRE STRATEGY

Size: px
Start display at page:

Download "BUILDING FIRE STRATEGY"

Transcription

1 UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: Occupying Department(s) / School(s) / Institute(s): University of London Observatory University College London 553 Watford Way, Mill Hill Park London,NW7 2QS Department of Physics & Astronomy Basement Lower Ground Ground 1st Floor 2nd Floor 3rd Floor 4th Floor 5th Floor Roof Level Roof Plant Roof Plant General Building Information: (NB: Height to top floor level & all measurements approx) Building Construction: Evacuation Time: Building Height: Approximate Floor Areas: Class B* 2½ Minutes* <12 m Fry Bldg: 135m² Wilson Bldg: 105m² Radcliffe Bldg: 490m² Fire Brigade Reference Number: N/A Previous Significant Fire Incidents: Occupants: Purpose Group(s) Guidance: Educational (PG 5) None UCL Staff / Students / Visitors General Building Occupancy Building Ownership: Property Tenants: A UCL Property UCL Departments Sleeping Accommodation: Occupant Numbers: None Approx: 75 Variable depending on Lectures etc BS Risk Profile(s): [Para 6.4] Risk profile Level: A2 BS Management Level: [Para 8.3. (Clause 2-10)] Management Level: 2 Date Last Amended: Nov 11 1 of 11.

2 CONTENTS: 1.0. Record of Fire Brigade Equipment & Facilities General Building Information Legislative Requirements Risk Profile Level (BS ) Construction and Compartmentation Means of Escape (Moe) Means of Warning in Case of Fire Means of Securing the Means of Escape Fire Brigade Access and Facilities Disability Provision and Facilities Fire Incidents & Departmental Cooperation on Fire Safety Issues Fire Safety Management Landlord Responsibilities General Statement... 9 A1. General Fire Alarm Cause & Effect Arrangements B1. UCL Building Fire Alarm Aide Memoir to the Fire Alarm System FIRE ALARM INFORMATION & DEFINITIONS (To Assist with Annex B) 1. In buildings (other than dwellings) where shouting fire or ringing a manual gong would not be heard by all occupants in the building is required to have fire alarm meeting BS 5839: Part The law requires that there is the following basic provision of fire alarm systems: A means for raising the alarm to give warning to occupants (e.g. Manual Call points) A means of giving warning of fire to all occupants (bells or electronic sounders that can be heard in all parts f the building) 3.. Automatic Fire Detection (smoke detectors etc) are not a legal requirement but help offset certain risk conditions and may provide other protection to valuable or essential property etc (a). MCP - Manual Call Points (break glass units raising the alarm manually instead of raising the alarm automatically though smoke or heat detection. (b). AFD - Automatic Fire Detection or smoke, flame or heat detection (c). FAP - Fire Alarm Panel (d). FADE - Fire Alarm Activated Do not Enter illuminated warning signs located at building internal / external boundaries (e). Category M - manual systems and, therefore, incorporate no automatic fire detectors. (f). Category L1 - systems installed throughout all areas of the building - the objective of a L1 system is to offer the earliest possible warning of fire, so as to achieve the longest available time for escape. (g). Category L2 - systems installed only in defined parts of the building - the objective of a L2 system is identical to that of a L3 system, with the additional objective of affording early warning of fire in specified areas of high fire hazard level and/or high fire risk. (h). Category L3 - systems designed to give a warning of fire at an early enough stage to enable all occupants, other than possibly those in the room of fire origin, to escape safely, before the escape routes are impassable owing to the presence of fire, smoke or toxic gases. To achieve the above objective it will normally be necessary to install detectors in rooms, which open onto an escape. (i). Category L4 - systems installed within those parts of the escape routes comprising circulation areas and circulation spaces, such as corridors and stairways. The objective of a L4 system is to enhance the safety of occupants by providing warning of smoke within escape routes. Date Last Amended: Nov 11 2 of 11.

3 1.0. RECORD OF FIRE BRIGADE EQUIPMENT & FACILITIES: ITEMS FIRE BRIGADE PROVISION IN THIS BUILDING REMARKS INTERNAL FIRE HOSE REELS: DRY RISING / DROPPING FIRE FIGHTING MAINS: FOAM INLETS: FIRE FIGHTING LIFT: FIRE FIGHTING STAIRS: FIRE SHUTTERS: Internal Dropdown Fire Shutters Provided SPRINKLERS: Basement Only Other Areas GAS SUPPRESSION SYSTEMS Fixed Gas Fire Suppression System Inergen / Carbon Dioxide (CO 2 ) Room Flood System SPECIFIC BASEMENT MECHANICAL SMOKE EXTRACT MEASURES: SMOKE CONTROL MEASURES ELSEWHERE: Smoke Control and Venting Equipment FIREMAN S SWITCHES: Fireman s Switches to isolate High Voltage Hazards by the Fire Brigade EXPLOSIVE SUBSTANCES OR CONDITIONS: Bulk Storage Facility / Other Locations: FIRE ENGINEERING DESIGN & SOLUTIONS PROVIDED: Natural smoke venting using window and doors only Date Last Amended: Nov 11 3 of 11.

4 2.0. GENERAL BUILDING INFORMATION 2.1. General Building Description The University of London Observatory has three buildings, which house the five telescopes on site. In addition to the equipment rooms, other accommodation includes classroom, office, workshop and staff facilities. All buildings on site are small, with the Radcliffe and Wilson Observatories providing all the ancillary accommodation on site. In 1925, Mr J. G. Wilson offered to the University of London a 24-inch reflecting telescope owned by his late father. The telescope had been built by Grubb of Dublin in 1881 and was located at W. E. Wilson's private observatory in Daramona, County Westmeath, Ireland. After consideration of many sites for the permanent location of the telescope, an agreement was reached with Hendon Urban District Council to lease a site in Mill Hill Park for 999 years at a nominal rent. The Observatory building was designed by Mr L. Rome Guthrie and constructed by Messrs Leslie and Co; construction commenced in July 1928 and was completed in The original reinforced concrete observatory building contained the dome for the Wilson 24- inch reflector, a Solar spectrographic laboratory and darkroom, a computing room and a workshop. In January 1930, Mr HR Fry of Barnet presented the University with an 8-inch refractor made by Cooke of York in 1862: Mr Fry met most of the cost of its reconditioning and subsequent re-erection. A new small building was erected in 1931 to house the Fry refractor. In 1934, the Radcliffe Observatory (then at Oxford) was being relocated near Pretoria in South Africa; the Radcliffe Trustees offered the University the twin 24-inch/18-inch astrographic refractor made by Grubb of Dublin in The offer was accepted and the telescope was dismantled and brought to London in 1935 together with its dome and rising floor. Additional land was rented from Hendon Urban District Council and a new building was constructed between 1937 and July The building cost 2300, with an additional 1000 for auxiliary equipment and furnishings and for the re-erection of the telescope, dome and rising floor. The new building was opened on 1 st July Building works completed in 2000 provided a new structure on the Observatory's southern perimeter to house three telescopes (including the restored Fry refractor and an Electron C14) in the Fry Observatory, refurbished and expanded classroom areas, and much-needed office and workshop space. The Department of Physics and Astronomy is based on site and, due to the nature of work, the premises are used during the hours of darkness. Apart from staff and students, the University of London Observatory is open to the public and to schools for educational visits, when around 15 to 20 visitors may attend the site. The site is also used for filming on an occasional basis, when both internal and external areas may be used LEGISLATIVE REQUIREMENTS 3.1. Building Regulations - any works undertaken in this building is subject to the statutory requirements of the latest edition of Part B of the Building Regulations Guidance to satisfying these requirements is provided in the Approved Document B (ADB), 2007 Edition Fire Engineering - there are no fire engineering design or strategies current used in these premises Section 20, London Building Act - the premises are of such a size that they have features and design requirements that are not subject to Section 20 of the London Building Acts Heritage Listing and Grading - the premises are listed Grade 2 by English Heritage. Date Last Amended: Nov 11 4 of 11.

5 3.5. Regulatory Reform (Fire Safety) Order the premises are subject to the provisions of the Regulatory Reform (Fire Safety) Order 2005 and a Fire Risk Assessment regime required under these regulations. A formal RRO Audit is carried out every three years or after any subsequent change Other Statutory Measures - none identified or applicable RISK PROFILE LEVEL (BS ) 4.1. Under BS 9999: Part 6 the following risk profile is given to this building subject to the information available at the time. This profile should always be checked by fire engineers, consultants and architects prior to its use in supporting any building design, resulting in changes to the premises overall fire strategy: Occupancy Characteristics: Level A (Awake and Familiar) Estimated Fire Growth Rate: Level 2 Medium Risk Profile: A2 Minimum Management Level: Level 2 Overall o Para Planning = Level 2 o Para Resources & Authority = Level 2 o Para Staffing Levels = Level 2 o Para Fire Training = Level 2 o Para Work Control = Level 2 o Para Communications Procedures: = Level 2 o Para Maintenance & Testing = Level 2 o Para Liaison with Fire Brigade = Level 2 o Para Contingency Planning = Level CONSTRUCTION AND COMPARTMENTATION All buildings are of brick, block and concrete construction, with sheet steel, domed roofs above telescope areas and some flat roofing. The Radcliffe Observatory building also has a pitched, tiled roof MEANS OF ESCAPE (MoE) 6.1. Time of Evacuation - time of evacuation is dependent on the building construction and occupancy. The construction of buildings is divided into three basic types: Class A - complete non-combustible construction, i.e. elements of structure, floors, and walls with supporting structure of brick or concrete; Class B - traditional construction, i.e. non-combustible walls with combustible floors; Class C - combustible construction, i.e. timber floors and walls Based on these classes arbitrary evacuation times were decided upon and the times that are generally accepted as: Class 'B' construction minutes Note: This is not a hard and fast time, and can be extended or reduced according to the particular circumstances. Date Last Amended: Nov 11 5 of 11.

6 6.3. The Means of Escape (MoE) strategy for this building is based on simultaneous evacuation of all occupants using all available exits and stair enclosures, and is summarised as follows: The occupied areas of the buildings are provided with protected staircase enclosures for means of escape purposes. The premises occupancy is unlikely to exceed the stair capacity, Fry Dome - simple, single storey building, with a maximum travel distance of 16m. Wilson Observatory - simple building, with an observatory level on the upper ground floor level. All travel distances are less than 10m. The upper ground floor is provided with external steps from the balcony and observatory areas. Radcliffe Observatory - the building is on two floors, with single staircase conditions in the Observatory and the south and north wings. o The Observatory has a moving floor that can change the level by around 2m, o A protected staircase enclosure is provided in the north wing. Fire resisting doors have been provided with intumescent strips, but not all doors have been fitted with cold smoke seals. The door to the understairs cupboard does not appear to be fire resisting, o The south wing staircase is not protected. However, travel distances do not exceed 18m, which complies with guidance for small buildings. The means of escape from the first floor classroom passes the high risk workshop and storeroom areas on the ground floor. Only the workshop doors are fire resisting, o The central observatory section is on the upper level and has a walkway around the circular perimeter on both working levels of the Observatory. The resulting travel distances exceed maximum guidelines for single direction escape. Whilst, in the observatory area, the risk is low having total vision, the ground floor area under the Observatory s platform is used for storage, which slightly increases the risk. The ground floor store is strictly controlled and automatic smoke detection has been provided at both ground floor and observatory levels as a compensatory feature. Therefore, the existing arrangements are considered acceptable, Mobility impaired disabled persons can only access the ground floor areas of these buildings, 7.0. MEANS OF WARNING IN CASE OF FIRE This building is equipped with a single stage addressable fire alarm system which when activated, emits a continuous alarm throughout the building, The fire alarm panel is interconnected with all of the three buildings, Automatic Fire Detection (AFD) - heat & smoke detecting devices are provided to Life Risk 3 (L3) Standard, Fire alarm manual call points are found in routes leading from the building (including corridors, landings, staircases & final exits), The fire alarm system is monitored on 24-hour basis by Alarm Receiving Company (ARC), The fire alarm system is being maintained and tested in accordance with: BS 5839: Part 1 through the UCL Director of Estates and the Head of Engineering & Maintenance, 8.0. MEANS OF SECURING THE MEANS OF ESCAPE: 8.1 Emergency lighting is provided in accordance with current standards and conventions and is in working condition. Date Last Amended: Nov 11 6 of 11.

7 8.2. An addressable emergency lighting system is provided in accordance with current standards and conventions and is in working condition The emergency lighting is being maintained in accordance with BS 5266: Part 1, through the UCL Director of Estates and the Head of Engineering & Maintenance FIRE BRIGADE ACCESS AND FACILITIES 9.1. The Fire Brigade have vehicular / other access to Site via the following: Main Entrance (Off Watford Way), 9.2. Dry Riser - dry rising valves are not provided in the premises Smoke Ventilation Provision - is not provided. However, natural smoke ventilation procedures can be applied to most areas including stairs and lift landings Fire Hose Reels - fire hose reels are not provided in the premises Sprinklers - sprinklers are not provided in the premises Gas Fire Suppression Systems - a gas system is not provided in the premises. 9.7 Fire Extinguishers - fire-extinguishing equipment is provided and maintained in accordance with BS 5306: Parts 3 and 8, throughout the building for the use of the staff and fire brigade Fire fighters' Switches for Luminous Tube Signs etc - none provided in the premises Fire Brigade Contingency Plans - the fire brigade contingency plans are provided for this building in information boxes adjacent to the master fire alarm panel, in accordance with BS 9999: 2008: Annex M Maintenance - maintenance of fire brigade equipment and facilities is the responsibility of the UCL Director of Estates and the Head of Engineering & Maintenance DISABILITY PROVISION AND FACILITIES Disabled Refuges - no designated disabled refuges are provided at present Refuge and other provisions will be made when a need arises and a student or staff PEEP requires changes to be made FIRE INCIDENTS & DEPARTMENTAL COOPERATION ON FIRE SAFETY ISSUES General - Heads of Departments occupying the premises are required to liaise and cooperate when dealing with a fire incident with all other Departments, the Landlord if different to UCL Estates and should have suitable arrangements in place as set out in the UCL fire safety standards at Fire Alarm Activation - on activation of the fire alarm system, (either manually or by automatic fire detection) the following arrangements are in place: The fire alarm system automatically sends a fire signal to the an Alarm Receiving Centre (ARC) who then dial 999 and call the fire brigade, directing them to the most appropriate building entrance depending on the location of the system (24/7 coverage), Date Last Amended: Nov 11 7 of 11.

8 Departmental Senior Fire Evacuation Marshals (SFEM) should liaise with each other and provided any assistance necessary to the Fire Brigade, Security and Duty Maintenance Staff etc on their arrival. In addition, they should provide specialist information to the fire brigade and the Local Authorities on the specific hazards related to the premises, laboratories and processes, Note: Departmental staff will need to be self-reliant when dealing with a fire incident at the premises and will need to deal with the fire brigade until the incident is terminated, FIRE SAFETY MANAGEMENT Fire Safety Management Policy: Statement of Fire Safety Management Policy, which reflects the importance University College London attaches to fire safety and is authorised by the Provost & President in his capacity as the Responsible Person, under the Fire Safety Order 2005 is provided. The statement and specific details for training provision can be viewed at the UCL Fire Safety Web Site: Fire Evacuation Marshals (FEMs) and Staff Training: Fire Evacuation Marshals - Heads of Departments shall designate sufficient staff to act as Fire Evacuation Marshals (FEMs), who are to be provided on a ratio of approximately three FEMs per floor or area occupied, during the Departments published opening or normal working hours. FEMs are necessary, as it is not practical to have a meaningful register of occupants. Formal Induction Safety Training (Staff and Postgraduate Research Students) - Heads of Departments shall ensure that all new members of staff and full-time postgraduate research students must attend the Health and Safety Induction Course run by UCL Safety Services, which includes an element of fire safety training and information. Local Fire Induction Familiarisation (Staff and Contractors Employed by the Department) - Heads of Departments shall provide Local Fire Safety Induction familiarisation as part of their local safety arrangements for permanent new and temporary staff. Whether or not directly employed by UCL, but working in their department, to comply with the Fire Safety Order 2005 and Health & Safety requirements. Local Fire Annual Familiarisation (Staff and Contractors Employed by the Department) - Heads of Departments shall provide Local Annual Fire Safety Familiarisation as part of their local safety arrangements for permanent and temporary staff. Whether or not directly employed by UCL, but working in their department, to comply with the Fire Safety Order 2005 and Health & Safety requirements. Fire Evacuation Drills - a formal Annual Fire Evacuation Drill is carried out at the start of the Autumn Term (October) of each year by the UCL Fire Officer / or as required by local management. Any unwanted alarm activations throughout the year should only be treated as supplementary evacuation drills to the annual supervised fire exercise. Heads of Departments, whose premises are not part of the fire drill schedule undertaken by the UCL Fire Officer, must carry out and record at least one annual fire drill. The route for making reasonable adjustment and formulating an Personal Emergency Evacuation Plan (PEEP) is a form called 'Assessment for Emergency Evacuation Planning of People with Restricted Mobility or Sensory Disabilities from UCL Premises' and is available from the fire safety web site ( under Disabilities. Date Last Amended: Nov 11 8 of 11.

9 13.0. LANDLORD RESPONSIBILITIES The Landlord is (University of London) Director of Estates provides all maintenance and support to the premises and acts as the Landlord s representative GENERAL STATEMENT The Fire Risk Assessment and Audit is to provide an assessment of the risk to life from fire in building, and, where appropriate, to make recommendations to ensure compliance with fire safety legislation. It focuses primarily on the building structural condition and the physical adequacy of the building s fire safety and fire brigade provision and responsibility for the maintenance of fire equipment and will generally be undertaken approximately every 3 years. This audit will look at general departmental fire safety management and training requirements, but may not be departmental specific or in sufficient depth for occupying Departments within buildings to satisfy the Enforcing Authority. Therefore, it will be necessary for additional simple local Fire Risk Assessments to be undertaken by the Head of Department for their areas of responsibility. See Technical Note TN077 at A generic Emergency Evacuation Plan for the premises is also provided as part of the Fire Risk Assessment with a general statement on the current disability egress provision. Date Last Amended: Nov 11 9 of 11.

10 Annex A A1. GENERAL FIRE ALARM CAUSE & EFFECT ARRANGEMENTS FOR THE PREMISES WITHOUT MECHANICAL & ELECTRICAL INTERFACE: FIRE DETECTED Fire Alarm Raise Fire Alarm Sounds throughout all buildings Signal to Alarm Receiving Centre (ARC) Occupants Alerted & Evacuation Initiated 999 Call To Fire Brigade Use of Fire Extinguishers FEMs Assist Evacuation Fire Brigade Met at Bldg Escape Routes Clear of smoke or Fire Disable Occupants Assisted from Premises or into Disabled Refuges FB FB FIRE OUT! Professional Fire Fighting Intervention Professional Fire Fighters Aid Rescue PEOPLE OUT! Date Last Amended: Nov of 11.

11 Annex B B1. UCL BUILDING FIRE ALARM AIDE MEMOIR TO THE FIRE ALARM SYSTEM: Bldg No: UNIVERSITY OF LONDON OBSERVATORY MILL HILL Manual Call Points (MCP) with Automatic Fire Detection to Life 3 (L3) Fire Alarm Design Fire Panel Locations Master Fire Alarm Panel: Panel Access Enable: Secondary Panels: Main Entrance to Radcliffe Dome Offices 4 Digit Code N/A Is the system interfaced with any other fire alarm panels? Bldg Name: N/A Interconnected to Other Buildings Yes / No Are FADE signs provided? Fire Alarm Activated - Do Not Enter Signs (FADE) None Do Not Enter Signs Yes / No Is there a gas suppression system connected? Location: None Inergen Gas System Yes / No Is there an Impaired Hearing Pager transmitter connected? Impaired Hearing Pager System: None Deaf Pager Yes / No Fire Signal Monitored Other Information: Is the fire signal monitored? Yes / No Fire signal monitored by the UCL Security Control Room 24/7 All building covered by one fire alarm system Date Last Amended: Nov of 11.

12

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: DEVELOPMENT PLANNING

More information

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Safety Services Fire Safety Fire Strategy for: 132 Hampstead Road (317) UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY Fire Strategy for: Rockefeller & Medical School (201 & 374) UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H)

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

EMERGENCY EVACUATION PLAN

EMERGENCY EVACUATION PLAN UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s) / School(s) / Institute(s): Christopher Ingold

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s) / School(s) / Institute(s): Medical Sciences

More information

EMERGENCY EVACUATION PLAN

EMERGENCY EVACUATION PLAN UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY EVACUATION PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying

More information

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING University College London Gower Street, London WC1E 6BT Contents

More information

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) UCL Safety Services Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 188 TOTTENHAM COURT ROAD University College London 188 TOTTENHAM COURT ROAD, LONDON,

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: Bldg Name: Rockefeller & Medical School (201 & 374) UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 BIDBOROUGH HOUSE University College London 38-50 Bidborough Street, London, WC1H

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 1-19 TORRINGTON PLACE University College London 1-19 Torrington Place, London,

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

Policy for Safe Evacuation of Persons with Disabilities

Policy for Safe Evacuation of Persons with Disabilities Policy for Safe Evacuation of Persons with Disabilities 1. Policy Statement The London School of Economics is committed to promoting access for people who have a disability or long-term medical condition.

More information

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting Fire 5. 0 Discovering

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

FIRE SAFETY POLICY Revised March 2013

FIRE SAFETY POLICY Revised March 2013 FIRE SAFETY POLICY Revised March 2013 CONTENTS Page No 1.0 Statement of Intent 1 2.0 Fire Safety Accountability Structure 2 3.0 Roles and Responsibilities 3 4.0 Fire Safety Management 7 5.0 Fire Risk Assessment

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Middle School, St. Johns Hall, Machen Fire Safety Risk Assessment for Wyclif Christian School Introduction Regulatory Reform Order

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Mandatory Fire Safety Instruction Reference A: Reference B: NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Approved Document B Fire Safety

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

EVACUATION PROCEDURES IN EDUCATION PREMISES

EVACUATION PROCEDURES IN EDUCATION PREMISES EVACUATION PROCEDURES IN EDUCATION PREMISES MARCH 2009 ISSUE 01 1.0 INTRODUCTION 1.1 Every establishment will have its own individual evacuation procedure which should cover the following basic facts:

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

GDST Fire Safety Strategy March 2016

GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy v1.0 March 2016 Page 1 of 17 Contents 1. Introduction 3 2. Compliance Statement 3 3. Fire Safety Strategy Aims and Objectives 3 Strategic

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Ebenezer Chapel,Wyndham Street, Machen Fire Safety Risk Assessment for Small Premises Introduction Regulatory Reform Order The Regulatory

More information

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) Fire Safety Technical Guide FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) UCL Fire Alarm Standards & Specific

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019 Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad

More information

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Fire Safety Technical Note UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Reference: BS 5306-8: code of practice for fire extinguishing installations and equipment on premises. Selection and installation

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

Millfield Schools Fire Risk Prevention Policy

Millfield Schools Fire Risk Prevention Policy Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Health and Safety Services. Safety Guide 5. Fire drills

Health and Safety Services. Safety Guide 5. Fire drills Health and Safety Services Safety Guide 5 Fire drills Fire drills Contents Summary...iii 1. Scope...1 2. Responsibilities...1 2.1. Duties on managers... 1 2.2. Duties of all building occupants... 1 2.3.

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

University of London

University of London University of London Senate House and Stewart House Fire safety arrangements Contents 1. Introduction p.2 2. Fire Risk Assessment documentation p.2 3. Action to be taken by a person discovering a fire

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

Fire safety procedure

Fire safety procedure Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

Fire Safety Policy. Signed Date September on behalf of the Management Committee. on behalf of The Woodlands

Fire Safety Policy. Signed Date September on behalf of the Management Committee. on behalf of The Woodlands Fire Safety Policy Signed Date September 2018 on behalf of the Management Committee Signed Date September 2018 on behalf of The Woodlands To be reviewed: September 2019 All staff need to ensure that they

More information

Ruishton C of E Primary School

Ruishton C of E Primary School Ruishton C of E Primary School Fire Safety Policy (inc Induction Training) & Emergency Plan Date: April 2018 To be Reviewed: April 2020 Fire Safety Duties The following persons have fire safety responsibility

More information

Fire risk management plan. MH/05/Revised/06/17

Fire risk management plan. MH/05/Revised/06/17 Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned

More information

GREAT DENHAM PRIMARY SCHOOL FIRE SAFETY POLICY September 2017

GREAT DENHAM PRIMARY SCHOOL FIRE SAFETY POLICY September 2017 GREAT DENHAM PRIMARY SCHOOL FIRE SAFETY POLICY September 2017 OBJECTIVE This policy is designed to help our school comply with our duties under the Regulatory Reform (Fire Safety Order) 2005. Contents:

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Fire Evacuation Procedure Stroud Campus

Fire Evacuation Procedure Stroud Campus South Gloucestershire and Stroud College Fire Evacuation Procedure Stroud Campus If you would like this document in an alternate format Please contact the Human Resources Department Prepared by: Job Title/Role:

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017 Date: March 2017 Page 1 of 12 FIRE SAFETY POLICY Approval Approved by: University Court Date: March 28 th 2017 Page 1 of 12 Date: March 2017 Page 2 of 12 UNIVERSITY OF ABERDEEN FIRE SAFETY POLICY Contents

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

HEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School

HEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School HEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School OBJECTIVE This Fire Safety Policy is designed to help Putnoe Primary School comply with their duties under the Regulatory Reform (Fire Safety

More information

Fire Safety Awareness Workbook

Fire Safety Awareness Workbook Fire Safety Awareness Workbook For All Staff Please ensure you read the workbook thoroughly and complete the assessment at the end Version 2. Introduction Fire safety training is a mandatory element of

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

(Fire) Emergency Evacuation Plan

(Fire) Emergency Evacuation Plan LAZARI INVESTMENTS LIMITED (Fire) Emergency Evacuation Plan Lazari Investments Maple House 149 Tottenham Court Road London W1T 7BN Version: September 2016 MKDS (Services) Ltd Fire Safety Services & Solutions

More information

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018)

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) FIRE SAFETY POLICY Owner: Health and Safety Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) Review due date: May 2019 Update history: Approved by Council 8 March

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Premises Description Address Area Post Code Tel no. Num of Employees Normal Occupancy Max Allowed Use of Premises Building Length Building Breadth Area 0.00 M² Floors Storeys Below

More information

Kensington Aldridge Academy, London W10

Kensington Aldridge Academy, London W10 Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION

More information

DEF Fire Evacuation and Emergency Planning Criteria

DEF Fire Evacuation and Emergency Planning Criteria DEF Fire Evacuation and Emergency Planning Criteria This criteria should be used to devise individual DEF specific fire evacuation and emergency plans. It is the responsibility of the Clinic Team Leader

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

Areas of the building to which access was not available. Details of any onsite management (if known)

Areas of the building to which access was not available. Details of any onsite management (if known) SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

Fire Evacuation Procedure WISE Campus

Fire Evacuation Procedure WISE Campus South Gloucestershire and Stroud College Fire Evacuation Procedure WISE Campus If you would like this document in an alternate format Please contact the Human Resources Department Prepared by: Job Title/Role:

More information

FIRE SAFETY POLICY. A. Policy Statement

FIRE SAFETY POLICY. A. Policy Statement Overall responsibility for Fire Safety: Delegated responsibility for Fire Safety: Mr J Crocker (Principal) Ms C Lepeck (Student Services Manager) A. Policy Statement This policy has been prepared to help

More information

Fire Procedures. April 2016

Fire Procedures. April 2016 Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Manor House HS.F.119 (rev03) delivering promises improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description

More information

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management WILTSHIRE POLICE FORCE PROCEDURE Fire Safety Management Date of Publication: May 2018 Version: 8.0 Next Review Date: May 2019 TABLE OF CONTENTS PROCEDURE OVERVIEW... 3 GLOSSARY OF TERMS... 3 RELATED POLICIES,

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General

More information

FP-PGN-14 Part of NTW(O)41 Fire Policy

FP-PGN-14 Part of NTW(O)41 Fire Policy Fire Policy Practice Guidance Note Fire Evacuation in Trust Owned and Occupied Premises V02 Date Issued Issue 1 Aug 2017 Planned Review Aug - 2020 Responsible Officer Head of Estates & Facilities (NTW

More information

Fire Safety Policy & Fire Safety Management System Version October 2013 Emergency Evacuation Procedures

Fire Safety Policy & Fire Safety Management System Version October 2013 Emergency Evacuation Procedures Emergency Evacuation Procedures Contents 1. Raising the fire alarm 2. Schedule of patient evacuation 3. Designated fire officer roles 3.1 The Fire Team Leader 3.2 Security personnel 3.3 Shift Technicians

More information

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT Building : Postal Address : Mathematical Institute, Andrew Wiles Building Radcliffe Observatory Quarter Woodstock Road Oxford OX2 6GG OUED Building Number: 550

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

Fire alarm bells (and associated fire detection equipment) are tested on Wednesday mornings between

Fire alarm bells (and associated fire detection equipment) are tested on Wednesday mornings between FIRE SAFETY PROCEDURES, ST MARY S CAMPUS MEDICAL SCHOOL BUILDING These notes supplement the Imperial College London Fire Safety Policy and Code of Practice and give details of local fire safety management

More information