GENERAL FIRE SAFETY TERMS & DEFINITIONS

Size: px
Start display at page:

Download "GENERAL FIRE SAFETY TERMS & DEFINITIONS"

Transcription

1 UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS Fire Safety Vocabulary - for further information and definitions BS EN ISO : Fire Safety Vocabulary - for further information and definitions 1.0. FIRE SAFETY ABBREVIATIONS KEY 1.1. General shorthand and abbreviations used in UCL Fire Safety documentation: ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION FR 30/60 Fire Resisting Construction (30/60 minutes) T/T Thumb Turn fitted to door in direction of escape FRG 30/60 Fire Resisting Glazing (30/60 minutes Resistance FFF Free From Fastenings (i.e. No locking device to be fitted to door) FD30 FD60 Fire Door 30/30 minutes Fire Door 60/60 minutes EF Emergency Fastening (i.e. door to be fitted with an emergency device to allow escape at all times) (S) Cold smoke seals / brushes required. S13 Sign Fire Door Keep Shut or similar SC Self Closing Device S14 Sign Fire Door Keep Locked Shut When Not in Use or similar [Self Closing device not required] VP Vision Panel - If in a fire door must be appropriate FRG S22 Sign Running man Fire Escape FD30(S)SC&VP Fire Door, Smoke Seals, Self Closing with Vision Panel S26 Directional arrow used in conjunction with sign S22 () 3NM 3 Hour Non-Maintained Emergency Light Fitting AFD Automatic Fire Detection 3M 3 Hour Maintained Emergency Light Fitting required S(i) Smoke detector (Ionisation) type Test Key Fish tailed test key facility - wired to provide a local lighting circuit failure. S(o) Smoke detector (Optical) type Addressable Emergency Lighting Addressable Emergency lighting system as per Advance Electronics Ltd H (RoR) Heat detector (Rate of Rise) MCP Manual Call Point (Red - Fire Alarm Break Glass unit) H Heat detector (Fixed) normal setting 65C - unless specified Sounder (Voice) Voice Sounder to be used SCA Self-Closing Automatic Magnetic (Door hold open device connected to the fire alarm system). Date Last Amended: Dec statement of requirements and is in addition to relevant British Standards or any other instructions received from the Local

2 2.0. DEFINITIONS OF TECHNICAL FIRE SAFETY TERMS USED 2.1. In fire safety reporting and specifications, the terms / words and associated meanings will be used: 'Shall' and 'Must' 'Will' 'Should' 'Provide' 'Approved' 'Suitable' Are Mandatory (you will do) Is Informative Is Advisory Means - supply, fix or Install Means - Approved in Writing Means - suitable in the opinion of the authority having jurisdiction 2.2. Various terms are used in fire safety guides and documentation because of their importance concerning the Means of Escape for existing buildings, are defined below. Access Room Accommodation Stairway Cavity Barrier Compartment Compartment Wall or Floor Dead-End Condition Distance of Travel Emergency Escape Lighting Final Exit Means - a room, which forms the only, escape route from an inner room (See Inner Room); Means - a stairway, which is provided for the convenience of occupant; in addition, to that or those required for escape purposes; Means - a construction provided to close a concealed space against penetration of smoke or flame, or provided to restrict the movement of smoke or flame within such a space; Is a part of the building separated from all other parts of the same building by fire resisting compartment walls and /or compartment floors; Means - a fire-resisting wall or floor used in the separation of one fire compartment from another; Means - an area from which escape is possible in one direction only; Means - the actual distance that a person needs to travel between any point in a building and the nearest storey exit; Means - that part of the emergency lighting system provided for use when the supply to the normal lighting fails so as to ensure that the Means of Escape can be safely and effectively used at all material times; Means - the termination of an escape route from a building giving direct access to a Place of Safety such as a street, passageway, walkway or open space, and sited to ensure that persons can disperse safely from the vicinity of the building and the effects of fire; Date Last Amended: Dec 15 2.

3 2.2. Continued: Fire Door Fire-Resisting (Fire Resistance) Fire Safety Engineering Fire / Smoke stopping Inner Room Means of Escape Members of the Public Place of Safety Protected Corridor Means - a door assembly which is designed to hold back fire and smoke for a designated period, and has been tested under the following: Notes: The conditions of test for door assemblies described in British Standard 476: Part 22; or, The conditions of test contained in the British Standard currently in force at the time of the bringing into use of the premises as a factory, office, shop or railway premises; or, The conditions of test in the British Standard currently in force at the time the door was manufactured; would satisfy the criteria for integrity for 20 minutes or for such longer periods, as may be specified in particular circumstances; 1. Normally, such doors should be positively self-closing; 2. Door assemblies with non-metallic leaves should be maintained in accordance with the provisions of British Standard 8214; Means - the ability of a component or the construction of a building to satisfy for a stated period of time some or all of the appropriate criteria specified in the relevant part of British Standard 476; Note - in existing premises, it may not be possible to define the fire resistance of some elements of structure, and a judgement will need to be made on whether the fire resistance is acceptable; Means - an approach, which takes into account the total fire safety package and sets a range of fire safety features against an assessment of the fire hazard and fire risk for the particular premises; Means - seals provided to close an imperfection of fit or design tolerance between elements or components to restrict the passage of fire, heat and smoke; Means - a room from which escape, is possible only by passing through an access room (Note: Inner Rooms are not permitted (travel from inner room to Access Room, only discharging to safety such as corridor etc.) ; Means - the structural means whereby a safe route is provided for persons to travel from any point in a building to a place of safety beyond the building without outside assistance; Guests - not being employed or studying at UCL; Means - place beyond the building in which a person is no longer in danger from fire Means - corridor, which is adequately protected from fire in adjoining accommodation by fire-resisting construction (usually to a minimum of 30 minutes Fire Resting Standard; Date Last Amended: Dec 15 3.

4 2.2. Continued: Protected Lobby Protected Route Protected Stairway Storey Exit Vision Panel (VP) Means - a fire-resisting enclosure providing access to a protected stairway via two sets of fire-resisting and self-closing doors, into which no rooms open, other than toilets or lifts; Means - a route having an adequate degree of protection from fire including walls (other than any part that is an external wall of a building), doors, partitions, ceilings and floors separating the route from the remainder of the building; Means - a stairway, which is adequately protected from fire in adjoining accommodation by fire-resisting construction and either discharges through a final exit or a protected route leading to a final exit; Means - an exit through which persons are no longer at immediate risk from the effect of fire and includes a final exit, an exit to a protected lobby or protected stairway (including an exit leading on to an external stairway), and an exit provided for Means of Escape through a compartment wall via which a final exit can be reached; Means - a fire resisting or plain glazed panel found in doors or partitions, placed there for safety to view an access room circulation traffic beyond the door; Date Last Amended: Dec 15 4.

5 3.0. FIRE DOOR AND GLAZING ABBREVIATIONS: 3.1. In fire safety reporting and specifications, the following abbreviations shall be used when referring to fire doors: ABBREVIATION FD30 / 30 or FD60 / 60 FD30(I) FD30(S) FD30SC FD30VP FD30(S)SC&VP Means - Fire Resisting Door 30 or 60 minutes: Integrity (to keep its structural properties without failure during the specified period); Insulation (to keep its structural properties without failure and not allowing heat to pass through it during the specified period); Means - Fire Resisting Door 30 minutes fitted with Intumescent seals (Hot Smoke Seals) all new fire doors must now be fitted with intumescent seals with a minimum of 12 mm doorstops planted on the frame; Intumescent seals activate at approximately 100 c where they will swell to 70%+ of their volume and to form a seal around the door and frame to prevent hot gases passing through to escape routes or allowing the hot gases to spread the fire further through the building; Means - Fire Resisting Door 30 minutes fitted with Cold Smoke seals / brushes; Means - a Fire Resisting Door 30 minutes fitted with a suitable approved Self-Closing device; Means - Fire Resisting Door 30 minutes fitted with a Vision Panel (made from FRG); Fire Resisting Door 30 minutes fitted with Smoke seals, Self-Closing and fitted with Vison Panel can be commonly abbreviated to FD30(S)SC&VP; 3.2. In fire safety reporting and specifications, the following abbreviations will be used when referring to fire glazing: ABBREVIATION FRG30 / 30 FRG 60 / 60 Means - Fire Resisting Glazing 30 minutes, which can be specified with both: Integrity (to keep its structural properties without failure during the specified period); Insulation (to keep its structural properties without failure and not allowing heat to pass through it during the specified period); End Date Last Amended: Dec 15 5.

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS Fire Safety Technical Note FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS Fire Door Provision In UCL Buildings - what you need to know: Mandatory - all doors on main traffic and circulation routes,

More information

IDD 033C - Fire door sets

IDD 033C - Fire door sets IDD 033C - Fire door sets Why are fire door sets important? Fire doors are one of the most important features of a building s fire precautions and have two key functions: To protect escape routes from

More information

Design Guidelines Fire Safety in New and Refurbished Buildings

Design Guidelines Fire Safety in New and Refurbished Buildings Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

Unit 2 Fire Safety (Zone 1)

Unit 2 Fire Safety (Zone 1) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured

More information

FIRE DOORS RHUL REQUIREMENTS

FIRE DOORS RHUL REQUIREMENTS Fire Safety Technical Guide FIRE DOORS RHUL REQUIREMENTS This guide draws together the general requirements of a range of published standards and reference documents and is to be used in addition to any

More information

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002 a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?

More information

Element C3.5 Means of Escape

Element C3.5 Means of Escape .5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe

More information

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /) Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

A Guide To BS Understanding the selection, spacing and siting of detectors

A Guide To BS Understanding the selection, spacing and siting of detectors World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)

More information

Northern Ireland HMO Fire Safety Guide

Northern Ireland HMO Fire Safety Guide Northern Ireland HMO Fire Safety Guide 2 February 2018 Contents Equality Statement 5 Houses in Multiple Occupation (HMO) Fire Safety Standards 6 1.0 Introduction 6 2.0 Definition of Houses in Multiple

More information

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house THIS DOES NOT COVER 3 STOREY PROPERTIES you must consult with the Private Sector Housing Team on any 3 storey property.

More information

1.4 Provide and fix the following ironmongery.

1.4 Provide and fix the following ironmongery. Schedule of works required for Fire Protection in a first & second floor purpose built masionette above shops where the exit door is at first floor level. THIS DOES NOT COVER NORMAL 3 STOREY PROPERTIES

More information

1. A fire certificate is issued under Section 76 of the Occupational, Safety and Health ActNo. 28 of 2005.

1. A fire certificate is issued under Section 76 of the Occupational, Safety and Health ActNo. 28 of 2005. Guidelines for the issue of a Fire Certificate 1. A fire certificate is issued under Section 76 of the Occupational, Safety and Health ActNo. 28 of 2005. Extract from Occupational Safety and Health Act

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: DEVELOPMENT PLANNING

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B

More information

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS 5.1 General In the previous chapter, the importance of protecting escape routes from penetration by smoke and fire was discussed, so as to ensure they can be safely

More information

Chapter Nursing Homes

Chapter Nursing Homes Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of

More information

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Mandatory Fire Safety Instruction Reference A: Reference B: NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Approved Document B Fire Safety

More information

T e c h n i c a l G u i d a n c e D o c u m e n t. Fire Safety. Dwelling Houses. Volume 2

T e c h n i c a l G u i d a n c e D o c u m e n t. Fire Safety. Dwelling Houses. Volume 2 B Fire Safety Dwelling Houses Volume 2 Building Regulations 2017 T e c h n i c a l G u i d a n c e D o c u m e n t An Roinn Tithíochta, Pleanála, Pobail agus Rialtais Áitiúil Department of Housing, Planning,

More information

Dear Customer. Section Old F8 February 2014 Amendments to F8. Replace with new title page and document history pages 1 2B

Dear Customer. Section Old F8 February 2014 Amendments to F8. Replace with new title page and document history pages 1 2B Dear Customer Please find enclosed Amendment 3, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause F8 Signs of the New Zealand Building Code. THe previous amendment

More information

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Fire Safety Technical Note ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Access Security & Accessible Door Opening Systems - what you need to know: Access

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B

More information

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) Fire Safety Technical Guide FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation) UCL Fire Alarm Standards & Specific

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Safety Services Fire Safety Fire Strategy for: 132 Hampstead Road (317) UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order

More information

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Fire Safety Technical Note UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Reference: BS 5306-8: code of practice for fire extinguishing installations and equipment on premises. Selection and installation

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 BIDBOROUGH HOUSE University College London 38-50 Bidborough Street, London, WC1H

More information

Bristol City Council Private Rented Sector Fire Safety Standards

Bristol City Council Private Rented Sector Fire Safety Standards Bristol City Council Private Rented Sector Fire Safety Standards Introduction The purpose of this document is to provide a basic guide to the fire precautions that are required in privately rented properties

More information

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Fire Safety Technical Guide ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Access Security & Accessible Door Opening Systems - what you need to know:

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings The maintenance series Information sheet 8.1 Fire and Heritage Destruction of the Prince of Wales Theatre by fire on 3 October 1860. It was situated at the corner of King and Castlereagh Streets, Sydney.

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY Fire Strategy for: Rockefeller & Medical School (201 & 374) UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H)

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

Objectives. To review updated IBC and fire test requirements when designing for life safety.

Objectives. To review updated IBC and fire test requirements when designing for life safety. Objectives To review updated IBC and fire test requirements when designing for life safety. To understand the relationship of fire safety and human impact safety. To clarify the difference between fire

More information

LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 3-4, 20 CODE CHANGES Issue : Clarification of when 703.6 can be used rather than 76. 76.2 --rated glazing. --rated

More information

BSF GREENWICH: CROWN WOODS SCHOOL FIRE SAFETY STRATEGY. Report for. Building Design Partnership 16 Brewhouse Yard Clerkenwell LONDON EC1V 4LJ

BSF GREENWICH: CROWN WOODS SCHOOL FIRE SAFETY STRATEGY. Report for. Building Design Partnership 16 Brewhouse Yard Clerkenwell LONDON EC1V 4LJ BSF GREENWICH: CROWN WOODS SCHOOL FIRE SAFETY STRATEGY Report for Building Design Partnership 16 Brewhouse Yard Clerkenwell LONDON EC1V 4LJ TS06651-R01-Issue 4 Issue and amendment record Issue Date Author

More information

GUERNSEY STATUTORY INSTRUMENT

GUERNSEY STATUTORY INSTRUMENT GUERNSEY STATUTORY INSTRUMENT... The Fire Services (Guernsey) Law. 1989 Code of Guidance No 3 - Sleeping Accommodation (other than Hotels and Guest Houses) ----------------- Made............ 13th June

More information

Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No Date:

Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No Date: Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No. 27571 21.02.12 Metro House 79-80 Blackfriars Road London SE1 8HA 0207 960 3939 Fire risk assessment:

More information

BCBC 2012 CHANGES TO PART 3

BCBC 2012 CHANGES TO PART 3 BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization

More information

Technical reference Reference & design

Technical reference Reference & design The requirement for emergency lighting originates from the Fire Precautions Act 1971 and was further enforced by the Fire Precautions (Workplace) Regulations 1997 (Amended 1999). The Regulatory Reform

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

GUARDIAN - SPECIALIST ESCAPE LOCKS

GUARDIAN - SPECIALIST ESCAPE LOCKS Fire Safety Technical Guide GUARDIAN - SPECIALIST ESCAPE LOCKS Notes on Fire Escape Door Locks In general, doors on escape routes (whether or not the doors are fire doors), should either not be fitted

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 188 TOTTENHAM COURT ROAD University College London 188 TOTTENHAM COURT ROAD, LONDON,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

FIRE/SMOKE BARRIER FUNDAMENTALS

FIRE/SMOKE BARRIER FUNDAMENTALS FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection 6 Inside buildings there are two types of fire protection systems: Active Fire Protection and Passive Fire Protection. Both systems should actively work together in the event of a fire. 6.1.1 The four

More information

Building Fire Safety Regulation 2008

Building Fire Safety Regulation 2008 Queensland Building Act 1975 Fire and Rescue Service Act 1990 Building Fire Safety Regulation 2008 Reprinted as in force on 1 July 2009 Reprint No. 1C This reprint is prepared by the Office of the Queensland

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

Short-Term & Accessory Short-Term Rental Safety Certification

Short-Term & Accessory Short-Term Rental Safety Certification Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING University College London Gower Street, London WC1E 6BT Contents

More information

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) UCL Safety Services Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

Accreditation Program: Hospital

Accreditation Program: Hospital ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017 Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical

More information

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD. Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS 1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction

More information

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Kensington Aldridge Academy, London W10

Kensington Aldridge Academy, London W10 Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION

More information

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0)

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0) IS-ORANGE-01-15 Orange Book Ventilation Envirograf Innovators - Developers - Manufacturers Passive Fire Prevention Products T +44 (0) 1304 842 555 F +44 (0) 1304 842 666 sales@envirograf.com www.envirograf.com

More information

Fire Enforcement Report

Fire Enforcement Report AGENDA ITEM 4.4 Fire Enforcement Report Executive Lead: Director of Planning Author: Senior Fire Safety Adviser, Capital Planning & Estate Management Contact Details for further information: Frank Barrett,

More information

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: Occupying Department(s)

More information

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS CONTENTS 100 PERFORMANCE OBJECTIVES 200 DESIGN PARAMETERS 300 SYSTEM DESIGN 310 Design Guidance 320 Outstation Choice 330 Outstation Position 340 Documentation 400 SYSTEM COMPONENTS 410 Master Handsets

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carried out on behalf of EF international School On the 30 Aug 2017 By Matt Pate Copyright FCS Live Ltd 2017 Page 1 of 30 CONTENTS 1. Risk Summary 2. Risk Assessment 01 Persons at

More information

Fire and smoke protection for ventilation

Fire and smoke protection for ventilation IS-ORANGE-01-15 Ventilation Innovators - Developers - Manufacturers Passive Fire Prevention Products Fire and smoke protection for ventilation Products 14 Intumescent Fan Covers (FOR WINDOWS AND WALLS)

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 1-19 TORRINGTON PLACE University College London 1-19 Torrington Place, London,

More information

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL

More information

Maintenance. Why Maintain Fire Doors? Regulations

Maintenance. Why Maintain Fire Doors? Regulations Introduction Fire doors are commonly overlooked as an essential part of a commercial or public building maintenance regime. However, fire doors help sub-divide a building into compartments, slowing down

More information

Approved Document. Fire safety. Volume 1 Dwellinghouses. The Building Regulations Came into effect April 2007

Approved Document. Fire safety. Volume 1 Dwellinghouses. The Building Regulations Came into effect April 2007 The Building Regulations 2010 Approved Document Volume 1 Dwellinghouses B Fire safety Came into effect April 2007 For use in Wales* 2006 edition incorporating 2010 and 2016 amendments VOLUME 1 This 2016

More information