DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI

Size: px
Start display at page:

Download "DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI"

Transcription

1 EE 50 25(R1) SPECIFICATIONS OF ADDRESSABLE FLOOD ALARM SYSTEM ISSUING AUTHORITY DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI

2 2 RECORD OF AMENDMENTS Sl Amendment Authority Date Signature 2. Revision Note: Nil 3. Historical Record: Nil

3 3 CONTENTS SL No Description Page No 1 Scope 6 2 System Characteristics 6 3 Architecture of Flood Alarm System System Configuration Main Control Panel Secondary Control Panel 11 7 Construction Built in Test Equipment 13 9 Environmental conditions Documentation Spares Type Testing EMI/EMC Testing 14 Inspection Information to be supplied when Tendering System Performance Responsibility Services Of Engineers Maintenance Training Product Support Warranty. 21 EE (R1)

4 4 STATEMENT OF TECHNICAL REQUIREMENTS ADDRESSABLE FLOOD ALARM SYSTEM WITH CAPABILITY TO INTEGRATE WITH BDCS/ IPMS 1. Addressable Flood Alarm System (AFAS). 1.1 Scope. This technical specification covers the manufacturing, supply, testing and onboard commissioning of the Addressable Flood Alarm System with capability to integrate with Battle Damage Control System (BDCS)/ Integrated Platform Management System (IPMS) onboard Naval Ships. 2. System Characteristics. 2.1 The Flood Alarm System is required to detect ingress of water at specified locations and accordingly provide audio and visual indication at predetermined locations viz. DCHQ/ MCR/ Bridge/ outside the affected compartment or as decided by the Order placing Authorities. 2.2 The flood alarm sensors energise when the water level increases beyond a pre determined level and de energize when the water falls below the predetermined level, providing an audio and visual (light) alarm at the master and slave (repeater) monitoring panel and other specified locations. 2.3 The system should be suitable for operation on 115V/127V/230V 50/60Hz 1phase, AC as mains supply and all other secondary power supplies required for the operation of the system be derived from main supply. The power to the system should be provisioned through on line UPS. In case main supply fails, the UPS should power the system automatically without causing any interruption in system input power supply. The UPS shall be provided with a maintenance free battery to supply 2 hours back up power. The battery should be maintenance free having a service life of minimum 4 years. 3. Architecture of Flood Alarm System. 3.1 The addressable sensors should be configured with either a Centralised Control or a Distributed Control. In the Centralised Control and Distributed Monitoring, all the addressable sensors can be monitored and controlled from one Programmable Controller with display and the information can be repeated to other positions through digital networks. In Distributed Control and Distributed Monitoring architecture, the sensors can be monitored and controlled from more

5 5 than one Programmable Controller that resides in another host system, usually associated with BDCS/other machinery control platform management etc. The choice between the above two architecture would of course depend on size of platform, no. of sensors, co fitment of the host system, NBCD requirements etc. and to be defined by the Order placing authority. 3.2 Interface Requirements. The System shall have provision for interfacing with Battle Damage Control System (BDCS)/ Integrated Platform Management System (IPMS). Interface protocol shall be finalized between the vendors of Flood Alarm System & BDCS/ IPMS. Depending upon the interface requirement the protocol could be serial RS 485/422/232 or Ethernet gigabit network or any other latest protocol as finalized by the vendors and Order placing authority. The system should display following on BDCS/ IPMS display: (a) (b) (c) Alarm due to flooding (indicating place of flooding) System Fault Alarm (indicating type of fault) System health monitoring status. 4 System Configuration. The Flood Alarm System should be designed to have modular construction. Details of major units of the system are as follows: 4.1 Flood Sensors. The function of flood sensors is to provide requisite signal to flood alarm control panel in case of presence of water in vicinity of the sensor. The flood sensors will be located in underwater compartments as decided by Naval authorities. The sensors will be fitted at 15/ 25 cm above the lowest possible space in the compartment and should perform satisfactorily in both positions. The sensors should conform to IP 67 or better specifications and JSS specs. The flood sensors may come in contact with fluids other than sea water like oil etc and should therefore be able to function satisfactorily in presence of fluids/ contaminated water. Flood sensor should have dual pick up for redundancy. The sensors will be provided with bracket for facilitating fitment inside the compartment and should have provision to avoid bimetallic corrosion. Indication of flood alarm signal to main flood alarm control panel and secondary flood alarm control panel/ repeaters/ slave should be achieved without any time lag. The sensors may be configured in zones or directly connected to the main flood alarm control panel depending on the size of the ship/as required by the Indian Navy. 4.2 Type of Sensors. There are various types of flood detection sensors available for selection of Order placing authorities depending upon application and size of compartment. The types of sensors required for integration with flood alarm system are: EE (R1)

6 6

7 7 (i) (ii) (iii) (iv) (v) Magnetic Float Switch Sensor Pressure Sensor Vibrating Fork /Piezo electric Sensor Microwave Sensor Dual Level Flood Sensor 4.3 Selection of Flood Sensors. The type and number of flood sensors for installation onboard ship will depend upon the type and size of each compartment. The under mentioned guidelines though not limited to be followed for selection of flood sensors for use onboard naval ships: (a) Magazine Compartments. All magazine compartments onboard ships are to be provided with low level flood sensors. Each magazine compartment is to be provided with a minimum of two flood sensors to give indication of presence of water before the level reaches to 0.1 m. The flood sensors to be fitted in magazines must be electrically insulated, intrinsically safe and spark proof. Zener barrier units may also be connected in sensor circuit to make it intrinsic safe completely. Pressure type of flood sensors are suitable for magazine compartments. (b) Bilge Compartments. The sensors used in bilge compartment should conform to IP 68 specifications, easy to install and maintenance free. Microwave type of flood sensor is suitable for bilge compartments. (c) Other Underwater Compartments. All under water compartments are to be fitted with a minimum of two sensors (port & stbd). One of the sensor should have low as well as high level flood indication. The low level indication is to appear before water level rises to 0.3 mtr and high level at 1 mtr. The main machinery spaces are to be fitted with four sensors on port & stbd sides and fore and aft of the compartment. Dual Level sensor, Float Level switch sensor and Vibrating Fork type flood sensors are suitable for machinery and general under water compartments. 5. Main Flood Alarm Control Panel. The panel is used for indicating the presence of water based on signal received from flood sensors. It receives signal EE (R1)

8 8 directly from the sensors or through JBs with amplifiers units. The requirement of main flood alarm control panel are as follows:

9 9 (a) The panel should be LCD based, touch screen type and panel housing should conform to IP 55/ JSS specs. (b) The main flood alarm control panel is to provide audio and visual alarm in case of flooding in vicinity of any of the flood sensors. The number of indicators will be as many as the number of compartments in which sensors are installed. In case of compartments having more than one sensor, alarm will be triggered when any of the sensor detects presence of water. However, separate indications are to be provided for each sensor collocated in same compartment. (c) The system shall be designed to give an audio visual alarm indication within four seconds of water crossing the threshold value. The activation of any sensor is to initiate an audiovisual alarm at the control panel indicating the zone and compartment details in which the detector has operated. (d) Facility shall be provided in the control panel to connect external hooter fitted in crew accommodation, service space, control station & Machinery spaces if a flood alarm is not acknowledged within two minutes after activation. (e) The audio and visual alarm once triggered should continue to be ON until physically reset at the main flood alarm control panel. There should be provision for accepting the alarm (individually for audio and visual alarm) so that buzzer can be switched off and flashing stops. However, visual indication of flooding should still be available. (f) In no alarm state, all indications will be off, but power indication and system health indication must glow. (g) Fault Diagnostic. The system shall have inbuilt fault diagnostic and status scan programme which shall at a pre defined interval scan the status of each module/unit and sensor and indicate faults if any, on Main Control Panel along with its address, zone configuration, location text, loop number etc. (h) In addition, the system should have provision for self test and should be capable of checking following from the flood alarm control panel: EE (R1)

10 10 (i) (ii) (iii) (iv) (v) Defect/ malfunction of any sensor. Short circuit in system/ associated cabling. Open circuit in the cable. Defect in any of the system subunits. Power failure (j) Visual alarm is to be initiated in case of any fault as per para 5 (g) & 5(h) above. The indication will be cleared automatically when the fault has been cleared. (k) In fault condition audio visual alarm shall be initiated. The audio alarm will be made off by Accept push. However, steady visual alarm will persist until the Reset push is operated. (l) While one fault is existing and audio alarm is silenced or warning lights of cleared faults are restored to normal, indication of new faults must not be affected. (m) When Reset push is operated individual alarm or warning lights of cleared faults are restored to normal, but if any faults are still present, their indications must not be affected. (n) Password Protection. User control on the Main Control Panel shall be password protected. Pressing any control key on the panel shall prompt for appropriate level password. Authorisation to access higher level system functions such as device isolation and configuration data entry through panel keyboard should also be password protected. (p) Event Logging. The system should have provision of Online event logging of various alarms with date and time for each addressable detector. The data to be retained using non volatile memory. (q) The main control panel shall have provisions for interfacing with a graphic based PC / LCD front end to provide the ship s GA drawing as an

11 11 underlay. The individual address of each sensor along with all kill card data would enable speedier response to flooding.

12 12 (r) The interface network for sensors shall be in a loop which shall not be rendered ineffective due any fault occurring in it. Further, the system can be reconfigured in the event of a failure of the sensor(s). (s) The system architecture should cater for requirement of signal shaping or line repeaters to cater for longer distances between sensor and panel. (t) The design should have provision for isolation of any zone(s). 6. Secondary Flood Alarm Panel/Repeaters/ Slave Indicators. There may be requirement of secondary flood alarm panel/repeaters/ Slave Indicators in addition to the main flood alarm control panel depending upon the ship size and envisaged flood alarm system configuration. These panels should be able to provide audio and visual indication including location of flooding similar to main control panel. However, the resetting of alarms and self test will be done only from main control panel. The alarms in these panels will be reset once the alarm has been reset at the main control panel. The panel housing should conform to IP 55/ JS specs. 6.1 The exact configuration of the system will vary from ship to ship and may vary for different OEMs. The system may include other subunits like junction boxes, annunciators, isolation transformers etc. 7. Construction. 7.1 Enclosure. The construction of Main Control Panel and Secondary Flood Alarm Panel/Repeaters/ Slave Indicators etc. should be ruggedised to withstand the severe marine environment prevalent onboard ships. The enclosure of Main/Secondary/Repeater panels should conform to IP 65 specifications. 7.2 Mounting. The control panel shall be bulkhead mounted type, drip proof, enclosed in sheet steel cubicle made of 14 SWG sheet steel/ Aluminium. All the components shall be mounted such that they are accessible from front for operation, maintenance and replacement. The panel shall be hinged type provided with adequate number of latches operated by keys. EE (R1)

13 The size and weight of the panel shall be kept to a minimum consistent with electrical and mechanical requirements. Units weighing more than 40 Kgs are to be provided with suitable lifting arrangements. 7.4 Cable entry should be from the bottom of the panel. The panel should be supplied with detachable gland plate at the bottom of the panel. The panel and other components of the system should be supplied with cable entry glands suitable for yard supply cables. Yard will furnish overall dia of cables on receipt of interconnection diagram from the supplier. 7.5 Cable terminal connections and procedure for laying the system cables onboard ship etc. are to be clearly brought out at the time of submitting the technical proposal. 7.6 The supplier should generate detailed cable diagram for the complete system, render assistance in preparation of system cabling and connection diagrams and during STW / Harbour Acceptance Trials of the system. 7.7 All cables used in the system should be Fire retardant, zero halogen toxicity and should be capable to withstand operating temperature from 30 degree Centigrade to +120 degree centigrade. Cables in the bilges and magazines are to be laid through metallic conduit. 7.8 The cables used for internal wiring shall be provided with identification ferrules on both ends. 10% spare terminals are to be provided on the terminal block of the panel. Suitable crimping socket of reputed make shall be fitted in the terminals for cable termination. 7.9 Cable Glands. Cable glands, entry, termination and Junction components should be as per NES 514 in addition to DSG/EED/VI/1535/R Tally Plates. All units must have tallies and diagram plates conforming to NES Block diagram of system will be supplied in Aluminum anodized plate and to be fitted on inner side of the control panel front door.

14 14 8. BUILT IN TEST EQUIPMENT (BITE) 8.1 Features of BITE The BITE will be responsible for assessing the state of a sub system before the application software is invoked. The BITE software should run automatically at power up or in any other mode of operation. It should run without the operating system and will have total control over the sub system hardware and if there is no fatal errors detected the control will pass over to the operating system. The design of the system is to cater for the following features: (a) Built in test (BIT) facility to identify, locate and indicate to the operator any fault that has occurred in the system during operation. The BITE shall detect 100% of all fatal faults. BIT messages shall be displayed on the console. Further, the BIT shall isolate 95% of all detected faults to one line replaceable unit (LRU) and 100% of all detected faults to two or three LRUs. The BITE shall be capable of identifying the faults in at least (and not limited to) the following: (i) Sensors: Sensors faults like the sensor value going out of limit. (ii) Processors: Timeouts to identify the faulty programs sequences, power supply faults, memory faults, peripheral I/O faults. (iii) Communication: Detection of physical communication breaks and excessively high error rates. (b) Diagnostic Hardware and Software tools to enable trouble shooting up to component level repairs at a qualified shore based depot facility. (c) Results of built in tests of system shall be able to be displayed on HMI. If required, BIT results and contents of memory shall be able to be downloaded into the portable diagnostic terminal via the equipment s diagnostic port for more detailed troubleshooting. (d) On line help display of system maintenance manual for preventive and corrective maintenance procedures and Circuit Schematics of the sub systems of the AFAS (and operators manual) shall be possible from main console.

15 15 (e) The failures reported by BITE should be correlated to the Circuit Schematics and Maintenance manual online held display as mentioned above.

16 16 9. ENVIRONMENTAL CONDITIONS 9.1 The system is to be capable of operating in the following environmental conditions: (a) Storage temperature: (b) Operating temperature: (c) Humidity: (d) Vibration: (e) Ship motion: 0 to 70 deg. C 0 to 55 deg. C 95% RH condensing at 35 deg. C As per MIL STD 167 Type I Roll + or 30 deg, period of roll 10 s (f) Pitch 7 degrees fore and aft of centerline. Period 6 seconds. (g) List: permanent 20 degrees either side. 10. DOCUMENTATION 10.1 System Documents Provision of adequate documentation for effective operation and maintenance of AFAS is an important aspect of the contract. The documents should be as per MIL N 7298C whereas the format of the documents should be as per Service Standard JSS 0251 or equivalent. Document sizes shall be according to metric standards. All drawings and documents shall contain dimensions and other parameters in metric units. The following technical documents shall be prepared and supplied as required: (a) User Hand Book (b) Technical Manual Part I (Technical description/ circuit drawings) (c) Technical Manual Part II (Preventive and Corrective Maintenance routines and trouble shooting) (d) Technical Manual Part III

17 17 (Overhaul and Reconditioning)

18 18 (e) Technical Manual Part IV (Manufacturer s Parts List, Layout drawings of the PCB and sub units) 10.2 Drawings The drawing package is to include all drawings, specifications and details sufficient to enable complete repairs and maintenance of system. Drawings are to be delivered in full size reproducible form and as CAD files on electronic media. The following information is to be included in the engineering drawings and associated lists of the AFAS: (a) Dimensional outline, in metric units, of all major assemblies showing overall and principal dimensions in sufficient details to establish the limit of space in all directions required for installation, operation and maintenance. (b) A table of reference drawings to include drawing number of each major assembly. (c) A block diagram of all major assemblies showing interconnection between these assemblies. (d) etc. (e) (f) Location, type and dimension of cable entrance plates, connectors, Any special instructions for installation, preservation, painting, etc. Heat dissipation Manuals In addition to the general requirements covered by the data ordering document, the content and arrangement of the manuals shall be as follows: (a) (b) (c) Front matter General information Installation Specifications

19 19 (d) Operation (e) Maintenance, repair and trouble shooting for levels up to second level maintenance. Component level maintenance procedures shall be offered as an option. (f) (g) (h) (j) (k) Parts identification Test Data Drawings reduced size Appendix inserts on special components Software Validation The technical manuals shall be produced in accordance with MIL M 7298 C and shall be provided in both hard copy form and on optical media (CD ROM). Electronic documentation shall be compliant with the Computer Aided Logistics Support (CALS) standards. Evidence of prior experience in generating CALS compliant AFAS documentation shall be provided along with the technical offer Software Documentation The software documentation that has to be supplied as deliverables and as part of the software development process and the documentation template and description will be in accordance with MIL STD 498, MIL STD 2167A, and ISO Further, it is imperative that the supplier is to provide the complete source code of all the applications residing on all the AFAS nodes. In addition, it is imperative that the supplier submits references of past projects where the supplier has followed the above quoted standards for software development Trial Documents The trial documents have to be prepared by the vendor and the same has to be approved by NHQ before its promulgation. The document will outline the type of tests, test procedures, and the validation criteria for evaluating the system. The trial documents are as follows (not limited to): (a) (b) Factory Acceptance Test Schedule. Harbour Acceptance Test Schedule.

20 20

21 Hardware Documentation Hardware documentation in respect of hardware units like computers, interface units, data bus, I/O cards modules, control consoles, panels etc. specially designed by the firm must contain detailed information. The following documentation should be supplied by the firm: (a) System Description. This document shall describe the system level concepts, inter connectivity, technical description of interfaces, communication protocols including block diagrams, test procedures using BITE and first level maintenance procedures. (b) Circuit Diagrams. Detailed circuit diagrams depicting implementation of various schemes along with signal description to be supplied. (c) Maintenance Manuals. Manuals containing hardware details of all repairable units to undertake fourth level maintenance should be provided. (d) Technical Specifications. This document shall be described the technical specifications of the hardware equipment used including details of I/O cards controllers etc. (e) Installation Specification. This document shall include installation specifications and drawing of all hardware units. (f) Hardware User Manual. This document will contain all aspects pertaining to initial start up of the system, hardware configuration settings procedures. 11. MISCELLANEOUS Spares The onboard spares, base & depot spares and test equipment is to be recommended by the supplier. Such recommendations are to be commensurate with the reliability of critical components and component use in the system. Special tools and test equipment is to be supplied for onboard maintenance On Board Spares. An itemized list of OBS, special tool and special test equipment, which will be supplied with the main equipment, is to be furnished along with the quotation for the main equipment. The OBS and special tool are

22 22

23 23 to be catered for all of the ship s staff onboard maintenance routines and possible repair requirements. The OBS and tools should include following: (a) All spares required for exploitation of system up to 2 years. (b) One set of important assemblies to effect repair by replacement. (c) plant. One set of general purpose maintenance tools along with each (d) One set of special tools required for disassembling/assembling of components to effect repair by replacement. (e) One ships set of onboard spares recommended by supplier and approved by IHQ to be supplied along with equipment. CPL/PIL and item wise cost is to be forwarded along with the list of onboard spares while obtaining IHQ approval Five Year Base & Depot Spares/Comprehensive Part List. Base spares recommendation is to cover maintenance/overhaul requirements for 5 years including two refits. Recommendations for insurance holding of long lead items are also to be indicated. Itemized cost of B&D spares are to be forwarded with the main offer Supplier to forward a list of Base & Depot spares for 5 years maintenance indicating Makes, Part Number and Cost of the each item. The list is to be provided in INCAT documentation format List of OBS and B&D spares are to be provided as soft copies in addition to hard copies in the ILMS format mentioned above Installation Spares. A set of installation spares as recommended by Supplier is to be supplied along with main item Installation Materials. All installation materials are to be supplied by the firm e.g. (shock/vibration mounts, free end connectors/plug/sockets, crimping sockets/terminals etc.) required to complete the installation of system onboard ships. Any other material required for installation of the system to be supplied by the supplier. EE (R1)

24 Packing. Each of the item is to be individually PIP packed, suitable identification label giving details such as Sr. No. of the item, Order No. etc. are to be marked legibly on outside the packing, which should be prominently visible. On board spares/installation spares are to be packed in separate cases individually with word On Board Spares and B&D Spares and Installation Spares distinctly marked on each cases. The lists are to be attached to the cases. 12. Type testing. Type testing will be in accordance with JSS (for ship borne equipment protected (class N1). The applicable tests are as follows: Sl TEST SPECIFICATION (a) Vibration JSS Test 28 (b) High Temperature JSS Test 17 (c) Damp heat JSS Test 10 (d) Drip proof JSS Test 11 (e) Low Temperature JSS Test 20 (f) Immersion JSS Test 19 (g) Mould growth JSS Test 21 (h) Bump JSS Test 5 (j) Shock/Impact JSS Test 24 (k) Corrosion (salt) JSS Test 9 (l) Contamination JSS Test 6 (m) Ship Motion NWS 1000 Pt 1 Chap 1 Section 8 (n) Effectiveness of Enclosure Against Immersion NES EMI/EMC Testing. The AFAS should meet the EMI/EMC test requirements as per MIL STD 461 E.

25 Inspection and Testing Factory Acceptance Trial Report. Supplier to provide Factory Acceptance Trial Reports indicating details of tests conducted and test reports thereof. The supplier to prepare a draft ATP and submit for approval of Navy.FATs will be undertaken as per approved ATPs. Further, the equipment will be inspected by nominated inspector of Navy based on approved QAP and drawings. 15. Information to be supplied when Tendering. (a) A brief specification of the equipment offered, including a statement showing any way in which the equipment is not expected to meet the stipulated requirement. (b) (c) (d) (e) (f) Overall dimensions and proposed fixing arrangement. Estimated total weight Wiring diagram, circuit, Control and protection system. Control and indication facility. Heat dissipation (g) Confirmation is required that all tests indicated in the specification can be under taken at the manufacturer s works, otherwise any alternate arrangement proposed are to be stated. (h) (j) Maintenance space required for the equipment. Power load requirement. 16. System Performance Responsibility. Supplier has to under take full responsibility for ensuring satisfactory performance of the system onboard ship.

26 Services Of Engineers. Services of Engineers are to be made available for advice/assistance in connection with onboard installation, defect rectification, testing, tuning, Setting to Work, commissioning of the system and presentation of HATS. Any installations and spare material required during any of these stages are to be supplied/replenished by the supplier free of cost. Any special equipment required for testing/stw are to be brought by the service Engineers. 18. Maintenance. The 1 st /2 nd level maintenance will be carried by SS and 3 rd and 4 th level maintenance support will be provided by the vendor on the basis of Annual Maintenances Contract. 19. Training Complete training package for onboard exploitation, and maintenance, and for second level maintenance, along with tools and test kit, is to be offered. Third level (depot level) maintenance shall be offered together with the required special tools and test equipment. Training dockets for ship s staff and dockyard personnel are to be separately formulated. Training should preferably be carried out in India. Extensive use of simulators/stimulators may be made to provide a near real scenario of the total system to aid in the training. However, if such facilities are not feasible, the training may be conducted at the OEMs premises. 20. Product Support The supplier should confirm product support for a minimum period of 20 years for the equipment offered by them from the date of commissioning of the system. Essential infrastructure to sustain the system for 20 years from the time of commissioning should be recommended and included in the technical proposal. 21. Warranty. The equipment with associated controls/instrumentation is to be guaranteed for stipulated performance for 18 month after commissioning. The equipment supplied shall be warranted from defects, manufacturer and performance for the said period and cover all the defects arising from malfunction

27 27 through design faults, inappropriate material, bad production and nonconformance to specifications. Any expense because of repairs/supply of spares against guarantee defects is to be borne by the supplier.

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS EED- 50-23 SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS ISSUING AUTHORITY DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI 110011 2 RECORD

More information

Annexure - 1. Detectors: Fire Alarm Control Panel :

Annexure - 1. Detectors: Fire Alarm Control Panel : Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP),

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

QUESTIONNAIRE FOR DETAILS IN RESPECT OF MAGAZINE FIRE FIGHTING SYSTEM

QUESTIONNAIRE FOR DETAILS IN RESPECT OF MAGAZINE FIRE FIGHTING SYSTEM Appendix A (Refers to Para 3) QUESTIONNAIRE FOR DETAILS IN RESPECT OF MAGAZINE FIRE FIGHTING SYSTEM Ser Information Required 1. Can you design, supply, manufacture, install, setting to work and commission

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

EED STATEMENT OF TECHNICAL REQUIREMENTS OF SHIP INSTALLED RADIAC SYSTEM FOR NAVAL SHIPS

EED STATEMENT OF TECHNICAL REQUIREMENTS OF SHIP INSTALLED RADIAC SYSTEM FOR NAVAL SHIPS EED- 50-42 STATEMENT OF TECHNICAL REQUIREMENTS OF SHIP INSTALLED RADIAC SYSTEM FOR NAVAL SHIPS ISSUING AUTHORITY DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI 110011 2

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range Fire Detection MINERVA Marine MX T2000 Panel Range Features: Enhances fire detection and eliminates unwanted alarms using fuzzy logic Assists fire fighting and training by providing on-screen risk management

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

E-17 Flammable Gas Detection and Alarm System

E-17 Flammable Gas Detection and Alarm System Guideline No.E-17 (201705) E-17 Flammable Gas Detection and Alarm System Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Part: I TECHNICAL SPECIFICATION

Part: I TECHNICAL SPECIFICATION Part: I TECHNICAL SPECIFICATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR THE WORK OF DESIGN, SUPPLY, ERECTION AND COMMISSIONING INCLUDING CIVIL WORK OF NITROGEN INJECTION

More information

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS SPECIFICATIONS FOR LV DIGITAL PANEL METERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

SOUND RECEPTION SYSTEM

SOUND RECEPTION SYSTEM STANDARD FOR CERTIFICATION No. 2.9 SOUND RECEPTION SYSTEM APRIL 2009 Veritasveien 1, NO-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD (DNV) is an autonomous and independent foundation

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Presented By. BEI Security

Presented By. BEI Security Presented By BEI Security Fiber Optic Perimeter Intrusion Detection Systems BEI Security 30 years of experience in security and surveillance Fiber optic perimeter detection Video motion detection Covert

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A FIRECLASS Networking Addressable Fire Alarm Control Panels From Software version 21 Product Application and Design Information FC-A-FCNET-A Doc. version 1 23. March 2012 FIRECLASS. Hillcrest Business Park,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Advanced FireAlarm Panel 1-4Loop

Advanced FireAlarm Panel 1-4Loop Advanced FireAlarm Panel 1-4Loop Advanced Technologies Advanced Electronics Ltd IP Gateway Monitoring and interrogation via the internet Password protected multiple user permissions Event notification

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1100X December 2017 Page 1 of 14 AE-FP-001-IN-R5-E-12/17 This document is intended to provide

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150 Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1150 April 2018 Page 1 of 14 AE-FP-005-IN-R1-E-04/18 This document is intended to provide

More information

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone April 15, 2014 Page 1 of 14 G6DA0115-001 This document is intended to provide performance specifications

More information

Specification for On-Line UPS Battery Monitoring and Data Management System

Specification for On-Line UPS Battery Monitoring and Data Management System 1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008 TCD Telemetry Communications Device Installation Guide Interface for the Emizon managed network Issue 1: February 2008 This guide sets out a simple check list together with a step-by-step guide to the

More information

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family NexSysLink CAN Instruments Product Family 2 CAN Display Operation Manual Contact Beede Beede Electrical Instrument Company, Inc. 88 Village Street Penacook, NH 03303 (603) 753-6362 Toll-free 800-451-8255

More information

Technical Manual. Level Alarm Unit CARLA & WIDS

Technical Manual. Level Alarm Unit CARLA & WIDS CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

Indicators for Rudder Angle, Rate of Turn, Propeller Shaft Revolution and Propeller Pitch

Indicators for Rudder Angle, Rate of Turn, Propeller Shaft Revolution and Propeller Pitch STANDARD FOR CERTIFICATION No. 2.9 TYPE APPROVAL PROGRAMME NO. 844.40 - MED A1/4.20-4.21-4.22-4.9 Indicators for Rudder Angle, Rate of Turn, Propeller Shaft Revolution and Propeller Pitch FEBRUARY 2012

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No.

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No. Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi -110003, Ph. No. 011-49854100 TENDER NOTICE Sealed tender in two separate bids a) Technical bids,

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

7.3 Design and Development Design and development planning Design and development inputs Design and development outputs 7.3.

7.3 Design and Development Design and development planning Design and development inputs Design and development outputs 7.3. Rev. 1 03/05/2015 ANNEX A to the Yokogawa Corporation of America Quality Assurance Manual For Additional Requirements selectively applied to ATEX and IECEx certified products CONTENTS 1. Scope 2. Purpose

More information

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM Page 1 of 5 CONTENT 1.0 Content 2-2 2.0 Introduction 3-3 3.0 Intent 3-3 4.0 Scope of Work 3-3 5.0 System Component overview 4-4 6.0 Operation Philosophy

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

GRAVINER Mk 6 OIL MIST DETECTOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL

GRAVINER Mk 6 OIL MIST DETECTOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL GRAVINER Mk 6 OIL MIST DETECTOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL 59812-120 PROPRIETARY RIGHTS NOTICE The information contained in this manual is the property of Kidde Fire Protection Services

More information

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Manual# 1100334 User s Manual 200 Series DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Rev. March 2012 User's Manual for the Marine Pro 200 Series ~~~ DCU 210 Diesel Engine Control Unit DCU

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System UHF Partial Discharge Monitoring System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

ZXSe Range Data Sheet

ZXSe Range Data Sheet ZXSe Range Data Sheet Analogue addressable fire alarm control panel Product Overview The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and

More information

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS APPLICATION OVERVIEW Control and monitoring systems can play an essential role in heat tracing applications which

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Product Specifications

Product Specifications Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA (480) 783-0201 Fax (480) 783-0401 Product Specifications Procurement Specifications INTREPID MicroPoint Cable System Perimeter Detection

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

SIMPLIFIED VOYAGE DATA RECORDER (S-VDR)

SIMPLIFIED VOYAGE DATA RECORDER (S-VDR) STANDARD FOR CERTIFICATION No. 2.9 SIMPLIFIED VOYAGE DATA RECORDER (S-VDR) APRIL 2009 Veritasveien 1, NO-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD (DNV) is an autonomous and

More information

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 PPE-R/00.017 Version 2 RECOMMENDATION FOR USE Number of pages: 5 Approval stage : Approved on : Origin : Horizontal Committee, C2D Ad hoc group

More information

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

RTD TEMPERATURE SENSING SYSTEM

RTD TEMPERATURE SENSING SYSTEM General Overview RTD TEMPERATURE SENSING SYSTEM The Prime Technology RTD Temperature System 9219-00-0002 is a three-channel temperature measuring system that utilizes two RTD Temperature Sensor inputs

More information

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features Fire Safety ZXSe Range Analogue addressable fire alarm control panel The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and reliable microprocessor

More information

NB/ 0695/MFFS/P 17A Feb 18 REQUEST FOR INFORMATION (RFI) FOR SUPPLY AND INSTALLATION OF MAGAZINE FIRE FIGHTING SYSTEM

NB/ 0695/MFFS/P 17A Feb 18 REQUEST FOR INFORMATION (RFI) FOR SUPPLY AND INSTALLATION OF MAGAZINE FIRE FIGHTING SYSTEM Tele: +91-11-23793514 Fax: +91-11-23793514 Directorate of NBCD Integrated Headquarters of Ministry of Defence (Navy) 15, A - Block Hutments Dalhousie Road New Delhi 110011 NB/ 0695/MFFS/P 17A Feb 18 REQUEST

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

ID50series. intelligent fire alarm panels

ID50series. intelligent fire alarm panels ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of

More information

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder Pipo Communications Model ST-888 DTMF ANI/ENI Display Decoder 1516 Cassil Place Hollywood, California 90028-7106 Phone: 323-466-5444 Fax: 323-466-1520 www.pipo.cc Manual # 68-9888 May 1, 2002 Rev. 5/02

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

STANDARD TECHNICAL SPECIFICATION FOR AN ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM

STANDARD TECHNICAL SPECIFICATION FOR AN ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM STANDARD TECHNICAL SPECIFICATION FOR AN ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM Revision 2: November 1998 INDEX 1. SCOPE 2. GENERAL DESCRIPTION 3. STANDARDS 4. SYSTEM OPERATION 4.1 ACCESS LEVELS 4.2

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Complex alarming made simple

Complex alarming made simple SEL-2523 Annunciator Panel Complex alarming made simple Superbright LEDs provide easily visible alarm indication in any lighting condition. Sequential Events Recorder (SER) data help identify the root

More information

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone October 27, 2015 Page 1 of 15 AE-G6-IN-R4-E-10/15 This document is intended to provide performance

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas.

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Requirement under Rule 102 of the Petroleum Rules, 2002 lays down that no electrical wiring shall be installed and no electrical

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Technical Description. Laboratory Climate Test Chamber. System Weiss. Mat. No.: Type WKL 34/40

Technical Description. Laboratory Climate Test Chamber. System Weiss. Mat. No.: Type WKL 34/40 Technical Description Laboratory Climate Test Chamber System Weiss Mat. No.:67592625 Type WKL 34/40 FACTS The test chambers types WTL/WKL with compact exterior dimensions were especially developed for

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Intelligent Single Loop Fire Alarm Control Panel

Intelligent Single Loop Fire Alarm Control Panel Intelligent Single Loop Fire Alarm Control Panel The CAX-CTL-1L Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading Axis AX Series Intelligent Fre Alarm Control Panels

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

MARINE GYRO COMPASS STANDARD FOR CERTIFICATION. DET NORSKE VERITAS Veritasveien 1, N-1322 Høvik, Norway Tel.: Fax:

MARINE GYRO COMPASS STANDARD FOR CERTIFICATION. DET NORSKE VERITAS Veritasveien 1, N-1322 Høvik, Norway Tel.: Fax: STANDARD FOR CERTIFICATION No. 2.9 MARINE GYRO COMPASS JANUARY 2003 Veritasveien 1, N-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD is an autonomous and independent Foundation

More information

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements

More information

Fire control panels FC726 FC726-XA

Fire control panels FC726 FC726-XA Fire control panels FC726 FC726-XA Modular, pre-confectioned, microprocessor-controlled fire control panel for up to max. 1512 device addresses Integrated, user-friendly operating unit Detection and automatic

More information

IMR IX176 Portable Gas Detector User Manual

IMR IX176 Portable Gas Detector User Manual IMR Portable Gas Detector User Manual Read this manual carefully before using this device. (727) 328-2818 / (800) RING-IMR Fax: (727) 328-2826 www.imrusa.com Ver. 1.0A4 CONTENTS SERVICE GUIDELINES... 3

More information