PIVOT Architecture 44 West Broadway Suite 300 Eugene, OR t f pivotarchitecture.com

Size: px
Start display at page:

Download "PIVOT Architecture 44 West Broadway Suite 300 Eugene, OR t f pivotarchitecture.com"

Transcription

1 Project: LTD Facilities Maintenance Building and Bus Lot Expansion Title: Addendum No. 8 Solicitation No: Date: 4/13/17 From: John Stapleton, PIVOT Architecture To: Interested Bidders General Information 1. This Addendum includes: a. Revisions to the Civil, Architectural, and Electrical site plans showing the trenching needed in the existing concrete paving to accommodate the new electric bus charging systems. b. Revisions to drawing M-121 showing revised duct layout for FC-4; drawing M-131 showing refrigerant piping layout; and specification section Air Source Heat Pumps. c. Add Section Hardware Schedule. d. Changes to Section Pavement Markings e. Note the make and model of the existing fire alarm system. f. Replace drawing sheets that have scrambled or unreadable text. i. G011 ii. GO12 iii. A321 iv. A324 v. A411 vi. A452 vii. E111 viii. E603 ix. M002 x. M321 xi. M322 xii. M323 xiii. M324 Changes to the Project Manual 1. ADD Section Hardware Schedule. Doors are noted on this schedule. 2. Section A: ADD Manufacturer and model of the existing fire alarm system is Fire-Lite Alarms by Honeywell, MS-0900UDLS Fire Alarm Controls. The proposed system must integrate with this existing network, and be made by the same manufacturer. 3. Section Air Source Heat Pumps: Replace Section with attached. 4. Section Switchboards. PIVOT Architecture 44 West Broadway Suite 300 Eugene, OR t f pivotarchitecture.com

2 LTD FM Building 4/13/16 Addendum # 8 1. Add the following paragraph under 2.02: D. In addition to the circuit breakers provided per one line, the remaining spaces in the distribution board shall be provided with provisions for future 125 amp, 3-pole breakers. 5. Section Pavement Markings: ADD B. Marking at pedestrian walkway at east side of bus parking area use StreetBond 150 Pavement Coatings with StreetBond WB Concrete Primer by GAF, Inc. Changes to the Drawings 1. Sheets C002, C003, C004, C006, C007, C008, C010, and EC001. Revisions to the concrete removal and replacement at the new electric bus charging area and light pole bases. 2. Sheet A002. Revise Detail 4 to show the sawcut lines at the trenching for the installation of the electric bus chargers. 3. Sheet M121. Revise duct layout for fan coil FC-4. See attached M Sheet M131. Revise plan to show refrigerant pipe routing. See attached M Sheet E-110. Revise drawing per changes indicated in clouded areas. 6. Sheet E-601. Revise drawing per changes indicated in clouded areas. Substitution Requests Lighting: The following substitution requests have been approved: a. Type A (xx): Zumbtobel if it meets Buy America b. Type B1, B2, B3: Zumbtobel if it meets Buy America. c. Type D1: Lightolier if it meets Buy America d. Type P1 (pole only): Hadco if it meets Buy America End of Addendum # 8 PIVOT Architecture / DOWA - IBI Group Page 2 of 2

3 SECTION DOOR HARDWARE SCHEDULE MANUFACTURERS SPECIFIED: PRODUCT MANUFACTURER SYMBOL APPROVED SPECIFIED NAME SPECIFIED EQUAL BUTTS MCKINNEY MCK IVES LOCKSETS SARGENT SAR NONE PANICS SARGENT SAR NONE PULLS TRIMCO TRI IVES CLOSERS SARGENT SAR NONE KICKPLATES TRIMCO TRI IVES ELECTRIC STRIKES HESS HES NONE STOPS IVES I NONE THRESHOLDS PEMKO P NGP SEALS STEELCRAFT STE NONE KEYING: PROVIDE CONSTRUCTION CYLINDERS ON EXTERIOR DOORS. MASTER KEY INTO EXISTING GRAND MASTER KEY SYSTEM AS DIRECTED BY ARCHITECT AND OWNER. HARDWARE GROUPS: DOOR 100A GROUP 1 1 EA CONTINUOUS HINGE MCK-14HD ALUM MCK 1 EA PANIC AD8504 PSB 630 SAR 1 EA CLOSER 1431-CPS ALUM SAR 1 EA KICKPLATE 10 X 2LDW 630 TRI 1 EA THRESHOLD 271A (VERIFY DETAIL) ALUM P 1 EA DOOR SHOE 216_PK ALUM P 1 SET SEALS PS074 BLACK STE 1 EA ELECTRIC STRIKE 9600 HES INSTALLATION, WIRING, AND ACCESS CONTROL BY OTHERS LTD Facilities Maintenance Crew Building and Site DOOR HARDWARE SCHEDULE Bid Set April 3, 2017 Addendum 8 4/13/ PAGE 1 of 3

4 GROUP 2 DOOR 101A 1 EA CONTINUOUS HINGE MCK-14HD ALUM MCK 1 EA PUSH PLATE x I 1 EA PULL I 1 EA CLOSER 1431-CPS ALUM SAR 1 EA KICKPLATE 10 X 2LDW 630 TRI 1 SET SEALS PS074 BLACK STE DOOR 103A GROUP 3 3 EA BUTTS TA X 4.5 NRP 652 MC 1 EA LOCKSET 8204 LNL 626 SAR 1 EA CLOSER 1431-CPS EN SAR 1 EA DOOR SHOE 216_PK ALUM P 1 EA THRESHOLD 271A (VERIFY DETAIL) ALUM P 1 SET SEALS PS074 BLACK STE 1 EA ELECTRIC STRIKE 9600 HES INSTALLATION, WIRING, AND ACCESS CONTROL BY OTHERS DOOR 107A, 108A, 109A GROUP 4 3 EA BUTTS TA X 4.5 NRP 652 MC 1 EA LATCHSET 8215 LNL 626 SAR 1 EA WALLSTOP I 1 SET SEALS PS074 BLACK STE DOOR 110A, 111A GROUP 5 3 EA BUTTS TA X 4.5 NRP 652 MC 1 EA LOCKSET 8266 LNL 626 SAR W/ OCCUPIED INDICATOR 1 EA WALLSTOP I 1 SET SEALS PS074 BLACK STE LTD Facilities Maintenance Crew Building and Site DOOR HARDWARE SCHEDULE Bid Set April 3, 2017 Addendum 8 4/13/ PAGE 2 of 3

5 GROUP 6 DOOR 113A 3 EA BUTTS TA X 4.5 NRP 652 MC 1 EA LATCHSET 8215 LNL 626 SAR 1 EA OVERHEAD STOP 90S 652 GJ 1 SET SEALS PS074 BLACK STE LTD Facilities Maintenance Crew Building and Site DOOR HARDWARE SCHEDULE Bid Set April 3, 2017 Addendum 8 4/13/ PAGE 3 of 3

6 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Split-system air-source heat pump SECTION B. Automatic Controls including control hardware; communication, control wiring, and power wiring; programming, start-up, and verification as required. (ADD-08) 1.02 SUBMITTALS A. Provide submittals for products listed in the Product Table below in accordance with Section General Mechanical Provisions. Submittal requirements indicated by column number designation as follows: 1. Materials List 2. Catalog Data 3. Product Data 4. Performance Data 5. Wiring Diagrams 6. Shop Drawings 7. Installation Instructions 8. Special Requirement listed herein. PRODUCT TABLE All Products in this Section X X X B. Special Requirements: Submit product data, technical and performance data, shop drawings, installation details and instructions, calculations, and reports detailing system design as follows: (ADD-08) 1. Product List: Summary table of all equipment, accessories, and control devices including manufacturer and model number for each. 2. Product Data: Submit manufacturer s catalog data for materials, devices, and equipment furnished including physical dimensions of equipment. 3. Floor Plans: Full size plans showing equipment, piping, and wiring locations and routing. Show maintenance service access requirements. Drawings shall be prepared in electronic format with AutoCAD or Revit using original construction document files. 4. Schematic Diagrams: a. Power wiring diagrams b. Control wiring diagrams including an overall building control schematic 5. Close-out Submittal: Submit Contractor s start-up and verification reports QUALITY ASSURANCE A. Unit shall be UL listed. B. Unit shall be AHRI and AHRI C. Unit and refrigeration system shall comply with ASHRAE 15, Safety Standard for Mechanical Refrigeration D. Unit (Seasonal) Energy Efficiency Ratio, (SEER) EER, shall be equal to or greater than prescribed by ASHRAE 90.1, Energy Efficient Design of New Buildings except Low-Rise Residential Building. Bid Set April 3, 2017 (SWE #R011.07) Add Page 1 of 9

7 E. Unit shall be factory assembled and tested including leak testing of the coils, pressure testing of the refrigeration circuit, and run testing of the completed unit. Run test report shall be supplied with the unit in the controls compartment s literature pocket 1.04 DELIVERY, STORAGE, AND HANDLING A. Unit shall be shipped with doors bolted shut and outside air hood closed to prevent damage during transport and thereafter while in storage awaiting installation. B. Follow Installation, Operation and Maintenance manual instructions for rigging, moving, and unloading the unit at its final location. C. Unit shall be stored in a clean, dry place protected from construction traffic in accordance with the Installation, Operation and Maintenance manual. PART 2 - PRODUCTS 2.01 SPLIT-SYSTEM AIR SOURCE HEAT PUMP A. Acceptable Manufacturers: Trane B. Indoor Blower Coil Air Handler: 1. General: Horizontal air handling unit. Dx coil, drain pan, and variable speed ECM motor. Coil connections independent for the same or opposite side connections. Motor access panels provided on both sides of units and accessories. Similar to Trane TAM7 Variable speed modular Air Handler. 2. Cabinet: 18-gauge, galvanized steel, double wall foamed cabinet system, insulated with R-4.2, waterproof, modular. 3. Fan: Forward curved, dynamically balanced with a variable speed direct drive motor. Fan shaft supported by heavy-duty, permanently sealed ball bearings. Fans dynamically balanced. 4. Motor: Variable speed ECM motor, polarized plug connections and integrated slide deck for easy removal. Factory installed and wired. 5. Direct Expansion Coil: Dx coil for R410a. Aluminum fin surface mechanically bonded to 3/8-inch outside diameter copper tubing. Factory pressure and leak tested. Coils rated in accordance with AHRI Drain Pan: Stainless steel drain pan, double sloped to allow condensate drainage. Removable for cleaning. Auxiliary drain connection provided on same side as the main connection. 7. Filter: 2-inch, pleated MERV 8 8. Electrical: Single point electrical power connection. Factory supplied disconnect switch with interlocking door on the heater control panel. 9. Controls: Thermostat control interface for use with a field-supplied, low voltage thermostat or controller. Control box shall contain a line voltage to low voltage transformer, and a one, two or three-pole fan contactor. C. Outdoor Condensing Unit 1. General: Condensing unit designed for exterior applications and designed to operate at ambient conditions as high as 115 o F. Similar to Trane 4TWR split system heat pump. 2. Casing: Heavy gauge, galvanized steel, painted with weather-resistant powder paint. 3. Compressor: Scroll-type with internal over-temperature and pressure protector and dipped hermetic motor. Centrifugal oil pump. D. Controls 1. Provide low voltage thermostat with scheduling capability and night-setback features. 2. Provide all associated control wiring, relays, and other components needed for a complete and fully operational system Page 2 of 9 Bid Set April 3, 2017 (SWE #R011.07) Add. 08

8 E. Capacity and Performance: As scheduled on Drawings System Controllers (ADD-08) A. Acceptable manufacturers: Reliable Controls B. Building Controller: Provide building controller with connection to the existing LTD campus BACnet communications system. Basis of design: Reliable Mach Pro Com. C. Integrate building controller into existing server. Provide point configuration, trending, graphics, and other administrative confirmation as required. D. Equipment System Controller: Provide equipment system controller with BACnet communication and inputs/outputs as needed. Basis of design: Reliable Mach Pro Zone. C. Automatic controls capable displaying and modifying individual zone input/output points: a. On/Off b. Mode (Cooling / Heating / Auto) c. Heating and Cooling Setpoints d. Schedule 1. Scheduling e. Temperature setbacks f. Setpoint range limitation a. Optimal start b. Holiday schedules c. Daylight savings 2. Ancillary Equipment Control: a. Provide digital output for scheduling HRU ventilation system and exhaust fan. b. Occupancy sensor input 3. Network Communication: Serial communications with split heat pump systems through two conductors, 18 gauge shielded wiring. 4. Alarm Processing: Any object in the system shall be configurable to alarm in and out of normal state. Operator able to configure alarm limits, alarm limit differentials, states, and reactions for each object in the system. 5. Alarm Messages: Alarm messages shall use English language descriptors allowing the operator to recognize the source, location, and nature of the alarm without relying upon acronyms or other mnemonics. 6. Time clocks in all controllers shall be automatically synchronized daily. An operator changes to the time clock in any controller shall be automatically broadcast to all controllers on the system. System shall automatically adjust for daylight savings and standard time. 7. Alarm and Event Log: Provide chronological alarm and event log. Authorized operator able to view alarm and event log from any location in the system and acknowledge and clear alarms. 8. Integration with Existing Campus Server Operator Interface: a. Configure all thermostat input/output points for monitoring, command and trend from graphics. b. System graphics: Provide navigation capability through all system graphics. Provide real time data display of all system point values. Bid Set April 3, 2017 (SWE #R011.07) Add Page 3 of 9

9 c. View trend graphics: Provide trend information via graphical display. User shall be able to select points to be viewed and set time period and display interval. d. Alarms: Users shall be able to receive, acknowledge, and silence alarms. e. Event Log: Users shall be able to view event log. f. Scheduling: Users shall be able to view and modify equipment operating schedules. 9. Network Port Connection: 10 Base-T Ethernet 10. Electrical: 24 VAC CONTROL DEVICES (ADD-08) A. Space Temperature Controllers (Zone Thermostats): 1. Type: wired wall mounted zone controller with LC display. a. Operation mode setting (Auto, Manual, Heat, Cool). b. Temperature setting. c. Room temperature display. d. Discharge air temperature. e. Fan Status f. Fan speed indicator (high or low). g. BACnet communications compatible with System Controller B. Relays and Switches: 1. Single Phase Motor Control Relays: a. Acceptable Manufacturer: Greenheck, Veris, b. General: Industrial grade load-switching relay, current status switch, and Hand-Off-Auto switch for control of fractional horsepower single-phase motors. The relay, current sensor, and HOA switch are combined in a series circuit. Once an H5xx is wired in series between the power source and motor, all three components are installed. c. Relay: Contacts rated for connected motor load, SPST relay is fieldselectable for N.O. or N.C. operation. LED status indicator light. d. Current Status Switch: Adjustable setpoint. e. Housing: Surface mounted. The housing provides physical separation and multiple wiring exits to isolate control and high voltage wiring. f. Similar to Veris, Hawkeye Model 500 Series C. Current Status Switches for Constant Load Devices 1. Acceptable Manufacturer: Hawkeye or approved equal. 2. General: Factory programmed current sensor to detect motor undercurrent situations such as belt or coupling loss on constant loads. Sensor shall store motor current as operating parameter in non-volatile memory. Pushbutton to clear memory. 3. Visual LED indicator for status. 4. Split core sensor, induced powered from monitored load and isolated to 600 VAC rms. Sensor shall indicate status from 2.5 A to 135 A. 5. Normally open current sensor output. 0.1A at 30 VAC/DC. 6. Similar to Hawkeye Model Page 4 of 9 Bid Set April 3, 2017 (SWE #R011.07) Add. 08

10 2.04 POWER SUPPLIES AND LINE FILTERING (ADD-08) A. Provide UL listed control transformers. Provide class 2 current-limiting type or furnish over-current protection in both primary and secondary circuits in accordance with NEC requirements. Limit connected loads to 80% of rated capacity WIRING AND RACEWAYS (ADD-08) A. Provide wiring, plenum cable, and raceways in accordance with NEC. B. All insulated wire to have copper conductor. UL labeled for 90º C service. PART 3 - EXECUTION 3.01 INSTALLATION A. General: Install in accordance with manufacturer's installation instruction. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. B. General Wiring (ADD-08) 1. All control and interlock wiring shall comply with national and electrical codes and Division 26. Where requirements of this section differ from those in Division 26, the requirements of this section shall take precedence. 2. All NEC Class 1 (line voltage) wiring shall be UL listed in approved raceway according to NEC and Division 26 requirements. 3. All low-voltage wiring shall meet NEC Class 2 requirements. Low voltage power circuits shall be sub-fused when required to meet Class 2 limits. 4. Where NEC Class 2 (current-limited) wires are in concealed and accessible locations, including ceiling plenum return air plenums, approved cable not in raceway may be used provided cables are UL listed for the intended application. 5. All wiring in mechanical, electrical, or service rooms, wiring located where it may be subject to damage, and wiring exposed in finished spaces shall be installed in raceway. 6. Do not install Class 2 wiring in raceways containing Class 1 wiring. Boxes and panels containing high-voltage wiring may not be used for low-voltage wiring except for the purpose of interfacing the two. 7. Where Class 2 wiring is installed exposed, wiring is to be routed parallel or perpendicular to building lines and neatly tied at a maximum of 10-foot intervals. 8. Where plenum cables are used without raceway, support or anchor cable from building structure. Do not anchor or support cable from ductwork, electrical raceways, piping, or suspended ceiling systems. 9. Provide all wire-to-device connections at terminal block or terminal strip. Provide all wire-to-wire connections at terminal block. 10. Neatly bundle wiring located within enclosures to permit access to devices and terminals. 11. Maximum allowable voltage for control wiring shall be 120V. If only higher voltages are available, Contractor shall provide a step-down transformer. 12. All wiring shall be installed as continuous lengths with no splices permitted between termination points. 13. Install plenum wiring in sleeves where it passes through walls and floors. Provide fire-stop foam where necessary to maintain fire rating. 14. Provide size of raceway and size and type of wire as required by NEC and as required to meet manufacturers recommendations for connected equipment. Bid Set April 3, 2017 (SWE #R011.07) Add Page 5 of 9

11 15. Include one pull string in each raceway 1-inch or larger. 16. Use color coded conductors throughout. 17. Locate control and status relays in designated enclosures only. Such enclosures include packaged equipment control cabinets unless such cabinets also contain Class 1 starters. 18. Conceal all raceways except within mechanical, electrical, or service rooms. Maintain minimum raceway clearance of 6-inches from high temperature equipment such as steam piping or boiler flues. 19. Secure raceways with raceway clamps fastened to the structure and spaced in accordance with code requirements. Raceways and pull boxes may not be hung on flexible duct strap or tie rods. Raceways may not be supported from ductwork, electrical raceways, piping, or suspended ceiling systems. 20. Install insulated bushings on all raceway ends and openings to enclosures. Seal top end of all raceways. 21. Maintain updated wiring diagrams (as-built) at site with terminations identified. 22. Flexible metal raceways and liquid-tight, flexible metal raceways shall not exceed 3-feet in length and shall be supported at both ends. Flexible metal raceway less than ½-inch electrical trade size shall not be used. In areas exposed to moisture, including but not limited to chiller and boiler rooms, liquidtight, flexible metal raceways shall be used. 23. No wiring shall be installed in raceway or cable trays used for building communications, fire alarm, or security systems. B. Communication Wiring (ADD-08) 1. Install in accordance with General Wiring above. 2. Follow manufacturers recommendations for all communications cabling including but not limited to maximum pulling, tension, and bend radius. 3. Do not install communications cabling in a raceway or enclosure containing Class 1 or other Class 2 wiring. 4. Verify the integrity of the entire network immediately following cable installation using test measures appropriate for each cable. 5. Provide a lightning arrestor between cables and grounds where cable enters or exits a building. Install arrestor in accordance with manufacturers recommendations. 6. All communications wiring shall be un-spliced length when that length is commercially available. 7. All communications wiring shall be labeled to indicate origination and destination. 8. Ground coaxial cable in accordance with NEC regulations article on Communications Circuits, Cable and Protector Grounding. C. Controllers/Thermostats (ADD-08) 1. Install where shown on Drawings, in accordance with General Wiring above SPLIT-SYSTEM AIR SOURCE HEAT PUMP A. Provide concrete pad for outdoor units. Pad located and sized to allow adequate clearance for unit operation and maintenance access START-UP A. Manufacturer's certified representative to provide the following services: Page 6 of 9 Bid Set April 3, 2017 (SWE #R011.07) Add. 08

12 1. Inspect after installation to ensure equipment is installed in accordance with manufacturer's recommendation. 2. Supervise initial start-up. 3. Adjust control system parameters and setpoints to obtain specified performance. 4. Provide minimum 2 hours of training, including operation and maintenance SEQUENCE OF OPERATIONS (ADD-08) A. General: Low voltage, adjustable room thermostat to control heating and cooling, compressor, and supply fan to maintain temperature setting. Include system selector switch (manual-auto-heat-cool). Thermostat monitors discharge air temperature, and supply fan status. B. Fan Motor Control: Operate subject to individual On-Off-Auto switch at motor controller as follows. 1. Auto Position: Operate motor subject to thermostat control signal. 2. On Position: Override automatic control and start motor. Safety control sequences enabled. 3. Off Position: Motor off. C. Time Control: Provide optimum start routine to control system operating modes. 1. Occupied Mode: Provide time schedule to define occupied times for each day of the week and holidays. 2. Warm-up and Cool Down Modes: Provide optimum start routine to calculate system warm-up/cool down duration subject to outside air temperature and space temperatures so that all spaces are at occupied temperature at the occupied start time. Optimum start routines shall use a sophisticated algorithm that monitors historical system performance to accurately predict start-up duration and shall be capable to achieving occupied space temperature in all spaces within 2 o F, unless the start-up duration exceeds the maximum start-up duration setpoint. Maximum start-up duration shall be adjustable and initially set to 2 hours. 3. Unoccupied Mode: Enable whenever Occupied, Warm-up, and Cool Down modes are off. D. Warm-up, Cool Down, and Occupied Mode: 1. Fan Operation: Supply fans on. 2. Space Temperature Control: Operate in accordance with Space Air Temperature Control. E. Unoccupied Mode: 1. Fan Control: Supply off. F. Night Low Limit Mode: 1. Mode Control: Enable during unoccupied periods if any space temperature is below 55 o F. Disable when all space temperatures are above 60 o F. 2. Fan Operation: Supply fan on. 3. Space Temperature Control: Operate in accordance with Space Air Temperature Control. G. Safety Control: 1. Fan Status: If a motor is commanded on, and the motor status after a 20- second delay indicates that the motor is off, activate status alarm. Maintain alarm until acknowledged by building operator. Bid Set April 3, 2017 (SWE #R011.07) Add Page 7 of 9

13 H. Input/Output Points List 1. Provide all control points required to perform the automatic control sequence described above, which as a minimum shall include all points listed below. BAS Points List Equipment Connection Digital Inputs FC-1 Supply fan status FC-2 Supply fan status FC-3 Supply fan status FC-4 Supply fan status Analog Inputs FC-1 Room space temperature FC-1 Discharge air temperature FC-2 Room space temperature FC-2 Discharge air temperature FC-3 Room space temperature FC-3 Discharge air temperature FC-4 Room space temperature FC-4 Discharge air temperature FC-5 Room space temperature FC-5 Discharge air temperature 3.05 SEQUENCE OF OPERATIONS ANCILLARY EQUIPMENT (ADD-08) A. General: The following functions by System Controller B. HRU-1: Start and stop supply and return fans in conjunction with regular building occupancy. Unit packaged controller operates fans, and heat recovery in response to building controller input. Outside air and exhaust dampers wired to open when unit is enabled. Building controller monitors fan operation, and provides alarm functions for equipment failure. C. Exhaust Fan EF-1: Start and stop exhaust fan in conjunction with regular building occupancy. Unit packaged controller operates fan in response to Building controller input. Building system controller monitors fan operation, and provides alarm functions for equipment failure. D. Safety/Emergency Control, Monitoring and Alarming 1. Fan Alarm Mode: If fan is commanded "on" and fan status after a 30 second delay indicates that the fan is off, provide an alarm. Maintain alarm until acknowledged by operator. 2. High Water Alarm: Provide an alarm when the sewage sump pump high water alarm system. Maintain alarm until acknowledged by operator. E. Input/Output Points List 1. Provide all control points required to perform the automatic control sequence described above, which as a minimum shall include all points listed below Page 8 of 9 Bid Set April 3, 2017 (SWE #R011.07) Add. 08

14 BAS Points List Equipment Connection Analog Input HRV-1 Supply air temp HRV-1 Exhaust air temp Digital Inputs HRV-1 supply fan status HRV-1 exhaust fan status SP-1 lead pump status SP-1 lag pump status EF-1 exhaust fan status Digital Outputs HRV-1 start/stop EF-1 exhaust fan start/stop 3.06 ADJUSTMENT (ADD-08) A. After installation is complete, check installation and start-up in accordance with manufacturer's instructions. B. Make necessary adjustments and cycle control to verify system performance. C. Verify discharge air temperature is 55 F (+/- 2 F) at supply outlet of all indoor units. D. Program fan coil thermostat to schedule of operation and temperature settings provided by Owner. Set thermostats to prevent users from making adjustments. E. Occupied Space Setpoints: 1. Cooling: 75 F 2. Heating: 70 F F. Unoccupied Space Setpoints: 1. Cooling: 85 F 2. Heating: 60 F G. Program controller(s) to resume previous mode of operation after power failure. H. Program equipment operating schedules as directed by Owner DEMONSTRATION A. Demonstration system operation and adjustment of control system setpoints and parameters to Owner s Authorized Representative. END OF SECTION Bid Set April 3, 2017 (SWE #R011.07) Add Page 9 of 9

15 SECTION PAVEMENT MARKINGS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes: 1. Permanent pavement markings and removal of existing roadway markings as shown on the Contract Drawings and Workaround Plans and as specified herein REFERENCES A. The publications listed below form a part of this specification to the extent referenced. Sponsor Number Subject ODOT / APWA Oregon Standard Specifications for Construction 2008 (OR-APWA) OR-APWA Common Provisions for Pavement Markings OR-APWA Pavement Marking Removal OR-APWA Pavement Markers OR-APWA Longitudinal Pavement Markings Paint ODOT Qualified Products List MUTCD Part 3 Markings MUTCD Part VI Traffic Controls for Street and Highway Construction, Maintenance, Utility and Emergency Operations 1.03 DEFINITIONS A. Painted Pavement Line: Sprayed Yellow painted line Paint material and beads shall be from ODOT s Qualified Product List. B. See the Contract Drawings for location and types of material to be used SUBMITTALS A. Submittals shall be made in accordance with the requirements of Section Contract Provisions. PAVEMENT MARKINGS Bid Set / Addendum 8 April 13, Page 1 of 2

16 B. Use material from ODOT s Qualified Product List. Material received on the project shall bear a label verifying the manufacturer or be accompanied by a certification stating the origin of the product. C. Certificates of compliance for all materials included in this Section. PART 2 - PRODUCTS 2.01 PAVEMENT MARKINGS MATERIALS A. Marking materials are as listed on the ODOT Qualified Products List (QPL) per the OR- APWA Section Materials B. Marking at pedestrian walkway at east side of bus parking area use StreetBond 150 Pavement Coatings with StreetBond WB Concrete Primer by GAF, Inc. PART 3 - EXECUTION 3.01 PAVEMENT MARKING REMOVAL A. Pavement marking removal from the pavement surface shall be done in accordance with the OR-APWA, Section Pavement Marking Removal supplemented and/or modified as follows: General Replace the paragraph that begins "Remove non- durable pavement " with the following paragraph: a. Remove durable and non-durable pavement markings by hydro blasting, steel shot blasting, or grinding so that the pavement surface is not damaged below a depth of 1/8 inch PAVEMENT MARKERS A. Permanent pavement markers shall be installed in accordance with the OR-APWA, Section Pavement Markers supplemented and/or modified as follows: (c) Installation In the paragraph that begins "Do not install ", replace the sentence that begins "Adjust spacing between " with the following two sentences: a. To avoid longitudinal cracks and joints, adjust pavement markers up to one half the width of the marker. To avoid transverse cracks and joints, adjust pavement markers ahead or back on line ±5 inches. END OF SECTION PAVEMENT MARKINGS Bid Set / Addendum 8 April 13, Page 2 of 2

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION BUILDING AUTOMATION SYSTEM

SECTION BUILDING AUTOMATION SYSTEM SECTION 25 10 00 BUILDING AUTOMATION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Work hereunder includes a complete and operational, fully-tested, distributed logic, direct digital control system for control

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR FCU RBVR 1.0 07 25 18 RBVR Vertical Concealed Floor Mount Unit Size 02 03 04 06 08 10 A 23 3/16 [589] 27 3/16 [691] 33 3/16 [843] 43 3/16 [1097] 45 3/16 [1148] 59 3/16 [1503] B 22 ¾ [578] 26 ¾ [679] 32

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

SECTION DOOR HARDWARE

SECTION DOOR HARDWARE PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 08 7100 DOOR HARDWARE A. Hardware for wood, aluminum, and hollow metal doors. B. Hardware for fire-rated doors. C. Electrically operated and controlled hardware.

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,

More information

University of Rochester October 17, 2008 Brooks Landing Business Center

University of Rochester October 17, 2008 Brooks Landing Business Center SECTION 087100 - DOOR HARDWARE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Commercial door hardware. 2. Cylinders for doors specified in other Sections. 1.2 SUBMITTALS A. Product

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

The ultimate fresh air solution.

The ultimate fresh air solution. Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged

More information

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections.

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15410 - Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections. 1.02 SUBMITTALS A. Submit properly identified

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

NFZP Variable Refrigerant Flow Guide Specification

NFZP Variable Refrigerant Flow Guide Specification PART 1 - GENERAL 1.01 SECTION INCLUDES SECTION 23 81 29 VARIABLE REFRIGERANT FLOW HVAC SYSTEM A. (VRF) HVAC system includes: 1. Outdoor/Condensing unit(s): a. Size Range: 14 Tons Nominal b. YANMAR VRF

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements ADDENDUM 1 CLIENT: PROJECT: TO: FROM: Guilford County Schools (GCS) Southeast High School Auditorium & Gymnasium HVAC Improvements All Prospective Bidders Derrick Giles, SAMR, PLLC. DATE: 6/6/2018 The

More information

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

Linear Floor Heaters

Linear Floor Heaters Linear Floor Heaters The Price Linear Floor Heater family provides ultimate flexibility in terms of style, performance, and ease of installation. Using room-side heat virtually eliminates the requirement

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design Fan motor (PSC or ECM). UL Listed 1 insulation conforms to UL Test 181 and NFPA 90A. Plenum air filter rack. (Filter Optional) Casing has

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2

INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2 FINANCE, RISK AND BUSINESS PLANNING GROUP Supply Chain Management November 4, 2015 INVITATION TO TENDER ITT NO. PS20151058 KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2 RE: Insert attached Section

More information

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION Page 1 of 7 25 00 00 25 10 00 NETWORK EQUIPMENT Standby Power 1. Consider whether the controls system should be on standby/emergency power, or UPS when central applications are controlled or the equipment

More information

DESIGN GUIDELINES SECTION HVAC

DESIGN GUIDELINES SECTION HVAC 3/15/17 Cooling Methodology Chiller Plants Configurations monitoring Preferred DESIGN GUIDELINES SECTION 15700 HVAC Air-cooled chillers < or = 300 tons; water-cooled chillers > 300 tons Variable volume

More information

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER PROJECT NO. CWA 2013-04 SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER BIDS RECEIVED: CITY HALL, CITY OF BESSEMER TIME: 2:00pm DATE: October 2, 2014 City of Bessemer --------------------------------------------------------------------------------------------------------------------------------------------

More information

THE ULTIMATE ROOFTOP SOLUTION

THE ULTIMATE ROOFTOP SOLUTION Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information

Integrated Automation

Integrated Automation Revision 04/27/2017 Purpose: The Architect and/or Engineer shall incorporate the Rice specific requirements indicated in this standard s section into their design. The Architect and/or Engineer shall further

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT February 29, 2012 RFP NO: 17 PROJECT: Josephine County Justice Center HVAC Upgrades BID CLOSING DATE: NO CHANGE: March 8, 2012 / NOT LATER

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

Preventative Maintenance Tables

Preventative Maintenance Tables Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit

More information

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW... SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...

More information

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

SECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS

SECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS 1.0 GENERAL SECTION 15740 SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS 1.01 DESCRIPTION Item A. Scope This section specifies four sizes of fan coil units designed for hydronic heating and air conditioning.

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13 Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing

More information

FOUNTAINS UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS APRIL 30,

FOUNTAINS UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS APRIL 30, 13 12 00 FOUNTAINS A. Due to water conservation efforts and the high maintenance requirements of fountains, new interior and / or exterior fountains are not allowed. B. If a variance is granted for a fountain,

More information

2. Interior doors shall be not less than 18 gauge steel.

2. Interior doors shall be not less than 18 gauge steel. DIVISION 8 - DOORS AND WINDOWS 08100 METAL DOORS AND FRAMES 1. Exterior doors shall be not less than 16 gauge steel. The top channel of each metal door shall be solid without pockets which collect dirt

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

SECTION CONVECTION HEATING AND COOLING UNITS

SECTION CONVECTION HEATING AND COOLING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Baseboard radiation. B. Finned tube radiation. C. Convectors. D. Unit heaters. E. Cabinet unit heaters. F. Fan-coil units. G. Unit ventilators. H. Blower-coil units.

More information

ARCHITECTURAL SPECIFICATIONS

ARCHITECTURAL SPECIFICATIONS 1 B9.1 In Ground Page 1 of 6, Aug 12 DIVISION 08 - OPENINGS SECTION 08 71 13 POWER DOOR OPERATORS Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information