DEVIATING VALVES ART K063
|
|
- Lewis Carter
- 5 years ago
- Views:
Transcription
1 FUNCTION The flow diverter valve Art.307 makes it possible to supply a branch circuit. Prepared to receive our electro-thermal controls Art. 978, 979, 980 or our thermostatic heads with remote sensor Art. 992, 995. The three-way mixing valve with thermostatic sensor with remote capillary Art. 323, allows to mix two fluids obtaining a third one with intermediate temperature. Adjustment range C. The probe also works on contact. For immersion, combine sensor holder well Art. 212 or 189. Art. 307 The adjustment and mixing group Art. K063 has been designed for use in radiant panel systems, in combination with distribution manifolds. Its function is to maintain constant, at the set value, the flow temperature of the fluid distributed in a low temperature radiant panel system. The thermal regulation takes place by means of a three-way thermostatic valve, equipped with a thermostatic control with remote sensor. TECHNICAL FEATURES TECHNICAL DATA: Fluid of use: Water and glycol solutions Maximum percentage of glycol: 30% Primary input temperature range: 5 95 C Adjustment temperature range: C Scale thermometers: 0 60 C Maximum working pressure: 10 bar Minimum operating pressure: 1 bar Power supply: 230 V - 50 Hz MATERIALS: Valve and fitting bodies: Brass CW617N - UNI EN Ferrule and nipples: Brass CW617N - UNI EN Thermometer: Steel/Alloy Gaskets: EPDM Perox CONNECTIONS: Secondary system connections (manifolds): G1 M Art. 323 Art. K063 pag. 1
2 MIXING VALVE ADJUSTMENT The thermostatic control with remote sensor that is to be installed on the 3-way mixing valve is supplied with the "fixed point regulating unit". By adjusting the thermostatic control it is possible to set the temperature of the heat transfer fluid that circulates within the low temperature circuit of the radiant panels. The thermostatic control has an adjustment range that goes from 20 to 50 C, it is advisable to set a temperature of about 35/40 C on the handwheel with the graduated scale (for a detailed description of the thermostatic control regulation refer to the sheet instructions in its package). The three-way mixing valve, on the other hand, is equipped with a "double regulation" which allows limiting the amount of water that is to be allowed to enter the low-temperature circuit in the condition in which the mixing valve is completely open. This "double adjustment" is set at the factory when the mixing valve is tested, it is advisable not to modify it except for special requirements. To change the "double adjustment" it is necessary to remove the white cap or the thermostatic control on the mixing valve (the valve will appear as in fig.a), insert a slotted screwdriver into the slot on the black pin (see the red arrow in fig.b), turn the pin by varying the mixing valve regulation as follows: Fig. A - Turning the black pin clockwise closes the passage of the heat transfer fluid to the low temperature system, limiting its passage to a maximum value even if the mixing valve is in the fully open position. - Turning the black pin anti-clockwise instead opens the passage of the heat transfer fluid to the low temperature system, increasing the maximum amount of water that is allowed to pass in the low temperature circuit in case the mixing valve is in position of complete opening. Fig. B pag. 2
3 MIXING VALVE FLOW DIRECTION CLOSED VALVE OPEN VALVE 130 FLOW DIRECTION SYSTEM SUPPLY BOILER SUPPLY SYSTEM RETURN BOILER RETURN pag. 3
4 ART. K063 - ADJUSTMENT GROUP WITH FIXED POINT Fixed point temperature regulation group complete with: 1) Thermostatic control C with remote sensor 2) 3-way mixing valve 3) Flow meter 4) By-pass valve with manual regulation 5) Sensor holder well 6) G1 "nozzles with O-ring seal for the manifold Connections for manifolds: G1 "Male. Installable both in the right version and in the left version BY-PASS VALVE ADJUSTMENT The manually controlled by-pass valve allows to regulate the circulation of the heatcarrying fluid coming from the heat generator in the event that the mixing valve is completely closed and does not allow anything to pass towards the collector of the low-temperature circuit of the radiant panels. To obtain a standard regulation of the by-pass valve, it is advisable to close it completely by rotating the white handwheel (indicated by the blue arrow in fig. C) clockwise until it stops and then open it by 1 / 1.5 turns by turning the handwheel counterclockwise. Fig. C pag. 4
5 HYDRAULICAL FEATURES pag. 5
6 DIMENSIONS SERIE CODE A B C D E AD05 1/2" , AE05 3/4" , AF ,5 45 SERIE CODE A B C D E AD05 1/2" ,5 104, AE05 3/4" ,5 104, AF ,5 104,5 pag. 6
7 SERIE CODE A B C D E F K063 87K063PG06 1" pag. 7
8 SAFETY Read the installation and commissioning instructions carefully before operating the appliance in order to prevent accidents and system failures caused by improper use of the product. Please note that the right to the warranty is void in case of unauthorized modifications or tampering during the assembly and construction phase. In addition to the aforementioned directives, the following rules must necessarily be followed: DIN 4751 Water heating systems DIN 4757 Solar heating systems DIN Domestic water heating and heating systems DIN Electrical and conduction systems in buildings DIN Solar thermal systems and their construction WORKING CONDITION The limit values shown must in no way be exceeded. Operational safety is therefore ensured by respecting the general conditions and operating limit values described in this sheet. SAFETY RULES FOR MOUNTING AND INSPECTION Assembly and inspection must be performed by qualified, authorized personnel who are familiar with the instructions given here. Before any work on the equipment is necessary to make sure that they are in rest conditions. ELECTRICAL CONNECTIONS The electrical connections must be made by qualified personnel. Before powering up the relay unit, check that the data indicated on the nameplate regarding the type and voltage values supplied by the electricity grid are respected. All connections must be made as prescribed by law. MAINTENANCE Maintenance operations must be performed by qualified, authorized personnel who are familiar with the instructions given here. Before any work on the equipment is necessary to make sure that they are in rest conditions. If the pump is to be replaced, the shut-off valves should be turned to the closed position. Warning! Depending on the operating conditions of the pump and the characteristics of the system, the surface temperature may be very high. Therefore, if you touch the pump directly, you are in danger of burns! DECLARATION OF CONFORMITY (CE) The circulators supplied as part of the ICMA relay groups comply with the following harmonization directives: EEC Machinery Directives 89/392 / EEC, 91/368 / EEC, 93/44 / EEC, 93/68 / EEC. Electromagnetic compatibility 89/336 / EEC, 92/31 / EEC, 93/68 / EEC General harmonized rules EN 809, EN , EN , EN , EN pag. 8
THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES
FUNCTION Thermostatic expansion valves are used to regulate and cut-off the flow of the heat transfer fluid that circulates inside airconditioning system terminals (radiators, fan coils, etc.). Thermostat
More informationTHERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES
FUNCTION Thermostatic expansion valves are used to regulate and cut-off the flow of the heat transfer fluid that circulates inside airconditioning system terminals (radiators, fan coils, etc.). Thermostat
More informationINSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE
INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE SPECIFICATIONS... 1 OVERVIEW... 2 PRECAUTIONS... 2 MOUNTING LOCATION... 2 CONNECTION TO BOILER PRIMARY PIPING:... 3 ELECTRICAL CONNECTION... 4 FLUSHING THE
More informationMercury Mixing Kit (Code: ME1053)
Mercury Mixing Kit (Code: ME1053) The installation and commissioning of the UFH mixing kit system must be exclusively performed by qualified personnel in accordance with the national guidelines and/or
More informationThermostatic mixing valves with replaceable cartridge for centralized systems
Thermostatic mixing valves with replaceable cartridge for centralized systems series REGISTERED BS EN ISO 9: Cert. n FM UNI EN ISO 9: Cert. n / N Replaces /9 N Function The thermostatic mixing valve is
More informationR586R. Distribution and Regulation units. Datasheet 0861EN 04/2019 R586RY103 R586RY102 R586RY101 R586RY104
R8R Distribution and Regulation units Datasheet 08EN 0/09 R8RY0 R8RY0 R8RY0 R8RY0 Unit with insulation and actuator (optional) R8RY R8RY R8RY R8RY R8R distribution units control heating and cooling for
More informationThermostatic mixing valves with interchangeable cartridges
www.caleffi.com R37. Thermostatic mixing valves with interchangeable cartridges Installation, commissioning and servicing instructions 3 Series Function The thermostatic mixing valve is used in systems
More informationAquastrom T plus Thermostatic valve with adjustable temperature control range and fixed residual volume flow for circulation pipes
Thermostatic valve with adjustable temperature control range Technical information Tender specification: Oventrop thermostatic valve Aquastrom T plus with presetting for circulation pipes. Thermal control
More informationMetering systems 0548EN April 2014
08EN April 0 0U8 GEY - Y - Y (GE- series) 900 000/ 00 00A/ 800 00L/ Versions and product codes Product code Type Heat exchanger nominal power GEY, - GEY and production GEY and production Table - Product
More informationLight oil / kerosene burner
Installation, use and maintenance instructions Light oil / kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 290238 (5) - 05/20 TECHNICAL DATA Thermal power output 28 60 kw 2.3 5 kg/h
More informationCALEFFI. Thermostatic regulating unit for heating systems. 166 series 01238/17 GB. replaces dp 01238/15 GB. Function
Thermostatic regulating unit for heating systems 66 series ACCREDITED ISO 9 FM 6 8/7 GB replaces dp 8/ GB Function The thermostatic regulating unit performs the function of keeping the flow temperature
More informationCALEFFI. Thermostatic mixing valves with replaceable cartridge for centralized systems. 5230, 5231 series 01080/13 NA ASSE Replaces 01080/11 NA
Thermostatic mixing valves with replaceable cartridge for centralized systems 3, 3 series CCREDITED ISO 9 FM ISO 9 No. 3 /3 N Replaces / N Function The thermostatic mixing valve is used in systems producing
More informationTHERMOSTATIC SINGLE-PIPE AND DOUBLE-PIPE VALVES
ST.07.05.00 THERMOSTIC SINGLE-PIPE AND DOUBLE-PIPE VALVES 1. Art.1420 THERMOSTIC SINGLE-PIPE VALVE Single-pipe valves allow manual, thermostatic or thermo-electric regulation. Separation of the lockshield
More informationRoth fixed-value control set with high-efficiency pump
Energy Systems Roth fixed-value control set with high-efficiency pump Assembly Instructions Living full of energy Contents General information Intended use 3 Benefits 3 Layout/Components 3 Installation/Electrical
More informationComponents for solar heating systems
solarorkli Components for solar heating systems Components for heating and plumbing Components for solar heating systems Manifolds and distribution equipment Thermostatic valves Manual valves Motorised
More informationCALEFFI. Set point thermostatic regulating unit. 182 series 01190/18 GB. replaces dp 01190/15 GB
Set point thermostatic regulating unit 8 series FM 65 00 CALEFFI 090/8 GB replaces dp 090/5 GB Function The thermostatic regulating unit is made to be used in radiant panel systems, in combination with
More informationInstallation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump
Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump Reduced Installation time Precision regulation Minimal tooling required 100% tested prior to packaging High quality
More informationR557R EN January 2012
R7R- 077EN January 0 07U 00 00 00 WITH HIGH TEMPERATURE MANIFOLDS Example: R7RY0 + RAY00 R7R- WITH THERMAL ENERGY METERING Description R7R- group is used for the regulation of the fixed point heating for
More information5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341
NA31 www.caleffi.com Low Lead High Flow Thermostatic Mixing Valves Copyright 1 Caleffi Installation, commissioning and service instructions Function 531 Series ASSE 17 model 531 series high flow thermostatic
More informationcaleffi hydronic valves page 1 of 12
caleffi hydronic valves page 1 of 12 page 2 of 12 MANUAL RADIATOR VALVES 1601811 - Series 340 1601812 - Series 341 1603748 - Seies 411 1603749 - Series 412 CONVERTIBLE RADIATOR VALVES 1601816 - Series
More informationTHERMOSTATIC RADIATOR VALVES FOR IRON, COPPER, POLYETHYLENE AND MULTILAYER PIPE PRODUCTION RANGE IRON PIPE CODE CONNECTION
THERMOSTATIC RADIATOR VALVES FOR IRON, COPPER, POLYETHYLENE AND MULTILAYER PIPE CT0031.0_10 EN August 2016 THERMOSTATIC RADIATOR VALVES * * * * 028 * LICENSED USE OF TRADEMARK NR. 43 PRODUCTION RANGE IRON
More information521 Series. MixCal adjustable three-way thermostatic mixing valve. Installation, commissioning and service instructions
MixCal adjustable three-way thermostatic mixing valve 37. www.caleffi.com Copyright 15 Caleffi 51 Series Installation, commissioning and service instructions Function The Caleffi MixCal three-way thermostatic
More informationForced draught gas burner
Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1
More informationWARNINGS FOR THE USER: Connect BASE conforms to: Low Voltage Directive 73/23/EEC. Electromagnetic Compatibility Directive 89/336/EEC
Connect BASE conforms to: Low Voltage Directive 73/23/EEC Electromagnetic Compatibility Directive 89/336/EEC Warnings and safety considerations Page 13 Description of the equipment 14 Technical data 14
More informationACCREDITED. Product range Code A2L Pre-assembled set point temperature regulating unit with manifolds and box, with UPM3 Auto L pump
Set point temperature regulating unit series ACCREDITED ISO 9 FM / GB replaces dp / GB Function The temperature regulating unit is made to be used in radiant panel systems, in combination with distribution
More informationDIRTMAG dirt separator with magnet, adjustable for vertical or horizontal pipe
DIRTMAG dirt separator with magnet, adjustable for vertical or horizontal pipe Copyright 206 Caleffi NA0322.02 www.caleffi.com NA5453 Series Installation, commissioning and servicing instructions Function
More information5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341.
NA3. www.caleffi.com Low Lead High Flow Thermostatic Mixing Valves Copyright 5 Caleffi Installation, commissioning and service instructions Function 53 Series ASSE 7 model 53 series high fl ow thermostatic
More informationCALEFFI. Anti-condensation circulation unit. 282 series 01225/14 GB. replaces dp 01225/11. Code completion Setting 45 C 55 C 60 C 70 C.
Anti-condensation circulation unit 8 series ACCREDITED ISO 9 F 654 ISO 9 No. CALEFFI 5/4 GB replaces dp 5/ Function The anti-condensation circulation unit performs the function of connecting the solid
More informationSolar station DKP 6-8 / DKP Installation and Service Manual C
EN Solar station DKP 6-8 / DKP 9-20 Installation and Service Manual 300014274-001-C Contents 1 Introduction.............................................................................3 1.1 Used symbols...........................................................................................3
More informationInstallation, commissioning and servicing instructions
NA10322.01 www.caleffi.com DIRTMAG dirt separator Copyright 2015 Caleffi NA5453 Series Installation, commissioning and servicing instructions Function In heating and chilled water systems, the circulation
More informationFOR INSTALLING AND USING
FOR INSTALLING AND USING Description and function The Solarmix thermostatic mixing valve is designed to reduce the water temperature to a safer level. Unlike the under basin, or bath/shower type valves
More informationModel: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100
1 Safety instructions Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100 1.1 Proper use Any improper use, intervention in the design and deviation from the design data automatically lead
More informationConvertible radiator valve for one-pipe systems, centre distance 35 mm
Convertible radiator valve for one-pipe systems, centre distance 35 mm 56 series ACCREDITED ISO 900 FM 65 033/6 GB Function 56 series convertible radiator valves are used on one-pipe radiator systems.
More informationR146C. Adjustable magnetic dirt separator. Versions and product codes. Datasheet 0840EN 10/2018
R146C Adjustable magnetic dirt separator Datasheet 0840EN 10/2018 The R146C adjustable magnetic dirt separator separates and removes debris inside hydraulic circuits of modern heating and cooling systems.
More informationTHERMOSTATIC MIXING VALVES FOR CONDENSATION PREVENTION
DT SHEET THERMOSTTIC MIXING VLVES FOR CONDENSTION PREVENTION woody art.v13 woody art.v14 Description Barberi thermostatic mixing valves woody are devices with side mixed water and are used to set the fluid
More informationV. DIFFERENTIAL THERMOSTAT
DTC 200/2G DTC 200/2G is a differential thermostat, designed for heating DHWT (domestic hot water tank) from one heating source (solar collectors, boilers, heat pumps) with possibility to control the burner
More informationS170 - SOLAR STORAGE-TO-BOILER CONNECTION KIT WITH THERMAL INTEGRATION
FUNCTION The solar storage-to-boiler connection kits automatically control and optimize the terminal energy contained in a solar water storage, ensuring that domestic hot water is distributed throughout
More informationINSTALLATION AND MANINTENANCE INSTRUCTIONS
INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional
More informationLight oil - kerosene burner
Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 374374 G3B 437T 90 (4) - 05/0 TECHNICAL FEATURES TYPE 437T Thermal power output 9 35 kw.6
More informationProduct range Code HE1 Connection and energy management compact unit without anti-condensation valve
Connection and energy management compact unit 2850 series ACCREDITED CALEFFI 01259/14 GB ISO 9001 FM 21654 ISO 9001 No. 0003 Function The connection and energy management compact unit enables combining
More informationMounting and Operating Instructions EB 2231 EN
Self-operated Regulators Thermostats Type 223 and Type 2232 Bulb Sensors Type 2233, Type 2234, and Type 2235 Air Sensors Type 223 with bulb sensor Type 2232 with bulb sensor (separate) Type 2233 with air
More informationHIGH POWER. VICTRIX PRO 2 ErP. High power, wall-hung condensation boiler
HIGH POWER VICTRIX PRO 2 ErP High power, wall-hung condensation boiler MAIN INDEX INDEX 1 VICTRIX PRO 35-55 2 ErP SPECIFICATIONS...5 2 VICTRIX PRO 80-100-120 2 ErP SPECIFICATIONS...6 3 VICTRIX PRO 35-55
More informationFlush individual room control for floor heating systems
Multibox Flush individual room control for floor heating systems Pressurisation & Water Quality Balancing & Control Thermostatic Control ENGiNEERiNG ADVANTAGE Multibox is used for decentralized control
More informationInstallation, commissioning and servicing instructions. Technical Characteristics. -Lead Plumbing Law Certifi ed by IAPMO R&T
www.caleffi.com 37. MixCal adjustable three-way thermostatic mixing valve Copyright Caleffi Installation, commissioning and servicing instructions Series Function The Caleffi MixCal three-way thermostatic
More informationAdjustable three-way thermostatic mixing valve... connections ½", ¾", 1" NPT male union and sweat union and ¾" press
MixCal djustable three-way thermostatic mixing valve series CCRIT ISO 9 FM ISO 9 No. CLFFI / N Replaces / N Function The Caleffi MixCal series three-way thermostatic mixing valve is used in systems producing
More informationMultibox. Floor Heating Controller Flush individual room control for floor heating systems
Multibox Floor Heating Controller Flush individual room control for floor heating systems IMI HEIMEIER / Floor Heating Control / Multibox Multibox K, RTL and K-RTL Multibox K, RTL and K-RTL is used for
More information2. General information Page Warnings Page Technical characteristics Page Installation Page Front panel Page 7
INDEX 1. Symbols and warnings Page 3 2. General information Page 4 3. Warnings Page 5 4. Technical characteristics Page 6 5. Installation Page 6 6. Front panel Page 7 7. Set-up and calibrations Page 8
More informationData Sheet. Compact Mixing Shunt for Floor Heating, FHM-Cx. Application:
Data Sheet Compact Mixing Shunt for Floor Heating, FHM-Cx Application: FHM-C1 Mixing shunt FHM-C/ FHM-C Mixing shunt FHM-C Mixing shunt FHM-C The Danfoss floor heating compact mixing shunts are used for
More informationCa 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00
Ca 6s and BCa 6s 33-64 kw INSTALLATION AND OPERATING INSTRUCTIONS Page 1 CONTENTS: General specification Dimensions for Ca6s and BCa6s boilers. Boiler room clearance requirements Boiler block assembly
More informationCALEFFI. Thermostatic mixing valves, low-lead, high-flow series 01256/18 NA. Replaces 01256/15 NA
Thermostatic mixing valves, low-lead, high-flow 5 series CCREDITED ISO 9 FM 5 ISO 9 No. CLEFFI 5/ N Replaces 5/5 N Function The thermostatic mixing valve is used in systems producing domestic hot water
More informationSystems for central heating
www.far.eu Highlight Systems and Components for central heating Components for renewable energy systems Pressfar Fittings Presetting valves and thermostatic head Balancing devices Zone valves Metering
More informationMK 8706 / MB 8706 CONCEALED THERMOSTATIC SHOWER VALVE INSTALLATION GUIDE
MK 8706 / MB 8706 CONCEALED THERMOSTATIC SHOWER VALVE INSTALLATION GUIDE DIMENSIONS 150mm 55mm 200mm 67mm Hot water ¾ BSP Parallel Cold water ¾ BSP Parallel 160mm x 120mm aperture behind face plate for
More informationFor the user / for the installer. Instructions for Use and Installation. time SWITCH hour time clock
For the user / for the installer Instructions for Use and Installation time SWITCH 130 24 hour time clock GB GB Contents GB 24 hour time clock Operating instructions page 4-9 Installation instructions
More information4-way valve with thermostatic option with variable centre distance and pre-adjustment for Single pipe and Dual pipe systems.
4-way valve with thermostatic option with variable centre distance and pre-adjustment for Single pipe and Dual pipe systems. CT3101.0_00 EN June 2016 o o o o Valve with pre-adjustment; Variable centre
More informationSection - A. Radiator Valves
Section - Radiator Valves RDITOR VLVES EXMPLE OF PPLICTION 2 6 9 3 5 7 1 4 8 2 1 Thermostat adaptable valves. 2 Lockshield valves. 3 4-way thermostat adaptable valves for one-pipe and two-pipe systems.
More informationSECTION 3. OPERATING INSTRUCTIONS
SECTION 3. OPERATING INSTRUCTIONS 3-1. INTRODUCTION This section provides operating procedures for the heated display cabinets. The Introduction, Installation and Operation sections should be read, and
More informationASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM
ASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.817 Date: july 23, 2015 Supersedes: 10.817 Date: june 3, 2015 1.0 Typical installations 1 2.0 How it works
More informationProduct Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen
Hydronic Mixing Block Version 1.104 The Hydronic Mixing Block is a mixing device and boiler control, with a built in circulator and system controller. The block can provide either a fixed or reset water
More informationCALEFFI. Solar storage-to-boiler thermostatic connection kit series 01164/09 GB. Function
Solar storage-to-boiler thermostatic connection kit 6-63 series REGI STERED BS EN ISO 900:000 Cert. n FM 64 UNI EN ISO 900:000 Cert. n 0003 CLEFFI 064/09 GB Function The solar storage-to-boiler connection
More informationMODEL CMA-130VL PARTS MANUAL Rev 1.00
MODEL CMA-130VL PARTS MANUAL Rev 1.00 DISTRIBUTED EXCLUSIVELY BY CMA DISHMACHINES 12700 KNOTT AVENUE GARDEN GROVE, CALIFORNIA 92841 800-854-6417 FAX 714-895-2141 www.cmadishmachines.com TABLE OF CONTENTS
More informationfunction Adjustable thee-way thermostatic mixing valve... connections 1/2", 3/4", 1" NPT male union and sweat union
mixcal adjustable three-way thermostatic mixing valve series CCREITE ISO 9 FM ISO 9 No. CLEFFI / N Replaces / N LOW LE function The Caleffi MixCal three-way thermostatic mixing valve is used in systems
More informationSD2. Differential Controller. Operating and Installation Instructions F2 72.3
SD2 Differential Controller Operating and Installation Instructions F2 72.3 i Please follow the safety information and read these Instructions carefully before putting the system into operation. Safety
More informationSUN EQUINOX HEATING SYSTEMS
SUN EQUINOX HEATING SYSTEMS HIGH-EFFICIENCY HOT WATER SOLUTIONS INSTALLATION & OPERATION MANUAL Production Number: Customer Contact Information Other Resources 260-65-5605 http://www.solarusagenow.com
More information80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features
Comfort Module Range for Monobloc Heat Pumps Quality Management Systems Comfort module with two-zone kit Single-zone comfort module 8HMA Nominal heating capacity 4- kw Nominal cooling capacity 4- kw The
More informationCALEFFI. Anti-condensation recirculation and distribution unit. 281 series 01224/14 GB. Replaces dp 01224/12 GB. Function
Anti-condensation recirculation and distribution unit 8 series ACCREDITED ISO 900 FM 654 ISO 900 No. 000 CALEFFI 04/4 GB Replaces dp 04/ GB GB Function The anti-condensation recirculation and distribution
More informationOwner s Manual Crimping Machine CM 25-6
Owner s Manual Crimping Machine CM 25-6 Before starting any work please read operationg instructions Rev.: 2015-04-22 1 / 14 Table of Contents 1. Preface 3 2. Technical Data 3 2.1 Setup/Construction 4
More informationInstallation and instruction manual SOLAR STATION
INSTALLATION AND INSTRUCTION MANUAL SOLAR STATION Installation and instruction manual SOLAR STATION SST 25-1E / SST25-2E EN April 2015 1 Table of contents Usage 3 Warranty 3 Safety instructions and symbol
More informationgeothermal march 2011
geothermal march 2011 General information Office hours: Monday to Friday 8.30am - 5.00pm. Prices: Prices are exclusive of VAT, and are subject to change without notice. All prices displayed are recognised
More informationHG 675 CX 60 HG 675 CN 60 HG 675 CW 60
HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,
More informationCALEFFI. Modulating temperature regulating unit for heating and cooling with high temperature distribution kit. series /04 GB.
Modulating temperature regulating unit for heating and cooling with high temperature distribution kit series cert. n ISO / GB Function The modulating temperature regulating unit with high temperature distribution
More informationINSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS Please read these instructions thoroughly before installation and ensure they are passed on to the end-user 1 1.0
More informationteide termo plus+ HEATING SERIES SCOPE THERMOSTATIC VALVES SERVICE CONDITIONS COMPONENTS TECHNICAL SHEET 07/2017 IP20060 PAG. 1/9
HEATING SERIES QUALITY BY TRADITION teide termo plus+ TECHNICAL SHEET 07/2017 IP20060 SCOPE The thermostatic valves and heads from TEIDE TERMO PLUS series can be used in individual or collective heating
More informationROTEX RMX Heating circuit distributor
For certified companies ROTEX RMX Heating circuit distributor Installation and maintenance instructions Types ROTEX RMX 2 12 GB Edition 11/2009 Serial number Customer Guarantee and conformity Guarantee
More informationSMART Electronic control for towel radiators
SMART is an electronic thermostat for the automatic control of electric towel radiators. By means of an internal sensor it is capable of keeping the temperature of the towel radiator to a desired value.
More informationForced draught gas burner
Installation, use and maintenance instructions GB Forced draught gas burner One stage operation CODE MODEL TYPE 3751782 GAS 5 517T80 291 (4) - 07/2015 Declaration of conformity in accordance with ISO /
More informationTECHNICAL INFORMATION Touchtronic Clothes Dryers
TECHNICAL INFORMATION Touchtronic Clothes Dryers Includes: T1302, T1303, T1322, T1329ci T1403 & T1405 2004 Miele This page intentionally left blank. Table of Contents GENERAL INFORMATION A. Warning and
More informationGeneral System Layout Sketch
General System Layout Sketch EZ-37 Solar Panels PV panel Glycol Fill Valve Expansion Tank ` 1 Introduction This document describes how to install a Heliatos GH type solar water heating system. These systems
More informationHEAT RECOVERY AIR HANDLING UNIT
HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty
More informationproduct overview ProControl
product overview ProControl 2016 product overview ProControl 2016 4 The company AFRISO Sp. z o.o. was founded in 1997. Since that time we keep doing our best to increase AFRISO brand awareness among Installers.
More informationModel: 1100 Float-Controlled Condensate Trap, PN 25
1 Safety instructions Model: 1100 Float-Controlled Condensate Trap, PN 25 1.1 Proper use Any improper use, intervention in the design and deviation from the design data automatically lead to termination
More informationTS RD 7761 RD, 7761 RD
1/2 HERZ Calis TS RD three way valve HERZ Calis TS RD 100% three-way valve for heating and cooling Datasheet for 1 7761 RD, Issue 0716 Dimensions in mm Order number Dimension R A B C kvs dp (bar) maximum
More informationLYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE LYRA 1000 VVS
www.regulus.eu LYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE EN LYRA 1000 VVS CONTENTS 1 Description... 3 1.1 Models... 3 1.2 Tank protection... 3 1.3 Thermal insulation...
More informationDRAIN WATER TEMPERING INSTALL
! WARNING! CAUTION DRAIN WATER TEMPERING KIT - 0601-00-07-86 WARNING! This kit should be installed only by qualified service personnel to reduce the risk of electric shock, serious injury, or fire. A plumbing
More information2.A MANIFOLD SHUNTS MINI SHUNTS
2.A MANIFOLD SHUNTS MINI SHUNTS ROTH HEATING SYSTEMS 2A. MANIFOLD SHUNTS Roth Manifold Shunts 4"/5.8cv and 1"/7.0cv Preassembled, manually adjusted, proportional temperature mixing station with built-in,
More informationMultibox. Flush Individual Room Control for Floor Heating Systems. To be precise.
Flush Individual Room Control for Floor Heating Systems To be precise. Contents Page Multibox K, Multibox RTL and Multibox K-RTL Description Construction Application 4 Temperature Setting 4 Function Article
More informationRadiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function
HERZ-3000 Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function Standard Sheet for 3791 3792 Edition 1000 (0999) Dimensions in mm 1 3001 01 Cone sleeve 1 3002 01 Connection
More informationDOMESTIC STEAM GENERATOR Installation Instructions
DOMESTIC STEAM GENERATOR Installation Instructions Please read all of the instructions carefully before commencing installation or using the facility. Contents INTRODUCTION Page 2 TECHNICAL SPECIFICATION
More informationVST Series. INAIL approved and calibrated safety valves. Technical Data Sheet. WattsIndustries.com
VST Series INAIL approved and calibrated safety valves Technical Data Sheet WattsIndustries.com Description VST Series INAIL approved and calibrated safety valves automatically discharge enough liquid
More informationOperating & Safety Instructions
EUROPEAN FINISHING EQUIPMENT Corp. 901 PENHORN AVE., UNIT #2 SECAUCUS, NJ 07094 PHONE (201) 210-2247 FAX (201) 210-2549 sales@histeam.com www.histeam.com Operating & Safety Instructions - - - - - - - -
More informationINLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL
INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data
More informationPHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE
TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE
More informationDynalux. Floor Heating Manifolds Underfl oor heating circuit manifold
Dynalux Floor Heating Manifolds Underfl oor heating circuit manifold IMI HEIMEIER / Floor Heating Control / Dynalux Dynalux Dynalux adjusts the flow rate in the individual heating circuits directly in
More informationHERZ Differential Pressure Control Valve 4002
HERZ Differential Pressure Control Valve 4002 Data sheet 4002, Issue 0118 Dimensions in mm B1 B2 1 4002 41 1 4002 61 1 4002 71 1 4002 42 1 4002 62 1 4002 72 1 4002 43 1 4002 63 1 4002 73 1 4002 44 1 4002
More informationIH 025 VOLCANO. Portable Induction Heater. smart mounting
Portable Induction Heater IH 025 VOLCANO Bedienungsanleitung Instructions for use Mode d emploi Manuale d istruzioni Manual de usuario 2 Portables Induktions-Anwärmgerät IH 025 VOLCANO simatec ag Table
More informationTDS 20 R / TDS 30 R / TDS 50 R
TDS 20 R / TDS 30 R / TDS 50 R EN OPERATING MANUAL ELECTRICAL FAN HEATER TRT-BA-TDS20R-30R-50R-TC-001-EN Table of contents Notes regarding the operating manual... 1 Safety... 1 Information about the device...
More informationFHM-Cx Mixing Shunts for Floor Heating
FHM-Cx Mixing Shunts for Floor Heating Application Mixing shunt FHM-C5/C6 (UPS pump) The Danfoss compact mixing shunts are used for regulation of flow and supply temperature in hydronic floor heating systems.
More informationTechnical information. Remeha P200. Pressurized boiler. Heat output: kw
Technical information Remeha P200 R e m e h a P 2 0 0 Pressurized boiler Heat output: 59-256 kw Remeha P 200 CONTENTS Preface 3 1. Description of the unit 4 1.1 General 4 1.2 Burners 4 2. Construction
More informationControl valves for floor heating systems. Floor Heating Manifolds
Control valves for floor heating systems Floor Heating Manifolds IMI HEIMEIER / Floor Heating Control / Control valves for floor heating systems Control valves for floor heating systems Supply control
More informationRA2000 Thermostatic Radiator Valves
Data Sheet RA2000 Thermostatic Radiator Valves Application regulate the flow of hot water or steam through free-standing radiators, baseboards or convectors in hot water and two-pipe low pressure steam
More informationLight oil burners. One stage operation
Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR
More information