AIR COOLED CHILLERS MODELS: MPCA0005 MPCA0150 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Size: px
Start display at page:

Download "AIR COOLED CHILLERS MODELS: MPCA0005 MPCA0150 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL"

Transcription

1 MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MPCA0005 MPCA0150 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This chiller has been factory run tested to the specified water pressure *****DO NOT OVER PRESSURIZE CHILLER WHEN LEAK CHECKING PIPING OR FILLING HYDRAULIC SYSTEM***** *Isolate chiller from piping if higher test pressure is required for leak checking* *Chiller damaged caused by over pressurization is NOT covered by warranty* 85 Woodridge Dr. Amherst, NY Phone# Fax#

2 INDEX TABLE OF CONTENTS PAGE LEGAL PROVISIONS & SAFETY INSTRUCTIONS 1 TRANSPORTING & SITE HANDLING 2-3 CHILLER INSTALLATION 4-13 PIPING INSTALLATION MAIN ELECTRICAL INSTALLATION 19 WATER/GLYCOL INSTRUCTIONS 20 CHILLER SEQUENCE OF OPERATION 21 MPCA0005 MPCA0150 PROGRAMMING AND ALARM CODES MPCA0005 MPCA0150 STANDARD CONTROLLER LAYOUT 26 COMMISIONING AND STARTUP INSTRUCTIONS TROUBLESHOOTING PREVENTIVE MAINTENANCE CHILLER REPAIR INFORMATION CLEANING THE PLATE EXCHANGER (EVAPORATOR) 38 REFRIGERANT INFORMATION 39 TERMS AND CONDITIONS OF SALE 40

3 PROVISIONS AND SAFETY Operation of these systems involves potentially Iethal dangers (high voltage and high pressures). Therefore, all safety precautions and warnings described in this manual must be precisely observed. Otherwise, severe or fatal injury may be caused. Operator's Responsibility This chiller MUST be installed, maintained and operated by a person(s) qualified for this equipment. This chiller contains refrigeration, water circulation and electrical components. The person(s) most suited for this equipment is a qualified licenced refrigeration technician. Intervention by unauthorized or unqualified parties may void the warranty. SAFETY INSTRUCTIONS The installation, start-up and maintenance of the chillers are dangerous, Due to: High pressures is generated in the equipment Electrical parts are energized The equipment contains hot pipes (Refrigeration system) Rotating parts (fans and or pumps) can cause injury the chillers themselves may be installed in a dangerous position (roof, high built frame etc.) For these reasons, the chiller must be installed and connected to the electricity/water installations by qualified companies only. Startup and maintenance must be conducted by a qualified refrigeration company only. Simple maintenance operations on the equipment without opening them may be performed by the operator. All other work must be performed by specially qualified personnel.

4 LIFTING - UNLOADING POSITIONING Notices (symbols) on device packing must be observed. Check the center of gravity of the chiller. Use appropriate unloading equipment. Remove protective film from chiller and cardboard. behind condenser before use. TRANSPORT AND HANDLING MANUFACTURER'S NOTE The machine may be damaged by: Dropping or tipping it on the ground. Pulling the chiller by cords, straps, etc. Lifting the chiller by its piping system. Excessive shaking by cranes. Damage of this type is not covered by warranty. ECA ECA MAX 45 ECA ECA

5 LIFTING - UNLOADING POSITIONING Notices (symbols) on device packing must be observed. Check the center of gravity of the chiller. Use appropriate unloading equipment. Remove protective film from metal panels before use. MANUFACTURER'S NOTE The machine may be damaged by: Dropping it or tipping it on the ground. Pulling the chiller by cords, straps etc. Lifting the chiller by its piping system. Excessive shaking by crane. Damage of this type is not covered by warranty. Installing with a fork lift truck Use the forks to lift with: they must be as long as the chiller. Use of fork extensions if required, OR SERIOUS DAMAGE MAY RESULT. LIFTING WITH A CRANE Use the holes in the bottom framework for lifting. To distribute the weight evenly place a strong L-shaped section between the belts and structure work. INSERT SPREADER BARS TO PREVENT CRUSHING HOOKING TO THE STRUCTURE Hook only to the points indicated by the lifting labels. Make sure there is no possibility that the hooks can slip out due to swinging or movements from the crane

6 CHILLER INSTALLATION Foundation Site Installation All chillers must be mounted on a solid, horizontal surface, suitable for the weight of the chiller.* Note the chiller weight is incresed by filling with glycol/water mixture. Observe all local regulations. Must be dry and protected against freezing. The room temperature must not be colder than 41 0 F. The system must be installed horizontally. The components are not suitable for exterior installation, without factory modification and approval. Consult Motivair if chiller will be installed outdoors Installation Structure-borne noise Compliance with the following basic rules for the erection of devices with radial fans wiil ensure problem-free operation and the rated refrigeration capacity. Basic rules: 1. The condenser air is blown out vertically or horizontally. 2. Do not install the device close to heat sources. Heated air intake must be avoided. 3. The condenser fans are rated for ZERO external static pressure. The fan do not have the capacity to push air through ducting, which means that NO DUCTS OR MUFFLERS may be used on the inlet ot outlet of the chillers. 4. No air short-circuit is permitted, i.e. the heated discharge air from the condenser fans must never be drawn back into the condenser inlet. This will occur if the chiller is too close to a wall, or a low ceiling or other obstructions. 5. In the case of shaft or trench mounting, contact the manufacturer for advice on the installation site. It is possible that noise or vibration may be transmitted through the ground, or building structure. If this occurs, it may be necessary to install a vibration elimination device. The construction specifications of the customer/engineering contractor regarding structure transmitted noise or vibration must be observed. Vibrations May be transmitted through the chilled water piping. This can be avoided by the use of flexible piping connections. Clearances Must be maintained for servicing and ventilation purposes. All removable side panels must be available service. A minimum of 3 feet on all sides is required. Consult Motivair for irregular space requirements.

7 INSTALLATION GUIDE Location: Locate the unit to provide proper airflow to the condenser (see Figure 1 page 2) Due to the placement of the condenser coils on the MPCA chillers, it is desirable to orient the unit so that prevailing winds blow parallel to the unit length, thus minimizing the wind effect on condensing pressure performance. If low ambient temperature operation is expected, it is recommended that optional fan VFD system be factory installed. Using less clearance than shown in Addendum A can cause discharge air recirculation to the condenser and could have a significant negative effect on unit performance. See Restricted Airflow beginning on page 3 for further information. For pad-mounted units, it is recommended that the unit be raised a few inches with suitable supports, located at least under the mounting locations, to allow water to drain from under the unit to facilitate cleaning under it. Service Access: The main control box contains either the microprocessor or PLC (Programmable Logic Controller) for optimum chiller control. The solid state compressor starter, fan control and other power equipment are located in the main control box. Condenser fan VFD s and overloads are either located in an independent box on the side of the chiller or in the main cabinet. The side clearance required for airflow provides sufficient service clearance. CAUTION Disconnect all power to the chiller while servicing condenser fan motors or compressors. Failure to do so can cause bodily injury or death. Do not obstruct access to the sides or ends of the chiller with piping or conduit. These areas must be open for service access. Do not obstruct any access to the control panel(s) with field mounted disconnect switches. Make sure that the power conduit to control panel(s) does not restrict access to removable panels.

8 Clearance Requirements: Figure 1 AIR FLOW NO OBSTRUCTIONS ALLOWED ABOVE UNIT AT ANY HEIGHT SEE NOTES 2&4 PERTAINING TO WALL HEIGHT AT UNIT SIDES Notes: 1. Minimum side clearance between units is 6 feet (1.8 meters) with no perimeter obstructions within 10 feet of the units. 2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit unless extra clearance is provided per note Minimum clearance on each side is 8 feet (2.4 meters) when installed in a pit no deeper than the unit height. 4. Minimum side clearance to a side wall or building taller than the unit height is 7 (2.1 meters) feet provided no solid wall above 7 (2.1 meters) feet is closer than 12 (3.7 meters) feet to the opposite side of the unit. 5. Do not mount electrical conduits where they can block service access to compressor controls, refrigerant driers or valves. 6. There must be no obstruction of the fan discharge. 7. Field installed switches must not interfere with service access or airflow. 8. MPCA chillers use axial fans and are NOT suitable for ducted applications. 9. See the following pages if the airflow clearance cannot be met.

9 Restricted Airflow: General The clearances required for design operation of MPCA air-cooled condensers are described in the previous section. Occasionally, these clearances cannot be maintained due to site restrictions such as units being too close together or a fence or wall restricting airflow, or both. The Motivair MPCA chillers have several features that can mitigate the problems attributable to restricted airflow. The single side of the condenser formation allows inlet air for the coil(s) to come in from that side and allows for smaller distances between the opposite side and encroaching obstructions to allow for maximum air flow to the condenser side. Facing the chiller control cabinet, the right-side of the unit is generally where the condenser(s) are located. NOTE: This is not exclusive as Motivair reserves the right to change chiller design without notice. The VFD option allows for optimum air flow at multiple year round conditions. This is best utilized when units are placed parallel to prevailing winds. Figure 2 The following sections discuss the most common situations of condenser air restriction and give capacity adjustment factors for each. CAUTION The unit capacity adjustment charts in this engineering bulletin serve only as a guide, and DO NOT take into account prevailing site conditions. 7

10 Case 1, Building or Wall on One side of One Unit: The presence of a screening wall or the wall of a building, in close proximity to an air-cooled chiller is common in both rooftop and ground level applications. Hot air recirculation on the coils adjoining the wall increases compressor discharge pressure, decreasing capacity and increasing power consumption. When close to a wall, it is desirable to place chillers on the north or east side of them (to minimize solar effect). It is also desirable to have prevailing winds blowing parallel to the unit s long axis. The worst scenario is having wind blowing hot discharge air into the wall. Figure 3 D H Figure 4, Adjustment Factor

11 Case 2, Two Units Side By Side: Two or more chillers positioned side by side are common. If spaced closer than 6 feet it is necessary to adjust the performance of each unit; circuits adjoining each other are affected. If one of the two units also has a wall adjoining it, see Case 1. Add the two adjustment factors together (Figure 4 and Figure 6) and apply to the unit between the wall and the other unit. Mounting units end to end will not require adjusting performance. Depending on the actual arrangement, sufficient space must be left between the units for access to the control panel door opening. See Clearance section of this guide for requirements for specific units. Pit or solid wall surrounds should not be used where the ambient air temperature exceeds 95 F. Figure 5, Two Chillers Side by Side D Figure 6, Adjustment Factor

12 Case 3, Three or More Units Side By Side: When designs call for three or more units to be side by side; contact Motivair with the desired placements of the units for approval. Capacity reduction is dependent on multiple possible orientations of the units. Figure 7, three or more chillers D D D

13 Case 4, Open Screening Walls: Decorative screening walls are common to help conceal a chiller either on grade or on a rooftop. These walls should be designed such that the combination of their open area and distance from the chiller do not require performance adjustment. It is assumed that the wall height is equal to, or less than the chiller height when mounted on its base support. This is usually acceptable for concealment. If the wall height is greater than the unit height, see Case 5 (Pit Installation). The distance from the sides of the unit to the side walls should be sufficient for service and opening control panel doors. If each side wall is a different distance from the unit, the distances can be averaged, providing either wall is not less than 8 feet from the unit. For example, do not average 4 feet and 20 feet to equal 12 feet. Figure 9, Open Screening Walls D D Figure 10, Wall Free Area Graph

14 Case 5, Pit/Solid Wall Installation: Pit installations can cause operating problems and great care should be exercised if they are to be used on any installation. Recirculation and restriction are probable. A solid wall surrounding a unit is effectively the same as a pit and the data given in Case 5 should be used. Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The grating material and installation design must be strong enough to prevent such accidents, yet provide abundant open area or serious recirculation problems will occur. Have any pit installation reviewed by Motivair application engineers prior to installation to discuss whether it has sufficient airflow characteristics. The installation design engineer must approve the work and is responsible for design criteria. Figure 11, Pit Installation H D Figure 12, Adjustment Factor D=10Ft 12

15 Addendum: A Control Panel 40 Control Panel 40 MIN. CLEARANCE FOR MPC-A MIN. CLEARANCE FOR MPC-A 0150

16

17 NOTE: VENTS ARE REQUIRED AT ALL "LOCAL" HIGH POINTS IN SUPPLY AND RETURN

18 PIPING INSTALLATION This section is intended as a guide for the correct installation of the chilled water piping system, including this chiller. However, the chiller manufacturer accepts no responsibility what so ever for the installation of the chiller or the associated piping. All piping must be installed only by a licensed plumbing contractor, and in compliance with local codes. DO NOT USE GALVANIZED PIPING IF GLYCOL IS TO BE USED IN THE CHILLED WATER SYSTEM. Chemical reaction between the glycol and the galvanized piping can be detrimental to the cooling system, the glycol and chiller. Piping material may be copper, plastic, carbon or stainless steel depending on the requirements of each installation. It is the responsibility of the engineer and/or the piping contractor to insure that the piping is correctly sized in relation to the installation, and the available dynamic head of the pump installed inside the chiller. The chilled water pipe connections on the chiller are not necessarily the appropriate size for the system piping. As a general guide, the chiller pipe connections should be considered as the minimum pipe size required for the installation. Drastic reduction in pipe sizing (small hoses, etc.) will reduce the chilled water flow and may cause a low flow alarm, or freezing damage to the evaporator. Note: Installation with low water flow/high water temperature rise should always have a full-ported by-pass installed between the chiller inlet and outlet connections, with a manually adjustable gate valve in the by-pass line. Correctly adjusted, this blended return water will maintain an adequate flow through the chiller, at an acceptable return temperature. ALWAYS install a filter/strainer on the inlet off the chiller, in order to prevent particulates (rust, dirt and installation debris) from blocking the evaporator. Blockage will severely impair chiller performance and is not covered by warranty. Always install a pressure gauge in the return piping close to the chiller. This is essential for monitoring system pressure and pump performance. It is good piping practice, especially on systems with short piping runs and/or low system pressure loss, to install a gate valve in the DISCHARGE line from the chiller for throttling purposes. This allows the operator to maintain optimum pump performance by adding resistance to the system. NEVER throttle the water flow on the return line to the chiller. This will cause cavitations and over-heating of the pump. AUTOMATIC WATER MAKE-UP If the chilled water cooling system is expected to lose water during normal operation an automatic water make-up system should be installed, or can be supplied as a factory option. The auto make-up system must include a water pressure regulator and pressure gauge. CAUTION: The tank inside the chiller has a maximum pressure rating of 15 PSIG. Do not discharge city water (which can be 60-80psig) directly into the chiller. Instantaneous pressurization can cause the tank to rupture before the pressure relief valve opens. NOTE: Do not use an automatic water make-up system if glycol is installed for antifreeze protection. The glycol will become diluted and the freeze protection point will be higher (less protection from freezing). Some critical applications require the installation of emergency city water and drain solenoid valves, in the event of a chiller failure. In this case, the chiller MUST be isolated from the city water pressure to avoid damage. After operation of the emergency city water system, the glycol concentration must be carefully checked using a spectrometer. Add glycol to maintain the correct antifreeze concentration if required. NOTE: Vertical piping immediately connected to and from the chiller will impose a static (or standing) head pressure, which can be read on the pump discharge gauge of the chiller, and the gauge installed on the return line to the chiller, when the system is not operating. For example, if the supply and/or return piping from the chiller rises 15 feet before running above a ceiling, etc. this will show a gauge static

19 pressure of approximately 6-7psig on the gauges (feet x.424 = psig). This is simply the weight of water in the vertical piping at that location, and does not indicate an overall system pressure. SYSTEM VENTING The single most common problem in chiller piping installations is lack of chilled water flow caused by poor piping practices and/or inadequate venting of the system. The symptom is a repeated flow alarm, when the flow switch installed in the return line inside the chiller contacts open which in turns triggers the flow alarm on the control panel. The size chillers are CLOSED CIRCUIT system and is open to atmosphere. This means that air will remain in all local high points above chiller of the system when it is initially filled with water. NOTE: A local high point is any point in the piping, which can be described as an inverted U section. More clearly defined, if the piping rises vertically ANYWHERE, AND AT ANY ELEVATION IN THE SYSTEM, travels horizontally, then drops again vertically, this inverted U section of piping IS A PERMANENT AIR LOCK AND MUST BE VENTED. Venting is required AT ALL LOCAL HIGH POINTS, and is required on both the supply and return pipes. Vents can be either manual, or automatic. Automatic vents should always be installed with an isolation valve for future service access, repair or replacement. Automatic vents are particularly susceptible to drawing air into the return chilled water piping if this line is allowed to fall into a vacuum. NOTE: The expansion tank should not normally be pressurized to more than 15 psig, measured when the system is not operating. The final discharge pump pressure should NEVER be allowed to exceed the maximum pump rating pressure (normally around 35-50psig). CAUTION: Supercharging the pump with city water pressure higher than nominal rating of the pump, can damage the mechanical pump seal(s), or cause damage to the chiller, piping system or customer equipment. This damage is not covered by the chiller warranty.

20 WATER/GLYCOL FILLING If glycol is required for antifreeze protection, ALWAYS use an industrial inhibited ethylene glycol, or propylene (food grade) glycol. DO NOT use automobile antifreeze. Suitable glycols are manufactured by the Dow Chemical Company for this purpose, and available nationwide. There are other glycol suppliers available, but always exercise great caution in the selection of a glycol supplier, and always confirm the freeze protection after installation, using a spectrometer. Damage caused by freezing is not covered under warranty. Glycol can be pre-mixed with water to the correct concentration, then pumped into the system, or pumped in separately from the water, provided the system capacity is calculated accurately. The most common method for filling the system is to pump the water glycol into the fill or drain connection of the chiller, with all system vents open. There is a manual vent located at the back of the chiller for initial filling/venting purposes, in addition to the high point piping vents. NOTE: The system should be filled slowly and carefully, allowing all the air to escape. The system can only be filled as fast as the air can escape. Be patient, and do not over-pressurize the system. After initial operation, check all air is vented from the system. GLYCOL CHART Ethylene Glycol Propylene Glycol % of Glycol Freeze Point % of Glycol Freeze Point 0% 32F 0% 32F 10% 26F 10% 26F 20% 16F 20% 19F 30% 4F 30% 8F 40% -12F 40% -7F 50% -34F 50% -28F 60% -60F 60% -60F

21 The manufacturer of the supplied chiller accepts NO LIABILITY for the work supplied by the customer or civil engineering contractor. MAIN ELECTRICAL INSTALLATION WIRING DIAGRAM INSPECTION Check that the wiring diagram supplied with the chiller is correct and complete: MAIN ELECTRICAL CONNECTION The connection of the device to the main electrical power supply must only be carried out by an licensed electrician, and in strict accordance with local electrical codes and safety standards. ELECTRICAL COMPONENTS FuIIy wired electrical panel The electrical panel is mounted in the chiller and contains all necessary controls for the chiller. Additional wiring in the electrical panel Additional wiring is permitted but must not modify the original condition of the factory-installed wiring. All changes must be recorded in the original wiring diagram and must be available to the manufacturer. MODEL INFORMATION: REFER TO DATA ON SERIAL STICKER FOR EACH MODEL MANUFACTURER S NOTICE The main disconnect switch on the chiller must be switched off before carrying out any wiring work. Do not switch on the microprocessor until startup and commissioning has been successfully completed. MAIN VOLTAGE SUPPLY MPCA MPCA V/60Hz/1~ 230V/60Hz/1~ The permissible voltage tolerance is ±5%. These values are BINDING and COMPULSORY. INFORMATION ON EXTERNAL WIRING Main power feed Note: If for local code or other reasons the cable size of the power supply line is larger than the terminal size on the main disconnect or power block: 1. A junction box must be fitted to the chiller in compliance with local codes in order to reduce the cable size Or 2. The main disconnect switch or power block of the chiller must be replaced (prior approval of the manufacturer is required).

22 WATER/GLYCOL INSTRUCTIONS MANUFACTURER'S SPECIFICATIONS The chiller circuit must be 100% filled with water/glycol for operation. If the cooling process causes a loss of water/glycol in the circuit a automatic water make-up vavle must be installed. Insufficient fluid in the water/glycol circuit wiil lead to failure of chiller 1. Safety devices 2. Controls,due to compressor fluctuations/ hunting (frequent switching). And compressor starts. 3. Cooling Capacity These can be avoided by adding a reservoir on the inlet side of the chiller. OnIy operate the chiller with a flow switch (supplied) that switches off the chiller in the event of insufficient water or a faulty pump. If this condition is not satisfied: ALL WARRANTY CLAIMS SHALL BE VOIDED Flow meter and a automatic water make-up system can be purchased from the factory. COLD WATER PIPING Water piping and connection to the chiller must conform with all generally accepted piping practices and local codes. All piping should be performed by a qaulified person(s) or company. The following specifications are intended to prevent damage to the chiller. 1. Avoid unnecessary pressure drop by ensuring correct pipe sizes and routing. 2. Connect the chiller with vibration eliminators to avoid transmission of noise and vibrations. 3. Shut-off valves should be installed at the inlet and outlet of the chiller so that maintenance and repair work can be performed without draining the piping system. 4. Y-Strainer (40 mesh) should be installed on the inlet piping to the chiller to ensure no foreign particles enter the evaporator and or pump.*without a Y-Strainer installed blockage of the evaporator will occur 5. Automatic vents should be installed at all local high points of the piping system to eliminate air locks. See chilled water system diagram for location(s). COLD WATER PIPING CONT. 6. Ensure that the water circuit is maintained at the correct pressure by installing an appropriate sized diaphragm expansion tank close to the inlet of the chiller. The return side of the chiller must be 5-10psig when the pump is running. 7. Install temperature and pressure gauges at the inlet and outlet of the chiller and the heat load to ensure easy inspection and maintenance. 8. All chilled water lines should be insulated. Only insulate pipes AFTER the circuit was tested for leaks. GLYCOL IN CIRCUIT Glycol mixture The following basic rules must be followed: 1. The freezing point of the mixture must be lower than the minimum evaporation temperature. Or the lowest outside piping temperature, whichever is the lower of the two. 2. See correction factors for glycol concentration on back page of the MPCA chiller brochure. 3. Use only an industrial grade inhibited ethylene glycol or food grade propylene glycol solution. DO NOT use automotive antifreeze. 4. Check the ph-value of the solution. lt should be about 9 and must never be less than Check the ph-value regularly (maintenance). 6. DO NOT use galvanized piping or fittings Operating the devices with a glycol mixture Check the extemal cold water network and pumps: sufficient pressure for increased water volume pumps suitable for glycol operation bleed valves (rapid bleeder unsuitable) IMPORTANT: NEVER change the antifreeze alarm parameter on chiller without written authorization from factory. If parameter is changed withour factory consent WARRANTY WILL BE VOIDED.!!!!!! The glycol/water mixture must not be discharged into the normal water drainage system. lt must be collected in suitable containers and disposed of in accordance with legal regulations.

23 MPCA0005 MPCA0150 Mechanical cooling inlet control On a call for cooling set point = 50*F + diff = 7*F entering temperature = 57*F glycol pump running the compressor starts. The controller reads the Inlet temperature and the compressor operates to pull down to set point. As the loop temp falls 0.1*F below set point the compressor shuts off glycol pump remains running. Compressor will turn back on when set point + differential is exceeded.

24 dixel Installing and Operating Instructions Digital controller with off cycle defrost and AUX relay XR30CX 4. FRONT PANEL COMMANDS CONTENTS 1. GENERAL 1 2. GENERAL DESCRIPTION 1 3. CONTROLLING LOADS 1 4. FRONT PANEL COMMANDS 1 5. MAX & MIN TEMPERATURE MEMORIZATION 1 6. MAIN FUNCTIONS 1 7. PARAMETERS 2 8. DIGITAL INPUT (ENABLED WITH P3P = N) 3 9. TTL SERIAL LINE FOR MONITORING SYSTEMS X-REP OUTPUT OPTIONAL INSTALLATION AND MOUNTING ELECTRICAL CONNECTIONS HOW TO USE THE HOT KEY ALARM SIGNALS TECHNICAL DATA CONNECTIONS DEFAULT SETTING VALUES 4 1. GENERAL 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application limits before proceeding. 1.2 SAFETY PRECAUTIONS Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to Dixell S.p.A. (see address) with a detailed description of the fault. Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful. 2. GENERAL DESCRIPTION Model XR30CX, format 32 x 74 mm, is a digital thermostat with off cycle defrost designed for refrigeration applications at normal temperature. It provides two relay outputs, one for the compressor, the other one can be used as light, for alarm signalling or as auxiliary output.. It is also provided with 2 NTC or PTC probe inputs, the first one for temperature control, the second one, optional, to connect to the HOT KEY terminals to signal the condenser temperature alarm or to display a temperature. The digital input can operate as third temperature probe. The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a network line ModBUS-RTU compatible such as the dixel monitoring units of X-WEB family. It allows to program the controller by means the HOT KEY programming keyboard. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard. 3. CONTROLLING LOADS 3.1 COMPRESSOR The regulation is performed Temper. according to the temperature measured by the thermostat probe SET with a positive differential from the set point: if the temperature Time increases and reaches set point plus Compr. differential the compressor is started ON and then turned off when the temperature reaches the set point value again. In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF. 3.2 DEFROST Defrost is performed through a simple stop of the compressor. Parameter IdF controls the interval between defrost cycles, while its length is controlled by parameter MdF. : To display target set point; in programming mode it selects a parameter or confirm an operation. (DEF) To start a manual defrost (UP): To see the max. stored temperature; in programming mode it browses the parameter codes or increases the displayed value. (DOWN) To see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. To switch the instrument off, if onf = off. To switch the light, if oa1 = Lig KEY COMBINATIONS: + To lock & unlock the keyboard. + To enter in programming mode. + To return to the room temperature display. 4.1 USE OF LEDS Each LED function is described in the following table. LED MODE FUNCTION ON Compressor enabled Flashing Anti-short cycle delay enabled ON Defrost enabled ON An alarm is occurring ON Continuous cycle is running ON Energy saving enabled ON Light on ON C/ F ON C/ F Flashing Auxiliary relay on Measurement unit Programming phase 5. MAX & MIN TEMPERATURE MEMORIZATION 5.1 HOW TO SEE THE MIN TEMPERATURE 1. Press and release the n key. 2. The Lo message will be displayed followed by the minimum temperature recorded. 3. By pressing the n key again or by waiting 5s the normal display will be restored. 5.2 HOW TO SEE THE MAX TEMPERATURE 1. Press and release the o key. 2. The Hi message will be displayed followed by the maximum temperature recorded. 3. By pressing the o key again or by waiting 5s the normal display will be restored. 5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 1. Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rst message will be displayed) 2. To confirm the operation the rst message starts blinking and the normal temperature will be displayed. 6. MAIN FUNCTIONS 6.1 HOW TO SEE THE SETPOINT 1. Push and immediately release the SET key: the display will show the Set point value; 2. Push and immediately release the SET key or wait for 5 seconds to display the probe value again. 6.2 HOW TO CHANGE THE SETPOINT 1. Push the SET key for more than 2 seconds to change the Set point value; 2. The value of the set point will be displayed and the C or F LED starts blinking; 3. To change the Set value push the o or n arrows within 10s. 4. To memorise the new set point value push the SET key again or wait 10s. 6.3 HOW TO START A MANUAL DEFROST Push the DEF key for more than 2 seconds and a manual defrost will start XR30CX GB m&m r doc XR30CX 1/4

25 dixel Installing and Operating Instructions HOW TO CHANGE A PARAMETER VALUE To change the parameter s value operate as follows: 1. Enter the Programming mode by pressing the Set + n keys for 3s (the C or F LED starts blinking). 2. Select the required parameter. Press the SET key to display its value 3. Use UP or DOWN to change its value. 4. Press SET to store the new value and move to the following parameter. To exit: Press SET + UP or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 6.5 THE HIDDEN MENU The hidden menu Includes all the parameters of the instrument HOW TO ENTER THE HIDDEN MENU 1. Enter the Programming mode by pressing the Set + n keys for 3s (the C or F LED starts blinking). 2. Released the keys, then push again the Set+n keys for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN THE HIDDEN MENU. 3. Select the required parameter. 4. Press the SET key to display its value 5. Use o or n to change its value. 6. Press SET to store the new value and move to the following parameter. To exit: Press SET + o or wait 15s without pressing a key. NOTE1: if none parameter is present in Pr1, after 3s the nop message is displayed. Keep the keys pushed till the Pr2 message is displayed. NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL (user level) by pressing SET + n. In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 6.6 HOW TO LOCK THE KEYBOARD 1. Keep pressed for more than 3 s the UP + DOWN keys. 2. The POF message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored 3. If a key is pressed more than 3s the POF message will be displayed. 6.7 TO UNLOCK THE KEYBOARD Keep pressed together for more than 3s the o and n keys, till the Pon message will be displayed. 6.8 THE CONTINUOUS CYCLE When defrost is not in progress, it can be activated by holding the o key pressed for about 3 seconds. The compressor operates to maintain the ccs set point for the time set through the CCt parameter. The cycle can be terminated before the end of the set time using the same activation key o for 3 seconds. 6.9 THE ON/OFF FUNCTION With onf = off, pushing the ON/OFF key, the instrument is switched off. The OFF message is displayed. In this configuration, the regulation is disabled. To switch the instrument on, push again the ON/OFF key. : Loads connected to the normally closed contacts of the relays are always supplied and under voltage, even if the instrument is in stand by mode. 7. PARAMETERS REGULATION Hy Differential: (0,1 25,5 C / F) Intervention differential for set point. Compressor Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. LS Minimum set point: (- 50 C SET/-58 F SET): Sets the minimum value for the set point. US Maximum set point: (SET 110 C/ SET 230 F). Set the maximum value for set point. Ot Thermostat probe calibration: ( C; F) allows to adjust possible offset of the thermostat probe. P3P Third probe presence (P3): n= not present:, the terminal operates as digital input.; y= present:, the terminal operates as third probe. O3 Third probe calibration (P3): ( C; F). allows to adjust possible offset of the third probe. P4P Fourth probe presence: (n = Not present; y = present). o4 Fourth probe calibration: ( C) allows to adjust possible offset of the fourth probe. OdS Outputs activation delay at start up: (0 255min) This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter. AC Anti-short cycle delay: (0 50 min) minimum interval between the compressor stop and the following restart. CCt Compressor ON time during continuous cycle: ( h; res. 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products. CCS Set point for continuous cycle: ( C) it sets the set point used during the continuous cycle. COn Compressor ON time with faulty probe: (0 255 min) time during which the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF. COF Compressor OFF time with faulty probe: (0 255 min) time during which the compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always active. CH Type of action: CL = cooling; Ht = heating. DISPLAY CF Temperature measurement unit: C=Celsius; F=Fahrenheit. : When the measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary). res Resolution (for C): (in = 1 C; de = 0.1 C) allows decimal point display. dly Display delay: (0 20.0m; risul. 10s) when the temperature increases, the display is updated of 1 C/1 F after this time. DEFROST IdF Interval between defrost cycles: (0 120h) Determines the time interval between the beginning of two defrost cycles. MdF (Maximum) length for defrost: (0 255min) When P2P = n, (not evaporator probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost. dfd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start; SEt = set point; def = def label) dad MAX display delay after defrost: (0 255min). Sets the maximum time between the end of defrost and the restarting of the real room temperature display. ALARMS ALC Temperature alarms configuration: (Ab; re) Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. re = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the SET+ALU or SET-ALL values. ALU MAXIMUM temperature alarm: (SET 110 C; SET 230 F) when this temperature is reached the alarm is enabled, after the ALd delay time. ALL Minimum temperature alarm: (-50.0 SET C; F when this temperature is reached the alarm is enabled, after the ALd delay time. AFH Differential for temperature alarm recovery: (0,1 25,5 C; 1 45 F) Intervention differential for recovery of temperature alarm. ALd Temperature alarm delay: (0 255 min) time interval between the detection of an alarm condition and alarm signalling. dao Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling. CONDENSER TEMPERATURE ALARM (detected by the fourth probe) AP2 Probe selection for temperature alarm of condenser: np = no probe; P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug. AL2 Low temperature alarm of condenser: ( C) when this temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay. Au2 High temperature alarm of condenser: ( C) when this temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay. AH2 Differential for temperature condenser alarm recovery: (0,1 25,5 C; 1 45 F) Ad2 Condenser temperature alarm delay: (0 255 min) time interval between the detection of the condenser alarm condition and alarm signalling. da2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min) bll Compressor off with low temperature alarm of condenser: n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case regulation restarts after AC time at minimum. AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case regulation restarts after AC time at minimum. SECOND RELAY tba Alarm relay silencing (with oa1=alr): (n= silencing disabled: alarm relay stays on till alarm condition lasts, y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm). oa1 Second relay configuration: ALr: alarm; Lig: light; AuS: Auxiliary relay; onf: always on with instrument on; db = do not select it; def: do not select it!.; FAn: do not select it!.; df2: do not select it. AoP Alarm relay polarity: it set if the alarm relay is open or closed when an alarm happens. CL= terminals 1-2 closed during an alarm; op = terminals 1-2 open during an alarm DIGITAL INPUT i1p Digital input polarity: op: the digital input is activated by opening the contact; CL: the digital input is activated by closing the contact. i1f Digital input configuration: EAL = external alarm: EA message is displayed; bal = serious alarm CA message is displayed. PAL = pressure switch alarm, CA message is displayed; dor = door switch function; def = activation of a defrost cycle; AUS =to switch on the second relay if oa1 = AUS; Htr = kind of action inversion (cooling heating); FAn = not set it; ES = Energy saving. did: (0 255 min) with i1f= EAL or i1f = bal digital input alarm delay: delay between the detection of the external alarm condition and its signalling. with i1f= dor: door open signalling delay with i1f = PAL: time for pressure switch function: time interval to calculate the number of the pressure switch activation XR30CX GB m&m r doc XR30CX 2/4

26 dixel Installing and Operating Instructions nps Pressure switch number: (0 15) Number of activation of the pressure switch, during the did interval, before signalling the alarm event (I2F= PAL). If the nps activation in the did time is reached, switch off and on the instrument to restart normal regulation. odc Compressor status with door open: no, Fan = normal; CPr; F_C = Compressor OFF. rrd Outputs restart after doa alarm: no = outputs not affected by the doa alarm; yes = outputs restart with the doa alarm; HES Temperature increase during the Energy Saving cycle : (-30,0 C 30,0 C/ F) it sets the increasing value of the set point during the Energy Saving cycle. OTHER Adr Serial address (1 244): Identifies the instrument address when connected to a ModBUS compatible monitoring system. PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc = NTC probe. onf on/off key enabling: nu = disabled; off = enabled; ES = not set it. dp1 Thermostat probe display dp3 Third probe display- optional. dp4 Fourth probe display. rse Real set point: (readable only), it shows the set point used during the energy saving cycle or during the continuous cycle. rel Software release for internal use. Ptb Parameter table code: readable only. 8. DIGITAL INPUT (ENABLED WITH P3P = N) The free voltage digital input is programmable in different configurations by the i1f parameter. 8.1 DOOR SWITCH INPUT (i1f = dor) It signals the door status and the corresponding relay output status through the odc parameter: no, Fan = normal (any change); CPr, F_C = Compressor OFF. Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the display shows the message da and the regulation restarts is rtr = yes. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled. 8.2 GENERIC ALARM (i1f = EAL) As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message. The outputs status don t change. The alarm stops just after the digital input is de-activated. 8.3 SERIOUS ALARM MODE (i1f = bal) When the digital input is activated, the unit will wait for did delay before signalling the CA alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 8.4 PRESSURE SWITCH (i1f = PAL) If during the interval time set by did parameter, the pressure switch has reached the number of activation of the nps parameter, the CA pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the nps activation in the did time is reached, switch off and on the instrument to restart normal regulation. 8.5 START DEFROST (i1f = dfr) It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired. 8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1f = Htr) This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 8.7 ENERGY SAVING (i1f = ES) The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) sum. This function is enabled until the digital input is activated. 8.8 DIGITAL INPUTS POLARITY The digital input polarity depends on the i1p parameter. i1p=cl: the input is activated by closing the contact. i1p=op: the input is activated by opening the contact 9. TTL SERIAL LINE FOR MONITORING SYSTEMS The TTL serial line, available through the HOT KEY connector, allows by means of the external TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU compatible such as the X-WEB500/3000/ X-REP OUTPUT OPTIONAL As optional, an X-REP can be connected to the instrument, trough the HOY KEY connector. The X-REP output EXCLUDES the serial connection. To connect the X-REP to the instrument the following connectors must be used CAB- 51F(1m), CAB-52F(2m), CAB- 55F(5m), 11. INSTALLATION AND MOUNTING Instrument XR30CX shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 0 60 C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes. 12. ELECTRICAL CONNECTIONS The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 mm 2. Before connecting cables make sure the power supply complies with the instrument s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination. 13. HOW TO USE THE HOT KEY 13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 1. Program one controller with the front keypad. 2. When the controller is ON, insert the Hot key and push o key; the "upl" message appears followed a by flashing End 3. Push SET key and the End will stop flashing. 4. Turn OFF the instrument remove the Hot Key, then turn it ON again. NOTE: the Err message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the Hot key to abort the operation HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 1. Turn OFF the instrument. 2. Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON. 3. Automatically the parameter list of the Hot Key is downloaded into the Controller memory, the dol message is blinking followed a by flashing End. 4. After 10 seconds the instrument will restart working with the new parameters. 5. Remove the Hot Key.. NOTE the message Err is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation. 14. ALARM SIGNALS Message Cause Outputs P1 Room probe failure Compressor output acc. to par. Con and COF P3 Third probe failure Outputs unchanged P4 Fourth probe failure Outputs unchanged HA Maximum temperature alarm Outputs unchanged. LA Minimum temperature alarm Outputs unchanged. "HA2" Condenser high temperature It depends on the Ac2 parameter "LA2" Condenser low temperature It depends on the bll parameter da Door open Compressor according to rrd EA External alarm Output unchanged. CA Serious external alarm All outputs OFF. (i1f=bal) CA Pressure switch alarm All outputs OFF (i1f=pal) 14.1 ALARM RECOVERY Probe alarms P1, P3 and P4 start some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms HA, LA HA2 and LA2 automatically stop as soon as the temperature returns to normal values. Alarms EA and CA (with i1f=bal) recover as soon as the digital input is disabled. Alarm CA (with i1f=pal) recovers only by switching off and on the instrument OTHER MESSAGES Pon Keyboard unlocked. PoF Keyboard locked nop In programming mode: none parameter is present in Pr1 On the display or in dp2, dp3, dp4: the selected probe is nor enabled noa None alarm is recorded XR30CX GB m&m r doc XR30CX 3/4

User Instructions Lab* Frost. Ultra Low Temperature Freezers Model LAB

User Instructions Lab* Frost. Ultra Low Temperature Freezers Model LAB User Instructions Lab* Frost Ultra Low Temperature Freezers Model LAB SAFETY INFORMATIONS The LAB freezers contains environmentally friendly but flammable refrigerants. It means danger of explosion if

More information

Digital Controller XR70CX. Operating Manual. 5/10 Rev. B

Digital Controller XR70CX. Operating Manual. 5/10 Rev. B Digital Controller XR70CX Operating Manual 5/10 Rev. B 139734 Contents General Warnings 3 General Description 3 Regulation 3 Defrost 3 Fans 4 Front Panel Commands 4 Parameters 6 Installation and Mounting

More information

dixel Installing and Operating Instructions

dixel Installing and Operating Instructions XW20K AND T620 V620 CX620 1. GENERAL WARNING PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument

More information

OPERATING INSTRUCTIONS ULTF 80 / 220 / 320 / 420

OPERATING INSTRUCTIONS ULTF 80 / 220 / 320 / 420 OPERATING INSTRUCTIONS ULTF 80 / 220 / 320 / 420 INDEX........................................................... PAGE Before using the appliance...............................................................

More information

Top Mount Full Length Swinging Doors

Top Mount Full Length Swinging Doors Top Mount Full Length Swinging Doors *Shown in FT103SD3 model Model FT77SD FT103SD3 FT138SD Width 77 103 138½ Depth 32 32 32 Height 86 ½ 86 ½ 86 ½ Volume/cu. Ft. 77 103 140 Doors 3 3 4 Door Size 23 x 66

More information

XWA11V. Walk-In Temp / Door /Alarm / Light Module

XWA11V. Walk-In Temp / Door /Alarm / Light Module XWA11V Walk-In Temp / Door /Alarm / Light Module 1. GENERAL DESCRIPTION Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature monitoring and alarming in a walk-in

More information

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 1. GENERAL DESCRIPTION Model XWA11V-KIT, 100x64 mm format, is a microprocessor based light and alarm management controller,

More information

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module XWA11V Walk-In Temp / Door /Alarm / Light Module 1. GENERAL DESCRIPTION Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature monitoring and alarming in a walk-in

More information

XH50P - XH55P Temperature/relative humidity probe with RS485 serial line

XH50P - XH55P Temperature/relative humidity probe with RS485 serial line XH50P - XH55P Temperature/relative humidity probe with RS485 serial line 1. GENERAL WARNINGS 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument

More information

dixel Installing and Operating Instructions PRELIMINAY

dixel Installing and Operating Instructions PRELIMINAY . GENERAL WARNING XW6K - AFV PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used

More information

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 1. GENERAL DESCRIPTION Model XWA11V-KIT, 100x64 mm format, is a microprocessor based light and alarm management controller,

More information

XR60CX. Installation and Operating Instructions. Digital controller with defrost and fans management. + + To return to the room temperature display.

XR60CX. Installation and Operating Instructions. Digital controller with defrost and fans management. + + To return to the room temperature display. Digital controller with defrost and fans management XR60CX CTENTS 1. GENERAL WARNING 1 2. GENERAL DESCRIPTI 1 3. CTROLLING LOADS 1 4. FRT PANEL COMMANDS 1 5. MAX & MIN TEMPERATURE MEMORIZATI 1 6. MAIN

More information

XR60C ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV. Digital controller with defrost and fans management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS

XR60C ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV. Digital controller with defrost and fans management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS Digital controller with defrost and fans management XR60C CONTENTS 1. GENERAL WARNING 1 2. GENERAL DESCRIPTION 1 3. CONTROLLING LOADS 1 4. FRONT PANEL COMMANDS 1 5. TEMPERATURE ALARM AND ITS DURATION RECORDING

More information

Dixell Installing and Operating Instructions release 7.0

Dixell Installing and Operating Instructions release 7.0 XR160C - XR160D - XR170C - XR170D - XR162C - XR172C CONTENTS 1. GENERAL WARNING 2 1.1 Please read before using this manual 2 1.2 Safety Precautions 2 2. GENERAL DESCRIPTION 2 3. CONTROLLING LOADS 2 3.1

More information

XW40K AND T620T - T620 V620 CX620

XW40K AND T620T - T620 V620 CX620 XW40K AND T620T - T620 V620 CX620 1 GENERAL WARNING... 1 2 GENERAL DESCRIPTI... 1 3 CTROLLING LOADS... 1 4 SPECIAL FUNCTIS... 1 5 KEYBOARDS... 1 6 AUTOMATIC KEYBOARD LOCK (LY FOR T620T)... 2 7 CTROLLER

More information

dixel Installing and Operating Instructions 1592027050 Digital controller for medium-low temperature refrigeration applications XW60L 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual

More information

Time KEY COMBINATIONS: + To lock & unlock the keyboard. + To enter in programming mode. + To return to the room temperature display. 4.

Time KEY COMBINATIONS: + To lock & unlock the keyboard. + To enter in programming mode. + To return to the room temperature display. 4. Digital controller for medium-low temperature refrigeration applications XW40L 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the

More information

MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL MOTIVAIR COOLING SOLUTIONS AIR COOLED CHILLERS MODELS: MLC-SC-FC 0200 MLC-SC-FC 1100 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This chiller has been factory run tested to the specified water pressure

More information

XR77CX. dixel Installing and Operating Instructions Digital controller for medium-low temperature refrigeration applications

XR77CX. dixel Installing and Operating Instructions Digital controller for medium-low temperature refrigeration applications Digital controller for medium-low temperature refrigeration applications XR77CX 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the

More information

Commercial Refrigerator Service Manual

Commercial Refrigerator Service Manual Commercial Refrigerator Service Manual SOLID DOOR TOP MOUNT REACH-IN PTM49R Please read this manual completely before attempting to install or operate this equipment. TABLE OF CONTENTS 1. FEATURE CHART

More information

XW70L. Digital controller for medium-low temperature refrigeration applications AUX 1. GENERAL WARNING 2. GENERAL DESCRIPTION 3.

XW70L. Digital controller for medium-low temperature refrigeration applications AUX 1. GENERAL WARNING 2. GENERAL DESCRIPTION 3. Digital controller for medium-low temperature refrigeration applications XW70L 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the

More information

Rev 0 09-FEB XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual

Rev 0 09-FEB XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual 026-1210 Rev 0 09-FEB-2011 XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual Retail Solutions 3240 Town Point Drive NW Suite 100 Kennesaw,

More information

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. 1 ON Fan1 enabled (only for XC30CX) 2 ON Fans enabled (only for XC30CX) kpa. Time

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. 1 ON Fan1 enabled (only for XC30CX) 2 ON Fans enabled (only for XC30CX) kpa. Time Digital controller for CDU management XC10CX and XC30CX 1. GENERAL WARNING... 1 2. GENERAL DESCRIPTION... 1 3. CONTROLLING LOADS... 1 4. FRONT PANEL COMMANDS... 1 5. OTHER FUNCTIONS... 1 6. MAIN INTERFACE...

More information

Commercial Freezer Service Manual

Commercial Freezer Service Manual Commercial Freezer Service Manual SOLID DOOR TOP MOUNT REACH-IN PTM49F Please read this manual completely before attempting to install or operate this equipment. TABLE OF CONTENTS 1. FEATURE CHART 1-1.

More information

Electronic Controller For Refrigeration XLR130 XLR170

Electronic Controller For Refrigeration XLR130 XLR170 Electronic Controller For Refrigeration XLR130 XLR170 Instructions Manual COOL OOLMATE XLR130C XLR170C INDEX 1. GENERAL WARNING 3 2. GENERAL DESCRIPTION 3 3. CONTROLLING LOADS 3 4. KEYBOARD 5 5. REAL TIME

More information

XC10CX and XC30CX. Digital controller for CDU management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS 2. GENERAL DESCRIPTION

XC10CX and XC30CX. Digital controller for CDU management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS 2. GENERAL DESCRIPTION Digital controller for CDU management XC10CX and XC30CX 1. GENERAL WARNING... 1 2. GENERAL DESCRIPTION... 1 3. CONTROLLING LOADS... 1 4. FRONT PANEL COMMANDS... 1 5. OTHER FUNCTIONS... 1 6. MAIN INTERFACE...

More information

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. DLT Prb. Ground

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. DLT Prb. Ground Digital controller for CDU management XC30CX 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference.

More information

Refrigerated Milk Drawer

Refrigerated Milk Drawer Refrigerated Milk Drawer Copyright Septamber 2016 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any

More information

XH260L XH260V. Dixell Operating instructions TEMPERATURE AND HUMIDITY CONTROLLER 1. GENERAL WARNING

XH260L XH260V. Dixell Operating instructions TEMPERATURE AND HUMIDITY CONTROLLER 1. GENERAL WARNING XH260L XH260V TEMPERATURE AND HUMIDITY CTROLLER 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick

More information

Rev 1 24-MAY XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual

Rev 1 24-MAY XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual 026-1210 Rev 1 24-MAY-2012 XR75CX Digital Controller for Medium-Low Temperature Refrigeration Applications Installation and Operation Manual Retail Solutions 3240 Town Point Drive NW Suite 100 Kennesaw,

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

XC1008D -XC1011D- XC1015D and VGC810

XC1008D -XC1011D- XC1015D and VGC810 Electronic Controller for Compressor Racks XC1008D -XC1011D- XC1015D and VGC810 Instructions Manual INDEX 1. GENERAL WARNING 4 1.1 PLEASE READ BEFORE USING THIS MANUAL 4 1.2 SAFETY PRECAUTIONS 4 2. WIRING

More information

MINITOP Refrigerated Self-Service Display underneath

MINITOP Refrigerated Self-Service Display underneath MINITOP Refrigerated Self-Service Display underneath Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4 Spare parts page 6 Rue Charles

More information

Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4 Spare parts page 6

Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4 Spare parts page 6 INOUK Upright refrigerated display Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4 Spare parts page 6 Rue Charles Hermite Z.I. des

More information

OMNITOP Refrigerated Display with Ventilated Cooling

OMNITOP Refrigerated Display with Ventilated Cooling OMNITOP Refrigerated Display with Ventilated Cooling Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4 Spare parts page 6 Rue Charles

More information

Inline GN Series Refrigerated Well

Inline GN Series Refrigerated Well Inline GN Series Refrigerated Well Copyright June 2017 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in

More information

Refrigerated Cabinets Square Format

Refrigerated Cabinets Square Format Refrigerated Cabinets Square Format Copyright December 2017, Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

UNIVERSAL R V3.0. NEW FEATURES on the V3.0

UNIVERSAL R V3.0. NEW FEATURES on the V3.0 UNIVERSAL R V3.0 NEW FEATURES on the V3.0 HEATING : As well as cooling, the Universal-R can now be used to control heating applications up to +105c, using the NTC probes supplied in box. For temperatures

More information

XH340L-V TEMPERATURE AND HUMIDITY CONTROLLER FOR SEASONING-MATURING CABINETS 1. GENERAL WARNING

XH340L-V TEMPERATURE AND HUMIDITY CONTROLLER FOR SEASONING-MATURING CABINETS 1. GENERAL WARNING XH340L-V TEMPERATURE AND HUMIDITY CTROLLER FOR SEASING-MATURING CABINETS 1. GENERAL WARNING 1.1 PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument

More information

REVERSO. Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4-6 Spare parts page 7

REVERSO. Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4-6 Spare parts page 7 REVERSO Instructions of use and maintenance page 2 Electric and refrigerating diagrams page 3 Manual of the thermostat page 4-6 Spare parts page 7 Rue Charles Hermite Z.I. des Sables BP 59 54110 Dombasle

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES KNA4C9DP47L-1

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES KNA4C9DP47L-1 GUARDIAN SERIES KNA4C9DP47L-1 Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents AIR CONDITIONER

More information

XW90LT. Digital controller for medium-low temperature refrigeration applications AUX 1. GENERAL WARNING 2. GENERAL DESCRIPTION 3.

XW90LT. Digital controller for medium-low temperature refrigeration applications AUX 1. GENERAL WARNING 2. GENERAL DESCRIPTION 3. Digital controller for medium-low temperature refrigeration applications XW90LT 1. GENERAL WARNING... 1 2. GENERAL DESCRIPTI... 1 3. CTROLLING LOADS... 1 4. FRT PANEL COMMANDS... 1 5. AUTOMATIC KEYBOARD

More information

Refrigerated Cabinets

Refrigerated Cabinets Refrigerated Cabinets Copyright June 2017 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or

More information

Open Front Food & Drinks Cabinet AS/NZS

Open Front Food & Drinks Cabinet AS/NZS Open Front Food & Drinks Cabinet AS/NZS Copyright November 2017 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

SSGB. EPH Certified to NSF-7 G B. Technical Data Sheet P/N _E. January Data sheet-excel SSGB

SSGB. EPH Certified to NSF-7 G B. Technical Data Sheet P/N _E. January Data sheet-excel SSGB H SSGB Technical Data Sheet P/N 3018921_E EPH Certified to NSF-7 January 2018 F A C D E A G B We reserve the right to change or revise specifications and product design in connection with any feature of

More information

REFRIGERATED ROOM & TEMPERATURE/HUMIDITY CONTROLLERS

REFRIGERATED ROOM & TEMPERATURE/HUMIDITY CONTROLLERS SECTION INDEX FUNCTIONS MODELS XLR100 COOL MATE - NT, MT AND LT APPLICATIONS - SERIAL OUTPUT Advanced multifunction controllers for NT refrigerated rooms XLR130 Advanced multifunction controllers for MT

More information

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL WATER HEATER ELECTRONIC CONTROLLER USER MANUAL UPPER LED READOUT LED ICONS LOWER LED READOUT PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654 Page 1 / 7 PV500-40 03/17

More information

Surna 25-Ton Chiller Operating & Maintenance Manual

Surna 25-Ton Chiller Operating & Maintenance Manual www.surna.com 303.993.5271 Surna 25-Ton Chiller Operating & Maintenance Manual Models: 300F3-3. 300F4-3, 300FW-3 Revised: July 2015 Table of Contents Warranty Information 4 Limited Warranty 4 Limitation

More information

Food & Beverage Cabinet

Food & Beverage Cabinet Food & Beverage Cabinet Copyright June 2017 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

Refrigerated Cabinets Curved Format

Refrigerated Cabinets Curved Format Refrigerated Cabinets Curved Format Copyright August 2018, Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173) Evco S.p.A. Code 104K204E05 page 1/5 EVK204 Digital controller for ventilated refrigerating units, with HACCP and Energy Saving functions version 1.05 GB ENGLISH 1 PREPARATIONS 1.1 Important Please read

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

Read and save these instructions

Read and save these instructions www.winemate.com Wine Cooling System WM-1500HZD, WM-2500HZD WM-3500HZD, WM-4500HZD WM-6500HZD, WM-8500HZD Installation, Use & Care Manual www.vinotemp.com Read and save these instructions Important Safety

More information

Bulletin (Jan 2011) And User s Guide

Bulletin (Jan 2011) And User s Guide Bulletin 30 32 (Jan 2011) Unichiller Installation And User s Guide Customer Service If you have questions about Installation, operation and Maintenance of the Unichiller or would like to order replacement

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

Power s Sliding Glass 2 Door Floral Coolers For Bush Refrigeration

Power s Sliding Glass 2 Door Floral Coolers For Bush Refrigeration Power s Sliding Glass 2 Door Floral Coolers For Bush Refrigeration Features Save space and money with a sliding door cooler. Sliding door models fit into tight spaces where there isn t enough aisle space

More information

Refrigerated Cabinets Curved Format

Refrigerated Cabinets Curved Format Refrigerated Cabinets Curved Format Copyright August 2018 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017

Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017 Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017 Model No. HX-36DX Model No. HX-120DX Check packing slip and product to see if they match. If not, contact Aqua Logic immediately!! Important:

More information

SERVICE & SETUP MANUAL WATER HEATER ELECTRONIC CONTROLLER

SERVICE & SETUP MANUAL WATER HEATER ELECTRONIC CONTROLLER SERVICE & SETUP MANUAL WATER HEATER ELECTRONIC CONTROLLER PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654 Page 1/ 24 PV500-41 03/17 INDEX 1. TECHNICAL DATA 3 2. WIRING

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

CH250 AND CH251 CHILLERS

CH250 AND CH251 CHILLERS CH250 AND CH251 CHILLERS Operator s & Installation Manual Release Date: April 19, 2004 Publication Number: 620914801 Revision Date: May 15, 2015 Revision: G Visit the Cornelius web site at www.cornelius.com

More information

OWNER S MANUAL STAINLESS STEEL REACH-IN SERIES. Model: ATF1 ATF2 ATF3 ATR1 ATR2 ATR3 ATF2 ATR2

OWNER S MANUAL STAINLESS STEEL REACH-IN SERIES. Model: ATF1 ATF2 ATF3 ATR1 ATR2 ATR3 ATF2 ATR2 OWNER S MANUAL STAINLESS STEEL REACH-IN SERIES Model: ATF1 ATF2 ATF3 ATR1 ATR2 ATR3 ABF1 ABF2 ABF3 ABR1 ABR2 ABR3 ABF1 ABR1 ATF2 ATR2 ABF3 ABR3 Please read the manual carefully and follow all instructions.

More information

IKEA USA Refrigerated Cabinets

IKEA USA Refrigerated Cabinets IKEA USA Refrigerated Cabinets Copyright March 2017 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

XB570L XB570L. dixel Operating and Instructions Manual BLAST CHILLER - QUICK CHILL AND HOLD FUNCTION

XB570L XB570L. dixel Operating and Instructions Manual BLAST CHILLER - QUICK CHILL AND HOLD FUNCTION XB570L BLAST CHILLER - QUICK CHILL AND HOLD FUNCTION Contents 1. General warning 1 2. General Features 1 3. Mounting & Installation 1 4. Electrical Connections 1 5. Connections 1 6. Frontal panel 1 7.

More information

User Manual Ichill 200 L/D (Firmware version 1.7)

User Manual Ichill 200 L/D (Firmware version 1.7) User Manual Ichill 2 L/D (Firmware version 1.7) Pag. 1 of 142 INDEX 1. GENERAL FEATURES...8 1.1 Main Function... 8 2. ICHILL 2L/D TABLE OF THE FEATURES...1 3. USER INTERFACE...11 4. REMOTE KEYBOARD...15

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

Read and save these instructions

Read and save these instructions www.winemate.com Wine Cooling System WM-1500HZD, WM-2500HZD WM-3500HZD, WM-4500HZD WM-6500HZD, WM-8500HZD Installation, Use & Care Manual www.vinotemp.com Read and save these instructions Important Safety

More information

CH750, CH751 & CH951 CHILLERS

CH750, CH751 & CH951 CHILLERS CH750, CH751 & CH951 CHILLERS Operator s & Installation Manual Release Date: April 19, 2002 Publication Number: 91256 Revision Date: March 25, 2014 Revision: F Visit the Cornelius web site at www.cornelius.com

More information

CHILLER. Model CH3000. Operator s & Installation Manual

CHILLER. Model CH3000. Operator s & Installation Manual CHILLER Model CH3000 Operator s & Installation Manual Release Date: February 14, 2011 Publication Number: 620054173OPR Revision Date: May 08, 2014 Revision: B Visit the Cornelius web site at www.cornelius.com

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

Read and save these instructions

Read and save these instructions Split Ceiling-Mounted Cooling System Operation Care Installation Manual WM-2500SSD WM-2500SSD-LA WM-4500SSD WM-4500SSD-LA WM-6500SSD WM-6500SSD-LA WM-8500SSD WM-8500SSD-LA WM-12000SSD WM-12000SSD-LA www.vinotemp.com

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTREPID SERIES K2A6C30EP56TR-4

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTREPID SERIES K2A6C30EP56TR-4 INTREPID SERIES K2A6C30EP56TR-4 Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents AIR CONDITIONER

More information

OPERATING INSTRUCTIONS BLOOD BANK REFRIGERATOR 100/300/500/700/1400/-D

OPERATING INSTRUCTIONS BLOOD BANK REFRIGERATOR 100/300/500/700/1400/-D OPERATING INSTRUCTIONS BLOOD BANK REFRIGERATOR 100/300/500/700/1400/-D INDEX..... PAGE Safety Precautions... Installing the appliance... Electrical Connection... Information... 3 7 7 7 Descriptions of

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner SLIMKOOL SERIES K_NA4C4SP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner SLIMKOOL SERIES K_NA4C4SP28L SLIMKOOL SERIES K_NA4C4SP28L Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents AIR CONDITIONER

More information

User Instructions Ultra Low Temperature Freezers Model LAB/ULT

User Instructions Ultra Low Temperature Freezers Model LAB/ULT Elcold Frysere Hobro ApS Løgstørvej 81 Hørby 95 Hobro Denmark Phone +45 9657 2222 Fax +45 9852 4685 Email elcold@elcold.com www.elcold.com i.c. graphics cph User Instructions Lab* Frost Ultra Low Temperature

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

INSTALLATION AND OPERATION INSTRUCTIONS ARCTICPOUR ADVANCED REFRIGERATION TECHNOLOGY

INSTALLATION AND OPERATION INSTRUCTIONS ARCTICPOUR ADVANCED REFRIGERATION TECHNOLOGY INSTALLATION AND OPERATION INSTRUCTIONS ARCTICPOUR ADVANCED REFRIGERATION TECHNOLOGY Table of Contents Dimensional Drawings... 2 Product Description... 5 Installation... 5 Important Safety Warnings...

More information

INSTALLATION AND OPERATING MANUAL

INSTALLATION AND OPERATING MANUAL INSTALLATION AND OPERATING MANUAL Refrigerated Merchandisers with Air-Over Displays Refrigerated Low-Profile Mobile Merchandiser Refrigerated High-Profile Mobile Merchandiser Refrigerated Grab-N-Go Merchandiser

More information

Read and save these instructions

Read and save these instructions Split Through-Ceiling Cooling System Operation Care Installation Manual WM-2500SSO WM-2500SSO-LA WM-4500SSO WM-4500SSO-LA www.vinotemp.com Read and save these instructions Vinotemp International Corp 17631

More information

INSTALLATION AND OPERATING MANUAL

INSTALLATION AND OPERATING MANUAL INSTALLATION AND OPERATING MANUAL Refrigerated Island Merchandiser FOR PARTS & SERVICE Contact: Piper Products, Inc. Phone: (800) 544-3057 Ask for Service Department IMPORTANT! This manual contains important

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Split Wall-Recessed Cooling System Operation Care Installation Manual

Split Wall-Recessed Cooling System Operation Care Installation Manual Split Wall-Recessed Cooling System Operation Care Installation Manual WM-2520SSW 2520SSW-LA WM-4520SSW 4520SSW-LA www.vinotemp.com Read and save these instructions Vinotemp International Corp 17631 S Susana

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. DP SERIES KA4C3DP21L with Serial Numbers L18A3965 and above

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. DP SERIES KA4C3DP21L with Serial Numbers L18A3965 and above DP SERIES KA4C3DP21L with Serial Numbers L18A3965 and above Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below.

More information

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature EVCO S.p.A. EV3B24 Data sheet ver. 1.0 Code 1043B24E104 Page 1 of 6 PT 12/15 EV3B24 Basic controller for low temperature bottle coolers, cabinets, refrigerated cabinets, tables and pizza counters, with

More information

JCC2 Cellar and Product Coolers

JCC2 Cellar and Product Coolers TECHNICAL MANUAL JCC2 Cellar and Product Coolers Contents Nomenclature 3 Standard Product Configuration 3 Specifications Capacity data 4 System data 4 Unit dimensions & weights 5 Electrical data & requirements

More information

Read and save these instructions

Read and save these instructions Split Water-Cooled Through-Ceiling Cooling System Operation Care Installation Manual WM-2500SSOWC WM-4500SSOWC www.vinotemp.com Read and save these instructions Vinotemp International Corp 17631 S Susana

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L GUARDIAN SERIES K2NA6C14DP50L Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents AIR CONDITIONER

More information

Ceiling Split Cooling System Installation, Operation & Care Manual WM-2500SSD WM-4500SSD WM-6500SSD WM-8500SSD

Ceiling Split Cooling System Installation, Operation & Care Manual WM-2500SSD WM-4500SSD WM-6500SSD WM-8500SSD www.winemate.com Ceiling Split Cooling System Installation, Operation & Care Manual WM-2500SSD WM-4500SSD WM-6500SSD WM-8500SSD www.vinotemp.com Read and save these instructions Important Safety Information

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C18DP53L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C18DP53L 480 VOLT GUARDIAN SERIES K3NA6C18DP53L Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C26DP60L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C26DP60L 480 VOLT GUARDIAN SERIES K3NA6C26DP60L Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. GUARDIAN SERIES K3NA4C3DP24L 480 Volt 1-PHASE

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. GUARDIAN SERIES K3NA4C3DP24L 480 Volt 1-PHASE GUARDIAN SERIES K3NA4C3DP24L 480 Volt 1-PHASE Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents

More information

ER52 - Evaporator Controller

ER52 - Evaporator Controller ER52 - Evaporator Controller Electronic Refrigeration Line Product Bulletin Devices are standalone digital controller for static or ventilated refrigeration units working at positive temperatures. They

More information

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE KA6C4NP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE KA6C4NP28L TRIMLINE KA6C4NP28L Keep This Manual With Air Conditioner Find additional information on this model at kooltronic.com, or use the Technical Documents QR code below. Technical Documents AIR CONDITIONER

More information

Read and save these instructions

Read and save these instructions Split Water-Cooled Central-Ducted Cooling System Operation Care Installation Manual WM-2500SSHWC WM-4500SSHWC WM-6500SSHWC WM-8500SSHWC WM-12000SSHWC www.vinotemp.com Read and save these instructions Vinotemp

More information

CHILLERS. Operator s & Installation Manual

CHILLERS. Operator s & Installation Manual CHILLERS MODELS: CH750, CH751 & CH951 Operator s & Installation Manual Release Date: April 19, 2002 Publication Number: 91256 Revision Date: May 5, 2010 Revision: D Visit the IMI Cornelius web site at

More information