1 Two Park Avenue New York, NY U.S.A. tel fax SUPLEMENTAL AGENDA A17 Hoistway Committee Doubletree by Hilton New Orleans 300 Canal Street New Orleans, LA Tuesday, October 25, 2016 from 8:30 am 5:00 pm Wednesday October 26, 2016 from 8:30 am 12:00 pm This Agenda is for Committee use only and is subject to adoption. It is not to be duplicated or quoted for other than committee business. 7 REQUESTS FOR INTERPRETATION 7.12 Inquiry Attachment A Committee: A17 Hoistway Subject: Requirement Edition: A /CSA B Question(s): For a Class A freight elevator, is a horizontally sliding car door prohibited? Proposed Response: None. October 2016 Discussion: The committee is asked to respond Inquiry Attachment B Committee: A17 Hoistway Subject: Requirement Edition: A /CSA B
2 Question(s): Question (1): Does the requirement for landing sills to be illuminated to 100 lx apply after normal building power has failed, for example (a) while a hydraulic elevator is moving on battery lowering, (b) while a traction elevator is moving on a brake-pulsing operation, (c). while either a traction or hydraulic elevator is returning to the designated level on emergency or stand-by power in accordance with ? Question (2): If the answer to Question (1), is yes, does this apply to all landing sills, only the designated level landing sill or other criteria? Proposed Response(s): None. October 2016 Discussion: The committee is asked to respond. 9 TECHNICAL REVISIONS 9.9 Record ; Requirement PM: D. McColl Update to October 2016 Discussion: Please see Attachment C for Mr. McColl s proposed responses to ballot results comments and revised proposal. 11. NEW BUSINESS/ DISCUSSION ITEMS 11.1 Safe Hoistway Access Sincerely, Task group: Nuschler (Chair), Henderson, Stockstill, McColl, Rehman, Boucher, Marinelli, Witt, Gervais, Burch, Hultstrom and Warren. Update to October 2016 Discussion: Please see latest draft of HW lighting alarm proposal found in Attachment D. The task group will be working further on this item during their task group meeting on Monday October 24, Grace Bolan Safety S&C Engineer American Society of Mechanical Engineers Two Park Avenue, New York, NY T: BolanG@asme.org
3 Attachment A Page 1 of 4
4 Attachment A Page 2 of 4
5 Attachment A Page 3 of 4
6 Attachment A Page 4 of 4
7 Attachment B Page 1 of 4
8 Attachment B Page 2 of 4
9 Attachment B Page 3 of 4
10 Attachment B Page 4 of 4
11 A17 Hoistway Committee Record Attachment C Page 1 of Each elevator shall be provided with auxiliary lighting and shall conform to the following: (g) Battery-operated units, where provided, shall (1) comply with CSA C22.2 No. 141 or UL 924 (see Section 9) (2) have a 4 h rating minimum (3) be permanently connected to the car light branch circuit (4) have an output rating that includes the auxiliary lights and if connected, the emergency signaling device (see ) Rationale: Update reference to include all emergency signalling devices. Ballot#: Ballot Level: Standards Committee Date Opened: 06/30/16 Date Closed: 08/03/16 Approved: 20 Disapproved: 0 Abstained: 0 Not Voting: 0 Not Returned: 6 [BarkandT, HerrityJ, MeyerJa, RobiberoV, TurnerDa, WithamD] Total: 20/26 Comments posted on this ballot HendersonD (Comment) Date Posted: 07/01/16 Approved. KoshakJ (Approved) Date Posted: 07/28/16 I agree with the proposal with one small change is Car Emergency Signaling Devices is Emergency Communications only, this is not what the rationale says. Change "(see )" to read "(see )". Responses Thank you Accepted. See revised proposal. Revised Proposal (October 2016): Each elevator shall be provided with auxiliary lighting and shall conform to the following: (g) Battery-operated units, where provided, shall (1) comply with CSA C22.2 No. 141 or UL 924 (see Section 9) (2) have a 4 h rating minimum (3) be permanently connected to the car light branch circuit
12 A17 Hoistway Committee Record Attachment C Page 2 of 2 (4) have an output rating that includes the auxiliary lights and if connected, the emergency signaling devices (see ) Rationale: Update reference to include all emergency signalling devices.
13 Attachment D Page 1 of 2 A17 Hoistway Committee page 1 Task Group on Hoistway Access Proposal to revise requirements for car top lighting, car bottom lighting, and car alarm device The current is shown below for reference only; note that the current requirements are not altered: Each elevator shall be provided with lighting and a duplex receptacle fixture on the car top. The lighting shall be permanently connected, fixed, or portable, or a combination thereof, to provide an illumination level of not less than 100 lx (10 fc) measured at the point of any elevator part or equipment, where maintenance or inspection is to be performed from the car top. All lighting shall be equipped with guards. The light switch shall be accessible from the landing when accessing the car top. Revise A17.1/B44 as follows: Each elevator shall be provided with lighting and a duplex receptacle fixture on the car top conforming to the following:. (a) thethe car top lighting shall be permanently connected, fixed, or portable, or a combination thereof, to provide an illumination level of not less than 100 lx (10 fc) measured at the point of any elevator part or equipment, where maintenance or inspection is to be performed from the car top. All lighting shall be equipped with guards. (b) thethe car top light switch shall be accessible from the landing when accessing the car top. (c) the car top lighting shall illuminate when the hoistway access operation switch labeled "ACCESS" ( ) is placed in the "ENABLE" position. (d) the car top lighting shall illuminate within 2 s after a hoistway door is unlocked while the car door or gate is in the closed position Each elevator shall be provided with lighting on the car bottom conforming to the following: (a) the car bottom lighting shall provide illumination of not less than 100 lx (10 fc) measured at any point between 915 mm (36 in.) and mm (48 in.) vertically down from the lowest part of the bottom of the car. All lighting shall be equipped with guards.
14 Attachment D Page 2 of 2 A17 Hoistway Committee page 2 Task Group on Hoistway Access (b) the car bottom lighting shall illuminate when the hoistway access operation switch labeled "ACCESS" ( ) is placed in the "ENABLE" position. (c) the car bottom lighting shall illuminate within 2 s after a hoistway door is unlocked while the car door or gate is in the closed position Car Alarm Device Each elevator shall be provided with car alarm device(s) conforming to the requirements in and Location and Sound Pressure Rating. One or more car alarm devices shall be located in the hoistway and shall be capable producing of a continuously sounding audible signal with a sound pressure rating greater than 40 dba at every location within the hoistway but shall not exceed 80 dba when measured 1 m (40 in.) from the source. In hoistways where more than one car alarm device is required, the devices shall be no further apart than 20 m (65 ft.) Operation. The car alarm device(s) shall sound within 2 s after a hoistway door is unlocked while the car door or gate is in the closed position. Rationale: to allow elevator personnel to more safely observe where a car is located in the hoistway and to more safely access and egress the car top at a landing. The two second delay allows time for the car door to begin opening after the hoistway door is unlocked preventing unnecessary light illumination and nuisance alarms during normal operation.
A17 Standards Committee Interpretations Volume 3
A17 Standards Committee Interpretations Volume 3 Page Interpretations Approved at the September 2009 A17 Standards Committee Meeting 2 Interpretations Approved at the January 2010 A17 Standards Committee
More informationGuide for Inspection of Elevators, Escalators, and Moving Walks
ASME A17.2-2012 (Revision of ASME A17.2-2010) Guide for Inspection of Elevators, Escalators, and Moving Walks Includes Inspection Procedures for Electric Traction and Winding Drum Elevators, Hydraulic
More informationPort of Portland Conveying Equipment Guidelines
Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate
More informationInterfacing Fire Alarm, Sprinkler and Elevator Systems
1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators
More informationASME A17.1/CSA B44 Handbook
2016 Edition ASME A17.1/CSA B44 Handbook ASME A17.1-2016, Safety Code for Elevators and Escalators CSA B44-16, Safety Code for Elevators Kevin L. Brinkman, PE 2016 Edition ASME A17.1/CSA B44 Handbook ASME
More informationAPPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS
APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS CHAPTER K1 MODIFICATIONS TO ASME A17.1-2000, SAFETY CODE FOR ELEVATORS AND ESCALATORS K101.1 General. As referenced by Chapter
More informationOctober 2018 Draft for Public Review. A XX/B44-XX, Safety Code for Elevators and Escalators (Proposed Revisions of ASME A17.
A17.1-20XX/B44-XX Page 1 of 102 October 2018 Draft for Public Review A17.1-20XX/B44-XX, Safety Code for Elevators and Escalators (Proposed Revisions of ASME A17.1-2016/CSA B44-16) TENTATIVE SUBJECT TO
More informationMD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia
, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC Scope: The Purpose of Elevator Controls History of Elevator
More information9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement
Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions
More informationE25 (D) Automatic controls for general means of egress lighting
Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress
More informationEmergency Power & Fire Service Checklist
Emergency Power & Fire Service Checklist www.technicalsafetybc.ca contact@technicalsafetybc.ca Toll Free: 1 866 566 7233 The intended purpose of this form is to provide a mechanism for inspectors to be
More informationMEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities
More information1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])
FINAL MINUTES Healthcare Interpretations Task Force Tuesday, June 15, 2016 Mandalay Bay Convention Center South Convention Center, Level 2 Room Surf F Las Vegas, NV 1. Call to Order. The meeting was called
More informationAS 1851:2012 The Use and Adoption of the New Standard The impacts and challenges for the fire protection and property management industries.
AS 1851:2012 The Use and Adoption of the New Standard The impacts and challenges for the fire protection and property management industries. Development of the new Standard Chris Wyborn Senior Technical
More informationDoc. Number: N Report of CEN/TC 267 Secretariat "Industrial piping and pipelines" for the 30 th Plenary Meeting 27 October 2016 (Paris)
«Industrial piping and pipelines» CEN/TC 67 Date: 016-09-7 Assistant: Patricia DUFOUR Direct line: + (0)1 7 17 67 8 p.dufour@unm.fr Doc. Number: N 1069 Your contact: Patrick AMESLON Direct line: + (0)1
More informationCommittee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases
Committee on 51A M E M O R A N D U M To: From: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant Date: June 14, 2010 Subject: NFPA 51A ROC Letter Ballot Circulation
More informationDIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.
DIVISION 14 - CONVEYING SYSTEMS I. GENERAL A. This division contains: 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. B. Elevators in schools are for the disabled, furniture
More informationA Study into the Standardization of Using Fire Detectors in Rail Vehicles for China
Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 240 244 A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China LIU Xiao-lu *, WANG Wen-qing Shenyang
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Testing and Maintenance
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly
More informationMEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies
More informationNFPA Changes
Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function
More informationAppendix C. Community Facilities Correspondence
Appendix C Community Facilities Correspondence From: Sent: To: Subject: Thursday, February 06, 2014 4:30 PM dhughes@wpccos.org Westchester Pavilion EIS: Parks/Open Space Statistics Hello Mr. Hughes, I
More informationPublic Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August
More informationU.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group
U.S. Codes & Standards for Energy Storage Systems Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group Regulatory Update: U.S. Codes & Standards Agenda NFPA 70 (NEC) UL 1973 & 9540 Fire Codes NFPA
More informationPipeline Personnel Qualification. ASME B31Q Update. Presented by: Mike Gruenberg Southwest Gas Corporation
Pipeline Personnel Qualification ASME B31Q Update Presented by: Mike Gruenberg Southwest Gas Corporation Historical Perspective 1999: PHMSA published Operator Qualification (OQ) rule 2002: NTSB labeled
More informationStandard Development Timeline
Standard Development Timeline The drafting team maintained this section while developing the standard. It will be removed when the standard becomes effective. Description of Current Draft This draft is
More informationNational Fire Protection Association
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationDelayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.
9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers
More informationProposed Changes to NFPA
2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels
More informationTECHNICAL COMMITTEE ON FIRE CODE
TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationPreliminary Agenda Technical Committee on Liquefied Petroleum Gas
Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.
More informationInternational Code Council
Page 1 of 7 International Code Council ICC 300-2012 edition Committee Actions Report for Committee Actions taken at the March 9th, 2011 meeting The ICC Standard Development Committee for Bleacher Safety
More informationISO INTERNATIONAL STANDARD. Agricultural engineering Electrical and electronic equipment Testing resistance to environmental conditions
INTERNATIONAL STANDARD ISO 15003 First edition 2006-02-15 Agricultural engineering Electrical and electronic equipment Testing resistance to environmental conditions Génie agricole Matériel électrique
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationDelayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.
Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 6772 Third edition 2012-10-01 Aerospace Fluid systems Impulse testing of hydraulic hose, tubing and fitting assemblies Aéronautique et espace Systèmes de fluides Essai d impulsion
More informationAn Urgent Bulletin from CSA Group
An Urgent Bulletin from CSA Group Hazardous Locations Products No. 28 (Supersedes Electrical Certification Notice No. 544A) Date: January 3, 2018 See Attachment 1 for Effective Dates. See Attachment 1
More informationISO INTERNATIONAL STANDARD. Sensory analysis Guidelines for sensory assessment of the colour of products
INTERNATIONAL STANDARD ISO 11037 Second edition 2011-07-15 Sensory analysis Guidelines for sensory assessment of the colour of products Analyse sensorielle Lignes directrices pour l'évaluation sensorielle
More informationBaseline Data Required for AS
Baseline Data Required for AS 1851-2012 Name: Brett Dundules Position: Technical Officer Organisation Fire Protection Association Australia Introduction Brief History of AS 1851-2012 Introduction of Baseline
More informationFIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES
Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,
More informationNEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule
NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to comprehensively update Section 3004-01 of Title
More informationNational Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction
More informationHeathcare Interpretations Task Force
Healthcare Interpretations Task Force MEMORANDUM TO: FROM: Heathcare Interpretations Task Force Robert Solomon DATE: May 30, 2014 SUBJ: HITF Meeting Agenda and Meeting Room Location Information Attached
More informationLife Safety Code Potpourri
Life Safety Code Potpourri JAMES P. LOVELAND P.E. MINNESOTA DEPARTMENT OF HEALTH Engineering Services Section FEDERAL MONITORING SURVEYS 2007 2008 2009 No. of FMSs 20 20 20 No. of Deficiencies 332 252
More informationScreen 1 Corridors and Profiles Evaluated
Corridors and Profiles Evaluated Universe of Corridors and Profiles Considered CORRIDORS PROFILES I-57 Expressway Halsted Street UP Railroad Wentworth Avenue State Street Michigan Avenue King Drive Cottage
More informationCodes Update Part 1: The NYC Codes on Lighting Design
New York City Section Codes Update Part 1: The NYC Codes on Lighting Design Wednesday, October 8 Presented in partnership with. A three part series on recent changes to building, design, construction,
More informationLOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION
CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...
More informationWORKING DRAFT OF COMMITTEE MEETING OUTPUT
WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013
More informationISO INTERNATIONAL STANDARD. Road vehicles Four-pole electrical connectors with pins and twist lock Part 2: Tests and requirements
INTERNATIONAL STANDARD ISO 15170-2 First edition 2001-12-01 Road vehicles Four-pole electrical connectors with pins and twist lock Part 2: Tests and requirements Véhicules routiers Connecteurs électriques
More informationISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization
INTERNATIONAL STANDARD ISO 12239 Second edition 2010-12-15 Smoke alarms using scattered light, transmitted light or ionization Détecteurs de fumée à lumière dispersée, lumière transmise ou ionisation Reference
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005
ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building
More informationARB ACTION MEMO. Mr. Missel called the meeting to order at 1:00 p.m. and established a quorum.
COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902-4596 (434) 296-5823 Fax (434) 972-4012 Date: Time: 1:00 PM Meeting Room: Room #241
More informationCity of Garden Ridge M a s t e r L a n d U s e P l a n
City of Garden Ridge Master Land Use Plan P u b l i c M e e t i n g # 1 A p r i l 2 4, 2 0 1 7 Agenda 1. Planning 101 2. Project Details 3. Steering Committee 4. Your Input 5. Public Comments 6. Input
More informationNCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )
NCEHSA Conference Carbon Monoxide Detector Regulations for Lodging Establishments (S.L. 2013-413) 1 Purpose of this session The purpose of this session is to review the provisions of Session Law 2013-413
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and
More informationIRO Reliability Coordinator Real-time Reliability Monitoring and Analysis Capabilities
A. Introduction 1. Title: Reliability Coordinator Real-time Reliability Monitoring and Analysis Capabilities 2. Number: IRO-018-1 3. Purpose: Establish requirements for Real-time monitoring and analysis
More informationThe Owner will provide the QEI inspection and certification services.
General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use
More informationFIRE PREVENTION CODE
164.01 Purpose 164.03 Amendments to Fire Prevention Code 164.02 Adoption of Fire Prevention Code 164.04 Board of Appeals 164.01 PURPOSE. The purpose of this chapter is to prescribe regulations governing
More informationELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017
12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics
More informationISO TR TECHNICAL REPORT. Rubber and rubber products - Hydraulic hose assemblies - External leakage classification for hydraulic Systems
TECHNICAL REPORT ISO TR 11340 First edition 1994-07-01 Rubber and rubber products - Hydraulic hose assemblies - External leakage classification for hydraulic Systems Caoutchouc et produits en caoutchouc
More informationConsultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes.
DIVISION 14 - CONVEYING SYSTEMS Section 14000 - General Discussion Introduction The size, number, and location of elevators must be addressed at the earliest stages of the design, to ensure that neither
More informationSecond Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM
1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,
More informationFIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)
INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-
More informationSection: TABLE OF CONTENTS Lighting. 07.A General B Lighting Levels Minimum Lighting Requirements
EM 78-1-1 EM 78-1-1 Section 7 TABLE OF CONTENTS Lighting Section: Page 07.A General... 7-1 07.B Lighting Levels... 7-1 Tables: 7-1 Minimum Lighting Requirements... 7-3 7-ii EM 78-1-1 EM 78-1-1 THIS PAGE
More informationISO 7491 INTERNATIONAL STANDARD. Dental materials Determination of colour stability. Produits dentaires Détermination de la stabilité de couleur
INTERNATIONAL STANDARD ISO 7491 Second edition 2000-09-01 Dental materials Determination of colour stability Produits dentaires Détermination de la stabilité de couleur Reference number ISO 2000 PDF disclaimer
More informationISO 5010 INTERNATIONAL STANDARD. Earth-moving machinery Rubber-tyred machines Steering requirements
INTERNATIONAL STANDARD ISO 5010 Third edition 2007-06-01 Earth-moving machinery Rubber-tyred machines Steering requirements Engins de terrassement Engins équipés de pneumatiques Systèmes de direction Reference
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationOperation & Maintenance Manual
Operation & Maintenance Manual for Model 2100 Fire+Smoke systems from Smoke Guard, Inc. 287 N. Maple Grove - Boise, ID 83704 Phone: (800) 574-0330 Fax: (208) 639-7851 E-Mail: info@smokeguard.com Website:
More informationARB ACTION MEMO. Mr. Missel called the meeting to order at 1:00 p.m. and established a quorum.
COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902-4596 (434) 296-5823 Fax (434) 972-4012 Date: Time: 1:00 PM Meeting Room: Room #241
More informationSC # /16/17/18/19/23/24 D#03-24
SC #03-7-15/16/17/18/19/23/24 D#03-24 Casey C. Grant, P.E. Secretary, Standards Council 26 July 2003 To: Interested Parties Subject: Standards Council Decision (Final): D#03-24 Standards Council Agenda
More informationReport to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA
Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA This report is provided for information only. BMHA is not asking for Adhoc Health Care to sponser as
More informationCOUNTY OF SACRAMENTO Inter-Departmental Correspondence
COUNTY OF SACRAMENTO Inter-Departmental Correspondence For the Agenda of December 10, 2003 To: From: BOARD OF SUPERVISORS PLANNING AND COMMUNITY DEVELOPMENT DEPARTMENT Subject: WORKSHOP ON THE FLORIN-VINEYARD
More informationTECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016
TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:
More informationMEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly
More informationM E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 3059 Third edition 2012-12-01 Non-destructive testing Penetrant testing and magnetic particle testing Viewing conditions Essais non destructifs Contrôles par ressuage et contrôles
More informationSeptember 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal
M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and
More informationIMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016
IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the
More informationManhattanville Development Proposal: Project Description
Manhattanville Development Proposal: Project Description Columbia University Community Board 9 Public Meeting, Tuesday, October 11, 2005 1 A Collaborative Process: Times and Topics Thursday, Oct. 6, 6:30
More informationA Bridge to Inspection
A Bridge to Inspection Mr. Roy L. Murphy Senior Marine Inspector US Coast Guard Towing Vessel National Center of Expertise 270-444-7715 Roy.L. Murphy @USCG.MIL 1 4/5/2013 Towing Vessel Bridging Program
More informationISO 9050 INTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 9050 Second edition 2003-08-15 Glass in building Determination of light transmittance, solar direct transmittance, total solar energy transmittance, ultraviolet transmittance
More informationEVALUATION OF THE PROPOSED CENTAL BEACH MASTER PLAN BY T H E C E N T R A L B E A C H A L L I A N C E October 2010 INTRODUCTION
Please read this report which will be presented to the membership for approval at the meeting on November 4, 2010. To read the Master Plan go to www.fortlauderdale.gov/planning_zoning/central_beach_masterplan.htm
More informationDIMENSIONAL STANDARD FOR M22 THREAD CONNECT COUPLER RECEPTACLES AND PLUG COLLARS FOR PORTABLE PRESSURE WASHERS
PWMA PW203-2014 PWMA Standard DIMENSIONAL STANDARD FOR M22 THREAD CONNECT COUPLER RECEPTACLES AND PLUG COLLARS FOR PORTABLE PRESSURE WASHERS Pressure Washer Manufacturers Association Sponsor: 1300 Sumner
More informationUser s Manual and Warranty Information ThyssenKrupp Access
User s Manual and Warranty Information ThyssenKrupp Access Welcome to your Destiny ThyssenKrupp Access would like to thank you for choosing the Destiny. You have purchased one of the finest residential
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More information61(Delft/Chairman)2a May 2005 INTERNATIONAL ELECTROTECHNICAL COMMISSION TECHNICAL COMMITTEE NO. 61: SAFETY OF HOUSEHOLD AND SIMILAR ELECTRICAL APPLIANCES Report from the Chairman of TC 61 A. Inquiries
More informationELEVATOR MODERNIZATION PROPOSAL
ELEVATOR MODERNIZATION PROPOSAL Submitted to: AQUA VISTA HOLDINGS, INC. 1800 SUNSET HARBOR DRIVE, SUITE 2 MIAMI BEACH, FL 33139 ATTN: KEREN BAJAROFF OFFICE: 954-606-0111 CELL: 305-968-7454 EMAIL: KERENB@RISINGREALTYFL.COM
More informationAdobe Connect - Invitation to NFPA 385 Second Draft Web Conference
Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/
More informationNORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:
Housekeeping/Laundry/Maintenance NORTH CAROLINA Downloaded 01.15.11 (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: (3) a soiled utility room with counter,
More informationINFORMATIONAL PUBLICATION SECURITY VS. EXITING... Door Locking Hardware in Schools
INFORMATIONAL PUBLICATION SECURITY VS. EXITING... Door Locking Hardware in Schools DSA Guidelines for Door Locking Hardware in Schools Egress doors shall be readily openable from the egress side without
More informationOwner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON
Owner s Manual Part Number 33CSSP2-FC 33CS Fan Coil Programmable Thermostat SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation.
More information