PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE

Size: px
Start display at page:

Download "PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE"

Transcription

1 PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE 100 West Washington Street, Room 320 Hagerstown, MD P: F: PUR-1331 ADDENDUM NO. 3 NOTICE TO PROSPECTIVE BUYERS REQUEST FOR PROPOSALS FOR THE SALE AND USE OF PROPERTY LOCATED AT 59 WINTER STREET (ELEMENTARY SCHOOL) HAGERSTOWN, MD DATE: Friday, October 28, 2016 PROPOSALS DUE: Wednesday, November 9, :00 P.M. To Proposers: This Addendum is hereby made a part of the Contract Documents on which all proposals will be based and is issued to correct and/or clarify the original Request for Proposal (RFP) documents. Please acknowledge receipt of this Addendum in your Proposal. This Addendum consists of two (2) pages and one (1) attachment consisting of thirteen (13) pages. ITEM NO. 1: Inquiry: Is the heating system set up as a 2-zone system? Or is it a single zone? Response: The school is heated with 2 Natural Gas Steam Boilers. The boilers are independently zoned, 1 zone per boiler. ITEM NO. 2: Inquiry: Do you know the age of the heating/ac system? Response: See the attached documentation provided by the Washington County Public Schools. ITEM NO. 3: Inquiry: When was the fire alarm system last updated? Response: See the attached documentation provided by Washington County Public Schools. Per County Facilities, the fire alarm system is operating properly as it has been activated during the time the Countyhas had ownership. ITEM NO. 4: Inquiry: Is a payment/deposit required with the initial bid proposal? After awarding the bid, when will full payment be expected? Response: A deposit is not being required at the time of the submittal of proposals. Final settlement/closing (to formally transfer the property and at which time full payment shall be due to the County) shall occur no later than one hundred eighty (180) calendar days after written notification from the County of the acceptance/approval of the proposal by the (NOTE: The wording of all Inquiries submitted are displayed exactly as received.)

2 ADDENDUM NO. 3 Sale and Use of Winter Street Elementary School Property PUR-1331 Page 2 Board of County Commissioners of Washington County, Maryland (which shall not occur until after the proposed transfer has been formally approved by the Maryland Board of Public Works as well as any other required agencies). Extensions to the hereinbefore specified time period as mutually agreed upon by the parties and as determined to be in the best interest of Washington County, Maryland. ITEM NO. 5: Inquiry: Do the County Commissioners have the right to make a counter-offer to any proposal? Response: The Board of County Commissioners of Washington County, Maryland reserves the right in its sole and absolute discretion to take whatever action it determines to be in the best interest of Washington County, Maryland. By Authority of: Karen R. Luther, CPPO Director of Purchasing (NOTE: The wording of all Inquiries submitted are displayed exactly as received.)

3 Item Number Description Location Classification Type Model Number Serial Number Placed In Service Area Description Manufacturer Notes WNE-GEN KW Kohler Generator Winter Street Elementary School Electrical Lighting 35RZ /1/2006 Onan WNE-BLR Section Cast Iron Boiler Winter Street Elementary School HVAC Boiler 28 A J /1/2006 Boiler Room H.B. Smith Power Flame Burner Fireye Type-EPD-160 Power Flame Burner WNE-BLR Section Cast Iron Boiler Winter Street Elementary School HVAC Boiler 28 A J Boiler Room H.B. Smith 9/1/2006 Fireye Type-EPD-160 WNE-CUV-001 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator /1/1973 Room Beacon/Morris Room#1 WNE-CUV-002 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#2 WNE-CUV-003 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#3 WNE-CUV-004 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#8 WNE-CUV-005 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#9 WNE-CUV-006 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator /1/1973 Room Beacon/Morris Room#10 WNE-CUV-007 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator /1/1973 Room Beacon/Morris Room#10 WNE-CUV-008 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#11 WNE-CUV-009 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#12 WNE-CUV-010 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 1/1/1973 Room Herman Nelson Room#12 WNE-CUV-011 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator 3223-MJBS 1/1/1973 Room Herman Nelson HV#1 Auditorium Unit WNE-CUV-012 Cabinet Unit Ventilator Winter Street Elementary School HVAC Cabinet Unit Ventilator /1/1973 Room Herman Nelson HV#2 Auditorium Unit WNE-DFW-001 Direct Fired Water Heater Winter Street Elementary School HVAC Direct Fired Water Heater SBD100199NES HO4M /1/2006 Boiler Room State 80 GAL. WNE-DFW-002 Direct Fired Water Heater Winter Street Elementary School HVAC Direct Fired Water Heater BRT-199-MON MA /1/2006 Boiler Room A&O Smith 80 GAL. WNE-MDS-001 Ductless Split System Winter Street Elementary School HVAC Ductless Split System PU12EK 1/1/2000 Roof Mitsubishi Serves Server Room (Paired With Indoor Model:PK12FK) WNE-FOP-001 Pump Winter Street Elementary School HVAC Pump 940 9/1/2006 Boiler Room Cummins-Wagner WNE-PMP-002 Pump Winter Street Elementary School HVAC Pump BW90A N03-BW90A-M 9/1/2006 Boiler Room Gould Booster Pump WNE-PMP-003 Pump Winter Street Elementary School HVAC Pump /1/2006 Boiler Room Shipco WNE-RTU-001 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W 5688HO1729 1/1/1973 Roof Lennox (A01) WNE-RTU-002 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W MLC8-8132J 1/1/1973 Roof Lennox (A02) WNE-RTU-003 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W 6688HO1736 1/1/1973 Roof Lennox (A03) WNE-RTU-004 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W MIC8-8132D 1/1/1973 Roof Lennox (A04) WNE-RTU-005 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W 5889F01467MLC8-8133D 1/1/1973 Roof Lennox (A05) WNE-RTU-006 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA W 1/1/1973 Roof Lennox (On High Roof) Serial Could Not Read WNE-RTU-007 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA Y 5689E /1/1973 Roof Lennox (A07) WNE-RTU-008 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA Y 5689E /1/1973 Roof Lennox (A08) WNE-RTU-009 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA Y 5689E /1/1973 Roof Lennox (A09) WNE-RTU-010 Roof Top Unit Winter Street Elementary School HVAC Roof Top Unit CHA Y 5489C /1/1973 Roof Lennox (A010)

4 Annual Fire Alarm and Life Safety System Inspection Report For WCPS - Winter Street ES 59 Winter Street Williamsport, MD This Inspection was performed in accordance with applicable NFPA 72 Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Inspection Date Feb 24, 2015 Contact: Mark Mills Title: Director of Maintenance Company: ARK Systems, Inc. Contact: Charles Everett Title: Service Manager

5 Executive Summary Generated by: BuildingReports.com Building Information Contact: Mark Mills Address: 59 Winter Street Phone: Address: City/State/Zip: Williamsport, MD Country: United States of America Inspection Performed By Company: ARK Systems, Inc. Fax: Mobile: Inspector: Darrin Jones Address: 9176 Red Branch Road Phone: Address: City/State/Zip: Columbia, MD Fax: Mobile: Country: United States of America System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 02/24/2015 IDC Style: Model Number: 4020 Install Date: 02/25/1997 SLC Style: Software Version: Version Date: 08/18/2011 NAC Style: Location: 1st At Front Entrance Monitoring Current Protection: Breaker Company: Phone: Account #: Central Station Signal Verification Type: Mfg: Model #: Test Time/Date: Restore Time ARK Systems, Inc. 1 10/28/2016

6 Inspection Summary Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty % Auxiliary % % % 0 0% Initiating % % % 0 0% Indicating % % % 0 0% Control % % % 0 0% Totals % % % 0 0% Certification Company: ARK Systems, Inc. Inspector: Darrin Jones Contact: Mark Mills Signed: Signed: ARK Systems, Inc. 2 10/28/2016

7 Inspection & Testing Generated by: BuildingReports.com Control Panel: 1 - SimplexGrinnell 4020 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date Passed Auxiliary Fan Shutdown 1st Above Ceiling in Classroom 2 AHU 1 Visually Checked 8:47:38 AM 02/24/2015 Fan Shutdown 1st Above Ceiling in Classroom 6 AHU 2 Visually Checked 8:47:49 AM 02/24/2015 Fan Shutdown 1st Above Ceiling in Classroom 9 AHU 3 Visually Checked 8:36:09 AM 02/24/2015 Fan Shutdown Fan Shutdown 1st Above Ceiling in Kindergarden Classroom 1st Above Ceiling in Kindergarden Classroom Visually Checked 8:47:11 AM 02/24/2015 Visually Checked 8:47:24 AM 02/24/2015 Fan Shutdown 1st Above Ceiling in Principal Office Visually Checked 8:46:55 AM 02/24/2015 Fan Shutdown 1st Above Ceiling in Teacher Work Room AHU 6 Visually Checked 8:46:31 AM 02/24/2015 Control Battery 1st Inside FACP Visually Checked 8:31:41 AM 02/24/2015 Battery 1st Inside FACP Visually Checked 8:31:44 AM 02/24/2015 Battery 1st Inside N.A.C. Power Extender Above FACP Visually Checked 8:33:02 AM 02/24/2015 Battery 1st Inside N.A.C. Power Extender Above FACP Visually Checked 8:33:04 AM 02/24/2015 Battery 1st Inside Voice Evac Visually Checked 8:32:42 AM 02/24/2015 Battery 1st Inside Voice Evac Visually Checked 8:32:45 AM 02/24/2015 Control Panel 1st At Front Entrance Visually Checked 8:31:11 AM 02/24/2015 Disconnect 1st Inside Boiler Room Breaker 24 Panel BR PH Visually Checked 8:31:18 AM 02/24/2015 Power Supply 1st At Front Entrance Visually Checked 8:32:59 AM 02/24/2015 Voice Evacuation 1st At Front Entrance Next to FACP Tested 8:32:20 AM 02/24/2015 Indicating Horn/Strobe 1st Visually Checked 8:31:15 AM 02/24/2015 Indicating Device 1st Above Ceiling in Classroom 2 AHU 1 Tested 8:46:42 AM 02/24/2015 Indicating Device 1st Above Ceiling in Classroom 6 AHU 2 Tested 8:47:45 AM 02/24/2015 Indicating Device 1st Above Ceiling in Classroom 9 AHU 3 Tested 8:36:11 AM 02/24/2015 Indicating Device Indicating Device 1st Above Ceiling in Kindergarden Classroom 1st Above Ceiling in Kindergarden Classroom AHU 9 Tested 8:47:05 AM 02/24/2015 Tested 8:47:30 AM 02/24/2015 Indicating Device 1st Above Ceiling in Principal Office Tested 8:46:51 AM 02/24/2015 Indicating Device 1st Above Ceiling in Teacher Work Room AHU 6 Tested 8:46:38 AM 02/24/2015 Initiating Duct Detector 1st Above Ceiling in Classroom 2 AHU 1 Visually Checked 8:47:35 AM 02/24/2015 Duct Detector 1st Above Ceiling in Classroom 6 AHU 2 Visually Checked 8:35:03 AM 02/24/2015 Duct Detector 1st Above Ceiling in Classroom 9 AHU 3 Visually Checked 8:36:14 AM 02/24/2015 ARK Systems, Inc. 3 10/28/2016

8 Device Type Location Service Time Date Passed Duct Detector 1st Above Ceiling in Kindergarden Classroom Visually Checked 8:47:16 AM 02/24/2015 Duct Detector 1st Above Ceiling in Kindergarden Classroom Visually Checked 8:47:20 AM 02/24/2015 Duct Detector 1st Above Ceiling in Principal Office Visually Checked 8:46:59 AM 02/24/2015 Duct Detector 1st Above Ceiling in Teacher Work Room AHU 6 Visually Checked 8:46:27 AM 02/24/2015 Pull Station 1st Hallway Exit at Franklin St Visually Checked 8:38:09 AM 02/24/2015 Pull Station 1st Maintenance Area Tool Storage Visually Checked 8:45:58 AM 02/24/2015 Pull Station 1st Maintenance Area Top of Ramp Visually Checked 8:45:54 AM 02/24/2015 Pull Station 1st Rear Side Corridor Yard Exit Visually Checked 8:35:14 AM 02/24/2015 Pull Station 1st Rear W. Franklin Exit Maintenance Area Visually Checked 8:45:50 AM 02/24/2015 Ramp Pull Station 1st Rear West Corridor Exit Between Rm 3 & 4 Visually Checked 8:39:44 AM 02/24/2015 Pull Station 1st Rear Yard Exit at Basketball Court Visually Checked 8:38:50 AM 02/24/2015 Pull Station 1st Side Corridor Exit Visually Checked 8:40:04 AM 02/24/2015 Pull Station 1st At Front Entrance Visually Checked 8:32:04 AM 02/24/2015 Pull Station 1st At Front Entrance Visually Checked 8:45:27 AM 02/24/2015 Pull Station 1st At Side Exit by Girls Restroom Visually Checked 8:34:10 AM 02/24/2015 Pull Station 1st Inside Back Stage Exit Door Visually Checked 8:45:33 AM 02/24/2015 Pull Station 1st Inside Boiler Room Visually Checked 8:37:42 AM 02/24/2015 Pull Station 1st Inside Classroom 1 Rear Exit Visually Checked 8:41:22 AM 02/24/2015 Pull Station 1st Inside Classroom 1 Side Exit Visually Checked 8:41:26 AM 02/24/2015 Pull Station 1st Inside Classroom 1 Yard Exit Visually Checked 8:46:08 AM 02/24/2015 Pull Station 1st Inside Classroom 10 Rear Exit Visually Checked 8:36:35 AM 02/24/2015 Pull Station 1st Inside Classroom 10 Yard Exit Visually Checked 8:36:49 AM 02/24/2015 Pull Station 1st Inside Classroom 2 Rear Exit Visually Checked 8:41:00 AM 02/24/2015 Pull Station 1st Inside Classroom 2 Yard Exit Visually Checked 8:41:13 AM 02/24/2015 Pull Station 1st Inside Classroom 3 Rear Exit Visually Checked 8:40:50 AM 02/24/2015 Pull Station 1st Inside Classroom 3 Yard Exit Visually Checked 8:40:34 AM 02/24/2015 Pull Station 1st Inside Classroom 4 Rear Exit Visually Checked 8:39:34 AM 02/24/2015 Pull Station 1st Inside Classroom 5 Rear Exit Visually Checked 8:39:25 AM 02/24/2015 Pull Station 1st Inside Classroom 6 Rear Exit Visually Checked 8:39:13 AM 02/24/2015 Pull Station 1st Inside Classroom 7 Rear Exit Visually Checked 8:38:58 AM 02/24/2015 Pull Station 1st Inside Classroom 8 Rear Exit Visually Checked 8:35:50 AM 02/24/2015 Pull Station 1st Inside Classroom 8 Yard Exit Visually Checked 8:35:36 AM 02/24/2015 Pull Station 1st Inside Classroom 9 Rear Exit Visually Checked 8:36:24 AM 02/24/2015 Pull Station 1st Inside Classroom 9 Yard Exit Visually Checked 8:46:03 AM 02/24/2015 Pull Station 1st Inside Kindergarden East Exit Across From Visually Checked 8:46:13 AM 02/24/2015 Restroom Pull Station 1st Inside Kindergarden South Exit Visually Checked 8:42:42 AM 02/24/2015 Pull Station 1st Inside Kindergarden West Exit Visually Checked 8:46:17 AM 02/24/2015 Pull Station 1st Inside Kitchen Area Exit Visually Checked 8:45:46 AM 02/24/2015 Pull Station 1st Inside Kitchen Sink/Dish Wash Area Visually Checked 8:45:40 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 1 Visually Checked 8:49:12 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 1 Visually Checked 8:49:18 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 2 Visually Checked 8:49:36 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 2 Visually Checked 8:49:39 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 3 Visually Checked 8:49:29 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 3 Visually Checked 8:49:33 AM 02/24/2015 Pull Station Ground Outside in Portable Classroom 4 Visually Checked 8:49:22 AM 02/24/2015 ARK Systems, Inc. 4 10/28/2016

9 Device Type Location Service Time Date Passed Pull Station Ground Outside in Portable Classroom 4 Visually Checked 8:49:26 AM 02/24/2015 ARK Systems, Inc. 5 10/28/2016

10 Auxiliary Functions Testing Generated by: BuildingReports.com Control Panel: 1 - SimplexGrinnell 4020 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated. Type Location Comment ScanID Simulated Passed Fan Shutdown 1st Above Ceiling in Classroom 2 AHU 1 Passed st Above Ceiling in Classroom 6 AHU 2 Passed st Above Ceiling in Classroom 9 AHU 3 Passed st Above Ceiling in Kindergarden Classroom Passed st Above Ceiling in Kindergarden Classroom Passed st Above Ceiling in Principal Office Passed st Above Ceiling in Teacher Work Room AHU Passed ARK Systems, Inc. 6 10/28/2016

11 Smoke Management Testing Generated by: BuildingReports.com Control Panel: 1 - SimplexGrinnell 4020 The Smoke Management Testing section details the test and inspection of device items that are involved in controlling the spread of smoke in a building. Items are grouped by Passed or Failed/Other. Location Description Comment ScanID Simulated Passed Fan Shutdown 1st Above Ceiling in Classroom 2 AHU 1 Passed st Above Ceiling in Classroom 6 AHU 2 Passed st Above Ceiling in Classroom 9 AHU 3 Passed st Above Ceiling in Kindergarden Classroom Passed st Above Ceiling in Kindergarden Classroom Passed st Above Ceiling in Principal Office Passed st Above Ceiling in Teacher Work Room AHU Passed ARK Systems, Inc. 7 10/28/2016

12 Inventory & Warranty Report Generated by: BuildingReports.com Control Panel: 1 - SimplexGrinnell 4020 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Device or Item Category % of Inventory Quantity Control Panel Control 1.33% 1 Horn/Strobe Indicating 1.33% 1 Disconnect Control 1.33% 1 Battery Control 8.00% 6 Pull Station Initiating 57.33% 43 Voice Evacuation Control 1.33% 1 Power Supply Control 1.33% 1 Duct Detector Initiating 9.33% 7 Fan Shutdown Auxiliary 9.33% 7 Indicating Device Indicating 9.33% 7 Type Qty Model # Description Install Date Battery Mart In Service - 3 Years to 5 Years Battery 2 SLA-12V18 Sealed Lead Acid 02/01/2012 Energy Battery 2 EP-SLA12-8T2 Sealed Lead Acid 02/01/2012 Embassy In Service - 5 Years to 10 Years Battery 2 12CE7.5 T1 Sealed Lead Acid 02/25/2009 In Service - 15 Years to 25 Years Disconnect 1 Breaker 02/25/1997 Fan Shutdown 1 02/25/1997 SimplexGrinnell Control Panel /25/1997 Duct Detector /25/1997 Duct Detector Ionization 02/25/1997 Duct Detector Photoelectric 02/25/1997 Fan Shutdown 1 02/25/1997 Fan Shutdown /25/1997 Horn/Strobe /25/1997 Indicating Device 2 Key Switch 02/25/1997 Indicating Device Duct Detector 02/25/1997 Power Supply /25/1997 Pull Station Dual Action 02/25/1997 Voice Evacuation /25/1997 ARK Systems, Inc. 8 10/28/2016

13 Zone Address Report Generated by: BuildingReports.com Control Panel: 1 - SimplexGrinnell 4020 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference. Address Device Type Location Type ScanID 10 Pull Station 1st Rear Side Corridor Yard Exit Dual Action Pull Station 1st Inside Classroom 8 Yard Exit Dual Action Duct Detector 1st Above Ceiling in Classroom 9 AHU Fan Shutdown 1st Above Ceiling in Classroom 9 AHU Indicating Device 1st Above Ceiling in Classroom 9 AHU 3 Duct Detector Pull Station 1st Inside Classroom 9 Yard Exit Dual Action Pull Station 1st Inside Classroom 10 Yard Exit Dual Action Pull Station 1st Hallway Exit at Franklin St Dual Action Pull Station 1st Rear W. Franklin Exit Maintenance Dual Action Area Ramp 18 Pull Station 1st Maintenance Area Top of Ramp Dual Action Pull Station 1st Maintenance Area Tool Storage Dual Action Pull Station 1st Inside Classroom 10 Rear Exit Dual Action Pull Station 1st Inside Classroom 9 Rear Exit Dual Action Pull Station 1st Inside Classroom 8 Rear Exit Dual Action Pull Station 1st Rear Yard Exit at Basketball Court Dual Action Pull Station 1st Inside Classroom 7 Rear Exit Dual Action Pull Station 1st Inside Classroom 6 Rear Exit Dual Action Duct Detector 1st Above Ceiling in Classroom 6 AHU Fan Shutdown 1st Above Ceiling in Classroom 6 AHU Indicating Device 1st Above Ceiling in Classroom 6 AHU 2 Duct Detector Pull Station 1st Inside Classroom 5 Rear Exit Dual Action Pull Station 1st Inside Classroom 4 Rear Exit Dual Action Pull Station 1st Rear West Corridor Exit Between Rm Dual Action & 4 3 Pull Station 1st Inside Back Stage Exit Door Dual Action Pull Station 1st Inside Classroom 3 Rear Exit Dual Action Pull Station 1st Inside Classroom 2 Rear Exit Dual Action Pull Station 1st Inside Classroom 1 Rear Exit Dual Action Pull Station 1st Inside Classroom 1 Side Exit Dual Action Pull Station 1st Inside Classroom 1 Yard Exit Dual Action Pull Station 1st Inside Classroom 2 Yard Exit Dual Action Pull Station 1st Inside Classroom 3 Yard Exit Dual Action Pull Station 1st Side Corridor Exit Dual Action Duct Detector 1st Above Ceiling in Principal Office Ionization Fan Shutdown 1st Above Ceiling in Principal Office Indicating Device 1st Above Ceiling in Principal Office Duct Detector Duct Detector 1st Above Ceiling in Kindergarden Ionization Classroom 41 Duct Detector 1st Above Ceiling in Kindergarden Classroom Ionization ARK Systems, Inc. 9 10/28/2016

14 41 Fan Shutdown 1st Above Ceiling in Kindergarden Classroom 41 Fan Shutdown 1st Above Ceiling in Kindergarden Classroom 41 Indicating Device 1st Above Ceiling in Kindergarden Duct Detector Classroom 42 Pull Station 1st Inside Kindergarden South Exit Dual Action Pull Station 1st Inside Kindergarden East Exit Across Dual Action From Restroom 45 Pull Station 1st Inside Kindergarden West Exit Dual Action Pull Station Ground Outside in Portable Classroom 1 Dual Action Pull Station Ground Outside in Portable Classroom 1 Dual Action Pull Station Ground Outside in Portable Classroom 2 Dual Action Pull Station Ground Outside in Portable Classroom 2 Dual Action Pull Station 1st At Side Exit by Girls Restroom Dual Action Pull Station Ground Outside in Portable Classroom 3 Dual Action Pull Station Ground Outside in Portable Classroom 3 Dual Action Pull Station Ground Outside in Portable Classroom 4 Dual Action Pull Station Ground Outside in Portable Classroom 4 Dual Action Pull Station 1st Inside Kitchen Sink/Dish Wash Area Dual Action Pull Station 1st Inside Kitchen Area Exit Dual Action Duct Detector 1st Above Ceiling in Teacher Work Room AHU 6 Photoelectric ARK Systems, Inc /28/2016

15 WASHINGTON COUNTY PUBLIC SCHOOLS 5/4/2015 Winter Street Elementary 59 Winter Street Elementary Hagerstown, MD PK O A R Total Adj. 0 5,782 27,198 32,980 Not Adequate System Description Condition Roof: ply BU A & G Adequate Portables: 4 Latitude: Longitude: Deg. North Deg. West Flooring: ,407 sq. ft. VCT Good AC: (10) RTU DX cooling Poor Utility Source Electric: Amp Not Adequate Emer. Gen.: KW Kohler natural gas Superior Sprinkler: None None Fire Alarm: Simplex 4100 / 4020 DD-9 PSSA-41 Adequate Security: Electronic access control Adequate Digital camera system (19) Electronic visitor log system Heating: (12) CUV heating only Not Adequate (2) HVU heating (2) 2.5 MBTU Steam H.B. Smith Tech Wiring: Category 6 wiring and wireles network Good Electric: City of Hagerstown Acct # Phone: Gas: Columbia Gas Account # Phone Water: City of Hagerstown Acct # Phone: Sewer: City Of Hagerstown Acct # Phone: Fuel: Police: ,000 gallon steel tank HazMat Phone Hagerstown Police Dept. Phone WASHINGTON COUNTY PUBLIC SCHOOLS

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection

More information

Sprinkler Inspection Certificate

Sprinkler Inspection Certificate Sprinkler Inspection Certificate For New Dimensions High School 4900 Old Pleasant Hilll Road Kissimmee, FL 34746 Tested to NFPA 25 Standards This Inspection was performed in accordance with applicable

More information

VSC Fire & Security, Inc.

VSC Fire & Security, Inc. JOB#: 12775876 VSC Fire & Security, Inc. 10640 Iron Bridge Road, Suite G Jessup MD 20794 (301) 575-1500 www.vscfs.com Important: Deficiencies, Comments and Explanations any FAIL or NEGATIVE responses are

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report Facility Attachment F Campus Capital Needs Sales Surtax Funded Detail Report Facilities Services 2700 Judge Fran Jamieson Way Viera, Florida 32940-6601 Condition Code Estimate Longleaf Elementary 1.78

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

CCDC EXPANSION PROJECT

CCDC EXPANSION PROJECT CCDC EXPANSION PROJECT TEMPORARY MOBILE KITCHEN RFP NO. 12-0132-3 Addendum #1 ADDENDUM #1 IS BASED ON THE INFORMATION DISCUSSED AT THE MANDATORY PRE-BID MEETING THAT WAS HELD ON THURSDAY, JANUARY 10, 2013

More information

Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department

Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA Purchasing Department Ventura County Community College District 761 E. Daily Drive, West Stanley Avenue, St. 200, Camarillo, CA 93010 Purchasing Department TO: All Jobwalk Attendees July 19, 2018 FROM: Janice Kisch, Purchasing

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

SecurityScan Inspection Certificate

SecurityScan Inspection Certificate SecurityScan Inspection Certificate For Sample Inspection Report 123 Main Street Kalamazoo, MI 49007 Tested to applicable Standards This Inspection was performed in accordance with applicable Standards.

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION

CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION Instructions to ders: Please complete this bid form in its entirety. Provide the following information about your company's bid: Name of Company

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY

Inspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

The attached information details the bids, purchases and/or services being recommended as follows:

The attached information details the bids, purchases and/or services being recommended as follows: MEMORANDUM TO: Paul Soma, Superintendent FROM: Christine Thomas-Hill, Executive Director of Finance/Operations DATE: March 4, 2016 RE: APPROVAL OF BIDS, PURCHASES AND/OR SERVICES The attached information

More information

THIS ADDENDUM MUST BE ACKNOWLEDGED.

THIS ADDENDUM MUST BE ACKNOWLEDGED. Denver Public Schools Purchasing Department 1350 East 33 rd Avenue Denver, Colorado 80205 INVITATION TO BID 13-MC-Fire Extinguisher ADDENDUM NUMBER ONE December 14, 2012 THIS ADDENDUM MUST BE ACKNOWLEDGED.

More information

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN PURPOSE To protect our employees, students, and occupants from the dangers of fire, Oak Grove School District has developed a fire prevention

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

ADDENDUM No. 3 BID NO TRANSMISSION WAREHOUSE OFFICE REMODEL

ADDENDUM No. 3 BID NO TRANSMISSION WAREHOUSE OFFICE REMODEL 205 E. 28 th St. P.O. Box 1000 Bryan, TX 77805 Phone: 979-821-5860 FAX: 979-821-5747 http://www.btutilities.com September 15, 2015 ADDENDUM No. 3 BID NO. 150-11-15 TRANSMISSION WAREHOUSE OFFICE

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction CITY HALL ADA ENHANCEMENT/REMODEL 2016 ACTION PLAN 1978 Construction 1 HISTORY At the February 2, 2016 Council Workshop Council Motions included: The direction to staff to move forward with the City Hall

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM.

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM. City of Raleigh, Fire Station No. 11 Renovation September 28, 2018 274-CM2018-15A Page 1 HUFFMAN ARCHITECTS, PA 632 PERSHING ROAD RALEIGH, NORTH CAROLINA 27608 PHONE (919) 740-5669 TO: ALL PRIME BIDDERS

More information

NYC Department of Education

NYC Department of Education Asset: A. PHILLIP RANDOLPH HS - MANHATTAN, 443 WEST 135 STREET, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-02 8:11 AM 2018-06-14 1:21 PM Asset Data Are there

More information

ADDENDUM/AMENDMENT NUMBER 5 (October 7, 2016) Fire/Security Alarm-Intercom/Clock/Bells-Audio/Video Systems

ADDENDUM/AMENDMENT NUMBER 5 (October 7, 2016) Fire/Security Alarm-Intercom/Clock/Bells-Audio/Video Systems ADDENDUM/AMENDMENT NUMBER 5 (October 7, 2016) RIO RANCHO PUBLIC SCHOOLS PURCHASING DEPARTMENT 500 LASER ROAD NE RIO RANCHO, NEW MEXICO 87508 REQUEST FOR PROPOSALS: RFP#2017-002-IT TITLE: Fire/Security

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 19 - STATEN ISLAND, 780 POST AVENUE, New York, 10310 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-26 8:58 AM 2017-11-14 1:37 PM Asset Data Are there fuel tanks?

More information

AGENDA. 1. Call to Order. 2. Approval of Minutes. 3. Approval of Invoices and Commitments. 4. Review Updated Site Analysis and Permitting

AGENDA. 1. Call to Order. 2. Approval of Minutes. 3. Approval of Invoices and Commitments. 4. Review Updated Site Analysis and Permitting PROJECT MANAGEMENT AGENDA Project: George Keverian School Feasibility Study Project No.: 16049 Re: School Building Committee Meeting Meeting Date: 3/22/2017 Meeting Location: Mayor s Conference Room, City

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

SECTION INSPECTION AND TESTING OF WORK

SECTION INSPECTION AND TESTING OF WORK SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

New School Construction: Safe School Opening. OAR and IOR Joint Training February 17, 2005

New School Construction: Safe School Opening. OAR and IOR Joint Training February 17, 2005 New School Construction: Safe School Opening OAR and IOR Joint Training February 17, 2005 1 Purpose Provide information on process moving from construction to occupancy and opening schools 2 School Opening

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Evaluation. ems. Prepared By: Martha. a s Vineyard. Box P.O. Box June 2015

Evaluation. ems. Prepared By: Martha. a s Vineyard. Box P.O. Box June 2015 Martha a s Vineyard Regional High School Vineyard Haven, MA 2 2015 HVAC Syste ems Evaluation Prepared For: Martha s Vineyard Regional School District Box 1385 Oaks Bluff, MA 02557 Prepared By: BLW Engineers,

More information

BALTIMORE COUNTY PUBLIC SCHOOLS

BALTIMORE COUNTY PUBLIC SCHOOLS Exhibit N BALTIMORE COUNTY PUBLIC SCHOOLS DATE: December 18, 2007 TO: FROM: RE: BOARD OF EDUCATION Dr. Joe A. Hairston, Superintendent RECOMMENDATIONS FOR AWARD OF CONTRACTS ORIGINATOR: J. Robert Haines,

More information

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan. ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of

More information

Final EC Inspection Report 03/2010

Final EC Inspection Report 03/2010 2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers

More information

The blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno.

The blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno. San Antonio Independent School District 1702 N. Alamo Street, Suite 307 San Antonio, Texas 78215-1213 Telephone (210) 554-2420 Fax (210) 271-3330 Office of Construction Services TO: FROM: All Principals

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements ADDENDUM 1 CLIENT: PROJECT: TO: FROM: Guilford County Schools (GCS) Southeast High School Auditorium & Gymnasium HVAC Improvements All Prospective Bidders Derrick Giles, SAMR, PLLC. DATE: 6/6/2018 The

More information

USAutomatic Sprinkler Corporation

USAutomatic Sprinkler Corporation Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION

More information

NYC Department of Education

NYC Department of Education Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 283112 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM VOICE NOTIFICATION PART 1 GENERAL 1.1 SUMMARY NETWORK FIRE ALARM CONTROL PANEL (NODE) A. Network fire alarm control panels shall include all features

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

SUBJECT: ADDENDUM NO. 1 RFP# , FIRE ALARM SYSTEM SERVICE (DISTRICTWIDE) REPOST

SUBJECT: ADDENDUM NO. 1 RFP# , FIRE ALARM SYSTEM SERVICE (DISTRICTWIDE) REPOST Larry Hammel Chief Financial Officer Veronica Jackson Office of Purchasing & Contracts DATE: March 15, 2018 TO: FROM: All Prospective Proposers Veronica Jackson, Purchasing and Contracts Coordinator SUBJECT:

More information

EVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402

EVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402 EVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402 Purpose The purpose of this plan is to establish procedures for the systematic, safe, and orderly evacuation of the building at 1202

More information

Campus Wide Fire Alarm Repairs

Campus Wide Fire Alarm Repairs BID # 15-24 Campus Wide Fire Alarm Repairs SECTION "C" TECHNICAL SPECIFICATIONS OWNER Board of Trustees Middlesex County College 2600 Woodbridge Avenue P.O. Box 3050 Edison, New Jersey 08818-3050 PREPARED

More information

NYC Department of Education

NYC Department of Education Asset: FORSYTH HS (AUXSVC-OLD 91) - M, 198 FORSYTH STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:07 AM 2018-03-20 4:47 PM Asset Data Are there fuel

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager. B A L A Consulting Engineers, Inc. PECO Line 13.2kV Incoming Service No. 1 Utility/Generator Medium Voltage Switchgear PECO Line 13.2kV Incoming Service No. 2 Unit Substation ELECTRICAL Seminar HVAC Equip.

More information

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 92 - BROOKLYN, 601 PARKSIDE AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 8:31 AM 2017-11-27 11:43 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: UNIVERSITY NEIGHBORHOOD - M, 200 MONROE STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-05 11:56 AM 2018-03-02 7:14 PM Asset Data Are there fuel

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

Subject: Addendum #3 IFB No CNG Gas Detection Repair and Maintenance

Subject: Addendum #3 IFB No CNG Gas Detection Repair and Maintenance October 12, 2012 Subject: Addendum #3 IFB No. 112-12 CNG Gas Detection Repair and Maintenance Please be advised of the following questions and responses: 1. Question #1: If the MBTA Everett and Arborway

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 198 - BRONX, 1180 TINTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:14 AM 2018-01-24 9:32 PM Asset Data Are there fuel tanks? Total

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

Norfolk Fire Department Fire Prevention & Information

Norfolk Fire Department Fire Prevention & Information Norfolk Fire Department Fire Prevention & Information For Permits and Inspections Contact (508)528-3207 EFFECTIVE JANUARY 1, 2015, THE NORFOLK FIRE DEPARTMENT, BY STATE REGULATIONS, NO LONGER ISSUES PERMITS

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 163 - BRONX, 2075 WEBSTER AVENUE, New York, 10457 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-22 8:33 AM 2018-03-22 3:13 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: CLINTON AF - BRONX, 100 W. MOSHOLU PKWY S, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-20 8:24 AM 2017-12-31 2:04 PM Asset Data Are there fuel tanks?

More information

2018 Annual Fire Safety Report

2018 Annual Fire Safety Report 2018 Annual Fire Safety Report University of California San Francisco For All UCSF Campus Housing: Parnassus and Mission Bay Issued October 2018 Contains fire statistics for calendar years 2015-2017 A

More information

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS Annex Laundry and Shower Alterations ADDENDUM #1 March 7, 2019 ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS A. Invitation to Bid - Call for Bids has been modified as follows: 1. Notice

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

Request for Proposals (RFP) for: Columbia County Facilities Fire Detection and Security Improvements

Request for Proposals (RFP) for: Columbia County Facilities Fire Detection and Security Improvements Request for roposals (RF) for: Columbia County Facilities Fire Detection and Security Improvements roposals Due: 4:30 M Friday November 13, 2015 Introduction: Columbia County is soliciting proposals from

More information

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?

More information