1 PRE QUALIFICATION CRITERIA : Vendor / Bidder of the Rim-seal Fire Protection system shall be manufacturer or manufacturer s authorised supplier/representative for the specified automatic heat detection and extinguishing system and shall meet the following pre-qualification criteria: a. The Vendor/Bidder must have experience of design, supply, installation and commissioning of offered rim seal fire protection system in EFRT tanks of minimum 30 metre diameter in hot & humid conditions like India within the last 5 years, to be counted prior to the bid due date. b. Further, the installed Rim-seal Fire Protection System (Hollow Metallic tube type Linear heat detection system with foam suppression system) installed by the vendor/bidder must be working satisfactorily for a period of minimum 12 months in any large petroleum / petrochemical or fertilizer installation. c. If the Vendor/Bidder is not the manufacturer, then the following documents to be submitted from the manufacturer of the Detection and Suppression system: i. Authorisation letter from the manufacturer mentioning clearly the specific tender as well as Name of the Bidder / Vendor as authorised supplier/representative for Indian territory. This letter shall include a d eclaration that manufacturer shall provide all necessary logistic support, technical support and after sales service. ii. Certificate from the manufacturer to certify that authorised supplier/representative has adequate technical expertise and service support from the manufacturer for Indian territory. d. The vendor/bidder shall have to submit an undertaking from the manufacturer of the detection system for support & supply of software & hardware required for operation and maintenance/ repair of detection system for all locations covered under the tender for a period of minimum 10 years from the date of installation of the system.

2 e. The vendor/bidder shall have to submit copy of the PESO approval for the offered heat detection system along with the technical bid. The Vendor/Bidder to submit copies of purchase/work order/experience certificate containing the item description, ordered quantity, proof of supply/commissioning/satisfactory performance of the system in support of the above vendor pre-qualification criteria.

3 ITEM : Rimseal Fire Protection System for External Floating Roof Storage Tank(EFRT). Type : Linear Hollow metallic Tube type detection & foam based suppression system. 1.0 Scope This specification covers design, engineering, supply, installation and commissioning of automatic Rimseal fire detection and suppression system of external floating roof tanks (EFRT). The automatic Rim seal fire protection system shall consist of: a) Hollow Metallic tube type Linear Heat Detection system b) Foam based Fire suppression system and c) Site specific Graphic display panel for monitoring of the system. 2.0 Objective The overall purpose of the system is to detect and extinguish the Rim seal fire at the incipient stage and simultaneously alert the personnel at the facility so that they can respond to the incident. 3.0 Basic Principle of Operation The system shall consist of a microprocessor based, site configurable Hollow Metallic Tube type Linear Heat Detection (LHD) system monitoring the rimseal area over the whole tank circumference. This shall rapidly detect the fire at its incipient stage, raise an alarm at manned location/s and automatically discharge firefighting foam over the rimseal area around the entire tank circumference. It shall also minimise the probability of post discharge re-ignition by establishing a vapour suppressing blanket of foam in the rimseal area. The detection system shall be capable for working on max temperature and rate of rise in temperature as basic parameters. The system shall be modular type with each module protecting a defined length of rimseal area and all modules shall discharge simultaneously on detection of fire at any location on the rim seal area. The detection system shall have inbuilt

4 programmable self checking facility with annunciation of status displayed at manned location/s. The said self checking facility shall be part of UL / FM / VdS approval. The system shall be such that after any Rim-seal fire event it can be quickly reinstated by trained site personnel without the need for specialist engineers. Site specific Graphic display panel shall be provided at manned locations for monitoring of the system. Repeater Panel for indications/alarm of FIRE and FAULT shall be provided at the other manned location depending upon the site requirement. The number & locations of such repeater panel shall be decided based on the specific site conditions. 4.0 Vendor s Scope of Supply/work: The provision and installation of the Rimseal Fire Protection by the Vendor shall be based on site specific requirements & shall consist of: a) Design, Engineering, Fabrication and Supply of all the components of Rimseal Fire Protection system as per the specification. b) Installation of the Rimseal fire protection system on the tank roof deck. c) Supply & Installation of Local Junction Box with audio/visual indication & manual actuation point outside each tank dyke. d) Supply and installation of all required signal cables, power cables, interface cables & junction boxes from tank top up-to Local Indication Panel. e) Supply & installation of Customized site specific Main Fire Alarm Panel dedicated to the Rimseal system in the relevant Control Room/operator cabin. f) Supply & Installation of Repeater Panel for indications/alarm of FIRE and FAULT at the other manned location depending upon the site requirement where applicable.(owner to specify) g) Provision of potential-free contacts at Rimseal Main Fire Alarm Panel for Fire and Fault Signals for each tank for necessary hook up with main fire alarm system at the location. h) Provision of RS485 or equivalent communication links up-to Rim Seal Main Fire Alarm Panel at control room/operator cabin for connection with laptop computer. i) Provision of Uninterrupted power supply at the Rimseal main Fire Alarm panel control room/operator room & repeater panel room for operation of

5 Entire rimseal fire protection system, if not available at site (Owner to specify). k) Power distribution from main fire alarm panel to, Local panel outside the dyke, rim seal fire protection system at tank & repeater panel shall be designed, supplied & installed by the vendor. l) One Laptop (HP/Dell/Sony/Lenovo/Toshiba make Standard laptop with 160 GB HDD, 2GB RAM, 2.4 GHz Intel processor & 14 inch screen) per each location/terminal/refinery with unique software along with hardware/software lock from the manufacturer of detection system to be provided for system configuration & diagnosis of detection system supplied by the Vendor. m) Supply & Installation of One Graphic Console (LG/Samsung/Sony/Panasonic make 21 inch size touch-screen LCD) with software for graphical representation of unique site based layout of tank farm to be protected for each site/terminal/refinery at the control room where rimseal main fire alarm panel is located. The software shall have features of tank number with active popup, event logging, history and prints. n) Provision of manual simulation from rimseal main fire alarm panel at the control room. o) Common audible/visual alarm for fire at Local junction box outside the dyke audible upto 200 m radial distance. p) Portable equipment including Nitrogen filling cylinder, trolley & hose reel to facilitate re-filling the foam modules.(owner to specify the no. of equipments depending on the no. of tanks protected by Rimseal fire protection system). q) The Vendor shall provide details of the equipment to be mounted on the tank roof and the total weight with foam solution charge. r) Supply of Manuals containing Operating and Maintenance procedures, as built drawings, technical documents & approvals in Hard copies & CD form. s) Supply of all software on CD alongwith required software licenses. t) Factory acceptance test as per clause 14.0 of the specification. u) Site acceptance test as per clause 15.0 of the specification. v) Commissioning of the system. w) Training of the buyer s personnel on functional, operational & routine maintenance aspects of the system.

6 x) All civil, mechanical, electrical & instrumentation work required for completion of the job Any other component and software required for completion and commissioning of Rimseal Fire Protection system shall be supplied & installed by the vendor except the items mentioned under the Owner s scope under clause Owner s Scope 230 V/110V(+ 10%),50 Hz(+ 3%) AC Power shall be made available at main fire alarm panel control room & repeater panel control room as a single point source by the owner. Further power distribution to Local panel outside the dyke & rim seal fire protection system at tank shall be designed, supplied & installed by the vendor. Vendor shall indicate the maximum and normal operating power loads along with the bid. 6.0 Operating Conditions The system shall be suitable for operating satisfactorily in humid and corrosive atmospheres found in oil terminals, refineries & petrochemical plants in India. The system shall be suitable for working in relative humidity up to 95% (non condensing) & temperature range of +1 deg C to +65 deg C. The system shall be tolerant to environmental influences such as high ambient temperatures, change in humidity, electromagnetic interference, Radio Frequency Interference (RFI), aggressive or corrosive vapour, UV radiation, and heavy rainfall. The system should be certified for response behavior on Class 1 as per EN 54/5 standard by UL / FM / Vds /LPC. The system should be site configurable type. All enclosures for electrical equipment shall be suitable for use in hazardous area as per facility hazardous area classification & vendor shall submit valid approval issued by PESO along with the technical bid. Flameproof enclosure which are manufactured outside India & certified by accredited international authorities shall also have approval of PESO, India. As a minimum all enclosures and instruments in the field shall be dust proof & weather proof to IP55.

7 7.0 Basic components The system shall consist of following basic critical components: a) Linear Heat Detection (LHD) System b) Foam Fire Suppression System. c) Site specific Graphic console. d) Main Rim seal Fire Alarm panel & repeater panel. e) Local junction box with indication of fire outside the tank dyke. f) Fail Safe Arrangement as per Annexure Approvals Following approvals shall be required to be submitted along with the technical bid: a) The Linear Heat Detector shall have UL listing or VdS/FM/LPC approved. b) All junction box, cable glands, electrical equipments, instruments & its accessories shall have PESO approval or housed in flame proof enclosure approved by PESO as per hazardous area classification. c) UL listing for 3% type AFFF/FFFP or 3%/3% type AR-AFFF foam to be used. d) The Foam spray Nozzles shall be UL listed or FM approved. Failure in submitting above approval would mean rejection of the offer at technical bid stage itself. 9.0 Linear Heat Detection 9.1 Principle of Operation The Principle of the system shall be based on a rapid rate of rise in temperature which results in corresponding rise in pressure of gas (air) in a pneumatically sealed metallic sensor tube which is normally non-pressurized. The sensor tube is connected to a microprocessor based evaluation unit. The microprocessor based LHD evaluation unit evaluates this change in pressure inside the sensor tube installed in the rim seal area to: a) Generate Fire Signal at pre-set levels for actuation of foam based suppression system. b) Generate alarm at the Rimseal fire alarm panels.

8 9.2 LHD Mounting LHD tube shall be securely fixed as close as possible to the highest point of the seal assembly. The maximum distance from the sensor to the top of the seal shall be 150mm. The sensor shall be located on the external face of the primary/secondary seal so that it can be inspected without the need for removal of any seal components. LHD tube mounts shall be such that they can accommodate tank flexing and movement without causing chafing or other damage to the tube. The Vendor shall supply all necessary fixing brackets, sleeves, clamps or other devices required to install the sensor tube on the tank roof. 9.3 General requirements a) The sensor (metallic tube) element shall be reusable after exposure to and rapid extinguishment of associated hydrocarbon fires and shall be resettable after actuation. The detection system shall be restored for service after event occurrence from the Control Room without the need for access to the protected area. b) The Sensor tube shall be hollow metallic tube, free from glass, fiber, and rubber & plastic for its long and dependable service. c) The LHD evaluation panel shall be installed on the tank pontoon. d) The detection system shall be self testing by means of inbuilt automatic pressurization by pump at preset regular intervals e) The detection system shall provide alarm/fault signals separately for each tank at the rim seal main fire alarm panel at Control Room. f) The system shall have the capability of storing system specific parameters and event logging for each tank. g) The Detection system shall be site configurable for rate of rise and maximum temperature as two different alarm thresholds. h) The Detection system shall be of decentralized type that is individual detection system (sensor tube with evaluation unit) for individual tank shall be independent & shall be mounted on the tank roof itself. i) The system shall have the facility for interface to the supplied Laptop for

9 configuration and setting the parameters of the system. Suitable port connectivity with Laptop at Control Room shall be provided for each tank. j) All field junction boxes/instruments/electrical equipment shall be provided with prefabricated canopy. k) Software for the detection system shall be site specific with authorisation for use of the software for life at a particular facility.the documented authorisation shall accompany the software at the time of supply. l) The system shall be fail safe as per the criteria given in Annexure Installation requirements: No modification or alterations will be allowed on the main tank shell. Rim seal fire protection system design shall be suitable in accordance with the individual tank design. It is recognised that installation may be required whilst the tank is in service. In this case the complete system shall be designed such that it can be installed without the need for welding or any kind of hot work on the tank. In case, the installation is required at the tank in service, the following condition shall apply: a) Vendor shall comply fully with all safe working practices and Permit to Work system of the owner. b) No hot work shall be allowed on the tank. c) No work shall be allowed to be performed during receipt and dispatch of material from the tank. d) Continuous monitoring of vapour levels shall be done on the tank roof when personnel are present on the roof. e) All persons working on the roof shall use required personal protective equipment & retractable type fall arrestor system Foam Fire Suppression System 10.1 Design The Rimseal fire suppression system shall include the appropriate number of equally spaced identical modular foam units mounted adjacent to but outside the containment

10 area of the foam dam so as to protect the entire rim seal area. The foam units shall be charged with pre-mixed foam solution pressurised with nitrogen as an expellant gas. All modules on a tank shall be actuated simultaneously in the event of automatic detection of fire from any detector(in case of more than one linear detector) on the tank roof or by actuation of a manual release station outside the bund. The system shall be designed for a minimum foam application rate of 18 lpm /m2 of rim seal area. An application period of 40 seconds (+10% variation is acceptable) shall be considered. The system shall be modular in design with each section of foam distribution manifold protecting the equal length of Rimseal area. In order to ensure full foam coverage in the entire rimseal area, the placement of the nozzle shall be such that foam application shall be uniform including the area at the ends of the manifold. Foam concentrate to be used in the rimseal fire protection system shall be UL listed 3% concentrate Aqueous film forming foam (AFFF) or 3% type Film Forming Flouro Protein (FFFP) or 3%/3% Alcohol Resistant-Aqueous Film Forming Foam (AR- AFFF) Foam solution modules a) Stainless Steel (SS316) Foam solution storage tank (foam module) shall be designed to meet foam application rate of minimum 18 lpm/m 2 of protected rim seal area for an application period of maximum 40 seconds. However, the maximum capacity of each foam solution storage tank shall not exceed 250 litres. b) Foam solution storage tank shall be manufactured to ASME-VIII, Div-1 requirements. c) Foam Discharge Manifold and distribution pipe work with semi aspirating foam spray nozzles (expansion ratio 1:3 to 1:6) shall be made of SS-31 6 and evenly spaced to cover one segment of rim seal up-to maximum length 50 meters. d) Automatic Foam Discharge actuation valve shall be provided at discharge outlet. e) Instrumentation Panel containing nitrogen charging port, Distribution Manifold, pressure switch to monitor foam module pressure, etc.shall be installed on each foam module.

11 f) Canopy shall be provided on each foam module for protection from direct impingement by sunlight & rain water. g) Clearly legible schematic and operating instruction plate shall be permanently fixed on each foam module. h) Suitable sized filling and draining facilities shall be provided for operation and maintenance of modules. i) Each foam module shall be fitted with a pressure gauge to manually identify module pressure. Additionally, the signal from the pressure switch shall terminated into the Local junction box and a common signal for Module pressure low shall be transmitted for each tank to the R imseal fire alarm panel at the control room. j) One Test discharge connection with nozzle shall be provided to allow testing of system without discharging foam into Rimseal area Foam system general requirements a) The discharge nozzles shall be mounted above the Primary seal and aligned such that the discharge pattern shall be directed at the tank shell above the primary seal around the complete circumference of the tank. b) The suppression system shall be capable of actuation without any signal from the Fire Alarm Panels outside the tank dyke. c) The foam discharge nozzles shall be UL listed / FM Approved. d) All the piping coming in contact with foam solution shall be of SS 316. e) Pipe supports shall be designed and located to effectively sustain the weight and thermal effects of piping system and to prevent its vibration. f) The piping shall be provided with the required number of valves, bends, and fittings for the efficient functioning of the system. g) Module Pressure Low signal shall be available from the unit Alarm & Control Panel

12 11.1 Local Panel/Junction box: Explosion proof local panel / Junction Box common per bund shall be provided outside the bund with system status annunciation lights and sounder (Fire, Fault, common Foam Module Pressure Low per tank) to alert the field personal of any alarm or fault condition of the Rimseal protection system. The panel shal be provided with a rust proof canopy. The cabinet for the panels shall be painted with powder coated paint There shall be no junction box within tank dyke area outside thetank Emergency Actuation point: Manual Actuation point shall be provided on the Local panel/junction box outside the tankdyke for manual action of foam suppression system. Manual Actuation Point (MAP) shall be painted & labeled with fluorescent paint clearly indicating the relevant tank numbers. It should require two operations for actuation e.g. Pull down flap & Push Button Rimseal Main Fire Alarm Panel at control Room/Operator Cabin: Site specific designed Rimseal main Fire Alarm Panel (FAP) shall be provided at the relevant Control Room/operator Cabin for r emote indication of the signals from the detection and suppression system. This panel should have visual and audible alarm with resetting facility. An annunciation window shall be provided on the front face of the panel. The following signals shall be available in the panel: Fire - flashing light and sounder Detector Fault flashing light and sounder Cable Fault flashing light and sounder Module pressure low (common per tank) flashing light and sounder Total system is healthy Constantly illuminated green light Additional Repeater Panel for indication of fire shall be provided at other manned location( If required- Owner to specify).

13 12.0 Tank Alarm Automation: One additional Graphic Console (LG/Samsung/Sony/Panasonic make 21 inch touchscreen LCD ) with software and graphical representation of tanks shall be provided at each Rimseal Main Fire Alarm Panel control room/operator cabinwith unique site based layout of tank farm to be protected by the Rimseal system. The console shal have features of tank number with Pop-up, event logging, history and prints. It shall be able to maintain historical data of alarm and faultsfor minimum 30 days Connection Cables/Junction boxes : 13.1 General requirement: The connection cable onto and from the tank roof shall a) Consist of stranded copper conductor of minimum 1.5mm 2 or higher according to power requirements. b) Have a working temperature range of -40 o C to +65 o C. c) Have length and mounting suitable for tank roof movement over the entire height. d) Cables between tank roof to Dyke wall and control room/operator cabin to Dyke wall shall be armoured FRLS. e) Cable Joints shall not be used for signal and control cables. f) There shall not be any cable joints for power cables inside the tank dyke. g) All cable glands shall be provided with PVC shrouds to prevent ingress of moisture and rain water inside the enclosures All main multi-core / multi-pair cables having more than three cores shall have a minimum of 20% spare cores / pair Power distribution network shall be designed in such a way that single point failure shall not cause tripping of the total system. Each distribution point shall be provided with a separate MCB of power rating for isolation of the system.

14 13.2 Cable routing onto the tank Provision shall be made to prevent snagging of the cable. It shall take account of tank roof movement and wind conditions. Routing shall be done along the rolling ladder with necessary arrangement to ensure that the cable does not snag under the ladder wheels Cable routing between tank dyke panel & main fire alarm panel/repeater panel: All the above ground cables shall be laid in galvanised metallic cable trays. Underground cables shall be laid in armored HDPE conduits as per ASTM F21 60 (Standard Specification for Solid Wall High Density Polyethylene Conduit) 14.0 Factory Acceptance Testing Vendor shall arrange following Factory Acceptance Test in presence of owner s representative/ Third Party Inspection (TPI) agency approved by the owner. Third party Inspection Charges shall be borne by the vendor. a) Positive Material Identification (PMI) test of 10 % material of all piping, vessel and fasteners and other pressure components and witness by TPI. b) Review of certification for electrical enclosures to be mounted in classified hazardous areas. c) Review of certificate of approval / listing of Linear Heat Detection. d) 100% welding joints of pressure vessel and piping shall be radiographed and reports will be reviewed by TPI. e) Inter granular corrosion test as per ASTM A-262 Practice-E (IGC) sampling and stamping to be done in presence of TPI. f) Weld joint fit up to 10 % will be witnessed by TPI randomly. g) Review of WPS (Welding Procedure Specification) WPQ (Welder s Performance Qualification) as per ASME Sec-II Part-C & ASME-Sec-IX, QAP (Quality assurance plan ) and mill test certificate of raw material and test certificate marking. h) TPI shall witness 100% of the following manufacturing activities of pressure

15 vessel and piping besides other inspection as per applicable codes : x Weld joint hardness test after PWHT if any x Final Visual and dimensional inspection x Air testing of nozzle pads x Hydro testing (Water quality should be monitored and shall not contain more than 25 PPM chlorides) Measurement of expansion ratio of the foam produced from nozzle at 7 KG/CM 2 Test for full discharge and actuation of foam module when exposed to a actual fire on Rimseal simulator. This Rimseal simulator shall consist of a tray 300 mm wide and 6 meter long. The detector tube shall be mounted 300 mm above the fire pan and run along the centre line of the pan. The test fuel shall be a liquid hydrocarbon such as motor spirit, or kerosene. The module and discharge Manifold with Nozzles for carrying out the test shall be selected by the owner/third Party Inspection Agency. On actuation, entire Foam Module should be discharged in approximately 40 seconds and fire should be extinguished Site Acceptance Test: Vendor shall arrange following Site Acceptance Test in presence of owner s representative at no extra cost to the owner: a) Simulation of discharge of one Foam module on each tank shall be done from the panel at control room. In case simulation on one module fails, Vendor shall demonstrate the simulation of all Foam Modules for that particular tank. Foam required for the simulation/testing shall be supplied by the vendor. b) Actuation of foam discharge valve by operation of manual Fire call point outside the dyke. c) Functioning of All signals at the control panels & Junction box outside the dyke. d) Demonstration of resetting of Detection system after simulation from control room itself. e) Demonstration of Site specific graphic console. f) UL listed 3% type AFFF/FFFP or 3%/3% type AR-AFFF foam suitable for foam nozzles required during testing & commissioning shall be supplied by

16 the owner. Specification / Datasheet Site Acceptance Test (SAT) as given above shall be conducted for each tank within maximum 15 days of completion of installation. Based upon the above test requirement, Vendor shall develop detailed Quality Assurance plan (QAP) & submit it to the owner for approval Testing and maintenance during operation Both the detection and the extinguishing system shall have a manual or automatic simulation facility to test system integrity and function during operation. A discharge test nozzle and appropriate valve shall be provided so that the system can be discharged without the need for discharging foam into the seal area Documentation: The supplier shall submit the following documents alongwith the technical bid while submitting the offer: i Detailed P&ID indicating the complete scheme of instrumentation and controls ii Control & Interlocking Philosophy iii Power supply requirements for field instruments along with consumption iv List of spares during commissioning and during 2 year warranty v Indicative Bill of Material for one no tank each of dia 16M, 32M, 48M, 64M vi UL Listing / FM / VdS / LPC certification for detection system vii UL listing approval for Nozzle viii Procedure for calibration of rim seal detection system, solenoid valves, etc. ix UL Certificate of foam manufacturer and foam container manufacturer from whom the bidder proposes to procure the foam x Detailed procedure for calibration of detection and control system xi Copy of PESO approval for all enclosures for electrical equipment which shall be suitable for use in hazardous area as per facility hazardous area classification xii Proven track record of the offered system alongwith satisfactory performance proof of at least for a period of 12 months

17 The supplier shall provide four sets manuals containing the following documents after commissioning of the system on the tanks: a) Complete Operating and Maintenance procedures. b) As built drawings (tank farm) showing the location of systems and associated alarm/control equipment. c) Data sheets providing technical details of all Major components. d) CIMFR/ PESO Certificates for Electrical Enclosure mounted in classified hazardous areas. e) UL listing/ FM approval document for the Nozzle. f) UL listing or FM/VdS/LPC approval for linear heat detector. All the manual shall be provided in hard bound A4 size folders with clear printed labels on it. In addition to the hard copies following software shall be supplied after the commissioning a) Soft copies of the documents/drawings placed in the manual. b) CD for Software to be used with the rim seal fire detection system along-with the authorization Training: Vendor shall impart training to site personnel for routine operation & maintenance of the rim-seal fire protection system. The training shall be imparted at owner s site for minimum two days immediately after commissioning Vendor Qualification Criteria: Vendor / Bidder of the Rim-seal Fire Protection system shall be manufacturer or manufacturer s authorised supplier/representative for the specified automatic heat detection and extinguishing system and shall meet the following pre-qualification criteria: f. The Vendor/Bidder must have experience of design, supply, installation and commissioning of offered rim seal fire protection system in EFRT tanks of minimum 30 metre diameter in hot & humid conditions like India within the last 5 years, to be counted prior to the bid due date.

18 g. Further, the installed Rim-seal Fire Protection System (Hollow Metallic tube type Linear heat detection system with foam suppression system) installed by the vendor/bidder must be working satisfactorily for a period of minimum 12 months in any large petroleum / petrochemical or fertilizer installation. h. If the Vendor/Bidder is not the manufacturer, then the following documents to be submitted from the manufacturer of the Detection and Suppression system: i. Authorisation letter from the manufacturer mentioning clearly the specific tender as well as Name of the Bidder / Vendor as authorised supplier/representative for Indian territory. This letter shall include a d eclaration that manufacturer shall provide all necessary logistic support, technical support and after sales service. ii. Certificate from the manufacturer to certify that authorised supplier/representative has adequate technical expertise and service support from the manufacturer for Indian territory. i. The vendor/bidder shall have to submit an undertaking from the manufacturer of the detection system for support & supply of software & hardware required for operation and maintenance/ repair of detection system for all locations covered under the tender for a period of minimum 10 years from the date of installation of the system. j. The vendor/bidder shall have to submit copy of the PESO approval for the offered heat detection system along with the technical bid. The Vendor/Bidder to submit copies of purchase/work order/experience certificate containing the item description, ordered quantity, proof of supply/commissioning/satisfactory performance of the system in support of the above vendor pre-qualification criteria Warranty Vendor shall offer performance guarantee for satisfactory and trouble free operation of the entire Rimseal protection system for a minimum period of 1 year from the date of commissioning of the system.

19 The Vendor shall repair any defect or replace any defective part during the guarantee period within two weeks of receiving such information from the owner Post Warranty Maintenance: The Vendor/bidder shall submit annual post-warranty maintenance proposal at the time of bid which will be as follows: a) The proposal shall include separate price item and at the Owner s request, the vendor shall provide comprehensive maintenance including supply of spares for period of three years after the expiry of the warranty period. b) The travel, boarding & lodging of service engineer/technician shall be borne by the vendor. The vendor shall also bring their own tools & tackles as required for maintenance of the system. c) The bid shall be made year-wise for three years & price validity shall be available for the entire period of the contract. d) The service under post warranty maintenance shall include : i. Preventive maintenance Preventive maintenance shall involve once in six month, complete checking, site acceptance test as per the specification, repair/replacement of defective part/components and detailed reporting. ii. Emergency maintenance In the event of any malfunction of the system, experienced service engineer shall be made available at site with-in two weeks on the receipt of such information from the owner & the system must be brought to the Normal within 24 hrs after reporting at site.

20 Annexure -I FAIL SAFE REQUIREMENT The system shall have features that ensure fail-safe operation of the rim seal fire protection system even under abnormal conditions. To ensure the fail-safe operation of the rim seal fire protection system, the system shall be designed in such a way that in the event of any failure within the system due to any reason like cable damage, power failure, mechanical damage to the system parts or adverse environmental condition, the system shall alert user through alarm. Rim seal fire protection system shall have following features to ensure the failsafe operation: CASE 1: Power failure from mains to the fire alarm panel in the control room/rim seal protection system: Power supply to all components of the Rimseal fire protection system including panels shall be taken from Un-interrupted Power Supply (UPS) source. In case of failure of AC Power, UPS should be rated to supply continuous power for minimum 2 hours. CASE 2: Any hardware/software problem in functioning of fire alarm panel in control room: System should independently be able to actuate the extinguishing system locally on the tank upon detection of fire without any support from the fire alarm panel in the control room. This feature should be of de-centralized and independent for each tank. CASE 3: Failure / cut of any or all signal cables communicating to / from tank to control room or vice versa: The system should have the feature whereby it would still remain functional locally on the tank i.e. detect fire, give alarm (actuation signal) locally and actuate the extinguishing system. Cable fault signal should be displayed on the fire alarm panel in control room. CASE 4: Failure of detection system installed on the tank The system should give detection fault alarm signal at fire alarm panel. CASE 5: Leakage / damage in detection Tube: Fault indication / alarm should be displayed on the fire alarm panel CASE 6: Pressure in the Foam module low: Low module pressure indication & alarm should be displayed on the fire alarm panel.

TECHNICAL SPECIFICATIONS:

TECHNICAL SPECIFICATIONS: TECHNICAL SPECIFICATIONS: SUPPLY, INSTALLATION & COMMISSIONING OF AUTOMATIC ACTUATED RIM SEAL FIRE DETECTION & FOAM BASED FIRE EXTINGUISHING SYSTEM AS PER OISD-117 FOR EXTERNAL FLOATING ROOF STORAGE TANKS

More information

TENDER CRFQ NO (E-TENDER REF NO.13020)

TENDER CRFQ NO (E-TENDER REF NO.13020) ADDENDUM NO:2 AGAINST TENDER FOR DESIGN, ENGINEERING, SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND POST WARRANTY AMC OF RIM SEAL FIRE PROTECTION SYSTEM FOR BPCL- MUMBAI REFINERY (BPCL MR) TENDER CRFQ

More information

CORRIGENDUM NO: 2 TO REQUEST FOR QUOTATION CRFQ NO E-Tender Ref. No: 9093

CORRIGENDUM NO: 2 TO REQUEST FOR QUOTATION CRFQ NO E-Tender Ref. No: 9093 CPO (REFINERIES) DESIGN, ENGINEERING, SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND POST WARRANTY AMC OF RIM SEAL FIRE PROTECTION SYSTEM FOR BPCL-MUMBAI REFINERY (BPC CL MR) CORRIGENDUM NO: 2 TO REQUEST

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System pg. 1 INTRODUCTION : HPCL is in the process of procurement of Water mist

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

Annexure - 1. Detectors: Fire Alarm Control Panel :

Annexure - 1. Detectors: Fire Alarm Control Panel : Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP),

More information

Size and rating wise typical Third Party Inspection certificates for the models of Valves

Size and rating wise typical Third Party Inspection certificates for the models of Valves For Item code star ting w i th 15 & 1 6 Control Valves: Supply references for valves supplies, for last three years, as per format A,B,C available in Annexure XVI (duly notarized/certified by statutory

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Part: I TECHNICAL SPECIFICATION

Part: I TECHNICAL SPECIFICATION Part: I TECHNICAL SPECIFICATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR THE WORK OF DESIGN, SUPPLY, ERECTION AND COMMISSIONING INCLUDING CIVIL WORK OF NITROGEN INJECTION

More information

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No.

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No. Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi -110003, Ph. No. 011-49854100 TENDER NOTICE Sealed tender in two separate bids a) Technical bids,

More information

RIM SEAL SYSTEMS E-BOOK

RIM SEAL SYSTEMS E-BOOK RIM SEAL SYSTEMS E-BOOK RIM SEAL SYSTEMS Rim Seal floating roof tank fires represent one of the most dangerous threats for chemical and petrochemical storage farms. Industry data base shows that the oil

More information

Survey of electrical equipment installed in hazardous areas on tankers

Survey of electrical equipment installed in hazardous areas on tankers (June 2015) Survey of electrical equipment installed in hazardous areas on tankers 1. Application The recommendations in this document apply for survey of electrical installation in hazardous areas on

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

Scope of Work and Other Terms & Conditions

Scope of Work and Other Terms & Conditions Annexture-II Scope of Work and Other Terms Conditions Sl. 1. Removal Disconnection (i) Removal of existing heating elements, insulation brickwork of the side walls, roof, the doors and the bogie hearth.

More information

SCOPE OF SUPPLY SUPPLY OF H2S ANALYZER

SCOPE OF SUPPLY SUPPLY OF H2S ANALYZER H2S Analyzer SCOPE OF SUPPLY SUPPLY OF H2S ANALYZER Scope of supply-h2s analyzer Page 1 of 9 SCOPE OF WORK 1.0 Introduction The Scope of work covers the following which includes Procurement of 3 H2S analyzers

More information

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas.

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Requirement under Rule 102 of the Petroleum Rules, 2002 lays down that no electrical wiring shall be installed and no electrical

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

Portable Banner Welder JC-2000-GM User Manual

Portable Banner Welder JC-2000-GM User Manual Portable Banner Welder JC-2000-GM User Manual i. Applications It can be applicable for welding PVC-P PE TPO ECB CSPE EPDM PVDF and other Coated fabric covering, foil and homogeneous or coating sealing

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations and with the International Convention

More information

NUCLEAR POWER CORPORATION OF INDIA LIMITED (A Government of India Enterprise)

NUCLEAR POWER CORPORATION OF INDIA LIMITED (A Government of India Enterprise) (A Government of India Enterprise) 2 X 1000 MWe KUDANKULAM NUCLEAR POWER PROJECT UNITS-1&2 TECHNICAL SPECIFICATI FOR PORTABLE FIRE EXTINGHISHERS Number of the Document I02 KK12 0 SGA TH TS P01 Title Total

More information

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GETCO/ENGG/TS/

More information

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup

More information

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer Annexure-4 TECHNICAL SPECIFICATIONS FOR NITROGEN INJECTION FIRE PREVENTION AND EXTINGUISHING SYSTEM FOR OIL

More information

The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2

The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2 The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2 Presented by: Bob Whiteley Engineering & Standards Manager Tyco Fire & Integrated Solutions Ltd Convenor CEN/TC191/WG2

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

E-17 Flammable Gas Detection and Alarm System

E-17 Flammable Gas Detection and Alarm System Guideline No.E-17 (201705) E-17 Flammable Gas Detection and Alarm System Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

Certificate of Conformity Certificate num. Registration date Version Valid until

Certificate of Conformity Certificate num. Registration date Version Valid until CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, Sapphire, engineered, total flooding

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

TENDER DOCUMENT FOR SUPPLY OF EPOXY MIXING & POURING PLANT

TENDER DOCUMENT FOR SUPPLY OF EPOXY MIXING & POURING PLANT BHARAT HEAVY ELECTRICALS LTD., CORPORATE R&D DIVISION VIKAS NAGAR, HYDERABAD-500093 (INDIA) Enquiry : Date : PURCHASE SECTION TECHNICAL SECTION SPEC.NO. 91 40 2377 8474 PHONE 91 40 2377 4494 Ext.7326 ST:ICH:08:001

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1100X December 2017 Page 1 of 14 AE-FP-001-IN-R5-E-12/17 This document is intended to provide

More information

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS SPECIFICATIONS FOR LV DIGITAL PANEL METERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

NET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300

NET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300 NET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300 PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent applicable. The publications

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150 Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1150 April 2018 Page 1 of 14 AE-FP-005-IN-R1-E-04/18 This document is intended to provide

More information

TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems

TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems A TOUGH SOLUTION FOR TOUGH FIRES No fire should be taken lightly. Yet, there are some that go far beyond a typical fire. These extremely hazardous

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:

More information

DRY BULK HANDLING SYSTEM

DRY BULK HANDLING SYSTEM DRY BULK HANDLING SYSTEM Parson Marine Equipment is established in Singapore since July 2005. Our team of engineers have more than 25 years of experiences in providing customised integrated dry and wet

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Newport Business Park New Port Road Ellesmere Port CH65 4LZ United Kingdom Contact:

More information

NOTICE INVITING TENDER

NOTICE INVITING TENDER NOTICE INVITING TENDER Ref No.: SCOPEMINAR/MMO/18-19/183 Dated :- 06.12.2018 1. Online e-tenders are invited by Dy.General Manager, SCOPE on behalf of Constituents of SCOPE MINAR, Laxmi Nagar Delhi- 110092

More information

Eligibility Criteria for Participation [Qualification Requirement (QR)]

Eligibility Criteria for Participation [Qualification Requirement (QR)] Eligibility Criteria for Participation [Qualification Requirement (QR)] 1. Only Manufacturers are eligible to Quote: a) Original manufacturers of High Voltage Detector in India will be eligible in the

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

Fiber Optic Cable Fence Disturbance Sensor

Fiber Optic Cable Fence Disturbance Sensor Architectural & Engineering Specification for Fiber Optic Cable Fence Disturbance Sensor Purpose of document This document is intended to provide performance specifications and operational requirements

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

THE FUTURE OF FIRE SUPPRESSION

THE FUTURE OF FIRE SUPPRESSION THE FUTURE OF FIRE SUPPRESSION MUSTER II LEADING EDGE FIRE SUPPRESSION TECHNOLOGY OUR MISSION At MusterFire International we re passionate about protecting your people and your assets from the inherent

More information

Hospitals and Major Medical Centers

Hospitals and Major Medical Centers Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

GAS FLOODING SYSTEM FOR CIFF AT BASEMENT

GAS FLOODING SYSTEM FOR CIFF AT BASEMENT CONSTRUCTION OF BUILDINGS FOR LABORATORIES AND ASSOCIATED FACILITIES INSTEM BANGALORE SCHEDULE OF QUANTITIES FOR (EQUIPMENT ROOM 3 & 4) Sl.No. Description Unit Quantity Rate (in INR) in figure HFC-227ea

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

TITLE: SPECIFICATION NO. PE-MSE-VD-ACC VOLUME:

TITLE: SPECIFICATION NO. PE-MSE-VD-ACC VOLUME: (For Vendor Registration Purpose) SHEET 1 of 6 1.00.00 GENERAL INFORMATION 1.01.00 The general guidelines as illustrated in the subsequent clauses of this section shall be applicable for air cooled condenser

More information

Hazardous goods management Latest trends in petroleum industry. C. Sasi Assistant Vice President Total LPG India Limited

Hazardous goods management Latest trends in petroleum industry. C. Sasi Assistant Vice President Total LPG India Limited Hazardous goods management Latest trends in petroleum industry C. Sasi Assistant Vice President Total LPG India Limited Buncefield UK (HOSL) - December 11, 2005 Training Behaviour SMS LOPA Risk Analysis

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS

EED SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS EED- 50-23 SPECIFICATIONS OF ADDRESSABLE AUTOMATIC FIRE DETECTION SYSTEM FOR NAVAL SHIPS ISSUING AUTHORITY DIRECTORATE OF ELECTRICAL ENGINEERING INTEGRATED HEADQUARTERS MOD (N) NEW DELHI 110011 2 RECORD

More information

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website:

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website: 7638 Standish Place Derwood, MD 20855 Tel: (301) 760-4016 Fax: (301) 762-2253 Page 1 of 12 Website: www.rbtec.com E-Mail: info@rbtec.com Purpose The purpose of this document is to provide performance specifications

More information

Technical Data Sheet No. JS-SM-40 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER

Technical Data Sheet No. JS-SM-40 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER PAGE: ISSUE: DATE: of A 00 07285 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER MODELS: R2WC 0 07285 ISSUE A FIRST RELEASE NEW DOCUMENT WJJ LRL LHG REV DATE REVISION DESCRIPTION

More information

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd.   Web:  ISO 9001:2015 certified Linear detection solution Product Brochure About Us Signaline is a comprehensive range of linear detection systems providing solutions for fire and water leak detection. Our linear detectors are 100% manufactured

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

LINEAR HEAT SENSING DETECTION. System Sensor India 2014

LINEAR HEAT SENSING DETECTION. System Sensor India 2014 LINEAR HEAT SENSING DETECTION VJ System Sensor India 2014 Linear Heat Sensing Cable: LINEAR - Across the Length HEAT - Heating of Cable SENSOR - Detector LHS Cable - Cable capable of detecting heating

More information

STANDARD TECHNICAL SPECIFICATION FOR PRESSURE SWITCH, DIFFERENTIAL PRESSURE SWITCH VOLUME - IIB. SPECIFICATION No: PES

STANDARD TECHNICAL SPECIFICATION FOR PRESSURE SWITCH, DIFFERENTIAL PRESSURE SWITCH VOLUME - IIB. SPECIFICATION No: PES STANDARD TECHNICAL SPECIFICATION FOR PRESSURE SWITCH, DIFFERENTIAL PRESSURE SWITCH VOLUME - IIB SPECIFICATION No: PES-145-031 BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECT ENGINEERING MANAGEMENT

More information

Transforming Challenges with Expertise. Total Protection. from concept to commissioning

Transforming Challenges with Expertise. Total Protection. from concept to commissioning Transforming Challenges with Expertise Total Protection from concept to commissioning About us FIRETECH is a leading Indian company in the field of Fire suppression technologies, with Best in Class Specification

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION DET-TRONICS SPECIFICATION DATA Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION The EQ2200UVHT UV Flame Detector is used with the Eagle Quantum

More information

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING Chapter 30 FIRE-FIGHTING This Chapter discusses events which may follow cargo spillage and the procedures which can be adopted to protect life and property in such circumstances. It also describes the

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.14 Control Number: A.0 Effective Date: 9/14/11 TITLE:

More information

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI FIRE PROTECTION 1 G.I.PIPES Supplying, installing, testing and commissioning of G.I Pipes confirming to IS 3589 Pt - I Heavy grade with painting, suitable type of supports, anchor fasteners, bolts nuts

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Material Description Quantity UOM

Material Description Quantity UOM Page : 1 / 5 OIL INDIA LIMITED Fax-0291 2727050 (A Govt. of India Enterprise) Ph-0291 2727048 Rajasthan Project, 02-A,SARASWATI NAGAR, Email: mat_rp@oilindia.in DISTRICT SHOPPING CENTRE, BASNI JODHPUR-

More information

TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC

TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC 1.0 SCOPE: MGVCL / PP /5013/HT AMR BOX TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC 1.1 This specification covers the design, manufacturing and testing of anticorrosive,

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL GASGUARD LEL 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL GasGuard LEL 3 Operating and Installation Manual 2 Table of Contents 3GasGuard LEL Operating and Instruction Manual General description. 4

More information

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING MODEL ZAC-32 32 ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING 32 HARD WIRED ZONES CAN BE NORMALLY-OPEN OR NORMALLY-CLOSED ZONE WIRING RUNS CAN BE AS FAR AS 10,000 FEET FROM

More information

Explosion Protection Engineering Principles

Explosion Protection Engineering Principles Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD

More information

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS RESOLUTION MSC.292(87) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, NOTING resolution MSC.98(73)

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

contents iii Drilling Tools 27 Adjustable Choke 27 Automatic Drillers 29 MWD and LWD Tools 30 How They Work 30 Uses 30

contents iii Drilling Tools 27 Adjustable Choke 27 Automatic Drillers 29 MWD and LWD Tools 30 How They Work 30 Uses 30 Figures v Foreword ix Acknowledgments xi Units of Measurement xii Introduction 1 Pipe Handling Equipment 3 Kelly Spinners 3 Maintenance 6 Spring Slips and Power Slips 7 Maintenance 9 Automatic Pipe Handlers

More information

Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements

Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements AUTOMOTIVE INDUSTRY STANDARD Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements PRINTED BY THE AUTOMOTIVE RESEARCH ASSOCIATION OF INDIA P.B.

More information

PIP PCTPA001 Testing of Process Analyzer Systems

PIP PCTPA001 Testing of Process Analyzer Systems January 2016 Process Control PIP PCTPA001 Testing of Process Analyzer Systems PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

ALARMLINE ANALOGUE Linear Heat Detection System

ALARMLINE ANALOGUE Linear Heat Detection System ALARMLINE ANALOGUE Linear Heat Detection System Alarmline Analogue cable senses temperature variations by continuously monitoring the resistance of specially doped Negative Temperature Coefficient (N.T.C.)

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

Installation of Glass Lined Equipment

Installation of Glass Lined Equipment Installation of Glass Lined Equipment Information given herein is for guidance only and may not be complete. It is important that only trained and competent personnel are permitted to handle glass lined

More information

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 FCA-150 Carbon Steel Construction INLET SIZE WORKING PRESSURE FCA-S 65, FCA-S 80 & FCA-S 100, FCA-S 150 Stainless

More information