AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-02A(5BPU0-01A)

Size: px
Start display at page:

Download "AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-02A(5BPU0-01A)"

Transcription

1 AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-02A(5BPU0-01A)

2 AIR-TO-WATER HEAT PUMP (50Hz/R410A)

3 CONTENTS Part 1. Introduction Part 2. Indoor Unit(Hydro kit) Part 3. Outdoor Unit Part 4. Accessories

4 Guide Revision History Pub. No. Frequency Type Product name Refrigerant Models Notes Published in 5BPU0-01A 50Hz Air to Water Heat Pump Therma V R410A AHUW096A1 (HU091 U41) AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) New edition of EPDB (Preliminary Version) July BPU0-02A 50Hz Air to Water Heat Pump Therma V R410A AHUW126A1 (HU121 U31) AHUW146A1 (HU141 U31) AHUW166A1 (HU161 U31) Added outdoor unit model April Air-to-Water Heat Pump _ 3

5 Part 1. Introduction 1. System Configuration 2. System Layout 3. Features 4. Advantages & Benefits 5. System Application Schematic Examples

6 1. System Configuration LG Supply Indoor Unit(Hydro kit) Outdoor Unit Introduction Radiator or Sanitary tank(only) or Sanitary tank + Solar heat source Fan coil unit Under floor pipe Field supply Refer to the installation manual regarding various applications in detail Air-to-Water Heat Pump _ 1

7 2. System Layout Introduction Outdoor Unit Refrigerant (R410A) Indoor Unit (Hydro kit) Water 9kW Hydro kit 12/14/16kW Heat exchange between Refrigerant and Water Internal electric heater Boiler can be interlocked Sanitary water tank (+ Solar heat source) Floor Heating Radiator or Fan coil unit Sanitary water tank Solar heat source Under floor pipe Radiator Fan coil unit Refer to the installation manual regarding various applications in detail 2 _ Air-to-Water Heat Pump

8 3. Features 3.1 Indoor Unit (Hydro kit) Compact & light weight Design Compact Size 850 x 490 x 315(H x W x D) Deluxe Design with Painted Cabinet 490mm 850mm 315mm Deluxe Controller Deluxe Controller Emergency Operation Mode Easy interface with Solar Thermal Central Control Weekly programmable 3rd Party Accessory Interface Ready to interface with 230V AC Thermostat (Heating-only or Cooling/Heating) Ready to interface with 24V AC Thermostat (Heating-only or Cooling/Heating) Ready to interface with 230V AC 3way valve (type : 3wire SPDT) Ready to interface with 230V AC 2way valve (type : 2wire Normal Open or 2wire Normal Closed) Ready to interface with 230V AC Thermal Switch High COP Plates Heat Exchanger High Reliability LG AC Smart Control Introduction 3.2 Outdoor Unit Inverter Control Heating / Cooling capacity variation Compact Design & Ez Control Compact Design Fuzzy control PFC step-up Technology Soft operation by sine wave BLDC Fan Motor Control High Efficiency fan & Grille High volume axial fan makes powerful cooling & Maintains system stable. Inner SVC Valve & Handle 4 pcs of Moving handle (for easy moving) 4 Way piping is possible (Front, Rear, Right, Down) Air-to-Water Heat Pump _ 3

9 4. Advantages & Benefits 4.1 High Efficiency Energy Efficiency Comparison 4.2 More Economical Nominal Price per Barrel Introduction Energy Efficiency Factor More than 4 times Max 4.5 The Increasing burden of maintaining the oil boiler on users. 0.8~0.9 Other Heating System (Electric Heater, Boiler) COP Comparison A Company *16kW Model Heating COP kW 12kW 14kW 16kW 4 _ Air-to-Water Heat Pump

10 4. Advantages & Benefits Central Control Introduction Air-to-Water Heat Pump VRF System Heat recovery Ventilation system Air-to-Water Heat Pump _ 5

11 4. Advantages & Benefits Emergency Control Easy checking of system failure Introduction Slight trouble Heavy trouble - Slight / Heavy trouble Emergency operating - Heavy trouble - Electric heater ON - Secure at least heating before A/S Easy Setting Feature Water Inlet temp. Water Outlet temp. Water Tank temp. Space temp. Solar Heating temp. Indoor temp. or Water temp. (Optional temp. setting) 6 _ Air-to-Water Heat Pump

12 4. Advantages & Benefits Controller Configuration 1 Display Panel Change Temperature Button Silent Mode On / Off Button Mode Selection Button Water Heating Enable / Disable Button ESC Button Introduction Direction Button (Up, Down, Left, Right) Power Button Function Setting Button Temperature Setting Mode Button Temperature View Mode Button Programming Button Set / Clear button Display Panel Cooling Heating Weather-dependent Heating Space Temp. Water Inlet Temp. Water Outlet Temp. Central Controller Thermostat Electric Heater (1) Electric Heater (2) Water Tank Electric Heater Water Pump Solar Heating Pump Water Tank Heating Enable / Disable Water Tank Heating (by Heat Pump) Silent Mode ON / OFF Water Tank Temp. Solar Heating Temp. Defrost Water-Pipe Anti-Freezing Water Tank Disinfection Outdoor Unit Child Lock Not Available Function Slight Trouble Heavy Trouble Air-to-Water Heat Pump _ 7

13 4. Advantages & Benefits Introduction 4.3 More Ecological Background for EU regulations... A. To preserve, protect and improve the quality of the environment, protect human health and utilise natural resources prudently and rationally B. Basic principle = preventive action, environmental damage should be rectified at source and the polluter should pay C. If waste cannot be avoided, it should be reused or recovered for its material or energy. LGE Environmental Policy ; LG Electronics has finalized the development strategy with the following goals to develop eco-friendly products to meet a range of environmental challenges and secure Advanced production technology 3 key Eco-design strategies LGE RoHS management ; Declared eliminating the six hazardous substances specified in the EUʼs RoHS Directive (Pb, Cd, Cr6+, HG, PBBs, PBDEs) from all LGEʼs products in July * RoHS : Restriction of Hazardous Substances LGE ECO-friendly Activity ; We are operating a special lab for analyzing Hazardous substance. - Fully equipped with precision analysis instruments such as ICP, IC, GC-MS, FR-IR - Developed and standardized methods to analyze and test hazardous substance - Certified as an official lab by the UL (Underwriters Laboratories) in February 2005, and by TÜV Rheinland in May Participating in the assessment done by external organizations - Enhancing the reliability of internal analysis through regular assessment of skills, education, workshops and six sigma activities 8 _ Air-to-Water Heat Pump

14 5. System Application Schematic Examples 5.1 Connecting Heat Emitters for Heating and Cooling (Under floor loop, Fan Coil Unit, and Radiator) Outdoor Unit Outdoor Indoor Indoor Unit Introduction NOTE Fan coil unit Floor heating loop Radiator Room thermostat - Type of thermostat and specification should be complied with chapter 4 and chapter 7 of THERMA V installation manual. 2way control valve - It is important to install 2way control valve to prevent dew condensation on the floor and radiator while cooling mode. - Type of 2way control valve and specification should be complied with chapter 4 and chapter 7 of THERMA V installation manual. - 2way valve should be installed at the supply side of the collector. By-pass valve - To secure enough water flow rate, by-pass valve should be installed at the collector. - By-pass valve should guarantee minimum water flow rate in any case. Minimum water flow rate is described in water pump characteristics curve. High Temperature Low Temperature Shut-off valve Room Thermostat(Field supply) 2way control valve(field supply) By-pass valve(field supply) CAUTION If is installed with pre-existing boiler, the boiler and should not be operated together. If entering water temperature of is above 55 C, the system will stop operation to prevent mechanical damage of the product. For detailed electric wiring and water piping, please contact authorized installer. Some installation scenes are presented for example. As these scenes are conceptual figures, installer should optimize the installation scene according to the installation conditions. Air-to-Water Heat Pump _ 9

15 5. System Application Schematic Examples 5.2 Connecting Sanitary Water Tank Introduction Outdoor Unit Outdoor Indoor Indoor Unit Fan coil unit Floor heating loop Radiator Hot water City water Sanitary water tank NOTE Sanitary water tank - It should be equipped with internal electric heater to generate sufficient heat energy in very cold season. 3way control valve - Type of 3way control valve and specification should be complied with chapter 4 and chapter 7 of installation manual. High Temperature Low Temperature Shut-off valve Room Thermostat(Field supply) 2way control valve(field supply) By-pass valve(field supply) 3way control valve (Field supply) CAUTION If is installed with pre-existing boiler, the boiler and should not be operated together. If entering water temperature of is above 55 C, the system will stop operation to prevent mechanical damage of the product. For detailed electric wiring and water piping, please contact authorized installer. Some installation scenes are presented for example. As these scenes are conceptual figures, installer should optimize the installation scene according to the installation conditions. 10 _ Air-to-Water Heat Pump

16 5. System Application Schematic Examples 5.3 Connecting Solar thermal system Outdoor Unit Outdoor Indoor Indoor Unit Introduction Solar heat source Fan coil unit Floor heating loop Radiator Hot water Sanitary water tank City water NOTE Sanitary water tank - It should have additional indirect heat exchanger to utilize heat energy by solar thermal system. Pump - Maximum power consumption of pump should be less than 0.25kW. High Temperature Low Temperature Shut-off valve Room Thermostat(Field supply) 2way control valve (Field supply) By-pass valve(field supply) 3way control valve (Field supply) Pump(Field supply) CAUTION If is installed with pre-existing boiler, the boiler and should not be operated together. If entering water temperature of is above 55 C, the system will stop operation to prevent mechanical damage of the product. For detailed electric wiring and water piping, please contact authorized installer. Some installation scenes are presented for example. As these scenes are conceptual figures, installer should optimize the installation scene according to the installation conditions. Air-to-Water Heat Pump _ 11

17 Part 2. Indoor Unit (Hydro kit) 1. Nomenclature 2. Model Line-up 3. List of Functions 4. Specifications 5. Dimensions 6. Wiring Diagrams 7. External Wiring Diagrams 8. Piping Diagrams 9. Pump Hydraulic Performance

18 1. Nomenclature 1.1 Global Model Name AH N W 16 A 06 A Europe Model Name H N Serial Number Chassis Name Heater Capacity (kw) Ex) 06 : 6kW Class Heater Electrical ratings 6 : 1 phase V 50Hz 8 : 3 phase V 50Hz A : 3 phase 220V 50Hz Heating Capacity (kw) Ex) 16 : 16kW Class Model Type W : DC Inverter Heat Pump H : Heat Pump Classification N : Indoor Unit U : Outdoor Unit - : Set Air-to-Water Heat Pump for R410A Indoor Unit Heater Capacity (kw) Ex) 04 : 4kW Class, 06 : 6kW Class, 09 : 9kW Class Electrical Ratings 1 : 1 Phase V 50Hz 2 : 3 Phase 220V 50Hz 3 : 3 Phase V 50Hz Classification 09 (Combined with 09kW of Outdoor Unit) 16 (Combined with 12/14/16kW of Outdoor Unit) N : Hydro kit (Indoor Unit) H : Air to Water Heat Pump Air-to-Water Heat Pump _ 1

19 2. Model Line-up 2.1 Hydrokit Model Name AHNW09604A1 (HN0914 NK1) AHNW16606A1 (HN1616 NK1) Electric Heater Capacity (kw) Power Source (Electric Heater) 4(2+2) 1Ø, V, 50Hz 6(3+3) 1Ø, V, 50Hz AHNW16A06A1 (HN1626 NK1) AHNW16806A1 (HN1636 NK1) 6(2+2+2) 3Ø, 220V, 50Hz 3Ø, V, 50Hz Indoor Unit AHNW16A09A1 (HN1629 NK1) AHNW16809A1 (HN1639 NK1) 2.2 Outdoor Unit Model Name 9(3+3+3) Capacity Cooling (kw) Heating (kw) 3Ø, 220V, 50Hz 3Ø, V, 50Hz Power Source AHUW096A1 (HU091 U41) AHUW126A1 (HU121 U31) AHUW146A1 (HU141 U31) Φ, V, 50Hz AHUW166A1 (HU161 U31) AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) Φ, V, 50Hz AHUW168A1 (HU163 U31) _ Air-to-Water Heat Pump

20 3. List of Functions Category Installation Reliability Convenience Individual control CAC network function Special function kit Others AWHP Function Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller(control panel) Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control General central controller (Non LGAP) Dry contact Network Soluation(LGAP) PDI(power distribution indicator) PI 485 Zone control CTIE Electro thermostat Remote room temperature sensor (TH8) Anti-Condensation on floor (cooling) Water Pump ON / OFF Control Flow Switch Control Thermostat Interface (230V AC) Thermostat Interface (24V AC) Sanitary Tank Heating Solar-Thermal Interface with Sanitary Tank PHEX Anti-Freezing Control Water Pump Forced Operation Autosetting according to Ambient Temperature Silent Operation Anti-overheating of Water Pipe Emergency Operation AHNW166**A1 (HN161* NK1) AHNW168**A1 (HN163* NK1) AHNW16A**A1 (HN162* NK1) PQDSA PQDSA PQDSA PQRSTA0 PQRSTA0 PQRSTA0 Indoor Unit Notes O : Applied, X : Not applied, : No relation * TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)' * Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. Air-to-Water Heat Pump _ 3

21 3. List of Functions Indoor Unit Category Installation Reliability Convenience Individual control CAC network function Special function kit Others AWHP Function Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller(control panel) Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control General central controller (Non LGAP) Dry contact Network Soluation(LGAP) PDI(power distribution indicator) PI 485 Zone control CTIE Electro thermostat Remote room temperature sensor (TH8) Anti-Condensation on floor (cooling) Water Pump ON / OFF Control Flow Switch Control Thermostat Interface (230V AC) Thermostat Interface (24V AC) Sanitary Tank Heating Solar-Thermal Interface with Sanitary Tank PHEX Anti-Freezing Control Water Pump Forced Operation Autosetting according to Ambient Temperature Silent Operation Anti-overheating of Water Pipe Emergency Operation AHNW09604A1 (HN0914 NK1) - - O - - O O O O O - O PQDSA O PQRSTA0 O O O O O O O O O O O O O Notes O : Applied, X : Not applied, : No relation * TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)' * Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. 4 _ Air-to-Water Heat Pump

22 4. Specifications Indoor Units Nominal Power Input W Nominal Running Current without Electric Heater A Operation Range Cooling(Fan coil unit) C (Min.~Max.) Cooling(Under floor) C Leaving Water Heating(Fan coil unit or Radiator) C Temperature Heating(Under floor) C Pump Type - Steps of Speed EA Power Input W Water Flowrate Limit LPM Heat Exchanger Type - Number of Plate EA Quantity EA Expansion Vessel Volume liter Water Pressure(Max.) bar Water Pressure(Pre) bar Strainer Mesh Size mm Material - Electric Heater Type - Number of Heating Coil EA Capacity Combination kw Operation - Heating Steps Step Power Supply Ø / V / Hz Rated Current A Maximum Current(MCA) A Water Circuit Safety Valve bar Entering Side Diameter inch Leaving Side Diameter inch Manometer - Drain Valve / Fill Valve - Shut Off Valve - Air Vent - Refrigerant Circuit Gas Side Diameter mm(inch) Liquid Side Diameter mm(inch) Dimensions Unit(H x W x D) mm Packed Unit(H x W x D) mm Weight Unit kg (Without water) Packed Unit kg Sanitary Water Tank Type - Heater Capacity kw Power Supply Ø / V / Hz Power Supply Type - Thermal Protector Range C Relay Contactor - ELB A Sensor Adaptor Diameter mm(inch) Accessory Kit - AHNW166**A1 (HN161* NK1) AHNW168**A1 (HN163* NK1) AHNW16A**A1 (HN162* NK1) ~ 30 6 ~ 30 6 ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 55 Canned type for hot water circulation 2 (In Max. / Med. / Min., Min. step is not used) At least 15.0 At least 15.0 At least 15.0 Brazed Plate HEX Brazed Plate HEX Brazed Plate HEX x 1 1 x 1 1 x 1 Stainless Steel Stainless Steel Stainless Steel Sheath Sheath Sheath or 9 6 or 9 Automatic Automatic Automatic / / 50 3 / / 50 3 / 220 / Male PT 1 Male PT 1 Male PT 1 Male PT 1 Male PT 1 Male PT (5/8) (5/8) (5/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 850 x 490 x x 490 x x 490 x x 563 x x 563 x x 563 x Indirect heating(+ Electric heater) Max. 3 1 / 230 / 50 Separated power source Max. 90 Needed (1/2) LG Supply(model : PHLTA) Indoor Unit Note : 1. The specification may be subject to change without prior notice for purpose of improvement. Air-to-Water Heat Pump _ 5

23 4. Specifications Indoor Unit Indoor Units Nominal Power Input W Nominal Running Current without Electric Heater A Operation Range Cooling(Fan coil unit) C (Min.~Max.) Cooling(Under floor) C Leaving Water Heating(Fan coil unit or Radiator) C Temperature Heating(Under floor) C Pump Type - Steps of Speed EA Power Input W Water Flowrate Limit LPM Heat Exchanger Type - Number of Plate EA Quantity EA Expansion Vessel Volume liter Water Pressure(Max.) bar Water Pressure(Pre) bar Strainer Mesh Size mm Material - Electric Heater Type - Number of Heating Coil EA Capacity Combination kw Operation - Heating Steps Step Power Supply Ø / V / Hz Rated Current A Maximum Current(MCA) A Water Circuit Safety Valve bar Entering Side Diameter inch Leaving Side Diameter inch Manometer - Drain Valve / Fill Valve - Shut Off Valve - Air Vent - Refrigerant Circuit Gas Side Diameter mm(inch) Liquid Side Diameter mm(inch) Dimensions Unit(H x W x D) mm Packed Unit(H x W x D) mm Weight Unit kg (Without water) Packed Unit kg Sanitary Water Tank Type - Heater Capacity kw Power Supply Ø / V / Hz Power Supply Type - Thermal Protector Range C Relay Contactor - ELB A Sensor Adaptor Diameter mm(inch) Accessory Kit - MCCB A Note : 1. The specification may be subject to change without prior notice for purpose of improvement. AHNW09604A1 (HN0914 NK1) ~30 16~30 15~55 15~55 Canned type for hot water circulation 2 (In Max. / Med. / Min., Min. step is not used) 135 At least 15.0 Brazed Plate HEX x 1 Stainless Steel Sheath Automatic 2 1 / / Male PT 1 Male PT (5/8) 9.52 (3/8) 850 x 490 x x 563 x Indirect heating(+ Electric heater) Max. 3 1 / 230 / 50 Separated power source Max. 90 Needed (1/2) LG Supply 32 6 _ Air-to-Water Heat Pump

24 5. Dimensions 5.1 Internal [Unit:mm] AWHP AHNW09***A1 (HN09** NK1) AHNW16***A1 (HN16** NK1) No Name Remarks 1 Refrigerant Pipe Ø15.88mm 2 Refrigerant Pipe Ø9.52mm 3 Entering Water Pipe Male PT 1 inch 4 Leaving Water Pipe Male PT 1 inch 5 Control Panel Built-in Remote Controller 6 Water Pump Max Head 7.5 / 6.5 meter 7 Safety Valve Open at water pressure 3 bar 8 8' Thermal switch Thermal switch Cut-off power input to electric heater at 90 centigrade (manual return at 55 centigrade) 9 Control Box PCB and terminal blocks 10 Flow Switch Minimum operation range at 12 LPM 11 Plate Heat Exchanger Heat exchange between refrigerant and water 12 Pressure Gage Indicates circulating water pressure 13 Expansion Tank Absorbing Volume change of heated water 14 Air Vent Air purging when Charging water 15 Electric Heater Additional heating source 16 Strainer 17 Shut-off valve 18 Carrying handle Cut-off power input to electric heater at 90(primary) and 200(secondary) centigrade (auto return at 70 centigrade for first thermal switch) Filtering and stacking particles inside circulating water When connecting water pipes,drain water or block the flow from indoor unit To carry the product Notice : Item 8 and Item 8 will be applied exclusively Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit should be grounded in accordance with the local regulations or applicable national codes. 3. All electrical components and materials to be supplied on the site must comply with the local regulations or international codes. 4. Electrical characteristics chapter should be considered for electrical work and design. Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter. Hydro kit Indoor Unit Air-to-Water Heat Pump _ 7

25 5. Dimensions 5.2 External [Unit:mm] Indoor Unit AWHP AHNW09***A1 (HN09** NK1) AHNW16***A1 (HN16** NK1) No Name Remarks 1 Door Control panel is shown after this door is opened. 2 Handle Used to cover or uncover the front case Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit should be grounded in accordance with the local regulations or applicable national codes. 3. All electrical components and materials to be supplied on the site must comply with the local regulations or international codes. 4. Electrical characteristics chapter should be considered for electrical work and design. Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter. Hydro kit 8 _ Air-to-Water Heat Pump

26 6. Wiring Diagrams AHNW**6**A1 (HN**1* NK1) Indoor Unit Air-to-Water Heat Pump _ 9

27 6. Wiring Diagrams AHNW**A**A1 (HN**2* NK1) AHNW**8**A1 (HN**3* NK1) Indoor Unit 10 _ Air-to-Water Heat Pump

28 7. External Wiring Diagrams AHNW**6**A1 (HN**1* NK1) Indoor Unit Air-to-Water Heat Pump _ 11

29 7. External Wiring Diagrams AHNW**A**A1 (HN**2* NK1) AHNW**8**A1 (HN**3* NK1) 1~ 230V 50Hz M/C 3 MCCB M/C Indoor Unit 3~ 220V 50Hz MCCB M/C 12 _ Air-to-Water Heat Pump

30 8. Piping Diagrams AHNW*****A1 (HN**** NK1) Sanitary water tan k is installed (Sanitary water tan k kit is necessary) Solar thermal syst em is connected (Solar thermal kit i s necessary) Indoor Unit Basic installation (IDU + ODU) Underfloor Heating Radiator Fan Coil Unit Solar Thermal Componets Air-to-Water Heat Pump _ 13

31 8. Piping Diagrams Indoor Unit Category Symbol Meaning PCB Connector Remarks TH1 Refrigerant temperature sensor (Gas side) CN_PIPE/OUT Indoor Unit Water Heating Solar Heating TH2 TH3 TH4 TH5 F/S E/HT W_PUMP1 EXP/TANK TH8 CTR/PNL 2WAY V/V_1 W/TANK B/HT 3WAY V/V_1 CITY WATER SHOWER TH6 TH7 3WAY V/V_2 W_PUMP/2 SOLAR THER- MAL SYSTEM Refrigerant temperature sensor (Liquid side) Entering Water temperature sensor Interim Water temperature sensor Leaving Water temperature sensor Flow Switch Electric Heater Internal Water Pump Expansion Tank Remote Air temperature sensor Control Panel (or Remote Controller ) To control water flow for Fan Coil Unit Sanitary Water Tank Electric Heater - Flow control for water which is leaving from indoor unit. - Flow direction switching between underfloor and water tank Water to be heated by Indoor unit and B/HT of W/TANK Water supplied to end-user W/TANK water temperature sensor Solar-heated water temperature sensor - Flow control for water which is heated and circulated by SOLAR THERMAL SYSTEM. - Flow direction switching between SOLAR THERMAL SYSTEM and W/TANK External Water Pump - This system can include following components : Solar panel, Sensors, Thermostats, Interim heat exchanger, Water pump, etc. - To utilized hot water heated by SOLAR THERMAL SYSTEM, end-user must by LG AWHP Solar-Kit. CN_PIPE CN_TH3 CN_FLOW1 CN_E/HEAT(A) CN_E/HEAT(B) CN_W/PUMP(A) (no connector) CN_ROOM CN_REMO CN_2WAY(A) (no connector) CN_B/HEAT(A) CN_3WAY(A) (no connector) (no connector) CN_TH4 CN_3WAY(B) CN_W/PUMP(B) (no connector) - Meaning is expressed based on Cooling mode. - TH3, TH4, and TH5 are connected at 6 pin type connector CN_TH3. - Heating capacity is divided into two level : partial capacity by E/HEAT(A) and full capacity by E/HEAT(A) + E/HEAT(B). - Operating power(230v AC 50Hz) of E/HEAT(A) and E/HEAT(B) are supplied by external power source via relay connector and ELB. - Operating power(230v AC 50Hz) of internal water pump is supplied by the connector. - Absorb volume change of heated water, - Optional accessory (sold separately) - Model : PQRSTA0 - Pre built-in at indoor unit - 3rd party accessory and Field installation (sold separately) - 2wire NO or NC type 2way valve is supported. - 3 rd party accessory and Field installation (sold separately) - Generating and storing sanitary hot water by AWHP or built-in electric heater- - 3 rd party accessory and Field installation (usually built-in at W/TANK) - Supplying additional water heating capacity. - 3 rd party accessory and Field installation (sold separately) - SPDT type 3way valve is supported. - Field installation - Field installation - TH6 and TH7 are connected at 4 pin type connector CN_TH4. - TH6 is a part of sanitary water tank kit. (model: PHLTA) - TH7 is a part of solar thermal kit (model: PHLLA) - 3 rd party accessory and Field installation (sold separately) - SPDT type 3way valve is supported. - 3 rd party accessory and Field installation (sold separately) - If water pump of SOLAR THERMAL SYSTEM is incapable of circulation,external water pump can be used. - 3 rd party accessory and Field installation (sold separately) 14 _ Air-to-Water Heat Pump

32 9. Pump Hydraulic Performance 9.1 Static Pressure Drop Model : AHNW09***A1 (HN09** NK1) Hydraulic Head Loss(mH2O) Med. 1.5 Max Water Flowrate(l/min) Indoor Unit Model : AHNW16***A1 (HN16** NK1) Hydraulic Head Loss(mH2O) Max. : high speed setting Med. : low speed setting Max. Med Water Flowrate(l/min) Warning : Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit. : Operation cutoff range Air-to-Water Heat Pump _ 15

33 Part 3. Outdoor Unit 1. Nomenclature 2. List of Functions 3. Specifications 4. Dimensions 5. Wiring Diagrams 6. Piping Diagrams 7. Performance Data 8. Capacity Correction Factor 9. Operation Range 10. Noise Criteria

34 1. Nomenclature 1.1 Global Model Name AH N W 16 A 06 A 1 Serial Number Chassis Name Heater Capacity (kw) Ex) 06 : 6kW Class Heater Electrical ratings 6 : 1 phase V 50Hz 8 : 3 phase V 50Hz A : 3 phase 220V 50Hz Heating Capacity (kw) Ex) 16 : 16kW Class Model Type W : DC Inverter Heat Pump H : Heat Pump Classification N : Indoor Unit U : Outdoor Unit - : Set Air-to-Water Heat Pump for R410A 1.2 Europe Model Name H N Heater Capacity (kw) Ex) 04 : 4kW Class, 06 : 6kW Class, 09 : 9kW Class Electrical Ratings 1 : 1 Phase V 50Hz 2 : 3 Phase 220V 50Hz 3 : 3 Phase V 50Hz Classification 09 (Combined with 09kW of Outdoor Unit) 16 (Combined with 12/14/16kW of Outdoor Unit) N : Hydro kit (Indoor Unit) H : Air to Water Heat Pump Outdoor Unit Air-to-Water Heat Pump _ 1

35 2. List of Functions Category Reliability Convenience CAC network function Function Defrost / Deicing High pressure switch Low pressure switch Phase protection Restart delay (3-minutes) Self diagnosis Soft start Test function Auto operation(artificial intelligence) Auto restart operation Network soluation(lgap) PDI(Power Distribution Indicator) PI485 Special function kit Low ambient operation Others Thermistor AWHP Sanitary Tank Heating Silent Operation Emergency Operation AHUW096A1 (HU091 U41) AHUW126A1 (HU121 U31) AHUW146A1 (HU141 U31) AHUW166A1 (HU161 U31) O O O O O O PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A O O O Outdoor Unit Reliability Convenience Category CAC network function Special function kit Others AWHP Function Defrost / Deicing High pressure switch Low pressure switch Phase protection Restart delay (3-minutes) Self diagnosis Soft start Test function Auto operation(artificial intelligence) Auto restart operation Network soluation(lgap) PDI(Power Distribution Indicator) PI485 Low ambient operation Thermistor Sanitary Tank Heating Silent Operation Emergency Operation AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) PMNFP14A0 PMNFP14A0 PMNFP14A Notes O : Applied, X : Not applied, : No relation * Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. 2 _ Air-to-Water Heat Pump

36 3. Specifications Outdoor Units Power Supply Ø / V / Hz Maximum Running Cooling A Current Heating A Wiring Connections For Power Supply (Included Earth) Number of wires For Connection with Indoor Unit (Included Earth) Number of wires * Capacity Cooling(A35/W18) kw Heating(A7W35) kw * Power Input Cooling(A35/W18) kw Heating(A7W35) kw * EER Cooling(A35/W18) W/W COP Heating(A7W35) W/W Operation Range(Min.~Max.) Cooling C DB Outdoor Temperature Heating C DB Compressor Type - Model - Quantity EA Displacement cm 3 /Rev. Capacity kw Compressor Motor Type - Quantity EA Rated Output W Refrigerant Type - Charge g(oz) Control - Refrigerant Oil Type - Charged Volume cc Heat Exchanger Quantity EA Rows EA Columns EA FPI Fins/inch Fan Type - Quantity EA Air Flow Rate CMM(l/s) Fan Motor Model - Quantity EA Output W Sound Pressure Cooling db(a)±3 Level Heating db(a)±3 Liquid Piping Type - Connection Outer Diameter mm(inch) Gas Piping Type - Connection Outer Diameter mm(inch) Piping Length Minimum m (Outdoor Unit ~ Standard m Indoor Unit) Maximum m Height Difference (Outdoor Unit ~ Indoor Unit) Maximum m Additional Refrigerant Charge g/m Dimensions Unit(W x H x D) mm Packed Unit(W x H x D) mm Weight Unit kg Packed Unit kg AHUW096A1 (HU091 U41) AHUW126A1 (HU121 U31) 1 / / 50 1 / / , , ~48 5 ~ 48-20~30-20 ~ 30 Hermetic Motor Hermetic Motor GJT240DAA Note : 1. Capacities and power inputs are based on the following conditions: * : Cooling conditions - Indoor Water Temperature 23 C/18 C; Outdoor Air Temperature 35 CDB/24 CWB Heating conditions - Indoor Water Temperature 30 C/35 C; Outdoor Air Temperature 7 CDB/6 CWB Standard piping length 7.5m 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement. GPT425DBA Brushless Brushless 1 1 1,700 4,000 R410A R410A 1,900(67.0) 2,850(100.5) Electronic Expansion Valve Electronic Expension Valve FVC68D FVC68D 900 1, Propeller Propeller (1,000) 60(1,000) SIC-72FW-F SIC-72FW-F Flare Flare 9.52(3/8) 9.52(3/8) Flare Flare 15.88(5/8) 15.88(5/8) x 834 x Χ 1,380 Χ 330 1,140 x 900 x 461 1,140 Χ 1,462 Χ Outdoor Unit Air-to-Water Heat Pump _ 3

37 3. Specifications Outdoor Unit Outdoor Units Power Supply Ø / V / Hz Maximum Running Cooling A Current Heating A Wiring Connections For Power Supply (Included Earth) Number of wires For Connection with Indoor Unit (Included Earth) Number of wires * Capacity Cooling(A35/W18) kw Heating(A7W35) kw * Power Input Cooling(A35/W18) kw Heating(A7W35) kw * EER Cooling(A35/W18) W/W COP Heating(A7W35) W/W Operation Range(Min.~Max.) Cooling C DB Outdoor Temperature Heating C DB Compressor Type - Model - Quantity EA Displacement cm 3 /Rev. Capacity kw Compressor Motor Type - Quantity EA Rated Output W Refrigerant Type - Charge g(oz) Control - Refrigerant Oil Type - Charged Volume cc Heat Exchanger Quantity EA Rows EA Columns EA FPI Fins/inch Fan Type - Quantity EA Air Flow Rate CMM(l/s) Fan Motor Model - Quantity EA Output W Sound Pressure Cooling db(a)±3 Level Heating db(a)±3 Liquid Piping Type - Connection Outer Diameter mm(inch) Gas Piping Type - Connection Outer Diameter mm(inch) Piping Length Minimum m (Outdoor Unit ~ Standard m Indoor Unit) Maximum m Height Difference (Outdoor Unit ~ Indoor Unit) Maximum m Additional Refrigerant Charge g/m Dimensions Unit(W x H x D) mm Packed Unit(W x H x D) mm Weight Unit kg Packed Unit kg AHUW146A1 (HU141 U31) AHUW166A1 (HU161 U31) AHUW128A1 (HU123 U31) 1 / / 50 1 / / 50 3/ / ,690 5, ,150 3, ~ 48 5 ~ 48 5~48-20 ~ ~ 30-20~30 Hermetic Motor Hermetic Motor Hermetic Motor GPT425DBA GPT425DBA GPT425DAA (at 60Hz) Brushless Brushless Brushless ,000 4,000 4,000 R410A R410A R410A 2,850(100.5) 2,850(100.5) 2,980(105.1) Electronic Expension Valve Electronic Expension Valve Electronic Expansion Valve FVC68D FVC68D FV50S 1,300 1,300 1, Propeller Propeller Propeller (1,000) 60(1,000) 60(1,000) SIC-72FW-F SIC-72FW-F SIC-72FW-F Flare Flare Flare 9.52(3/8) 9.52(3/8) 9.52(3/8) Flare Flare Flare 15.88(5/8) 15.88(5/8) 15.88(5/8) Χ 1,380 Χ Χ 1,380 Χ x 1,380 x 330 1,140 Χ 1,462 Χ 461 1,140 Χ 1,462 Χ 461 1,140 x 1,462 x Note : 1. Capacities and power inputs are based on the following conditions: * : Cooling conditions - Indoor Water Temperature 23 C/18 C; Outdoor Air Temperature 35 CDB/24 CWB Heating conditions - Indoor Water Temperature 30 C/35 C; Outdoor Air Temperature 7 CDB/6 CWB Standard piping length 7.5m 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement. 4 _ Air-to-Water Heat Pump

38 3. Specifications Outdoor Units Power Supply Ø / V / Hz Maximum Running Cooling A Current Heating A Wiring Connections For Power Supply (Included Earth) Number of wires For Connection with Indoor Unit (Included Earth) Number of wires * Capacity Cooling(A35/W18) kw Heating(A7W35) kw * Power Input Cooling(A35/W18) kw Heating(A7W35) kw * EER Cooling(A35/W18) W/W COP Heating(A7W35) W/W Operation Range(Min.~Max.) Cooling C DB Outdoor Temperature Heating C DB Compressor Type - Model - Quantity EA Displacement cm 3 /Rev. Capacity kw Compressor Motor Type - Quantity EA Rated Output W Refrigerant Type - Charge g(oz) Control - Refrigerant Oil Type - Charged Volume cc Heat Exchanger Quantity EA Rows EA Columns EA FPI Fins/inch Fan Type - Quantity EA Air Flow Rate CMM(l/s) Fan Motor Model - Quantity EA Output W Sound Pressure Cooling db(a)±3 Level Heating db(a)±3 Liquid Piping Type - Connection Outer Diameter mm(inch) Gas Piping Type - Connection Outer Diameter mm(inch) Piping Length Minimum m (Outdoor Unit ~ Standard m Indoor Unit) Maximum m Height Difference (Outdoor Unit ~ Indoor Unit) Maximum m Additional Refrigerant Charge g/m Dimensions Unit(W x H x D) mm Packed Unit(W x H x D) mm Weight Unit kg Packed Unit kg AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) 3/ /50 3/ / ~48 5~48-20~30-20~30 Hermetic Motor Hermetic Motor GPT425DAA GPT425DAA (at 60Hz) (at 60Hz) Brushless Brushless 1 1 4,000 4,000 R410A R410A 2,980(105.1) 2,980(105.1) Electronic Expansion Valve Electronic Expansion Valve FV50S FV50S 1,300 1, Propeller Propeller (1,000) 60(1,000) SIC-72FW-F SIC-72FW-F Flare Flare 9.52(3/8) 9.52(3/8) Flare Flare 15.88(5/8) 15.88(5/8) x 1,380 x x 1,380 x 330 1,140 x 1,462 x 461 1,140 x 1,462 x Outdoor Unit Note : 1. Capacities and power inputs are based on the following conditions: * : Cooling conditions - Indoor Water Temperature 23 C/18 C; Outdoor Air Temperature 35 CDB/24 CWB Heating conditions - Indoor Water Temperature 30 C/35 C; Outdoor Air Temperature 7 CDB/6 CWB Standard piping length 7.5m 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement. Air-to-Water Heat Pump _ 5

39 4. Dimensions Outdoor Unit 3 4 [Unit:mm] AHUW096A1 (HU091 U41) Liquid side service valve(mm) Gas side service valve(mm) Air discharge grill Control Cover Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit should be grounded in accordance with the local regulations or applicable national codes. 3. All electrical components and materials to be supplied on the site must comply with the local regulations or international codes. 4. Electrical characteristics chapter should be considered for electrical work and design. Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter. 6 _ Air-to-Water Heat Pump

40 4. Dimensions Supporter [Unit:mm] AHUW126A1 (HU121 U31) AHUW146A1 (HU141 U31) AHUW166A1 (HU161 U31) AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) Liquid side service valve(mm) Gas side service valve(mm) Air discharge grill Control Cover Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit should be grounded in accordance with the local regulations or applicable national codes. 3. All electrical components and materials to be supplied on the site must comply with the local regulations or international codes. 4. Electrical characteristics chapter should be considered for electrical work and design. Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter. 490 Outdoor Unit Air-to-Water Heat Pump _ 7

41 5. Wiring Diagrams AHUW096A1(HU091 U41) Outdoor Unit 8 _ Air-to-Water Heat Pump

42 5. Wiring Diagrams AHUW126A1 (HU121 U31) AHUW146A1 (HU141 U31) AHUW166A1 (HU161 U31) Outdoor Unit Air-to-Water Heat Pump _ 9

43 5. Wiring Diagrams AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) Outdoor Unit 10 _ Air-to-Water Heat Pump

44 6. Piping Diagrams All split type product INDOOR UNIT OUTDOOR UNIT LIQUID SIDE EEV Th2 3-Way Service Valve Th6 Th7 Indoor Unit Plate Heat Exchanger Th3 Low Pressure Switch Outdoor Unit Heat Exchanger Th8 GAS SIDE Th4 3-Way Service Valve Accumulator Th5 Reversing Valve COMPRESSOR High Pressure Switch COOLING HEATING Description Category Symbol Meaning Indoor Unit Outdoor Unit Th1 Th2 Th3 Th4 Th5 Th6 Th7 Remote air temperature sensor Inlet evaporator temperature sensor Outlet evaporator temperature sensor Compressor-suction pipe temperature sensor Compressor-discharge pipe temperature sensor Condenser temperature sensor Outdoor air temperature sensor PCB Connector CN_ROOM CN_PIPE CN_PIPE/O CN_TH3 CN_TH3 CN_TH2 CN_TH2 Remarks - Optional accessory (being sold separately) - Not shown in diagram - Meaning is expressed based on Cooling mode. - Th4 and Th5 are connected at 4 pin type connector CN_TH3. - Description is expressed based on Cooling mode. - Th6 and Th7 are connected at 4 pin type connector CN_TH2 Outdoor Unit Th8 *1 EEV Condenser middle temperature sensor Electronic Expansion Valve CN_TH3 CN_LEV1 - Th8 is connected at 4 pin type connector CN_TH3 *1:Applied Model : AHUW128A1, AHUW148A1, AHUW168A1, AHUW096A1, AHUW126A1, AHUW146A1, AHUW166A1 Air-to-Water Heat Pump _ 11

45 7. Performance Data 7.1 Cooling Operation Model AHUW096A1 (HU091 U41) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI Model AHUW126A1 (HU121 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI Model AHUW146A1 (HU141 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI Outdoor Unit Model AHUW166A1 (HU161 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI LWT : Leaving Water Temperature TC : Total Capacity (Averaged value) PI : Power Input Notice : Measuring procedure follows EN Notice : Above table values may not be matched according to installation condition 12 _ Air-to-Water Heat Pump

46 7. Performance Data Model AHUW128A1 (HU123 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI Model AHUW148A1 (HU143 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI Model AHUW168A1 (HU163 U31) Outdoor Temperature 20 C 30 C 35 C 40 C 45 C LWT 7 C LWT 10 C LWT 13 C LWT 15 C LWT 18 C LWT 20 C LWT 22 C TC PI TC PI TC PI TC PI TC PI TC PI TC PI LWT : Leaving Water Temperature TC : Total Capacity (Averaged value) PI : Power Input Notice : Measuring procedure follows EN Notice : Above table values may not be matched according to installation condition Outdoor Unit Air-to-Water Heat Pump _ 13

47 7. Performance Data 7.2 Heating Operation Model AHUW096A1 (HU091 U41) Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI Model AHUW126A1 Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI Outdoor Unit Model AHUW146A1 Model AHUW166A1 Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI LWT : Leaving Water Temperature TC : Total Capacity (Averaged value including defrost effect) PI : Power Input Notice : Measuring procedure follows EN Notice : Above table values may not be matched according to installation condition 14 _ Air-to-Water Heat Pump

48 7. Performance Data Model AHUW128A1 (HU123 U31) Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI Model AHUW148A1 (HU143 U31) Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI Model AHUW168A1 (HU163 U31) Outdoor Temperature -15 C -7 C -2 C 2 C 7 C 10 C LWT 35 C LWT 45 C LWT 50 C LWT 55 C TC PI TC PI TC PI TC PI LWT : Leaving Water Temperature TC : Total Capacity (Averaged value including defrost effect) PI : Power Input Notice : Measuring procedure follows EN Notice : Above table values may not be matched according to installation condition Outdoor Unit Air-to-Water Heat Pump _ 15

49 8. Capacity Correction Factor 8.1 Rate of change in the capacity by the piping length : 9kW model Cooling Operation Heating Operation HU (m) HU (m) HL (m) HL (m) Symbols HU : Level difference between indoor and outdoor units where indoor unit in inferior position (m) HL : Level difference between indoor and outdoor units where indoor unit in superior position (m) L : Equivalent pipe length (m) α : Capacity correction factor Outdoor Unit 16 _ Air-to-Water Heat Pump

50 8. Capacity Correction Factor 8.2 Rate of change in the capacity by the piping length : 12kW, 14kW, 16kW model Cooling Operation Heating Operation HU (m) HU (m) HL (m) HL (m) Symbols HU : Level difference between indoor and outdoor units where indoor unit in inferior position (m) HL : Level difference between indoor and outdoor units where indoor unit in superior position (m) L : Equivalent pipe length (m) α : Capacity correction factor Outdoor Unit Air-to-Water Heat Pump _ 17

51 9. Operation Range 9.1 Cooling Operation All split type product (Fan coil unit) (Under floor) Outdoor Temperature( ) Outdoor Temperature( ) Leaving Water Temperature( ) Leaving Water Temperature( ) Continuous Operation Operative 9.2 Heating Operation All split type product Outdoor Unit Outdoor Temperature( ) (Fan coil unit or Radiator) Outdoor Temperature( ) (Under floor) Leaving Water Temperature( ) Leaving Water Temperature( ) Continuous Operation Operative 18 _ Air-to-Water Heat Pump

52 10. Noise Criteria Overall 1m Microphone 1.5m Notes: - Sound measured at 1m away with 1.5m height. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference acoustic pressure acoustic 0dB-20Pa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard. (db(a)±3) 1Φ, V, 50Hz Model Cooling Heating AHUW096A1 (HU091 U41) AHUW126A1(HU121 U31) AHUW146A1(HU141 U31) AHUW166A1(HU161 U31) Sound pressure level Cooling(1Ø) AHUW096A1 (HU091 U41) AHUW126A1(HU121 U31) (db(a)±3) 3Φ, V, 50Hz Model Cooling Heating AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31) AHUW146A1(HU141 U31) Octave Band Sound Pressure Level (db re 20Pa ) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Octave Band Sound Pressure Level (db re 20Pa ) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Octave Band Sound Pressure Level (db re 20Pa ) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Outdoor Unit 80 AHUW166A1(HU161 U31) 70 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC-15 Air-to-Water Heat Pump _ 19

53 10. Noise Criteria Heating(1Ø) 80 AHUW096A1 (HU091 U41) 80 AHUW126A1(HU121 U31) 80 AHUW146A1(HU141 U31) Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC-15 AHUW166A1(HU161 U31) Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC-15 Octave Band Sound Pressure Level (db re 20µPa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Outdoor Unit Approximate Hearing Threshold Cooling(3Ø) 80 NC-25 NC-20 NC-15 AHUW128A1 (HU123 U31) 80 AHUW148A1 (HU143 U31) 80 AHUW168A1 (HU163 U31) Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC Approximate Hearing Threshold Octave Band Center Frequency (Hz) NC-25 NC-20 NC _ Air-to-Water Heat Pump

54 10. Noise Criteria Heating(3Ø) 80 AHUW128A1 (HU123 U31) 80 AHUW148A1 (HU143 U31) 80 AHUW168A1 (HU163 U31) Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 Octave Band Sound Pressure Level (db re 20Pa ) NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC Approximate Hearing Threshold NC-25 NC-20 NC Approximate Hearing Threshold NC-25 NC-20 NC Approximate Hearing Threshold NC-25 NC-20 NC-15 Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Approximated SPL at specific distance : SPL[dB] = A + 20xLog(B/C) where A[dB] : SPL at 1m distance B[m] : 1m C[m] : specific distance Outdoor Unit Air-to-Water Heat Pump _ 21

55 Part 4. Accessories 1. Dry Contact (PQDSA 2. Remote Temperature Sensor (PQRSTA 3. PI485 (PMNFP14A0) 4. Sanitary Water Tank Kit(PHLTA) 5. Solar Thermal Kit(PHLLA)

56 1. Dry Contact (PQDSA) 1.1 Overview LG Dry Contact is a solution for automatic control of air conditioning system at the ownerʼs behest. In simple words, itʼs a switch which can be used to turn the unit On/Off after getting the signal from external sources like key-in lock, door or window switch etc specially used in Hotel rooms. Itʼs a small PCB that either can be fit inside the control box of Indoor unit or can be outside the unit in a plastic case if there is no sufficient space inside the Indoor unit. Apart from simple installation, it can also be linked to Central Controller via Indoor unit PI485 pcb. For this, all connecting wires & an additional small pcb for looping is also provided along with Dry Contact. Dry Contact can be used in two ways. 1. It can be used to actually turn On/Off the system on receiving the signal from the source. In this case, user doesn't need to use remote controller anymore to turn On/Off the system. However all the further settings like temperature, fan speed, mode etc can be done through remote controller only. 2. Other way is almost similar as above but in this case, after getting the On signal from the external source, user has to turn On the system from remote controller only. Dry contact just activates the system. However system can be turned Off directly from the external source. So only On mode is different here. So in both of above conditions, system canʼt be operated without signal from external source which prevents unnecessary use of system & facilitates its operation only when its required. These settings can be selected from the remote controller whose details have been explained in the later part of this manual So depending upon the requirement, Dry Contact offers a variety of applications to suit the customerʼs requirement in the best possible way. Power Connector Indoor PCB Connector Accessories Dry Contact Controller Connector Air-to-Water Heat Pump _ 1

AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-03A(Replace:5BPU0-02A)

AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-03A(Replace:5BPU0-02A) AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-03A(Replace:5BPU0-02A) AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0-03A(Replace:5BPU0-02A) CONTENTS Part 1. Introduction Part 2. Indoor Unit(Hydro kit) Part 3. Outdoor

More information

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01G (Replace: 5BPM0-01F)

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01G (Replace: 5BPM0-01F) Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01G (Replace: 5BPM0-01F) P/No. : MFL66101106 CONTENTS Part 2. Design and installation Part 3. Accessories 1. Features 2. Nomenclature 3. List of functions 4.

More information

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01J (Replace: 5BPM0-01H)

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01J (Replace: 5BPM0-01H) Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01J (Replace: 5BPM0-01H) P/No. : MFL66101106 CONTENTS Part 2. Design and installation Part 3. Accessories 1. Features 2. Nomenclature 3. List of functions 4.

More information

AIR CONDITIONER INSTALLATION MANUAL ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH PORTUGUÊS

AIR CONDITIONER INSTALLATION MANUAL ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH PORTUGUÊS ENGLISH INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards

More information

Hydro Kit (For Medium Temperature) SVC MANUAL(Exploded View)

Hydro Kit (For Medium Temperature) SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Hydro Kit (For Medium Temperature) SVC MANUAL(Exploded View) MDEL : ARNH10GK2A2 / ARNH04GK2A2 CAUTIN Before Servicing the unit, read the safety precautions in

More information

(60Hz/R410A) 6CIM0-02B (Replace: 6CIM0-02A)

(60Hz/R410A) 6CIM0-02B (Replace: 6CIM0-02A) (60Hz/R410A) 6CIM0-02B (Replace: 6CIM0-02A) (60Hz/R410A) 6CIM0-02B (Replace: 6CIM0-02A) CONTENTS Part 1 General information Part 2 Product data Part 3 Design and installation Part 4 Special parts 2 Introduction

More information

NATURAL HEATING MACHINE

NATURAL HEATING MACHINE www.lgeaircon.com LG Electronics Air Conditioning & Energy Solution 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 55 Seoul 150-721, Korea Phone: 82-2-777-761 http://www.lgeaircon.com For continual product

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

Multi Zone Air Conditioner SVC MANUAL (Exploded View)

Multi Zone Air Conditioner SVC MANUAL (Exploded View) Multi Zone Air Conditioner SVC MANUAL (Exploded View) CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual. nly for authorized service personnel. MDEL: MD12Y3JM 960-920-06

More information

Multi Zone Air Conditioner SVC MANUAL (Exploded View)

Multi Zone Air Conditioner SVC MANUAL (Exploded View) Multi Zone Air Conditioner SVC MANUAL (Exploded View) CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual. nly for authorized service personnel. MDEL: MD18Y3JM 960-920-07

More information

History List. Version Date Update Information New EHS SPLIT TDB Released. (Modify the Spec Note)

History List. Version Date Update Information New EHS SPLIT TDB Released. (Modify the Spec Note) History List Version Date Update Information 1.0 15.02.27-2015 New EHS SPLIT TDB Released. (Modify the Spec Note) 1.1 15.03.06 1.2 15.04.06 - Modify : Note(Spec, Capacity Table) / Electric Diagram / OD

More information

Monobloc. Distributed by. Copyright 2018 LG Electronics. All rights reserved.

Monobloc. Distributed by. Copyright 2018 LG Electronics. All rights reserved. Monobloc LG Electronics Commercial Air Conditioning 56, Digital-ro 10-gil, Geumcheon-gu, Seoul, Korea www.lg.com http://partner.lge.com http://www.lgethermav.com Distributed by Copyright 2018 LG Electronics.

More information

Air Conditioner SVC MANUAL(Exploded View)

Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Air Conditioner SVC MANUAL(Exploded View) MDEL : AUUW423D[LUU425HV] CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual. nly for

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU183NJA2 ARNU243NJA2 ARNU303NJA2 ARNU363NJA2 ARNU423NKA2 ARNU483NKA2 ARNU543NKA2 CAUTIN Before Servicing

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

TABLE OF CONTENTS ERSQ-AAY1

TABLE OF CONTENTS ERSQ-AAY1 Daikin Altherma High Temperature Outdoor units ERSQ-AAY1 TABLE OF CONTENTS ERSQ-AAY1 1 Features............................................................ 6 2 Specifications......................................................

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU09GTL*4 ARNU12GTL*4 ARNU18GTL*4 ARNU24GTL*4 CAUTIN Before Servicing the unit, read the safety precautions

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU05GSB*4 ARNU07GSB*4 ARNU09GSB*4 ARNU12GSB*4 ARNU15GSB*4 ARNU18GSC*4 ARNU24GSC*4 CAUTIN Before Servicing

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

Digital Inverter 4 series 8 & 10HP

Digital Inverter 4 series 8 & 10HP E6-H Digital Inverter 4 series 8 & 0HP High static duct type Indoor unit RAV-SM2244DTP-E RAV-SM2804DTP-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents. Line up... 2. Indoor unit (High static duct

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2 CAUTIN Before Servicing the unit, read the safety precautions

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 CAUTIN Before Servicing the unit,

More information

EVI Scroll Air To Water Heat Pumps

EVI Scroll Air To Water Heat Pumps AIR TO WATER HEAT PUMPS 2013 heart of your home H E A T P U M P S Air To Water Heat Pumps Nowadays, people are increasingly focusing on the costs of heating as well as on environmental issues. Traditional

More information

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

INVERTER SCROLL. LG Electronics     Distributed by. Copyright 2017 LG Electronics. All rights reserved. LG Electronics http://www.lg.com http://partner.lge.com Distributed by Copyright 2017 LG Electronics. All rights reserved. FEATURES & BENEFITS High Efficient Inverter Technologies EER 2.65 / COP 3.2 /

More information

EEDEN technical data ERHQ AA

EEDEN technical data ERHQ AA EEDEN08-70 technical data Altherma Outdoor units R-410A Altherma Outdoor units 34 1 Features 1 O u t d o o r u n i A l t h e r m a E R H Q 0 1 1-0 1 6 A A R - 4 1 0 A Cost effective alternative to a fossil

More information

HEATING HEA TING

HEATING HEA TING MONOBLOC (LOW TEMPERATURE) SPLIT (HIGH TEMPERATURE) DOMESTIC HOT WATER TANK SPLIT (LOW TEMPERATURE) SPLIT (DHW TANK INTEGRATED) ACCESSORIES 262 263 THERMA V WHAT IS THERMA V Optimal Application Reliable

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU18GTL*2 ARNU24GTL*2 CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual.

More information

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics Distributed by

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics     Distributed by 4mm 이상 ~ 15mm 미만 (음화형 규정) LG Electronics http://www.lg.com http://partner.lge.com Copyright 2017 LG Electronics. All rights reserved. Distributed by FEATURES & BENEFITS High Efficient Inverter Technologies

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

Room Air Conditioner SVC MANUAL(Exploded View)

Room Air Conditioner SVC MANUAL(Exploded View) Internal Use Only http://biz.lgservice.com Room Air Conditioner SVC MANUAL(Exploded View) MODEL : AS-W183CSA5 AS-W243CSA5 CAUTION Before Servicing the unit, read the safety precautions in General SVC manual.

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU05GL1G4 ARNU15GL2G4 ARNU07GL1G4 ARNU18GL2G4 ARNU09GL1G4 ARNU21GL3G4 ARNU12GL2G4 ARNU24GL3G4 CAUTIN

More information

SINGLE. Technical Data Book. PAC for Europe (R410A, 50Hz, HP) Model : AC***KNPDEH/EU AC***KXAD*H/EU

SINGLE. Technical Data Book. PAC for Europe (R410A, 50Hz, HP) Model : AC***KNPDEH/EU AC***KXAD*H/EU SINGLE Technical Data Book PAC for Europe (R4A, 5Hz, HP) Model : AC***KNPDEH/EU AC***KXAD*H/EU History Version Modification Date Remark Ver 1. Release SINGLE PAC for Europe (R4A, 5Hz) 16.7.15 - Index 1

More information

S-Therm Air to Water Heat Pumps

S-Therm Air to Water Heat Pumps S-Therm Air to Water Heat Pumps AIR TO WATER HEAT PUMP Air to water heat pump Nowadays, people are increasingly focusing on the cost of heating as well as on environmental issues. Traditional heating systems

More information

TABLE OF CONTENTS RMXS-E8V1B

TABLE OF CONTENTS RMXS-E8V1B Outdoor Units R-410A RMXS-E8V1B TABLE OF CONTENTS RMXS-E8V1B! 1 Features........................................................... 814 2 Specifications.....................................................

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU183TL*2 ARNU243TL*2 CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual.

More information

SVC Manual(Exploded View)

SVC Manual(Exploded View) SVC Manual(Exploded View) Model : M18YJ M18CJ M24CJ Product Specifications System 18k 18k 24k System M18YJ M18CJ M24CJ FAC Model Name Outdoor Unit MR18Y3J MR18C3J MR24C3J Indoor Unit MW18Y3J MW18C3J MW24C3J

More information

Single Zone Air Conditioner SVC MANUAL (Exploded View)

Single Zone Air Conditioner SVC MANUAL (Exploded View) Single Zone Air Conditioner SVC MANUAL (Exploded View) CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel. MODEL: MR36UY3J 960-920-10

More information

EHS. EHS (Mono, LT, 50Hz)

EHS. EHS (Mono, LT, 50Hz) EHS EHS (Mono, LT, 50Hz) I. Products 1. Nomenclature.... 5 2. Line-up....... 7 1. Specification...... 9 2. Capacity Tables..... 13 3. Dimensional Drawings............. 19 4. Piping Diagrams..... 23 5.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round AIR TO WATER HEAT PUMPS Hot water and comfortable ambient temperature all year round HEAT PUMP PRINCIPLE CARRIER. A UNITED TECHNOLOGIES COMPANY Whether you need air conditioning for a new building or a

More information

SINGLE-ZONE CEILING-CONCEALED DUCTED SYSTEM ENGINEERING MANUAL

SINGLE-ZONE CEILING-CONCEALED DUCTED SYSTEM ENGINEERING MANUAL SINGLE-ZONE CEILING-CONCEALED DUCTED SYSTEM ENGINEERING MANUAL Single-Zone Ceiling-Concealed Ducted Heat Pump Systems 3/4 to 3 Tons Low Static LD097HV4 (9,000 Btu/h) LD127HV4 (12,000 Btu/h) High Static

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Product Line Introduction. Karl Zhang Technical support engineer

Product Line Introduction. Karl Zhang Technical support engineer Product Line Introduction Karl Zhang Technical support engineer Air Conditioning Solutions Heating & Hot Water Solutions Control Solutions Air Conditioning Solutions Residential Application Commercial

More information

Multi V Air Conditioner SVC MANUAL(Exploded View)

Multi V Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi V Air Conditioner SVC MANUAL(Exploded View) MDEL : ARNU07GTU*4 ARNU09GTU*4 ARNU12GTU*4 ARNU18GTT*4 ARNU24GTT*4 CAUTIN Before Servicing the unit, read the

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LMCA AS G09LMCA AS G12LMCA AS G14LMCA OUTDOOR AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA 1. INDOOR UNIT : AS G07LMCA AS G09LMCA

More information

PUHZ-SHW140YHA PUHZ-SHW230YKA

PUHZ-SHW140YHA PUHZ-SHW230YKA 1 Specifications Model Name PUHZ-SHW1YHA PUHZ-SHWYKA Power supply (phase, cycle, voltage) 3φ, 0V, Hz 3φ, 0V, Hz Max. current A 13.0 6.0 Breaker size A 16 3 Outer casing Galvanized plate Galvanized plate

More information

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units Features O u t d o o r U n i S p l i t S k y R Y N - E V B R - 4 0 a Outdoor units for pair application Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply

More information

Air Conditioning System

Air Conditioning System For continual product development, LG reserves the right to change specifications without notice. LG MULTI V Air Conditioning System 200 Air Conditioning System 200 Air Conditioning System Enjoy a clean

More information

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems Models: ACC 75D/DR ACC 100D/DR ACC - D2-2007 (Draft) Ceiling Concealed Split Systems CONTENTS 1. NOMENECLATURE... 2 2. FEATURES... 4 3. PRODUCT LINE UP... 5 4. SPECIFICATIONS... 8 5. OPERATING RANGE...

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

Water cooled VRV IV W-series

Water cooled VRV IV W-series Water cooled VRV IV W-series Ideal for high rise buildings, using water as heat source Unified range for heat pump & heat recovery and standard & geothermal series 22 Indoor units VRV type indoor units

More information

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45 Plug & Heat heat pump Quick and easy to install For new homes or boiler backup operation 50 HFC R410A CERTIFIED BY CERTITA Heating capacity: 5.5 to 22 kw option CERTIFIED BY CERTITA 30/35-40/45 USE The

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

and sanitary hot water Catalogue 2009

and sanitary hot water Catalogue 2009 heating, COOLING and sanitary hot water Catalogue 2009 LG Electronics Magyar Kft. H-1097 Budapest, Könyves K. krt. 3/a. (+36-1) 455-6060 www.lg.hu www.lgeaircon.com http://lgacademy.csx.hu For continual

More information

Single-Zone Four-Way Ceiling-Cassette System Engineering Manual

Single-Zone Four-Way Ceiling-Cassette System Engineering Manual Single-Zone Four-Way Ceiling-Cassette System Engineering Manual Single-Zone Four-Way Ceiling Cassette Heat Pump Systems 1.5 to 3.5 Tons LC187HV (18,000 Btu/h) LC247HV (24,000 Btu/h) LC367HV (36,000 Btu/h)

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB Air Conditioning Technical Data Concealed ceiling unit with high ESP EEDEN15-204 FXMQ-MB Indoor Unit FXMQ-MB TABLE OF CONTENTS FXMQ-MB 1 Features.............................................................

More information

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1 SPLIT-TYPE AIR CONDITIONERS Revision D: Changing defrost finish temperature has been corrected (10-1.). Please void OBH516 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED

More information

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control... R410A Tropical Split Type AC Technical Manual Content Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 88 Part 4 Installation... 120 Part 5 Control... 154 Indoor

More information

Room Air Conditioner SVC MANUAL(Exploded View)

Room Air Conditioner SVC MANUAL(Exploded View) Internal Use Only http://biz.lgservice.com Room Air Conditioner SVC MANUAL(Exploded View) MODEL : LSN090HYV / LSU090HYV LSN120HYV / LSU120HYV CAUTION Before Servicing the unit, read the safety precautions

More information

Room Air Conditioner SVC MANUAL(Exploded View)

Room Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Room Air Conditioner SVC MANUAL(Exploded View) MDEL : AS-W1838*H0 (LAN185HV / LAU185HV) AS-W2438*H0 (LAN245HV / LAU245HV) CAUTIN Before Servicing the unit, read

More information

mini-cassette W MULTI SPLIT R410A & VRF SERIES AUTO MODEL MDH13HLS MDH13HLS

mini-cassette W MULTI SPLIT R410A & VRF SERIES AUTO MODEL MDH13HLS MDH13HLS mini-cassette 18.000 24.000 AUTO MODEL MDH13HLS MDH13HLS Cooling capacity W 3852 3852 Cooling capacity BTU/h 13135 13135 The best Heating technology capacity W in air conditioning 4205 4205 Heating capacity

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Heat Pump 9K - 1K - 18K - 4K - 8K R-410A Compressor Super Quiet AMS Anti-dust Filters Auto Fan Speed Timer Functions Defrost Protection Smart LCD Wireless

More information

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air technical data RMXS-E7V3B1 Super multi plus air conditioning systems Split Sky Air Outdoor Units R-410A RMXS-E7V3B1 TABLE OF CONTENTS RMXS-E7V3B1 1 Features.............................................................

More information

Air Conditioner CONTENTS

Air Conditioner CONTENTS ORDER NO. MAC0509068C2 Air Conditioner CS-F24DD1E5 CU-B24DBE5 CS-F28DD1E5 CU-B28DBE5 CS-F28DD1E5 CU-B28DBE8 CS-F34DD1E5 CU-B34DBE5 CS-F34DD1E5 CU-B34DBE8 CS-F43DD1E5 CU-B43DBE8 CS-F50DD1E5 CU-B50DBE8 CONTENTS

More information

LG AIR CONDITIONERS 2013 Ducted Split System

LG AIR CONDITIONERS 2013 Ducted Split System Australia Pty Ltd. NEW SOUTH WALES / HEAD OFFICE 2 Wonderland Drive EASTERN CREEK NSW 2766 PH : 02-8805-4000 FAX : 02-8805-4248 AUS-DU113 QUEENSLAND 23 Terrace Place MURARRIE QLD 4172 PH : 07-3908-9000

More information

Modular Air Cooled Scroll Chillers

Modular Air Cooled Scroll Chillers Modular Air Cooled Scroll Chillers 65 80 130 Find out more at www.greeonline.com 160 249 High Efficiency Shell and Tube Heat Exchanger The Gree D Series Chillers utilise high efficiency shell and tube

More information

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)-

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)- Suary PAGE: 1 / 47 1 This Technical Bulletin introduces the new outdoor units of the SET-FREE FSXN1E Series (8 to 54HP) using R410A. 2 The details are indicated in the description. Index 1. Main concepts...

More information

Air Conditioner SVC MANUAL(Exploded View)

Air Conditioner SVC MANUAL(Exploded View) Internal Use Only http://biz.lgservice.com Air Conditioner SVC MANUAL(Exploded View) Type : Ceiling Concealed Duct MODEL : AMNW24GBGA0 [LMHN240HV] AMNW36GBGA0 [LMHN360HV] CAUTION Before Servicing the unit,

More information

LG AIR CONDITIONERS Ducted Split System. Quiet & Comfortable with LG HVAC.

LG AIR CONDITIONERS Ducted Split System. Quiet & Comfortable with LG HVAC. LG AIR CONDITIONERS Ducted Split System Quiet & Comfortable with LG HVAC. Enjoy Clean, Quiet, and Comfortable Air Conditioning with LG Making you and your environment more comfortable LG has a comprehensive

More information

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER Manual No. '06 PAC, KX-T-110 TECHNICAL MANUAL Collection data PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) FDUMVA201HEN2R 251HEN2R 302HEN2R 402HEN2R 502HEN2R 602HEN2R MULTI-TYPE (V-MULTI)

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G09LTCB AS G12LTCB AS G14LTCB OUTDOOR AO G09LTCN AO G12LTCN AO G14LTCN 1. INDOOR UNIT : AS G09LTCB AS G12LTCB AS G14LTCB DTR_AS057E_01

More information

Do you want a versatile solution

Do you want a versatile solution Do you want a versatile solution to make significant savings? ESTIA TOSHIBA AIR CONDITIONING RESIDENTIAL HEATING AIR-TO-WATER HEAT PUMP ESTIA hatever you need ESTIA TO MAKE SIGNIFICANT SAVINGS Toshiba

More information

V016-EN-01 AIR TO WATER HEAT PUMPS 2016 HEART OF YOUR HOME

V016-EN-01 AIR TO WATER HEAT PUMPS 2016 HEART OF YOUR HOME V016-EN-01 AIR TO WATER HEAT PUMPS 2016 HEART OF YOUR HOME H E A T P U M P S Air To Water Heat Pumps Nowadays, people are becoming increasingly focused on the costs of heating as well as on environmental

More information

Cozy Hi Wall Inverter Air Conditioner

Cozy Hi Wall Inverter Air Conditioner Cozy Hi Wall Inverter Air Conditioner the benefits What is an Inverter? Quiet Inverter air conditioners are more powerful and more energy efficient than fixed speed air conditioners. Gree inverters use

More information

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air technical data FDKS-CVMB Concealed ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDKS-CVMB TABLE OF CONTENTS FDKS-CVMB 1 Features.............................................................

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LLCC AS G09LLCC AS G12LLCC OUTDOOR AO G07LLCC AO G09LLCC AO G12LLCC 1.INDOOR UNIT : AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02

More information

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY Easy and fast installation Hydronic module available Compact, reliable and efficient Nominal cooling capacity : 8-40 kw Nominal heating capacity : 17-40 kw 50 410A Cooling or heating USE The air-to-water

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

Compact 4-way Cassette ( ) Type

Compact 4-way Cassette ( ) Type E08-0 Engineering Data Compact 4-way Cassette (600 600) Type Indoor Unit RAV-SM40MUT-E RAV-SM4MUT-E Outdoor Unit RAV-SP404AT-E RAV-SP44AT-E Contents. Specifications. Connecting pipe length and lift difference

More information

(Non-Inverter & Inverter) R410A

(Non-Inverter & Inverter) R410A LG Commercial Air Conditioner Sinlge Split Type (Non-Inverter & Inverter) R410A Distributed by LG Electronics www.lg.com http://partner.lge.com Copyright 2015 LG Electronics. All rights reserved. Non-Inverter

More information

Service Manual. Compact Series REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12

Service Manual. Compact Series REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP. Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12 Service Manual Compact Series Indoor Units Outdoor Units IOD 7 CON 7 IOD 9 CON 9 IOD 12 CON 12 REFRIGERANT R407C R22 COOLING ONLY HEAT PUMP SEPTEMBER - 2005 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES

More information

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Submittal Data: Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

A single answer for multiple zones.

A single answer for multiple zones. FJM - Free Joint Multi A single answer for multiple zones. More comfort with less. This powerful unit supports up to five indoor units for multi-zone control with one outdoor unit. It s also available

More information

Air to water Heat Pump System

Air to water Heat Pump System Air to water Heat Pump System 2 The heating and cooling systems of the future! A step in the right direction of reducing pollution and CO₂ emissions The increase of CO₂ and other green house gases is a

More information

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air technical data FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit air conditioning systems Split Sky Air Indoor Units R410A FDXS-CVMB TABLE OF CONTENTS FDXS-CVMB 1 Features.............................................................

More information

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer V4 Plus Heat Recovery VRF Linda Lin Pre-sales Engineer VRF Line-up DC inverter VRFs 2-pipe 3-pipe Combinable Individual Watercooled Mini Heat recovery V5 X 8-88HP V4+S 8-64HP V4+I (side) 20-45kW V4+I (top)

More information

TECHNICAL CATALOGUE MONO SPLIT RAK-25PSC RAK-35PSC RAC-35WSC

TECHNICAL CATALOGUE MONO SPLIT RAK-25PSC RAK-35PSC RAC-35WSC TECHNICAL CATALOGUE MONO SPLIT RAK-18PSC RAK-25PSC RAK-35PSC RAC-18WSC RAC-25WSC RAC-35WSC HITACHI Specifications in this catalogue are subject to change without prior notice in order for HITACHI to bring

More information

50A KP 70A KP 90A KP 120A KP 150A KP 210A

50A KP 70A KP 90A KP 120A KP 150A KP 210A DC inverter all in one Model KP 5A KP 7A KP 9A KP 12A KP 15A KP 21A Power supply V/Hz/Ph 23/5/1 23/5/1 23/5/1 23/5/1 38/5/3 38/5/3 Nominal heating capacity kw 5 7 9 12 15 21 Nominal cooling capacity kw

More information