ASHRAE Headquarters Building: GSHP vs. VRF systems
|
|
- Domenic Porter
- 5 years ago
- Views:
Transcription
1 Jeffrey D. Spitler Oklahoma State University ASHRAE Headquarters Building: GSHP vs. VRF systems Session C: Technical
2 Learning Objectives Understand how a GSHP system and VRF system compare when applied in the same building with very similar loads. Understand some of the real-world influences on system performance. 2
3 Acknowledgements Laura Southard Oklahoma State U. Xiaobing Liu Oak Ridge Nat. Lab. Financial Support GEO Southern Company US/China Clean Energy Research Center ASHRAE / Mike Vaughn 3
4
5
6
7 A Living Laboratory Over 1000 measurement points 2-story office building, built in 1965 Renovated and enlarged in Open plan office design allows for more daylighting Three systems: Variable refrigerant flow system serving 1 st floor Ground source heat pump system serving 2 nd floor Dedicated outdoor air system serving both floors
8 First Floor / VRF System 17,213 ft 2 (1599 m 2 ) served by VRF system Not served by metered VRF system: Computer server room Rear staircase Entry foyer Served: Office space Mailroom Learning Center Two outdoor heat-recovery units (28 tons nominal capacity) 22 indoor FCU
9
10 VRF Controls Single setpoint. Users can reset thermostats ±3 F System attempts to maintain setpoint, within ±1 F Individual units do not switch back and forth between heating and cooling, though. Adjacent units in open floor plan office do run in opposite modes.
11 Second Floor / GSHP System GSHP serves entire 2 nd floor + rear stairwell. Total floor area 15,558 ft 2. (1445 m 2 ) Office space and two conference rooms.
12 GSHP System 12 boreholes, 400 ft. deep 14 water-to-air heat pumps, 31.5 tons nominal capacity Heat pumps: Two-stage ECM fan motors, variable speed Staged controls: Separate heating/cooling setpoints 68 F/74 F typical Temperature deviates > 1.5 F: low-stage Temperature deviates > 2.5 F: high-stage Users can reset thermostats ±3 F
13 DOAS Provides partly conditioned ODA to both floors. Generally, always lower than room temperature. Sometimes overcools. Increases heating loads, decreases cooling loads.
14
15 Qualitative Comparison of Loads 1 st floor and 2 nd floor: same lighting and plug load densities. Occupancy: 1 st floor (normal): 400 ft 2 /person 2 nd floor (normal): 259 ft 2 /person 1 st floor, learning center: used ~26 hours/month DOAS average flow rate: 1 st floor: 2560 CFM 2 nd floor: 1480 CFM
16 Qualitative Comparison of Loads Rooms on 2 nd floor have heat gains from roof. 1 st floor has more glass façade, but part of this is conditioned by nonmetered VRF systems. As a result: 1 st floor has higher heating loads. 2 nd floor has higher cooling loads. Cooling loads are much higher than heating loads.
17 Results Energy consumption Heating and Cooling Loads System COP and EER Why?
18 Total Monthly Energy Use Monthly Energy Use, kwh 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 GSHP VRF DOAS
19 Monthly Energy Use per ft GSHP VRF 0.30 Monthly Energy Use, kwh/ft
20 Avg. Power vs. Outdoor Temperature 2.0 GSHP VRF DOAS Average Power Use, W/ft Ambient Dry Bulb Temperature, F
21 July June 2013 Temperatures Number of hours Temperature ( F)
22 VRF Heating and Cooling 2.0 VRF Heating Cooling 1.8 Average VRF Power Use, W/ft Ambient Dry Bulb Temperature, F
23 GSHP Heating and Cooling Average GSHP Power Use, W/ft GSHP Heating Cooling Unallocated Ambient Dry Bulb Temperature, F
24 Avg. Power Cooling Only Average Power Use, W/ft GSHP VRF Ambient Dry Bulb Temperature, F
25 Avg. Power Heating Only Average Power Use, W/ft GSHP VRF Ambient Dry Bulb Temperature, F
26 A moderate day April 3, 2013 Morning low: 43 F Afternoon high: 63 F
27 Power Use VRF GSHP 0.8 W/ft :00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00
28 GSHP Zone Temperatures Zone Temperature, F Zone 207 Zone 204 Zone 209 Zone 224C Zone 224D Zone 206 Zone 215A Zone 215B Zone 215C Zone 224B 69 7:00 10:00 13:00 16:00 19:00
29 VRF Zone Temperatures (Cooling) Zone Temperature, F Zone 116 Zone 117 Zone 119 Zone 120 Zone 134B Zone 134C Zone 134D Adjacent zone was heating 69 7:00 10:00 13:00 16:00 19:00
30 VRF Zone Temperatures (Heating) Zone Temperature, F Zone 103 Zone 104 Zone Zone 109 Zone 110 Zone 111 Zone 112 Zone 134A Zone Zone 140A Zone 140B Zone 140C 69 Zone 145 Zone 147 7:00 10:00 13:00 16:00 19:00
31 Why is GSHP So Much Better? Source temperatures. Equipment efficiency at actual source temperatures. Apparent control issue most VRF units run most of the time under moderate load conditions. Unnecessary (?) simultaneous heating and cooling. Loads are different. (Yes, but how much?)
32 Source Temperatures Ambient air Ground Loop Water Supply Temperature, F /1/11 12/31/11 7/1/12 12/31/12 7/2/13
33 Heating and Cooling Provided How much heating and cooling are provided by each system? Heat pumps and 14 VRF FCUs: Need air flow rate + temperatures and (for cooling) humidities.
34 Actual Available Measurements Airflow from flow hood measurements (VRF system changed control boards and flows in April 2012) Discharge air temperature Zone air temperature Zone air humidity
35 Estimated Quantities Entering and discharge air humidities GSHP system, from measurements in one zone Entering air humidity ratio without DOAS with DOAS 1:1 line Zone humidity ratio Discharge Air Humidity Ratio Zone 215B data 78% relative humidity Discharge Air Temperature, F VRF system, from mfr. data, SHF=f(EAT, ODAT); spot-checked by us
36 Uncertainty Analysis Details in 2nd ASHRAE Journal paper. Accounts for: Sensor errors Approximations like using the zone humidity to estimate entering air humidity Aggregation (reduces uncertainty) Final uncertainties for entire systems. GSHP VRF Cooling +14/-11% ±5% Heating ±7% ±4%
37 Monthly Heating Provided Heating Provided, kwh/ft GSHP VRF 0.0
38 Monthly Cooling Provided Cooling Provided, kwh/ft GSHP VRF
39 Heating and Cooling Provided For July 2011 March 2012: GSHP provides 62% less heating than VRF GSHP provides 6% more cooling than VRF GSHP System Cooling Provided (MBTU/sq. ft.) Heating Provided (MBTU/sq. ft.) VRF System
40 Monthly System Heating COP 6 5 GSHP VRF Heating System COP
41 Monthly System Cooling EER Cooling System EER GSHP VRF
42 Cooling Performance GSHP VRF System Cooling EER OA Temp, F
43 Heating Performance GSHP VRF System Heating COP OA Temp, F
44 Counterintuitive Trends GSHP system heating COP goes up from 1 st winter to 2 nd winter. For both systems, system cooling EER increases with increasing ODA temperature (to a point) For GSHP system, performance increases with higher loads. (next slide)
45 Why is GSHP EER Better in Hot Months? 18 Monthly GSHP System Cooling EER ,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 Monthly Cooling Provided by GSHP System, kwh
46 Why Does GSHP Heating COP Improve From 1st Year to 2nd Year? Pump 6 control: differential setpoint on loop reduced from 20 psig to 8 psig GSHP VRF Heating System COP Measured Power, kw psi loop dp 15 psi loop dp Loop Flow, GPM
47 Why Does GSHP Heating COP Improve From 1st Year to 2nd Year? Pump control: differential setpoint on loop reduced from 20 psig to 8 psig Measured Power, kw psi loop dp 15 psi loop dp Loop Flow, GPM
48 Why Are Trends Counterintuitive? For GSHP: Entering fluid temperature does not correspond directly to outdoorair temperature. Higher run time fractions correspond to less pumping energy and parasitic losses (per unit cooling or heating provided) For VRF (we speculate): Simultaneous heating and cooling may not be as efficient as imagined.
49 Conclusions GSHP system significantly outperforms VRF system. For July 2011-March 2012: GSHP VRF Heating System COP 3.3 ± ±0.1 Cooling System EER 14.5 ± ±0.4
50 Conclusions (Why?) GSHP has more favorable source temperatures. Heat pump unit efficiency is higher than VRF efficiency over actual range of operation. VRF controls lead to unnecessary (?) heating and cooling.
51 Bibliography Southard, L.E., X. Liu, J.D. Spitler Performance of HVAC Systems at ASHRAE HQ Part 1. ASHRAE Journal. September 2014, 56(9): Southard, L.E., X. Liu, J.D. Spitler Performance of HVAC Systems at ASHRAE HQ Part 2. ASHRAE Journal. December 2014, 56(12): Spitler, J.D., L.E. Southard, X. Liu Final Report - Performance of the HVAC Systems at the ASHRAE Headquarters Building. Available online at: 51
52 Questions? Jeff Spitler 52
Evaporative Cooling in a Hot-Dry Climate
Evaporative Cooling in a Hot-Dry Climate David Springer Davis Energy Group SWEEP Workshop July 10, 2007 Sponsors: Clarum Homes California Energy Commission U.S.Department of Energy Issues for Discussion
More informationSession: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island
Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down
More informationVariable Refrigeration Flow Systems Overview 10/11/2016
Variable Refrigeration Flow Systems Overview 10/11/2016 Executed by Data Power Technology Illinois Aggressively, relentlessly anticipating and exceeding our customer s and client s expectations every day,
More informationThe Ed Roberts Campus Berkeley, CA
The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating
More informationHigh Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO
High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO 2012 1 Learning Objectives for this Session Get acquainted with typical systems used in the
More informationNET ENERGY WATER LOOPS A clear path to net zero energy buildings
Presents NET ENERGY WATER LOOPS A clear path to net zero energy buildings Alan Niles WaterFurnace International This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer
More informationAIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS
AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationContinuous Commissioning: A Valuable Partner to Retrofit Projects
Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles
More informationSubmitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas
More informationDedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1
Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1 1 Peter Teige, Application Engineering Manager, AHRI Member Technical Training, October 12, 2016 AHRI 920: Establishes Efficiency Metric for
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationHigh Performance Building Guide 1
Description This Guide is intended to be used for projects with a Vermont Certified: High Performance energy efficiency goal. This High Performance goal is a whole-building efficiency approach rather than
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationContinuous Commissioning Report
Continuous Commissioning Report for the Bush Academic Facility (Bldg. 1607) Submitted to: Office of Energy Management Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationDesigning Energy Efficient Outdoor Air Systems
Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work
More informationApplication of Air Source Variable Refrigerant Flow in Cold Climates
PREPARED BY Seventhwave with the assistance of Daikin North America, LLC Masters Building Solutions Application of Air Source Variable Refrigerant Flow in Cold Climates A White Paper March 2015 275-1
More informationEnergy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE
This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationSubmitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University
More informationIncrease your flexibility.
DVM CHILLER Increase your flexibility. Get the best of two worlds. This easy to expand, modular unit combines the benefits of VRF and Chiller systems. Product Registration Required Conditions Apply 2018
More information2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC
2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC Mechanical Systems Agenda Changes in NREC Chapter 11 Changes in NREC Chapter
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationHVAC 101. H V A C S y s t e m s
H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationHVAC DISTRIBUTION and DELIVERY SYSTEMS
HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that
More informationComputing Services Center
Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY
SUPERIOR IAQ LOW FIRST COST BEST ROI ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY Pinnacle manages 100% of a building s ventilation and indoor humidity load in a single package. Chilled beams have
More informationUPGRADES. [Energy Efficiency] Base Points
SmartRegs Prescriptive Pathway Property Address: Dates of Inspections and Updates: Inspector: Owner: Agent: 123 Boulder Initial Inspection Date: Update Date: 7/9/5 Scott Home Inspection Unit: Compliance
More informationDesign Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationChilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle
Chilled Beam and Radiant Cooling Basics Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Radiant Ceilings & Chilled Beam Basics Energy & Space Savings First and
More informationENGINEERING AND CONSTRUCTION BULLETIN
ENGINEERING AND CONSTRUCTION BULLETIN No. 2016-15 Issuing Office: CECW-CE Issued: 23 May 16 Expires: 23 May 18 CATEGORY: Guidance 1. References: Jesse Dean, Lesley Herrmann, Eric Kozubal, and Jesse Geiger
More informationCONTROLLED CHILLED BEAM PUMP MODULE
FIRST COST SAVINGS PROACTIVE CONTROL CONTROLLED CHILLED BEAM PUMP MODULE Active condensation control system effectively eliminates chilled beam condensation High efficiency, variable speed pump uses a
More informationExhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.
1. State 2 75 o F Exhaust M amb T amb State 3 Room Q chiller State 1 60 o F M total A room at steady state has a supply air stream of cool air entering at 60 o F. The lights, office appliances and people
More informationImpacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation
Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas
More informationASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee
ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC
More informationASHRAE/IESNA Standard
ASHRAE/IESNA Standard 90.1-1999 An inside look at the requirements of Standard 90.1-1999 Energy Standard for Building Except Low-Rise Residential Building Mick Schwedler, PE Sr. Principal Applications
More informationImplications of GHP Fan Control Strategies on Humidity Control in Commercial Applications
Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications ASHRAE Winter Meeting February 9, 2005 Hugh I. Henderson, Jr., P.E. CDH Energy Corp. Cazenovia, NY DOE/NETL Project
More informationb.) Technical Information:
Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,
More informationEnergy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More informationSYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC
VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationMASS AND HEAT RECOVERY SYSTEM SALAH MAHMOUD HINDAWI DIRECTOR HINDAWI FOR ENGINEERING SERVICES & CONTRACTING NEW DAMIETTA, EGYPT
ESL-IC-10-10-56 MASS AND HEAT RECOVERY SYSTEM SALAH MAHMOUD HINDAWI DIRECTOR HINDAWI FOR ENGINEERING SERVICES & CONTRACTING NEW DAMIETTA, EGYPT ABSTRACT : In the last few years heat recovery was under
More informationBill McCullough. Director ERV Products. Dallas, TX
Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is
More information4. OVERVIEW OF MECHANICAL SYSTEM
4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in
More informationIn Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market
In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market Eric Urban Senior Energy Data Analyst Staengl Enginering Note: This presentation takes
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationIndoor Horticulture HVAC System Evaluation Project
Indoor Horticulture HVAC System Evaluation Project Sacramento Municipal Utility District November 30, 2018 Prepared by: John Walczyk Sepideh Shahinfard Allen Lee The information in this report is provided
More informationTechnology Applied. IGSHPA Conference
Technology Applied IGSHPA Conference October 2014 1 TECHNOLOGY APPLIED ClimateMaster leadership Technology available today Trilogy of variable speed w/q-mode full-time water heating vflow TM built-in variable
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,
More informationHONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING
ASHRAE s BEST This article was published in ASHRAE Journal, November 2010. Copyright 2010 American Society of Heating, Refrigerating and -Conditioning Engineers, Inc. Reprinted here by permission from
More informationGEOTHERMAL DESIGN GUIDE
GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS
More informationTechnical Report #3 Mechanical Systems Existing Conditions Evaluation
Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationPerformance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment
AHRI Standard 1230 with Addendum 1 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI STANDARD 1230-2014 WITH ADDENDUM 1,
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationSmall Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.
Small Commercial Business Energy Audits Recognizing and addressing the special requirements of the small business market segment. Class 7 Class 7: Refrigeration Fundamentals The Vapor-compression cycle
More informationLaboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate
Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate American Council for an Energy Efficient Economy ACEE Hot Water Forum Nov. 4-5, 2013 Carlos J. Colon
More informationCivil Engineering Building
Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationConstruction Fabrication Service
Construction Fabrication Service VRF vs Heat Pump Chicago VRF Design & Installation Considerations Presentation Overview o Premier Mechanical Background o VRF Project Resume o 2211 N Milwaukee Case Study
More information4-Pipe VAV vs. Active Chilled Beams for Labs
Steven T. Taylor 4-Pipe VAV vs. Active Chilled Beams for Labs BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE Variable air volume (VAV) laboratory HVAC systems, including VAV fume hoods, are now standard practice
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationPINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION
ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy
More informationEngineers and Contractors - Innovative Technologies to Achieve Highest GeoExchange System Efficiencies for Commercial Projects
Engineers and Contractors - Innovative Technologies to Achieve Highest GeoExchange System Efficiencies for Commercial Projects Presented by: Warren (Trey) Austin, PE, CEM, CGD, LEED-AP Geo-Energy Services,
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More information1 - This title will copy onto other forms Date
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM Project Title: 1 - This title will copy onto other forms Date 1/1/2015
More informationASHRAE Guideline 36 Advanced HVAC Control Sequences
ASHRAE Guideline 36 Advanced HVAC Control Sequences Rick Stehmeyer - Senior Engineer Matt Napolitan, P.E., CCP, CPMP, LEED AP BD+C - Principal Image Source: http://worldatdistance.com/2013/10/07/the-complete-noobs-guide-to-making-a-website//
More informationChiller Plant Design. Julian R. de Bullet President debullet Consulting
Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE
More informationENGINEERING. Edition No. 13 October 2002
Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more
More informationAndrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3
Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located
More information2009 IECC Commercial Mechanical Requirements
BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(
More informationA Technical Introduction to Cool Thermal Energy Storage Commercial Applications
A Technical Introduction to Cool Thermal Energy Storage Commercial Applications Cool Thermal Energy Storage is a new application of an old idea that can cut air conditioning energy costs in half while
More informationHeat Pump Water Heater Technology Development. EEBA High Performance Home Summit Ed Vineyard Oak Ridge National Laboratory
Heat Pump Water Heater Technology Development Ed Vineyard Oak Ridge National Laboratory EEBA High Performance Home Summit 2017 ORNL is managed by UT-Battelle for the US Department of Energy Residential
More informationEffect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load
Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load Philip Boudreaux, Roderick Jackson, Jeffrey Munk and Anthony Gehl, Oak Ridge National
More informationMID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN
MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationAMCA Webinar High Performance Air Systems Presented by:
AMCA Webinar High Performance Air Systems Presented by: Wade Smith, Executive Director Michael Ivanovich, Director of Strategic Energy Initiatives Hide or reveal Control Panel Status of your microphone.
More informationFeasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to
More informationTechnical Report Three
Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3
More informationMechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation
Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department
More information2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems
2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path
More information97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!
97.501B Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Monitored In-Situ Performance of Residential Air-Co onditioning Systems Sponsored By: Arizona Public Service Company
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationSESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:
SESSION 1-2015 Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE (90.1.2013) ASHRAE Detroit Members: AM Session is eligible for (X) Professional Development
More informationHot Water Distribution System Losses in a Net-Zero Home
Hot Water Distribution System Losses in a Net-Zero Home March 22, 2018 ACEEE Hot Water Forum William Healy Tania Ullah National Institute of Standards and Technology Overview of Presentation Purpose: To
More informationSOLAR THERMAL HEATING: ALIVE AND WELL
Michael E Dion michael.dion@stiebel-eltron-usa.com SOLAR THERMAL HEATING: ALIVE AND WELL Donavin A Gratz donavin.gratz@stiebel-eltron-usa.com E Christopher Wetherby chris.wetherby@stiebel-eltron-usa.com
More informationBOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationHeat Transfer Products. Product Line Update
Heat Transfer Products Product Line Update EP2 Portable Chiller Variable-Speed Compressor Option What s different with variable-speed option? Fixed-Speed Compressor Units Variable-Speed Compressor Units
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationEADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationSplit Type System. Air to Water Heat Pump
Split Type System Air to Water Heat Pump EXPERTISE AND INNOVATION Daikin Altherma offers complete flexibility for new construction and deep energy refurbishment projects. Using a low temperature hydronic
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.
ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2013 (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings July 7, 2017 The corrections listed in this errata sheet apply to ANSI/ASHRAE/IES
More informationSelection of air conditioning systems
Selection of air conditioning systems Prof. M. Ramgopal Department of Mechanical Engineering IIT Kharagpur Objectives 1. List the criteria used in the selection of air conditioning systems 2. List typical
More information