Technology for building automation. Ambient Air Humidity and Temperature Probes HT12 and HTF12. Device Description. Contents
|
|
- Jocelin Short
- 5 years ago
- Views:
Transcription
1 Ambient Air Humidity and Temperature Probes HT12 and HTF12 HT12 and HTF12 serve to seize the relative ambient air humidity and the ambient temperature. The probes are utilised with or without set-point adjuster for continuous measuring in connection with steady regulation. Contents subject to change Edition: 11/05/2004 Contents Ambient Air Humidity and Temperature Probes HT12 and HTF12 Page 1 Contents Page 1 Notes on the device description Page 2 Application Page 3 Types Page 3 Technical data Page 3 Assembly Page 4 Assembly Instructions Page 4 Installation Page 5 Connecting plan HT12 Page 6 Connecting plan HTF12 Page 6 Kieback & Peter GmbH & Co KG Tempelhofer Weg 50, D Berlin Telephone +49 (0) 30 / Telefax +49 (0) 30 / info@kieback-peter.de
2 Notes on the device description The description contains instructions on using and assembling the Ambient Air Humidity and Temperature Probes HT12 and HTF12. In case of questions which cannot be clarified with this device description, please refer to the supplier or manufacturer for further information. The indicated installation instructions/regulations are valid in the Federal Republic of Germany. When utilizing the devices in other countries, the builder or operator of the plant is responsible for the observation of the respective national regulations. The operating staff is to be instructed in accordance with the description of the technical data sheet. Safety Instructions When mounting and utilizing the devices, the respective worker s protection rules, regulations for prevention of accidents and VDE rules shall be observed Any work concerning the assembly, installation or initial operation of the devices shall be exclusively carried out by qualified specialists, see section Qualified specialists. Every person utilizing the devices shall have read and understood the descriptions in the technical data sheet. Meaning of the symbols in the technical data sheet: Danger Warning of dangerous electrical voltage Danger means mortal danger, severe bodily injuries or serious material damage in case of non-observance. Qualified specialists Qualified specialists for the purposes set out in this technical data sheet are persons who are familiar with the described devices and possess a qualification for their respective occupation. These are for instance: Authorization to connect the devices according to the local regulations and authorization to switch the devices on and off taking the in-house regulations into account. Knowledge of the regulations for prevention of accidents. Knowledge of the utilization of the devices within the plant system. etc. Page 2 / 8
3 Application The Ambient Air Humidity and Temperature Probes HT12 and HTF12 serve to continuously seize the relative air humidity and ambient temperature in housing space and business premises. The probes can be operated in connection with all Kieback & Peter regulators and regulation systems containing analogue V entries and sensor connections for the active measuring unit KP10. As an additional feature, the set-point adjuster of the Ambient Air Humidity and Temperature Probe HTF12 enables the setting of the required ambient temperature. Types HT12 HTF12 Combined Ambient Air Humidity and Temperature Probe with humidity probe and active measuring unit KP10 without setpoint adjuster Combined Ambient Air Humidity and Temperature Probe with humidity probe and active measuring unit KP10 with additional set-point adjuster (10 k Ohm) HT12 Technical data Mains 24 V AC ±10 %, 0,4 VA Measured variable relative ambient air humidity and ambient temperature in housing space and business premises Measuring system for humidity Humidity probe with measuring transmitter, Output: V DC, max. 5 ma for % r. h. for temperature active measuring unit KP10 Output: 2,73 V bei 0 C, TK 10 mv/k adjustment at works Exactitude rel. humidity ±3 % at 22 C Temperature ± 0,25 K at 22 C Measuring range rel. Humidity % r. h. Temperature C HTF12 Environmental max % r. h. non condensing humidity Ambient temperature Temperature C Set value adjuster (HTF12) potentiometer 10 k Ohm, linear, set knob with trend arrow Storage temperature C Housing Housing made of plastic material Colour RAL9010 (pure white) Degree of enclosure IP30 protection Dimensions HT12 L x H x W = 82 x 87,5 x 27,5 (mm) T HTF12 L x H x W = 82 x 87,5 x 28.3 (mm) H B Page 3 / 8
4 Assembly The assembly of the combined Ambient Air Humidity and Temperature Probes HT12 and HTF12 can be wallmounting or buried wiring respectively. For a quick and correct detection of the room temperature the room probe shall be installed as to be able to detect the airflow in the room. The vent slots of the hood must be located vertically above one another. Airflow 1,5 m Correct for housing space and business premises False Assembly Instructions Connect the room probe in accordance with terminal connecting plan, position the hood and tighten the safety screw. Release safety screw and 1 take off hood. 3 Tweak for cable entry 60 The cardboard box serves as protective cover during the installation phase. For this purpose, please fold the side boards to the inside and rip off the box cover. M3 x 20 Tweak for cable entry from above ,5 x 45 4 Page 4 / 8
5 Installation Danger Electric installation and probe connection shall be carried out by qualified experts only. Before connecting the Ambient Air Humidity and Temperature Probe to the regulation unit, the switchboard shall be switched voltage-free. In this context, the regulations of the VDE (Association of German Electro technical Engineers) as well as the local regulations shall be observed. The Ambient Air Humidity and Temperature Probes HT12 and HTF12 contain perforated bases and caps for connection purposes. These pieces can be tweaked out in order to insert cables. A B Cable inlet for assembly with flush-mounted box Cable inlets for wall-mounting Page 5 / 8
6 Connecting plan HT12 KP10 HT12 H% + _ Temperature KP Humidity V DC = % r. F V DC 0 V AC/DC 24 V AC 0 V AC/DC Mains 24 V AC Connecting plan HTF12 10 k KP10 HTF H% Temperature KP10 Humidity V DC = % r. F V DC 0 V AC/DC 24 V AC 0 V AC/DC Mains 24 V AC Page 6 / 8
7 Page 7 / 8
8 Page 8 / 8
TDE, TDE-10M, TDE-15M, TDE-S3, TDE-S4 Temperature Sensor
Issue 2009-05-15 Datasheet 1.10-12.010-11-EN Temperature Sensor Temperature sensors TDE, TDE-10M, TDE-15M, TDE-S3 and TDE-S4 can be used in existing thermowells with an internal diameter from 6.5 mm. The
More informationDDC111 and DDC111-2 room control modulel
Issue 2012-05-09 Datasheet 1.10-51.111-01-EN DDC111 and DDC111-2 room control modulel pplication The room control modules are used together with the technolon RCNxxx-L or FBR110-L room controllers. room
More informationTest Unit GTL 100 for Fire Detectors
Test Unit GTL 100 for Fire Detectors Description and Operation Manual Zertifiziertes QM System Nach DIN EN ISO 9001 Description and Operation Manual Table of Contents 1. Instructions 1.1 General 1.2 Standards
More informationOperating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content
8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity
More informationInstallation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode
Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER Low pressure with PI-control-mode Manufacturer: Phone: Fax: E-Mail: Website: Issue: Doc.-no.: Arthur Grillo GmbH Am Sandbach
More informationElectronic Temperature Controller 70304,
Electronic Temperature Controller 70304, 70304.2 Instruction Manual Version 1.00.01 List of content 1 General information... 4 2 Declaration of conformity... 4 3 Safety instructions... 5 4 Warranty...
More informationProcess Automation. Sensors and Systems: Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors
Process Automation Accurate Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors Flexible Sensors and Systems: www.fafnir.com Reliable Process Auromation Edition 08.13
More informationDuct Humidity and Temperature Transmitter. Features. IP65 protection. Ordering
Duct Humidity and Temperature Transmitter DHT Apr. 17 Features Humidity and Temperature outputs in same unit Humidity output 0-10 Vdc or 4-20 ma Temperature output 0-10 Vdc or 4-20 ma As option passive
More informationOperating instructions Safety-monitoring module SRB 302X3. 1 About this document
1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for
More informationISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V
Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480
More informationAirUnit. Installation instructions. mfh systems modern floor heating. Decentralised domestic ventilation
mfh systems modern floor heating AirUnit Decentralised domestic ventilation Installation instructions List of contents, Installation instructions Page 1. General information... 03 2. Function / planning
More informationInductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.
Process Analysis Systems Chem Energy Pharm Food Water Stratos Eco 2405 CondI Inductive Conductivity Measurement Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement
More informationPolyGard 2-channel Gas Controller MGC-03
PolyGard 2-channel Gas Controller MGC-03 DESCRIPTION Gas measuring and monitoring controller based on state-ofthe-art micro-technology with integrated buzzer for continuous monitoring of the ambient air
More informationPRODUCT INFORMATION. Sounder SG 200. BDL F.01U A3.en / ST FIR/ PRM1 / zab. Page 1 of 10
PRODUCT INFORMATION PI 38.43 Sounder SG 200 Page 1 of 10 Table of Contents 1. Product Description............................... 3 2. Features......................................... 3 3. Functional Description............................
More informationEHA Hoffmann International GmbH
EHA Hoffmann International GmbH Operating Instructions EHA - Embossing Press 50-75 Professional Machine number: Model year: The side shelfs are optional and are not included in the Standard scope of delivery.
More informationMinimal maintenance requirements - No consumables and low cost of ownership. Rapid, accurate results - for safe operation of coal handling systems
Product Data Sheet CODEL Continuous Mill Fire Detection Coal Mill CO Analyser Low cost, low maintenance devices for continuous monitoring. Robust infrared gas analyser - accurate and reliable operation
More informationWind Alarm Instrument x.x0x
THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for Use 000/0/0 Wind Alarm Instrument..0x.x0x ADOLF THIES GmbH & Co. KG Hauptstraße 0 Göttingen Germany Box
More informationInstallation manual extra-low-voltage socket outlets for panel- and surface-mounting
EN Installation manual extra-low-voltage socket outlets for panel- and 60003221 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal
More informationRegulated Ex-Heater HEX with internal controller, HEX with external controller II 3 G II 3 D
Regulated Ex-Heater HEX5-1.08 with internal controller, HEX5-2.08 with external controller II 3 G II 3 D Instruction Manual Version 1.02.00 Dear customer, we have made up this operating manual in such
More information2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC
2CKA001473B9007 19.05.2017 System Manual Busch-Infoline Handicapped toilet signal set 1510 UC-... -101 Table of contents Table of contents 1 Notes on the instruction manual... 3 2 Safety... 4 2.1 Information
More informationInstallation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets QUICK-CONNECT (63 A)
EN Installation manual surface mounting plugs and socket outlets, panel 60003506 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3
More informationRoom controller. RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.
revision 12 2016 RC Room controller RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC is a room controller in the Regio series. The controller
More informationTER Active Room Temperature Sensor (Controller),
Product sheet SN1.415 Type TER TER Active Room Temperature Sensors (Controllers) The TER active sensors are designed to detect temperature in the room spaces. The TER sensors have linear 0..10V signals
More informationMEAS CAL ALARM WASH CONF APT4000 PH ENCLOSURE TYPE 2. Description
APT4000 Series 4-Wire ph Transmitters 3/01 Page 1 of 8 Specification Overview The Honeywell Analytical Process Transmitter (APT) 4000 Series transmitter continuously measures ph or ORP in industrial processes
More informationOperating Manual MSF220V(VU)
ZIEHL industrie elektronik GmbH + Co KG Daimlerstr.13, 74523 Schwäbisch Hall, Germany + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperaturrelais und MINIKA Strom- und Spannungsrelais Messgeräte MINIPAN
More informationElectronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21
Electronic Standard Devices Annunciator Relay MR and MRE MR 2 and MRE 2 The products described in this brochure are intended for industrial use and meet the requirements laid down by the EU directive 7
More informationANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL
ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL Analox Sensor Technology Ltd 15 Ellerbeck Court Stokesley Business Park Stokesley TS9 5PT Tel: +44 (0)1642 711400 Fax: +44 (0)1642 713900 Email: info@analox.net
More informationTechnical data lumina PM
1. Product description Technical data The presence detector is suitable for detecting the movement of humans and animals through their radiant heat. The sensitive 4-element-PIR sensor technology for presence
More informationMEAS CAL ALARM WASH CONF APT4000 TC
APT4000 Series Toroidal Conductivity Transmitters Overview 70-82-03-42 3/01 Page 1 of 8 Specification The Honeywell Analytical Process Transmitter (APT) 4000 Series transmitter continuously measures conductivity,
More informationRoom controllers with manual forced ventilation function
revision 12 2016 RC-O Room controllers with manual forced ventilation function RC-O is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC-O is a room
More informationHomepage > Products > Control systems > Demand-based room control with X-AIRCONTROL > Sensors > X-SENS X-SENS
Homepage > Products > Control systems > Demand-based room control with X-AIRCONTROL > Sensors > X-SENS X-SENS SENSORS FOR X-AIRCONTROL ZONE MODULES AND OTHER EQUIPMENT Components for the measurement and
More informationVERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual
VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual EN Table of Contents 1. INSTALLATION MANUAL...3 1.1. Air Handling Units Sections Connection...3
More informationManual Power relay SR853
Manual Power relay SR853 Product types SR853.8.x.x, Rev. 1 SR853 manual page2 The symbols WARNING, CAUTION, NOTE This symbol warns of a serious hazard. Failure to observe this warning may result in death
More informationBL 200 Strobes. Page F.01U A1.en/ 6/2/2004 ST / PMF1 / zab
PRODUCT INFORMATION BL 200 Strobes Page 1 601- F.01U.000.862 A1.en/ 6/2/2004 ST / PMF1 / zab Table of Contents 1. Product Description............................... 2 2. Features.........................................
More informationPolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours
PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor
More informationProduct Description. Options. Fan Voltage. Electrical Connections Technical Data - Key Characteristics
Cirrus 25/1 The Cirrus 25/1 range of fan heaters uses PTC ceramic heating technology to provide the user with a product ideally suited to climate control. The heater can be controlled independently to
More informationConvertible radiator valve for one-pipe systems, centre distance 35 mm
Convertible radiator valve for one-pipe systems, centre distance 35 mm 56 series ACCREDITED ISO 900 FM 65 033/6 GB Function 56 series convertible radiator valves are used on one-pipe radiator systems.
More informationRosemount 4500 Hygienic Pressure Transmitter. Start
Quick Installation Guide June 2007 Rosemount 4500 Rosemount 4500 Hygienic Pressure Transmitter ProductDiscontinued Start Step 1: Mount the Transmitter Step 2: Set the Switches Step 3: Connect Wiring and
More informationISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)
ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits
More informationcompact office 24V compact office 24V Lux
Presence detector compact office 24V compact office 24V Lux Art. Nr. 201 4 000 Art. Nr. 201 4 001 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 21 Installation manual 40 Manual de
More informationInstallation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets with screw connection (16/32 A)
EN Installation manual surface mounting plugs and socket outlets, panel 60003214 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3
More informationExDetector IRCO2. ExDetector IRHC. Operating and Installation Instructions. Gas Detection and Warning Systems
IRCO2 IRHC Operating and Installation Instructions Gas Detection and Warning Systems Important Instructions Prerequisites for safe and reliable operation of the system: Appropriate transport and handling
More informationQAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers
1 37 Room Unit for use with heating controllers Digital, multi-functional room unit for the convenient operation of heating controllers from the living room. A setpoint knob and an economy button allow
More informationDipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:
Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Phone: 040 807-0 Fax: 040 807-259 Alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC display
More informationAlarm Switchgear AS1-M
Installation, Operating and Maintenance Instructions 1/7 Installation, Operating, and Maintenance Manual for Alarm Switchgear AS1-M These installation, operating and maintenance manual must be handed to
More informationSERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB
SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB TROX (U.K.) LTD CAXTON WAY GB-THETFORD NORFOLK IP24 3SQ TEL: 01842 754545 CONTENTS 1. INTRODUCTION 1. 1 DESCRIPTION 1.2 PACKAGING AND STORAGE 1.3 HANDLING
More informationCooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation
Cooling and heating systems Static cooling ceiling system SKS-/3 DS 10 E 01.010 Static cooling ceiling system SKS-/3 Main features Preliminary remarks / Applications 3 Main dimensions and materials 3 Construction
More informationcompact office 24V compact office 24V Lux
Presence detector compact office 24V compact office 24V Lux Art. Nr. 201 4 000 Art. Nr. 201 4 001 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de
More informationPolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen
PolyGard Single Point Controller SPC-X3-XX for Toxic Gases and Oxygen DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor and
More informationMEAS CAL ALARM WASH CONF APT4000 PH ENCLOSURE TYPE 2. Description
APT4000 Series 4-Wire ph Analyzers 70-82-03-44 10/03 Page 1 of 8 Specification Overview The Honeywell Analytical Process Analyzer (APT) 4000 Series 2 continuously measures ph or ORP in industrial processes
More informationMXD75 Multi Channel Suspended Solids and Turbidity Transmitter
~ Specialists in process suspended solids & turbidity ~ MXD75 Multi Channel Suspended Solids and Turbidity Transmitter Up to 3 Sensors on one Transmitter. Parameters include Suspended Solids, Turbidity
More informationEHA Hoffmann International GmbH
EHA Hoffmann International GmbH User manual EHA-TRANSPRINT HP 2020 Machine-No.: Year: EHA Hoffmann International GmbH Michelsbergstraße 24 D-57080 Siegen/Germany Telephone: +49 271 39 32-0 Telefax: +49
More informationA measured step forward
A measured step forward Operations & Maintenance Manual TM JESCO UV 405-412-440-450-480-550-80 2 LCD LCD PLUS Contents 1. Introduction...3 2. General Principles and Safety Instructions...4 3. Instructions
More informationOnline data sheet WS/WE45-P260S01 W45 PRODUCT PORTFOLIO
Online data sheet WS/WE45-P260S01 W45 B C D E F Illustration may differ Detailed technical data Features Ordering information Type Part no. WS/WE45-P260S01 1016031 Other models and accessories www.sick.com/w45
More informationTX6831 Data Sheet. Features. Benefits
Audio/Visual Alarm Combined audible and visual alarm signalling, for use with sensors and monitoring systems Environments: Mining Tunnelling Machine monitoring Features TX6831 For use with sensors and
More informationTHERMASREG TR 040 THERMASREG TR 060
THERMASREG TR 040 THERMASREG Temperature controllers, one-step, Mechanical temperature controllers wet room temperature controllers THERMASREG TR 040 with switching output and stainless steel capillary
More informationSafety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.
Edition 06.14 GB Operating and installation instructions Lago FB digital remote control Translation from the German 2014 Elster GmbH Safety Please read and keep in a safe place Please read through these
More informationCOMPACT FLAME CONTROLLER CFC 100
COMPACT FLAME CONTROLLER CFC 100 TECHNICAL DESCRIPTION EDITION: TB CFC100 EN REV. 1 2012-03-07 IMPORTANT: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring
More informationMEAS CAL ALARM WASH CONF APT4000 CC ENCLOSURE TYPE 2
APT4000 Series 4-Wire Contacting Conductivity Analyzers Overview 70-82-03-45 10/03 Page 1 of 8 Specification The Honeywell Analytical Process Analyzer (APT) 4000 Series2 continuously measures conductivity,
More informationToroidal Conductivity Transmitters Series APT4000 Specifications
Toroidal Conductivity Transmitters Series APT4000 Specifications 70-82-03-42 March 2001 Overview The Honeywell Analytical Process Transmitter (APT) 4000 Series transmitter continuously measures conductivity,
More informationGASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL
GASGUARD NH 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard NH 3 Operating and Instruction Manual General description. 4 Installation.. 4
More informationSELF PRESERVATION SOCIETY By Jim Creak
SELF PRESERVATION SOCIETY By Editor of the Means of Escape Magazine and Chairman of The Health & Safety Signs Association. w w w. m e a n s - of- e s c a p e. c o m Agenda Regulatory Reform Fire Safety
More informationMANUAL FOR ASSEMBLY AND OPERATION OF ELECTRIC FLOW-THROUGH BOILER/MODULE WITH THREE STAGE CONTROL
MANUAL FOR ASSEMBLY AND OPERATION OF ELECTRIC FLOW-THROUGH BOILER/MODULE WITH THREE STAGE CONTROL PASSPORT OF ELECTRIC BOILER WITH THREE STAGE CONTROL ECOTERMAL MRT/MODULE-T 6, 8, 10, 12, 15, 18, 24, 30
More informationVacuum Controller with Control Unit VC 900
Operating Instructions Read and observe these operating instructions! Vacuum Controller with Control Unit VC 900 KNF Neuberger GmbH Alter Weg 3 79112 Freiburg Germany Tel. +49 (0)7664 / 5909-0 Fax +49
More informationDuct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature
1 882 1882P01 Symaro Duct Sensors for relative humitidy (high accuracy) and temperature QFM31 Use Examples Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for relative humidity and
More informationDuct Humidity and Temperature Sensors 0-10 Vdc or 4-20 ma Outputs Passive sensor PT1000, PT100 NTC, NI1000 etc. Features. IP65 protection.
Features Humidity and Temperature outputs in same unit With or without display Humidity output 0-10 Vdc or 4-20 ma Temperature output 0-10 Vdc or 4-20 ma As option passive direct temperature output PT1000,
More informationFTW04. Application. Types Available. Security Advice Caution. Surface mounting room sensor for relative humidity and temperature.
FTW04 Surface mounting room sensor for relative humidity and temperature Data Sheet Subject to technical alteration Issue date: 06.04.2016 Application Combined sensor for measuring relative humidity and
More informationWater Leak Detector - Four Zone with open/short-circuit detection. Product overview
Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must
More informationOPTISENS TUR 2000 Technical Datasheet
OPTISENS TUR 2000 Technical Datasheet Sensor for turbidity measurement in water and wastewater Rugged design for harsh applications Integrated transmitter with direct 4...20 ma output Near infrared light
More informationFan-and-filter units 4.3. Features. Fast assembly. Application diversity and functions
Fan-and-filter units Features Fan-and-filter units are ideal for dissipating heat loads costeffectively. The pre-requisite is that the ambient air must be relatively clean and with a temperature below
More informationRosemount 3490 Series 4 20 ma + HART Compatible Controller
00825-0100-4841, Rev BA Rosemount 3490 Series 4 20 ma + HART Compatible Controller Quick Start Guide for Installation Failure to follow safe installation guidelines could result in death or serious injury
More informationOperating Manual MS220KA and MSR220KA
Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße
More informationDissolved Oxygen Analyzers
FEATURES DESCRIPTION The model 223 Dissolved Oxygen Transmitter measures dissolved oxygen over the range of 0 to 20mg/l or 0 to 200% saturation. The basic transmitter is available with either a 115VAC,
More informationInstallation manual plugs and connectors QUICK-CONNECT (63 A)
EN Installation manual plugs and connectors QUICK-CONNECT (63 A) 60003217 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal
More informationOPERATING MANUAL RAY-NC 1000 SERIES
Release Date: 24.01.2017 FRABA GmbH 1 / 12 1. Safety Regulations Risk of personal injury and damage to property! The RAY-NC 1000 must only be installed and put into service by qualified and certified electricians
More informationOperating manual GTL 369 GTL 369M GTL 389 GTL 389M. Temperature probe. Please keep the manual for future use.
Operating manual Temperature probe GTL 369 GTL 369M GTL 389 GTL 389M Please keep the manual for future use. L02.0.3X.6C-01 GREISINGER electronic GmbH Hans-Sachs-Str. 26 93128 Regenstauf Germany Fon +49(0)9402-9383-0
More informationInstructions for the fan motor control system, SILVER C
Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is
More information3-way switching valve
Operating Manual UK 3-way switching valve for domestic hot water charging USV 1" AG USV 5/4" AG USV 6/4" IG UK805189 / 201109 Translation of the original instruction manual Please read first This operating
More informationHYGROPHIL H process hygrometer
HYGROPHIL H 4230-10 process hygrometer Continuous humidity measurement in industrial processes. For very high demands in terms of being resistant to corrosion and dirt. Particularly suitable for cases
More informationMEAS CAL ALARM CONF APT2000 CC ENCLOSURE TYPE 2
APT2000 Series 2-Wire Contacting Conductivity Transmitters Overview The Honeywell Analytical Process Transmitter (APT) 2000 Series transmitter is a two-wire 24-Volt device that continuously measures conductivity,
More informationCarbon Monoxide CO Transmitter ADT-X3-1110
Page 1 Sep. 2017 CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air to detect carbon monoxide concentrations (CO).
More informationPH / ORP Analyzers MODEL OPM223/253. Wedgewood Analytical Inc. Liquid Analytical Measurement & Control Specialists DESCRIPTION FEATURES APPLICATIONS
FEATURES DESCRIPTION The model 223pH / ORP Transmitter is ideal for use where economy and reliability are the prime considerations. The basic transmitter is available with either a 115VAC, 220VAC or 24V
More informationBusch-Watchdog presence. Overview and applications of presence detectors.
Busch-Watchdog presence Overview and applications of presence detectors. Do without the unnecessary. And save energy. Presence detectors automatically detect the presence of someone inside the room to
More informationBranching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH
AAB 430-2410-001 EN11 EN Operating manual Branching and Connection Box AAB GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 D-41747 Viersen, GERMANY info@gte.de +49(0)2162 / 3703-0 www.gte.de Branching
More informationWIO200 Water in oil sensor
WIO200 Water in oil sensor User manual Rev. 1.15 Dato: 2011-11-03 Page 1 of 24 TABLE OF CONTENTS Table of contents... 2 Introduction... 3 Safety Advice... 4 Function... 6 Normal operation... 7 Failure
More informationPM100V PM80V PM15V. Ex works. Depending on the specific range of application a regular ecalibration of the sensor head (PMU-V) has to be effected.
Galltec Mess- und Regeltechnik GmbH MELA Sensortechnik GmbH D-71145 Bondorf. Germany D-07987 Mohlsdorf-Teichwolframsdorf. Germany Tel. +49 (0)7457-9453-0. Fax +49 (0)7457-3758 Tel. +49(0)3661-62704-0.
More informationInstallation Instruction Venturi-Air Duct Kit. (Part No. S )
Installation Instruction Venturi-Air Duct Kit (Part No. S4-34760) Intended purpose This product is designed for installation on a loop circuit of a Vigilon system. Warning In order to ensure correct and
More informationThermocouples and Resistance Thermometers
Operating Instructions 42/10-20-EN Thermocouples and Resistance Thermometers Contents Blinder Text Thermocouples and Resistance Thermometers Operating Instructions 42/10-20-EN 06.2006 Rev. 03 Manufacturer:
More informationProduct Manual Glue Applicators MS 80 and MS 200
Product Manual www.pakarte.com Glue Applicators MS 80 and MS 00 Translation from German to English Table of Contents Product Description General Safety Instructions Safety Measures to be taken during Operation
More informationINSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor
INSTRUCTION MANUAL Oil-in-Water Monitor Type OMD-12 DECKMA HAMBURG GmbH Kieler Straße 316, D-22525 Hamburg Tel.: ++49 40 54 88 76-0, Fax: ++49 40 54 88 76-10, email: post@deckma.com IMPORTANT NOTICE Replacement
More informationHold-open magnets DORMA
Hold-open magnets DOA DOA Hold-open magnets A modular system for fire and smoke doors Setting new standards for hold-open magnets DOA s new range of hold-open magnets provides the perfect complement to
More informationLED Compatible Daylight Harvesting and Motion Sensor System
MADE IN GERMANY BY OUR FRIENDS AT EPV DH1 Technical Data MAX. MOUNTING HEIGHT AMBIENT TEMP. CURRENT CONSUMPTION 5m 0 50 C (Indoor) max. 15mA at 24V SWITCHING CAPACITY Occupancy Signal: Max. Dimming Status
More informationSensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0
Sensor module Operating instructions Sensor module, Document No. 11-51P2-7D0001 Version: 17 May 2011/Rev. 0 Operating Instructions Sensor-Module Type: 17-51P2-. Document no.: 11-51P2-7D0001 Version: 17.
More informationPSC-ID-x-CM Series Ceiling Mount Occupancy Sensor
TECHNICAL SPECIFICATIONS PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor Basic Features Line voltage version: 120-277VAC, 60Hz Low voltage version: 24VDC, requires separate class 2 power supply PIR sensor
More informationTel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified
Linear detection solution Product Brochure About Us Signaline is a comprehensive range of linear detection systems providing solutions for fire and water leak detection. Our linear detectors are 100% manufactured
More informationSL V Potentiometer LED CONTROLLERS
SL5007 1-10V Potentiometer LED CONTROLLERS SL5007 1-10V POTENTIOMETER The SL5007 1-10V dimming potentiometer is a simple and inexpensive device that can interface 1-10V enabled devices, such as the Superlight
More informationWaste water ejection unit
Waste water ejection unit Over ground box SWH 500/50-80 SWH 500/50-80 Operation manual Table of contents: Page Declaration of conformity... 3 1. General... 4 1.1 Introduction... 4 1.2 Enquiries and orders...
More informationEKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS
ELECTRIC DUCT HEATERS EKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS USER MANUAL Subject to technical modification EKA_P0093_AZ_0001 SAFETY INSTRUCTIONS AND PRECAUTIONS 3 WARNING! SAFETY REQUIREMENTS
More informationResidual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)
Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010 Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC
More informationHygro/hygrothermal transducers (hygrometric)
Data Sheet 90.7031 Page 1/7 Hygro/hygrothermal transducers (hygrometric) for measuring relative humidity and temperature for mounting indoors, outdoors, and in air ducts with resistance, current or voltage
More information