DISTRIBUTION and CONTROL

Size: px
Start display at page:

Download "DISTRIBUTION and CONTROL"

Transcription

1 DISTRIBUTION and CONTROL Installation Planning Installation instructions & design manual e9717

2 Page 2 Table of Contents DISTRIBUTION and CONTROL 1 General information Safety information Distribution and control A few system diagrams (not intended to be exhaustive) Manifold cabinets Fixing bars (wall mounting without manifold cabinet): Manifold cabinet on-wall Manifold cabinet UF in-wall Bracket set and dimensions VarioManifold Assembly thermometer Possible variations Connecting the Variotherm pipes Filling/flushing/deaerating the system Pressure test Hydronic balancing Hydronic balancing handover protocol Flow characteristic curve Thermoelectric actuators Thermoelectric actuator Thermoelectric actuator with limit switch Installing the thermoelectric actuators Controllers Type overview Fitting dew point sensor Fitting heating surface sensor Pumped VarioManifold Description Weather-guided control station for surface heating for systems featuring a main pump Pump PVS (WILO Yonos PARA 15/6) Regulating valve Pressure loss in the boiler circuit WHR36 weather-guided controller Troubleshooting Pump Microstation Description Weather-guided control station for surface heating for systems featuring a main pump Pump PMS (WILO Yonos PARA 15/6) Regulating valve Pressure loss in the boiler circuit WHR36 weather-guided controller Modification for operation with thermoelectric actuator Troubleshooting Return temperature limiter (for one surface heating circuit) RTL valve RTLT valve (with thermostatic valve)... 3

3 - SET PROG + Installation instructions & design manual 1 General information Page 3 1 General information 1.1 Safety information - The electrical and hydraulic connection and service work on the device may only be provided by authorised specialist personnel. - The devices are designed for use in dry, closed rooms. - The electrical installation standards and regulations specified by the local energy supply companies should be observed, together with the locally applicable regulations and standards for heating installations. - Faults in the connection can cause damage to the device! We bear no liability for damage caused by incorrect connection and/or inappropriate handling of the device. - If the system components are installed or commissioned incorrectly, all claims on the basis of the manufacturer s warranty and guarantee become void. 1.2 Distribution and control Heating/cooling manifolds are installed for the distribution of water within the heating/cooling system. 1.3 A few system diagrams (not intended to be exhaustive) Skirting heating system PIANO H or PIANO HK(T) with clock PIANO HK or PIANO HKT System wall heating tr = tf = tf = tr = 5 C 6 C 4 C 3 C Boiler (also storage tank) tf = 6 C tr = 5 C Floor heating System with manifold Skirting heating system (with thermostatic valve) Radiator (existing) PIANO HK or PIANO HKT Modular wall heating tr = tf = tf = t R = 5 C 6 C 4 C 3 C Boiler (also storage tank) tf = 6 C tr = 5 C Drywall floor heating System with manifold and existing 2-pipe system

4 - SET PROG SET PROG Page 4 1 General information DISTRIBUTION and CONTROL PIANO HW Sensor fitted between pipes PIANO HKT Dew point sensor Tepidarium Tiled stove Cosy corner bench tf = 17 C t R = 21 C Modular ceiling cooling/heating tf = 6 C tr = 5 C Boiler (or buffer storage tank) Tepidarium, tiled stove or cosy corner bench system Heat pump (can be switched to cooling) Surface heating and cooling system PIANO HK-Funk (receiver) PIANO HK PIANO HK-Funk (thermostat/transmitter) Modular wall heating/ cooling Floor heating e.g. living room e.g. office Radio solution in the absence of ductwork between the room thermostat and thermoelectric actuator If you wish to create several surface heating circuits with low temperatures using an existing 2-pipe system, then install a microstation with a pump or a pumped manifold. Radiator (existing) Floor heating 1-2 heating circuits t F = 4 C Pump Microstation Optionally: PIANO HK(T) with clock in reference room (Antechamber) PIANO H 23V AC 5 Hz Radiator (existing) tr = 3 C System wall heating tf = 4 C Pumped Vario- Manifold tr = 3 C tr = tf = 5 C 6 C 2-14 heating circuits tf = tr = Boiler (or buffer storage tank) 6 C 5 C Boiler (or buffer storage tank) Pump Microstation and fixed-value regulator Weather-guided pumped manifold

5 Installation instructions & design manual 1 General information Page 5 Examples for cold water production (not provided and not intended to be exhaustive): Room thermostat e.g. PIANO HKT RT43 e.g. Module- Ceiling VarioManifold Pump Expansion tank Dew point sensor Variotherm components Ball valve 17 C * 21 C * Check valve RT43 Dew point sensor e.g. ModuleWall * Typical dimensioning temperatures Dirt trap Heat exchanger Cold production Outdoor use incl. safety devices (not provided) 8 C * 12 C * 3 way mixing valve Brine pipeline Heat generation e.g. gas, oil, solid fuel boiler, remote heating, buffer Safety valve Brine pipeline Brine pipeline Ground collector, deep-drill boreholes, etc. Production well Injection well Please note legal specifications for water!

6 Page 6 2 Manifold cabinets DISTRIBUTION and CONTROL 2 Manifold cabinets If you intend to use manifold cabinets, these are mounted before the manifolds are installed. 2.1 Fixing bars (wall mounting without manifold cabinet): The fixing bars are mounted to the wall at a suitable distance depending on the manifold size using the screws (4x) provided. The VarioManifold, Pumped VarioManifold or Pump Microstation can then be attached to them. 2.2 Manifold cabinet on-wall The manifold cabinet is placed on the wall and screwed tight. For the bracket installation, see section mm B 14 mm C-rails 123 mm Fixed back panel Front door Screed facing 565 mm - 18 mm 1 mm 465 mm Manifold cabinet types VSA1 VSA2 VSA3 VSA4 B (mm) VarioManifold circuits 2-3 1, Pumped VarioManifold circuits Pump Microstation circuits

7 Installation instructions & design manual 2 Manifold cabinets Page 7 Cutting check * Screed or pipe s minimum vertical cover for screed floor heating system FFOK... Upper edge of finished floor RDOK... Upper edge of raw slab 5 mm* 15 mm Floor covering FFOK Screed Raw slab RDOK mm 5 mm 5 mm Example for on-wall installation 2.3 Manifold cabinet UF in-wall D C 8 mm 13 mm 15 mm A B (±,5) C-rails mm Deviating pipe rail C + 8 mm Front door Front frame Screed facing 657 mm mm 11 mm 547 mm mm Manifold cabinet types VSU1 VSU2 VSU3 VSU4 A (mm) B (mm) C (mm) D (mm) VarioManifold circuits Pumped VarioManifold circuits Pump Microstation circuits

8 Page 8 2 Manifold cabinets DISTRIBUTION and CONTROL 1 Remove the front frame and the base cover from the cabinet. 2 Place the cabinet in the recess in the wall, straighten it using the adjustable feet and fix it to the unfinished floor. 3 Mount the bracket set to the rear side of the manifold (see chapter 2.4). 4 Snap the VarioManifold into the C-rails and affix with the screws. 5 Connect the connection pipes. To do so, pre-cut opening plates on the right and left can be broken open. 6 Fix the wall cabinet in the wall with quick setting cement. Screw it to the supporting structure in the drywall. 7 Lay out the heating/cooling distribution circuits. Feed the flow and return behind the deviating pipe bend into the floor and towards the heating surfaces. In-wall mounted front frame: 8a Attach the screed facing (this will not be plastered over later) - this covers the area between the front frame and the finished floor level. Cover all visible parts well (e.g. with painter's tape) - protect the opening from dirt with card or plastic film. 9a After completing the wall, remove the protective coverings or adhesive tapes and attach the doors. Cutting check 5 mm* 15 mm Floor covering FFOK Screed Lintel Raw slab * Screed or pipe's minimum vertical cover for screed floor heating system FFOK... Upper edge of finished floor RDOK... Upper edge of raw slab RDOK mm 595 mm 45 mm mm max. 8 mm for skirting board Example for in-wall mounted front frame

9 Installation instructions & design manual 2 Manifold cabinets Page 9 Wall-mounted front frame: 8b. Attach the screed facing (this will not be plastered over later) - this covers the area between the front frame and the finished floor level. Align the front box edge to the finished plaster edge or finished wall edge. Cover all visible parts well (e.g. with painter's tape) - protect the opening from dirt with card or plastic film. 9b. After completing the wall, remove the protective coverings or adhesive tapes and attach the front frames and doors. Cutting check 5 mm* 15 mm Floor covering FFOK Screed Lintel Raw slab * Screed or pipe's minimum vertical cover for screed floor heating system FFOK... Upper edge of finished floor RDOK... Upper edge of raw slab RDOK mm 585 mm 415 mm 8-1 mm max. 48 mm for skirting board Example for wall-mounted front frame 2.4 Bracket set and dimensions Demounting: 4.8 x 19 mm , Bracket 4.8 x 9.5 mm C-rail or fixing bar 4.8 x 19 mm 52, x 9.5 mm

10 Page 1 3 VarioManifold 5. DISTRIBUTION and CONTROL 3 VarioManifold 5. Manifold module with outlet facing upwards e.g. room thermostat PIANO H 2-25 mm Flow 23 V AC 5 Hz Electrical distribution box (in close proximity to the heating/cooling distribution manifold) for example 1,5 mm² Return Elbow fitting 6/4" 9 (optional): Installation length Locking ball valve, supply (1" female thread) Locking ball valve, return (1 female thread) Manual air vent Thermometer Feed & drain cock Flow indicator Flow segment with flow indicator Return segment with stop valve Technical data: Max. test pressure: 1 bar (only with water) Operating temperatures: -2 C bis +9 C (anti-freeze filling) Thermoelectric actuator Name labels blue End plates (isolated) Variotherm 3/4 Eurocone clamping screw fitting (for Variotherm pipes ø11.6, ø16 and ø2 mm Insulating grommet (optional) Max. operating overload pressure: 6 bar Installation depth of manifold: 93 mm or 8 mm with removed thermometers Manifold Inst. length installation length +15 mm Manifold Inst. length 1 circuit (1-beam) 345 mm 1 circuits 645 mm 2 circuits 245 mm 11 circuits 695 mm 3 circuits 295 mm 12 circuits 745 mm 4 circuits 345 mm 13 circuits 795 mm 5 circuits 395 mm 14 circuits 845 mm 6 circuits 445 mm 15 circuits 895 mm 7 circuits 495 mm 16 circuits 945 mm 8 circuits 545 mm 17 circuits 995 mm 9 circuits 595 mm The VarioManifold is made of plastic modules which are fitted together according to the number of heating/cooling circuits required. 3.1 Assembly thermometer Front side Rear side Screw the immersion sleeve into the connection block and tighten with 15 Nm. Then insert the thermometer. Do not completely tighten the feed cock remains just visible.. The seal

11 Installation instructions & design manual 3 VarioManifold 5. Page Possible variations Basic Version Example: 5 low-temperature circuits with floor heating system and wall heating system Example Beispielschema: diagram: M 55 C 45 C 4 C 3 C Combination - two different temperature circuits Example: 6 low-temperature circuits with wall and floor heating, 2 high-temperature circuits for trench heating and cosy corner bench Dividing plate Dividing plate Other variants: 1-beam variant Example: 1 low-temperature circuit with floor heating system Flow connected to the left, return to the right Dimensioning example for supply pipe to heating distribution manifold t (t F - t R ) = 1 K Heating circuits Heat output Dimensions for copper/multi-layer supply pipes kw for example Cu22x1. / 26x kw for example Cu28x1. / 32x kw for example Cu35x1.2 / 4x4 Dimensioning example for supply pipe to cooling distribution manifold t (t F - t R ) = 4 K Cooling circuits Cooling performance Dimensions for copper/multi-layer supply pipes kw for example Cu22x1. / 26x kw for example Cu28x1. / 32x kw for example Cu35x1.2 / 4x4 One circuit facing upwards All circuits facing upwards

12 Page 12 3 VarioManifold 5. DISTRIBUTION and CONTROL 3.3 Connecting the Variotherm pipes Straight, level cut with pipe cutting pliers Calibration and chamfering tool or ø 2 mm for ø 16 mm for ø 11.6 mm 1 The supply pipe is cut off straight across and then calibrated. 2 Push the pipe into the clamping screw fitting up to the stop, and in this position tighten the union nut hand-tight. 3 Tighten the clamping screw fitting for one more turn with an open-end wrench. The tightening torque is 35 Nm. Flow indicator VarioManifold flow module Clamping screw fitting* 3/4"EURO Insulating grommet, Protection against condensation at the clamping screw fitting in case of cooling. Clamping screw fitting* Supply pipe** ** Supply pipe * Clamping screw fitting Variomodular pipe 2x2 Laser 3/4"EUROx2 (Z15) VarioProFile pipe 16x2 Laser 3/4"EUROx16 (Z14) Variomodular/VarioProFile pipe 11.6x1.5 Laser 3/4"EUROx11.6 (Z13) Pre-insulated Variomodular pipe 16x2 Laser 3/4"EUROx16 (Z14) 3.4 Filling/flushing/deaerating the system Purified water as per ÖNORM H and VDI 235 OFF 1 Main locking ball valves and all return modules are closed. 2. All flow valves are opened. 3. Then connect the filling and flushing station to both feed & drain cocks on the supply and return pipes.

13 Installation instructions & design manual 3 VarioManifold 5. Page 13 Attention: Flushing only in flow direction! ON ON 4 Switch on the flushing and filling station. Then turn on the feed & drain cocks; the supply pipe is pressurised and the return segments of the first two heating/cooling circuits are opened. This thoroughly flushes water through the supply line into the two heating/cooling circuits. 5 Once the water comes out with no air bubbles, the opened return modules are to be closed. 6 Immediately afterwards, the next two return modules are to be opened. The same procedure is followed for the other circuits in sequential order, until the entire system is filled. ON OFF 7 Finally, this flushing procedure is repeated upon opening of all flow and return modules. 8. First turn off the feed & drain cock on the return pipe, then immediately turn off the feed & drain cock on the supply pipe. Turn off the flushing and filling station. Open the main locking ball valves. 3.5 Pressure test Close ball valves Test pressure: minimal 4 bar maximum 6 bar 24 hours Pressure test pump 4) Then retighten screws and reduce pressure to 2-3 bar. Maintain this pressure until completion of the object in order to identify any possible damage. Caution: Concrete (screed/industrial floor heating systems) heats up during the binding process, increasing the pressure in the heating system. Always use an expansion tank and a safety valve!

14 Page 14 3 VarioManifold 5. DISTRIBUTION and CONTROL 3.6 Hydronic balancing The length of the Variotherm pipe (heating surface + supply pipes), possible connection parts (e.g. press-fit couplings) and the distribution manifold determine the pressure loss in the individual heating/cooling circuits. For hydronic balancing, the relevant circulation pump must be running. A water flow rate is assigned to each heating/cooling circuit. Short circuit > Compensate by further closing the flow indicator valve. Hydronic balancing is performed by means of the flow rate valve in the flow (orange segment). 1. Fully open all return valves. Close all flow valves. Pull up the affixing ring and turn it anticlockwise until it stops. Then press down the affixing ring. 2. Slowly open the flow indicators in sequential order until the display has reached the required flow rate. Because the flow rates of the individual heating/cooling circuits affect one another, it may be necessary to make corrections to the values in a second flow. Pull up the affixing ring and turn it clockwise until it stops. The press the affixing ring down. Read here! * * Values may differ due to no purified water or polluted heating water (corrosion).

15 Installation instructions & design manual 3 VarioManifold 5. Page Hydronic balancing handover protocol Hydronic balancing has been carried out according to the values of the heat requirement calculation Hydronic balancing has been carried out with individual adjustments Heating/cooling distribution manifolds Heating/cooling circuit Designation Setting l/h Carried out by: Construction project: Place, date, signature (installer): Place, date, signature (installer):

16 Page 16 3 VarioManifold 5. DISTRIBUTION and CONTROL 3.8 Flow characteristic curve p To ascertain the pressure loss of the heating/cooling distribution manifold for the respective heating/cooling circuits (without pressure loss of pipes). Max. opened return valve - with clamping screw fitting for VarioProFile pipe 11.6x1.5 - with clamping screw fitting for VarioProFile pipe 16x2 1 Flow rate Q [l/h] Flow valve 1 turn opened Flow valve 3/4 turns opened Flow valve 1 turn opened Flow valve 3/4 turns opened Flow valve 1/2 turns opened Flow valve 1/2 turns opened Flow valve 1/4 turns opened Flow valve 1/4 turns opened Kv value 1,,1 1 2,,2 2 3,,3 3 4,,4 4 5,,5 5 6,,6 6 7,,7 7 8,,8 8 9,,9 9 1, 1, 1 [mwc] [bar] [Pa] Pressure loss p

17 Installation instructions & design manual 4 Thermoelectric actuators Page 17 4 Thermoelectric actuators The Thermoelectric actuator of the heating/cooling distribution manifold opens or closes the circuit depending on the requirements of the room thermostat. 4.1 Thermoelectric actuator PTC expansion material element function Technical data Type (voltage) 23 V AC 5/6 Hz 24 V AC/DC -6 Hz Activation current < 55 ma (max. 1 ms) < 3 ma (max. 2 min.) Operating current 4.3 ma 42 ma Operating power 1 W Design Closed when power off Closing and opening times approx. 3,5 min. Adjustment travel 4 mm Adjustment force 1 N ±5 % Media temperature - 1 C Storage temperature C... Ambient temperature C... Protection degree/protection IP 54 / II IP 54 class CE conformity as per EN 673 Housing/housing colour: Polyamide/light blue Weight 1 g with 1 m connection cable Connection line 2 x,75 mm² PVC grey / 1 m Overvoltage resistance as per EN min. 2.5 kv min. 2.5 kv 4.2 Thermoelectric actuator with limit switch This variant of the thermoelectric actuator is also fitted with an internal switch (open when power off), which closes as soon as voltage is applied to the actuator. PTC expansion material element First-Open- First-Open Funktion* First-Open- First-Open Funktion* function limit switch Technical data Type (voltage) 23 V AC 5/6 Hz 24 V AC/DC -6 Hz Activation current < 55 ma (max. 1 ms) < 3 ma (max. 2 min.) Operating current 4.3 ma 42 ma Operating power 1 W Design Closed when power off Closing and opening times approx. 3 min. Adjustment travel 4 mm Adjustment force 1 N ±5 % Limit switch - switching current 23 V AC: 5 A ohmic load, 1 A inductive load 24 V DC: 3 A ohmic load, 1 A inductive load Switching point approx. 2 mm Media temperature - 1 C Storage temperature C... Ambient temperature C... Protection degree/protection class IP 54 / II IP 54 / III CE conformity as per EN 673 Housing/housing colour: Polyamide/light grey Weight 15 g with 1 m connection cable Connection line 4 x,75 mm² PVC grey / 1 m Overvoltage resistance as per EN min. 2.5 kv 1 kv *First-Open function: The Thermoelectric actuator is switched to open when power off by default so that the installer can immediately start the system with installed thermoelectric actuators. If the thermoelectric actuator is energised for > 6 minutes, it will be switched to closed when power off.

18 Page 18 4 Thermoelectric actuators DISTRIBUTION and CONTROL Thermoelectric actuator with limit switch 1 2 Room thermostat N L1 PE Cabling diagram - basic wiring Load, e.g. pump N L1 PE Functionality description:: 1 No heating/cooling requirement, room thermostat relay output open > limit switch open, as the thermoelectric actuator is powered off > pump off 2 Heating/cooling requirement present, relay output of the room thermostat closed > limit switch closed, as voltage is applied to the thermoelectric actuator > pump running 23 V AC L1 S RT2 RT1 RT2 P RT S P N PE Thermoelectric actuator with limit switch Thermoelectric actuator (without limit switch) Thermoelectric actuators on room thermostat 1 (RT1), e.g. living room Thermoelectric actuators on room thermostat 2 (RT2), e.g. bedroom Wiring of limit switches for several thermoelectric actuators on a pumped manifold (example) Functionality description: The pump runs if voltage is applied to at least one thermoelectric actuator with a limit switch. The pump is off when all thermoelectric actuators with a limit switch are closed. 4.3 Installing the thermoelectric actuators It is not necessary to drain the system. 1 Remove the valve's protective cap 2 Screw on the grey adapter ring 3 Click thermoelectric actuator into place

19 Installation instructions & design manual 5 Controllers Page 19 5 Controllers 5.1 Type overview Central heating systems are to be equipped with state-of-the-art automatic devices for room-specific temperature control. Also see operating manual for installation instructions. PIANO H electronic room thermostat for heating mode. Item number: RT4 PIANO HK electronic room thermostat for heating/cooling mode. Item number: RT41 PE N L LOAD LAST DC AC PE N L LOAD LAST DC AC Operating voltage: 23 V AC, 5 Hz Relay output: floating input 1) (NO contact), 1 A, 23 V AC Temperature range: C Switching difference: ±.2 K Protection degree: IP 3 Features: KTY semiconductor sensor Screw connections On/off switch Switching status display Weight: 85 g Protection class: II Size (h x w x d): 81 x 81 x 16 (25) mm Attachment: to in-wall box Colour: RAL 91 Pure white Operating voltage: 23 V AC, 5 Hz Relay output: floating input 1) (NO contact), 1 A, 23 V AC Temperature range: C Switching difference: ±.2 K Protection degree: IP 3 Features: KTY semiconductor sensor Screw connections Off/heating/cooling switch Switching status display Weight: 95 g Protection class: II Size (h x w x d): 81 x 81 x 16 (25) mm Attachment: to in-wall box Colour: RAL 91 Pure white PIANO HKT electronic room thermostat for heating/cooling operation. Item number: RT42 PIANO HK(T) electronic room thermostat with clock for heating/cooling mode. Item number: RT43 PE N L LOAD LAST DC AC PE N L LOAD LAST DC AC - SET PROG + Optionally: 8 9 Dew point sensor Taupunktwächter Operating voltage: 23 V AC, 5 Hz Relay output: floating input 1) (NO contact), 5 A, 23 V AC Temperature range: C Switching difference: ±.2 K Protection degree: IP 3 Sensor cable: 5 m (extendible to max. 2 m with 2x1.5 mm²) Features: incl. dew point sensor KTY semiconductor sensor Screw connections Off/heating/cooling switch Switching status display LED red/orange Weight: 21 g Protection class: II Size (h x w x d): 81 x 81 x 16 (36) mm Attachment: to in-wall box Colour: RAL 91 Pure white 1) The required safety distances (EN 673-1) are to fulfill externally! 8 9 Dew Taupunktwächter point sensor (Optional) (optional) Operating voltage: 23 V AC, 5 Hz Relay output: floating input 1) (NO contact), 5 A, 23 V AC Temperature range: C Temperature switching difference: settable Protection degree: IP 3 Features: KTY semiconductor sensor Screw connections Switching status display Digital clock with weekly program 32 switching points (heating) and 32 switching points (cooling) (Optionally: operation with dew point sensor, item number: RT421) Weight: 19 g Protection class: II Size (h x w x d): 81 x 81 x 16 (36) mm Attachment: to in-wall box Colour: RAL 91 Pure white

20 Page 2 5 Controllers DISTRIBUTION and CONTROL PIANO HF electronic room thermostat with heating surface sensor for heating mode. Item number: RT44 PIANO HW electronic surface thermostat with clock for heating mode. Item number: RT6 PE N L LOAD LAST Sensor DC AC PE N L LOAD LAST Sensor DC AC - SET PROG + Operating voltage: 23 V AC, 5 Hz Relay output: non floating input (NO contact), 1 A, 23 V AC Temperature range room: C Temperature range surface: C Switching difference: ±.2 K Protection degree: IP 3 Sensor cable: Length: 4 m (extendible to max. 25 m with 2x.75 mm²) Features: KTY semiconductor sensor (room & surface) Screw connections On/off switch Switching status display Individual settings for room and surface temperature Weight: 21 g Protection class: II Size (h x w x d): 81 x 81 x 16 (25) mm Attachment: to in-wall box Colour: RAL 91 Pure white Surface mounting frame for room thermostat Item number: RT491 Operating voltage: 23 V AC, 5 Hz Relay output: non floating input (NO contact), 16 A, 23 V AC Temperature range surface: C Temp. switching difference: settable Protection degree: IP 3 Sensor cable: Length: 4 m (extendible to max. 25 m with 2x.75 mm²) Features: KTY semiconductor sensor Screw connections Switching status display Digital clock with weekly programme Weight: 28 g Protection class: II Size (h x w x d): 81 x 81 x 16 (36) mm Attachment: to in-wall box Colour: RAL 91 Pure white PIANO HK-Funk electronic room thermostat for heating/cooling mode. Item number: RT47 Radio receiver connection diagram: PE N L LOAD LAST DC AC Application: Weight: Size (h x w x d): Attachment: Colour: for installation without existing in-wall box, compatible with following room thermostates: PIANO H PIANO HK PIANO HF 35 g 81 x 81 x 18 mm surface mounting RAL 91 Pure white Arrangement of multiple room thermostats: > 3 mm Radio thermostat Radio receiver Radio thermostat (transmitter): Operating voltage: 3 V battery (durability approx. 2 years) Output: Radio transmitter, Radio signal MHz Temperature range: C Switching difference: ±.2 K Protection degree: IP 2 Features: KTY semiconductor sensor Screw connections Off/heating/cooling switch Weight: 7 g Protection class: III (extra-low voltage, DIN EN 673-1) Size (h x w x d): 81 x 81 x 16 mm Attachment: surface mounting Colour: RAL 91 Pure white Radio receiver: Operating voltage: 23 V AC, 5 Hz Relay output: non floating input (NO contact), 23 V AC, max. 16 A (cosφ = 1), max. 4 A (cosφ =.6) Receiving frequenzy: 433,92 MHz Features: Switching status display Weight: 9 g Protection class: II Protection degree: IP 3 Size (h x w x d): 71 x 71 x 31 mm Attachment: surface mounting or in-wall box (outside of the manifold box)

21 Installation instructions & design manual 5 Controllers Page Fitting dew point sensor With PIANO HKT and PIANO HK(T) with clock, the associated dew point sensor (available separately for PIANO HK[T] ) is connected. Use: SystemWall cooling, EasyFlexWall cooling, ModuleWall/ModuleCeiling cooling. The dew point sensor should be fitted at the position on the pipe that is expected to dew first. Generally this is the case at the flow entry. The dew point sensor is fitted to the pipe using cable ties. Make sure that there is good thermal contact between the pipe and the sensor (use heat transfer paste). The supply pipes should be sufficiently secured. Dew point sensor Inspection opening Wiring in ductwork Flow Flow Wiring in ductwork Flush-mounted junction box 1 x 1 mm Dew point sensor PIANO HKT, PIANO HK(T) with clock Dew point sensor PIANO HKT, PIANO HK(T) with clock Cable strap Thermal paste VarioProFile pipe Cable strap Thermal paste Variomodular pipe Example System wall cooling Example Modular ceiling cooling 5.3 Fitting heating surface sensor Electrical in-wall box ø 6 mm for PIANO HF/HW (usually outside or next to the wall heating). With PIANO HF and PIANO HW with clock, the supplied heating surface sensor is connected. Use: EasyFlex wall heating (e.g. centrally heated tile stoves). Before plastering, the ducting (e.g. Cu12 pipe) for the heating surface sensor is clamped in a suitable reference position between the Variotherm pipes. Cap e.g. ducting Cu12x1 for heating surface sensor Wiring in ductwork Empty pipe Cu12x1 Heating surface sensor Example EasyFlex wall heating

22 - SET PROG Page 22 6 Pumped VarioManifold 5. DISTRIBUTION and CONTROL 6 Pumped VarioManifold Description For installing surface heating systems (2 15 heating circuits) in high-temperature heating systems (2-pipe system) with existing circulation pump. The flow temperature of the boiler circuit must be at least 1 K higher than the set flow temperature of the surface heating circuit. Observe the required pipe diameter (capacity) to the Pumped Manifold. Primary pressure required! A Variant A or B 42 mm B mm Flow indicator Regulating valve Pump PVS (WILO Yonos Para 15/6) Flushing ball valve (close when flushing) Immersion sleeve for remote sensor (Fixed value control station A ) or for flow temperature sensor (weather-guided control station B ); contains heat transfer paste (Safety data sheet: Temperature limiter (Factory setting 6 C) 23V AC, 5 Hz (provided connection cable: 3 x.5 mm² [max. 3 A], please note the electrical protection!) Locking ball valve (3/4 female thread) Fixed value control station 23V AC 5 Hz Consumers with presettable flow rate A Optional: PIANO HK(T) with clock Weather-guided control station 23V AC 5 Hz WHR36 External sensor B Consumers with presettable flow rate 4 C 3 C 3 C Fixed value regulator 6 C 5 C Heat generator 4 C 3 C Actuator (VT3FC) 3 C 6 C 5 C Heat generator Main pump Main pump 6 C 45 C 6 C Die Kessel-Vorlauftemperatur 45 C muss mindestens 1 K höher als die eingestellte Heizkurventemperatur sein (= Flächenheizung Vorlauftemperatur ). Fixed value regulator: The flow temperature of the surface heating circuit can be continuously adjusted between 2 and 7 C. (Values of temperature scale are reference values for the flow temperature!) Vorlauftemperatur ( C) 7 Standard 65 Heating curve WHR36: -5 K +5 K K +1 K K Standard Außentemperatur ( C) +1 K

23 Installation instructions & design manual 6 Pumped VarioManifold 5. Page Weather-guided control station for surface heating for systems featuring a main pump Examples for power: Temperatures Flow temp. Power surface hea. cir. boiler circuit Volume flow in boiler circuit: 5 l/h 4/3 C 5 C 1163 W Flow indicator in boiler circuit 17 l/h 4/3 C 6 C 1745 W 4/3 C 7 C 2326 W Volume flow in boiler circuit: 15 l/h 4/3 C 5 C 3489 W 145 l/h 12 l/h 6 l/h Surface heating circuit Boiler circuit 4/3 C 6 C 5234 W 4/3 C 7 C 6978 W Read here! 6.3 Pump PVS (WILO Yonos PARA 15/6) 6, 1 1 Useful head [mwc] 5, 4, 3, 2, 1, Constant differential pressure ( p-c), for surface heating Venting function,2,4,6,8 1, 1,2 1,4 1,6 1,8 2, 2,2 2,4 2,6 Volume flow [m³/h] Variable differential pressure ( p-v) 6.4 Regulating valve Pressure loss in the boiler circuit The flow rate in the boiler circuit is adjusted using the regulating valve when the fixed-value regulator or actuator is fully opened ( ) Example 5 heating circuits: Pressure loss [mbar] Closed Open 2, 2,5 3, 4, Factory settings fully open Searching for: pressure loss and volume flow in boiler circuit, if regulating valve is 3 turns open. Desired: Boiler flow temperature: 55 C Surface heating temperature: 4/3 C Required volume flow in surface heating circuit: 5 x 75 l/h 4 C 2 mbar Example l/h Volume flow [l/h] 3 C 436 W 5 x 75 l/h p 436 W 15 l/h 3 C 55 C 2 mbar (.2 (,2 mwc) mws)

24 - + Page 24 6 Pumped VarioManifold 5. DISTRIBUTION and CONTROL 6.5 WHR36 weather-guided controller Terminal Klemmleiste block A A N 23V AC 1 L Terminal Klemmleiste block BB Electrical connection: Terminal block A, 23V AC 1 Power supply phase 2 Power supply neutral conductor 3-4 Bridge PVS pump incl. safety thermostat 5-6 Schaltstrom Relais max.,8 A 7-8 Thermoelectric actuator (only item no. VT3FC permissible) Boiler demand, with contact 5-6 switched (potential-free, max A) RoHS WHR36 opened Use block terminal provided by customer! PE N L WHR36, PIANO WHR36, terminal Klemmleiste HK(T) with B block clock Taupunktwächter Dew point sensor (optional) (Optional) DC AC Terminal block B, safety-low voltage 1-2 Bridge, or optionally: Room thermostat with clock (part no. RT43) (see connection diagram*) 3-4 External sensor 1) (cable for example 2 x.75 mm², max. 5 m) 5-6 Flow sensor 1) (cable for example 2 x.75 mm², max. 5 m) 7-8 Bridge, or switching contact for pump & actuator On/Off 1) Use original sensor! Control lamps: - + Setting the heating curve: Green LED... Thermoelectric actuator activation Red LED... Self diagnosis or alarm message Green LED... Pump PVS Orange LED... Power supply Self-diagnosis is performed when starting for the first time. The red LED flashes for about 5 seconds and goes out. After about 5 minutes the controller begins to adjust the flow temperature to the heating curve. If the red LED is continuously illuminated an alarm is present. In this case the wiring must be checked. An alarm occurs if the flow temperature in the surface heating circuits exceeds 55 C. The controller returns to normal operation when the flow temperature cools to below 52 C. Attachment: Rear Rückseite side 115 mm 155 mm Klettverschluss Hook & loop strips Dry heating: 25 C C During the heating-up process the outdoor sensor is disconnected (terminal strip B, 3-4). The controller works as a fixed value regulator from 25 C (knob turned fully counterclockwise to -) to 45 C (knob turned fully clockwise to +). The temperature is adjusted manually every day. Sensor resistance values: Flow temperature sensor (NTC resistor) Outdoor sensor (NTC resistor) +15 C +2 C +25 C +3 C +35 C +4 C -2 C -1 C C +1 C +2 C +25 C 18. kω 14. kω 1. kω 7.5 kω 5.5 kω 4.1 kω 8.23 kω 4.9 kω 3. kω 1.9 kω 1.25 kω 1. kω

25 Installation instructions & design manual 6 Pumped VarioManifold 5. Page Troubleshooting Fault Surface heating circuit temperature too low Surface heating circuit temperature too high Troubleshooting Main pump must be available and running Fixed value control station: Switch on the pump PVS Weather-guided control station: - Switch on the controller WHR36, orange LED (power on) & green LED (pump on) should glow - Check the heating curve setting Adjust the surface heating circuit flow Check and regulate the flow in the boiler circuit (regulating valve) Regulate the existing heating system (e.g. radiators) Switch main pump to a higher setting level Check if the flow/return in the boiler circuit has been reversed Air in system, flush again if necessary Fully open the flushing ball valve Consider the time for baking out, moisture in surface heating system (wet plaster, screed,...) Fixed-value control station: Fixed value regulator is not screwed all the way to the end stop Weather-guided control station: Actuator adapter is not screwed all the way to the end stop Check the heating curve setting

26 - SET PROG Page 26 7 Pump Microstation DISTRIBUTION and CONTROL 7 Pump Microstation 7.1 Description For installing surface heating systems (1 2 heating circuits) in high-temperature heating systems (2-pipe system) with existing circulation pump. The flow temperature of the boiler circuit must be at least 1 K higher than the set flow temperature of the surface heating circuit. Observe the required pipe diameter (capacity) to the Pump Microstation. Primary pressure required! A h = 415 mm Variant A or B B mm 1 mm mm mm Flow indicator Regulating valve Pump PMS (WILO Yonos Para 15/6) Feed / drain cock Immersion sleeve for remote sensor (Fixed value control station A ) or for flow temperature sensor (weather-guided control station B ); contains heat transfer paste (Safety data sheet: Manual air-vent Flow valve, adjustable via protection cap 23V AC, 5 Hz (provided connection cable: 3 x.5 mm² [max. 3 A], please note the electrical protection!) Locking ball valve (3/4 female thread) Check valve Fixed value control station 23V AC 5 Hz Consumers with presettable flow rate A Optional: PIANO HK(T) with clock Weather-guided control station 23V AC 5 Hz WHR36 External sensor Consumers with presettable flow rate B Fixed value regulator 5 C Actuator (VT3FC) 5 C 4 C 3 C 3 C 6 C Heat generator 4 C 3 C 3 C 6 C Heat generator Main pump Main pump 6 C 45 C 6 C 45 C Fixed value regulator: The flow temperature of the surface heating circuit can be continuously adjusted between 2 and 7 C. (Values of temperature scale are reference values for the flow temperature!) 7 Standard 65 Heating curve WHR36: -5 K +5 K K +1 K K Standard +1 K

27 Installation instructions & design manual 7 Pump Microstation Page Weather-guided control station for surface heating for systems featuring a main pump Examples for power: Temperatures Flow temp. Power surface hea. cir. boiler circuit Volume flow in boiler circuit: 5 l/h 4/3 C 5 C 1163 W Flow indicator in boiler circuit 17 l/h 4/3 C 6 C 1745 W 4/3 C 7 C 2326 W Volume flow in boiler circuit: 1 l/h 4/3 C 5 C 2326 W 145 l/h 12 l/h 6 l/h Surface heating circuit Boiler circuit 4/3 C 6 C 3489 W 4/3 C 7 C 5234 W Read here! 7.3 Pump PMS (WILO Yonos PARA 15/6) 6, 1 1 Useful head [mwc] 5, 4, 3, 2, 1, Constant differential pressure ( p-c), for surface heating Venting function,2,4,6,8 1, 1,2 1,4 1,6 1,8 2, 2,2 2,4 2,6 Volume flow [m³/h] Variable differential pressure ( p-v) 7.4 Regulating valve Pressure loss in the boiler circuit The flow rate in the boiler circuit is adjusted using the regulating valve when the fixed-value regulator or actuator is fully opened ( ) Example 2 heating circuits: Pressure loss [mbar] Closed Open 2, 2,5 3, 4, Factory settings fully open Searching for: pressure loss and volume flow in boiler circuit, if regulating valve is 3 turns open. Desired: Boiler flow temperature: 55 C Surface heating temperature: 4/3 C Required volume flow in surface heating circuit: 2 x 8 l/h 4 C 3 mbar Example l/h Volume flow [l/h] 3 C 186 W 2 x 8 l/h 3 C p 55 C 3 mbar (.3 (,3 mwc) mws) 186 W 74 l/h

28 Page 28 7 Pump Microstation DISTRIBUTION and CONTROL 7.5 WHR36 weather-guided controller Terminal Klemmleiste block A A N 23V AC 1 L Terminal Klemmleiste block BB Electrical connection: Terminal block A, 23V AC 1 Power supply phase 2 Power supply neutral conductor 3-4 Bridge PMS pump incl. safety thermostat 5-6 Schaltstrom Relais max.,8 A 7-8 Thermoelectric actuator (only item no. VT3FC permissible) Boiler demand, with contact 5-6 switched (potential-free, max A) RoHS WHR36 opened Use block terminal provided by customer! PE N L WHR36, PIANO WHR36, terminal Klemmleiste HK(T) with B block clock Taupunktwächter Dew point sensor (optional) (Optional) DC AC Terminal block B, safety-low voltage 1-2 Bridge, or optionally: Room thermostat with clock (part no. RT43) (see connection diagram*) 3-4 External sensor 1) (cable for example 2 x.75 mm², max. 5 m) 5-6 Flow sensor 1) (cable for example 2 x.75 mm², max. 5 m) 7-8 Bridge, or switching contact for pump & actuator On/Off 1) Use original sensor! Control lamps: - + Setting the heating curve: Green LED... Thermoelectric actuator activation Red LED... Self diagnosis or alarm message Green LED... Pump PMS Orange LED... Power supply Self-diagnosis is performed when starting for the first time. The red LED flashes for about 5 seconds and goes out. After about 5 minutes the controller begins to adjust the flow temperature to the heating curve. If the red LED is continuously illuminated an alarm is present. In this case the wiring must be checked. An alarm occurs if the flow temperature in the surface heating circuits exceeds 55 C. The controller returns to normal operation when the flow temperature cools to below 52 C. Attachment: Rückseite Rear side mm 155 mm Klettverschluss Hook & loop strips Dry heating: 25 C C During the heating-up process the outdoor sensor is disconnected (terminal strip B, 3-4). The controller works as a fixed value regulator from 25 C (knob turned fully counterclockwise to -) to 45 C (knob turned fully clockwise to +). The temperature is adjusted manually every day. Sensor resistance values: Flow temperature sensor (NTC resistor) Outdoor sensor (NTC resistor) +15 C +2 C +25 C +3 C +35 C +4 C -2 C -1 C C +1 C +2 C +25 C 18. kω 14. kω 1. kω 7.5 kω 5.5 kω 4.1 kω 8.23 kω 4.9 kω 3. kω 1.9 kω 1.25 kω 1. kω

29 Installation instructions & design manual 7 Pump Microstation Page Modification for operation with thermoelectric actuator Actuator (e.g. part no.: VT3) Return valve (part no.: PMX42) First remove the blind cap and fit the return valve. Then the actuator can be clipped onto the fitted adapter ring. 7.7 Troubleshooting Fault Surface heating circuit temperature too low Surface heating circuit temperature too high Troubleshooting Main pump must be available and running Fixed value control station: Switch on the pump PMS Weather-guided control station: - Switch on the controller WHR36, orange LED (power on) & green LED (pump on) should glow - Check the heating curve setting Adjust the surface heating circuit flow Check and regulate the flow in the boiler circuit (regulating valve) Regulate the existing heating system (e.g. radiators) Switch main pump to a higher setting level Check if the flow/return in the boiler circuit has been reversed Air in system, flush again if necessary Consider the time for baking out, moisture in surface heating system (wet plaster, screed,...) Fixed-value control station: Fixed value regulator is not screwed all the way to the end stop Weather-guided control station: Actuator adapter is not screwed all the way to the end stop Check the heating curve setting

30 2,5 2, 1,5 1,,5 2,5 2, 1,5 1,,5 2,5 2, 1,5 1,,5 Page 3 8 Return temperature limiter (for one surface heating circuit) DISTRIBUTION and CONTROL 8 Return temperature limiter (for one surface heating circuit) 8.1 RTL valve Feed cock 3/4" for flushing the surface heating circuit flow indicator adjustable between l/min with locking Feed cock 3/4" for flushing the surface heating circuit 2 Setting the return temperature* Mounting strap VL Consumer with presettable flow rate 1 Screw on the expanding element sensor Locking ball valve Lid dimensions W x H = 34 x 235 mm Return temperature limiter with expanding element sensor 2-4 C settable, swivel-mounted Boiler flow 3/4 Eurocone, max. 6 C Boiler return: 3/4" Eurocone Surface heating flow: 3/4" Eurocone Surface heating return: 3/4" Eurocone Heating pump: Caution: observe required pump performance! 2,5 2, 1,5 1,,5 Heat generator for example gas, oil, solid fuel boiler, remote heating and buffer VL Dimensions mounting box: W x h x d = 3 x 2 x 6 mm *The scale of 2-4 gives the following target temperatures (guideline): VL 2 2,5 3 3,5 4 2 C 25 C 3 C 35 C 4 C 8.2 RTLT valve (with thermostatic valve) Dimensions mounting box: W x h x d = 3 x 2 x 6 mm thermostatic valve Lid dimensions W x h = 34 x 235 mm Fork piece VL Lid of RTLT valve with opening for thermostatic valve Turn valve body upwards Attach fork piece and thermostatic valve Close mounting box

31

32 Variotherm have been developing, producing and selling innovative, ecological and economical heating and cooling systems since Your Variotherm partner VARIOTHERM HEIZSYSTEME GMBH GÜNSELSDORFER STRASSE 3A 2544 LEOBERSDORF AUSTRIA Phone: +43 ()2256/6487 Fax: +43 ()2256/ All rights pertaining to distribution and translation, in whole or in part, including film, radio, television, video recording, Internet, photocopying and reprinting, are reserved.

INDIVIDUAL HEATING. Installation Manual e Skirting Heating Classic. Skirting Heating Delta. HEATING. COOLING. COMFORT.

INDIVIDUAL HEATING. Installation Manual e Skirting Heating Classic. Skirting Heating Delta. HEATING. COOLING. COMFORT. www.variotherm.at INDIVIDUAL HEATING Skirting Heating Classic. Skirting Heating Delta. Installation Delta HEATING. COOLING. COMFORT. Classic Installation Manual e22111 Page 2 Table of Contents INDIVIDUAL

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

Dynalux. Floor Heating Manifolds Underfl oor heating circuit manifold

Dynalux. Floor Heating Manifolds Underfl oor heating circuit manifold Dynalux Floor Heating Manifolds Underfl oor heating circuit manifold IMI HEIMEIER / Floor Heating Control / Dynalux Dynalux Dynalux adjusts the flow rate in the individual heating circuits directly in

More information

Roth fixed-value control set with high-efficiency pump

Roth fixed-value control set with high-efficiency pump Energy Systems Roth fixed-value control set with high-efficiency pump Assembly Instructions Living full of energy Contents General information Intended use 3 Benefits 3 Layout/Components 3 Installation/Electrical

More information

INDIVIDUAL HEATING. Design manual e Classic, Delta & Beta skirting heating systems. Planning.

INDIVIDUAL HEATING. Design manual e Classic, Delta & Beta skirting heating systems. Planning. www.variotherm.at INDIVIDUAL HEATING Classic, Delta & Beta skirting heating systems Planning Classic Delta Beta Design manual e237 Page 2 Table of Contents INDIVIDUAL HEATING. Principles... 3. What does

More information

CIRCO 6 Solar Circulation Unit

CIRCO 6 Solar Circulation Unit TECHNICAL INFORMATION / INSTALLATION INSTRUCTIONS CIRCO Solar Circulation Unit CIRCO Solar Circulation Unit in combination with the intelligent SUNGO controllers, it is the safe and reliable heart of a

More information

HEATING. COOLING. COMFORT. For a cosy home.

HEATING. COOLING. COMFORT. For a cosy home. HEATING. COOLING. COMFORT. For a cosy home. www.variotherm.com VIDEO VIDEO THE VARIOTHERM WORLD AMAZING COMFORT. WITH ATTRACTIVE SAVINGS. Variotherm s floor heating systems, skirting heating systems, trench

More information

ROTEX RMX Heating circuit distributor

ROTEX RMX Heating circuit distributor For certified companies ROTEX RMX Heating circuit distributor Installation and maintenance instructions Types ROTEX RMX 2 12 GB Edition 11/2009 Serial number Customer Guarantee and conformity Guarantee

More information

THERMAL MANAGEMENT THERMAL MANAGEMENT. Accessories: GV 400/500 or GV 600/700 AM 420P TRS 60, TRW 60, TWR 60, TKW 60 FILTER FANS SERIES LV

THERMAL MANAGEMENT THERMAL MANAGEMENT. Accessories: GV 400/500 or GV 600/700 AM 420P TRS 60, TRW 60, TWR 60, TKW 60 FILTER FANS SERIES LV FILTER FANS SERIES LV ROOF MOUNTED FAN For the ventilation of control cabinets, enclosures and housings Different filter mats for dust collection LV series offers low shape and quick mounting EMC versions

More information

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS INSTALLATION INSTRUCTIONS FOR CONTROL BOXES Pay attention to the total pressure loss when connecting UV4- to the control boxes for heating areas > 16 m²!

More information

OEM Alpha Thermostat direct Analog

OEM Alpha Thermostat direct Analog OEM Alpha Thermostat direct Analog The OEM Alpha Thermostat direct Analog is a high-quality room thermostat in modern design for the registration and regulation of the desired room temperature, offering

More information

Metering systems 0548EN April 2014

Metering systems 0548EN April 2014 08EN April 0 0U8 GEY - Y - Y (GE- series) 900 000/ 00 00A/ 800 00L/ Versions and product codes Product code Type Heat exchanger nominal power GEY, - GEY and production GEY and production Table - Product

More information

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode

More information

Advantages / Characteristics

Advantages / Characteristics Air to Air 50 W 30 W cooling capacity 163x104x144mm (LxBxH) 1,9 kg Air to Air 70 W 36 W cooling capacity 163x104x144mm (LxBxH) 1,9 kg Air to Air 75 W 30 W cooling capacity 130x109x163mm (LxBxH) 1,5 kg

More information

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE SPECIFICATIONS... 1 OVERVIEW... 2 PRECAUTIONS... 2 MOUNTING LOCATION... 2 CONNECTION TO BOILER PRIMARY PIPING:... 3 ELECTRICAL CONNECTION... 4 FLUSHING THE

More information

Thermotech underfloor heating

Thermotech underfloor heating Thermotech underfloor heating Assortment and pricelist 2010 Copyright: Thermotech Scandinavia AB 2009 Cover photo: Michael Engman Graphic design: Ulrika Mattisson Other image material: Michael Engman,

More information

Multibox. Flush Individual Room Control for Floor Heating Systems. To be precise.

Multibox. Flush Individual Room Control for Floor Heating Systems. To be precise. Flush Individual Room Control for Floor Heating Systems To be precise. Contents Page Multibox K, Multibox RTL and Multibox K-RTL Description Construction Application 4 Temperature Setting 4 Function Article

More information

THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES

THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES FUNCTION Thermostatic expansion valves are used to regulate and cut-off the flow of the heat transfer fluid that circulates inside airconditioning system terminals (radiators, fan coils, etc.). Thermostat

More information

SHTH SKIRTING HEATING. TRENCH HEATING. The Classic, Delta and Beta skirting heating systems. Trench heating systems.

SHTH SKIRTING HEATING. TRENCH HEATING. The Classic, Delta and Beta skirting heating systems. Trench heating systems. SHTH SKIRTING HEATING. TRENCH HEATING. The Classic, Delta and Beta skirting heating systems. Trench heating systems. www.variotherm.com VIDEO Wonderfully discreet. Cosiness you can feel. The energy saving,

More information

Installation Manual. Electric Underfloor Heating. heatingthroughinnovation.

Installation Manual. Electric Underfloor Heating. heatingthroughinnovation. Installation Manual Electric Underfloor Heating heatingthroughinnovation. 02 Electric Underfloor Heating Contents 1.0 General Information 03 2.0 Preparation 04 3.0 Installation 05 4.0 Measuring Values

More information

TECHNICAL INFORMATION T1500 Series Clothes Dryers

TECHNICAL INFORMATION T1500 Series Clothes Dryers TECHNICAL INFORMATION T1500 Series Clothes Dryers 2003 Miele - Table of Contents 1.0 CONSTRUCTION & DESIGN 1.1 Appliance Overview - Vented 1 1.2 Appliance Overview Condenser Models 2 1.3 Controls Overview

More information

Danfoss Air Heating Surfaces

Danfoss Air Heating Surfaces MAKING MODERN LIVING POSSIBLE Installation Guide www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

Flush individual room control for floor heating systems

Flush individual room control for floor heating systems Multibox Flush individual room control for floor heating systems Pressurisation & Water Quality Balancing & Control Thermostatic Control ENGiNEERiNG ADVANTAGE Multibox is used for decentralized control

More information

RADIANT PANEL SYSTEM CONTROL QUICK GUIDE

RADIANT PANEL SYSTEM CONTROL QUICK GUIDE RADIANT PANEL CONTROL QUICK GUIDE 05 RADIANT PANEL CONTROL Terms and definitions The system temperature regulation can be carried out in only two basic ways: Flow rate control of the medium feeding the

More information

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses. Installation and service instructions for contractors VIESMANN Solar-Divicon and solar pump assembly Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

Economy Standard Comfort. Heat loss (W/K) Heat loss (kwh/24h) (3)

Economy Standard Comfort. Heat loss (W/K) Heat loss (kwh/24h) (3) 4 Technical Data The following tables and drawings provide an overview of the most important dimensions and properties of Solvis- Max Gas and SolvisMax Gas Pur. 4.1 Volumes and heat loss SX-356 SX-456

More information

Unibox Individual room temperature control and limitation of return temperature in surface heating systems

Unibox Individual room temperature control and limitation of return temperature in surface heating systems 4 3 2 4 4 3 2 Unibox Individual room temperature control Technical information Tender specification: Oventrop Unibox for temperature balance of floor and wall surface by limiting the return temperature

More information

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors Installation instructions for contractors VIESMANN Vitodens 200-W Type WB2C, 45 and 60 kw Wall mounted gas condensing boiler Natural gas and LPG version VITODENS 200-W 1/2010 Dispose after installation.

More information

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw Technical Guide Installation, Operation and Care EP E series 7 step electric boilers 26 and 42 kw Arkelstorpsvägen 88, 291 94 KRISTIANSTAD Tel +46 44-22 63 20, Telefax +46 44-22 63 58 e-mail: info@varmebaronen.se

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

TECHNICAL INFORMATION Touchtronic Clothes Dryers

TECHNICAL INFORMATION Touchtronic Clothes Dryers TECHNICAL INFORMATION Touchtronic Clothes Dryers Includes: T1302, T1303, T1322, T1329ci T1403 & T1405 2004 Miele This page intentionally left blank. Table of Contents GENERAL INFORMATION A. Warning and

More information

TECHNICAL CERTIFICATE USER MANUAL THERMOSTAT TP years warranty

TECHNICAL CERTIFICATE USER MANUAL THERMOSTAT TP years warranty TECHNICAL CERTIFICATE USER MANUAL THERMOSTAT TP510 3 years warranty TABLE OF CONTENT Application 4 Controls and indication 4 Adjustment and operation 5 Switch on / switch off the thermostat 5 Adjustment

More information

Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25

Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25 PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu Installation and operation instructions Solar stations SolarBloC

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

Technical information for installation and operation

Technical information for installation and operation Technical information for installation and operation PR 24002.65 12-04-2016 Subject to technical modifications LogoFresh 100 & 120 fresh water station Electronically controlled GB Meibes System-Technik

More information

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems E-Z Valve Thermostatic valves with radiator connection systems For single and two-pipe heating systems IMI HEIMEIER / Thermostatic heads and Radiator valves / E-Z Valve E-Z Valve E-Z Valve with immersion

More information

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S FACTORY AUTOMATION HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S Certification Type Tested Inhalt / Content / Sommaire / Indice Deutsch......................................................... 3 English.........................................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Unit 1 79 Friar Street Worcester WR1 2NT Tel: 01905 616 928 Fax:01905 611 240 E-mail: info@underfloorheatingsystems.co.uk Website: www.underfloorheatingsystems.co.uk ngsystems.co.uk

More information

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE 780EN www.caleffi.com Recess Mounted Heat Interface Unit - SATK series SATK0-60 series INSTRUCTIS FOR INSTALLATI, COMMISSIING AND MAINTENANCE Function The SATK series HIU allows independent control of

More information

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28 The competent brand for energy saving systems NEW Gas-combi boiler CGG-1K-24/28 Gas-combi boiler CGG-1K Technical data room sealed fannned flue model gas combi boiler for low temperature heating and d.h.w.

More information

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. Edition 06.14 GB Operating and installation instructions Lago FB digital remote control Translation from the German 2014 Elster GmbH Safety Please read and keep in a safe place Please read through these

More information

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump Reduced Installation time Precision regulation Minimal tooling required 100% tested prior to packaging High quality

More information

THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES

THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES FUNCTION Thermostatic expansion valves are used to regulate and cut-off the flow of the heat transfer fluid that circulates inside airconditioning system terminals (radiators, fan coils, etc.). Thermostat

More information

HKF 8180 Operating instructions

HKF 8180 Operating instructions Operating instructions EN Version 1.0en /Edition 05/2013 Contents 1 Important basic information... 3 1.1 Limitation of liability... 3 1.2 Operator's responsibilities... 3 1.3 Documentation... 3 1.3.1 Content

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

Manual and installation instructions. Function. Operating phase

Manual and installation instructions. Function. Operating phase LADDOMAT M120 Manual and installation instructions Thermal layering Function Thanks to its design and control features, the Laddomat M120 means optimal thermal layering in storage tanks, with a low and

More information

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer Installation instructions for contractors VIESMANN Mixer extension kit For one heating circuit with mixer Mixer extension kit 5/2017 Safety instructions Please follow these safety instructions closely

More information

WOLF VENTILATION SYSTEM PRICE LIST

WOLF VENTILATION SYSTEM PRICE LIST VENTILATION SYSTEM PRICE LIST JANUARY 2018 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build and modernisation

More information

Multibox. Floor Heating Controller Flush individual room control for floor heating systems

Multibox. Floor Heating Controller Flush individual room control for floor heating systems Multibox Floor Heating Controller Flush individual room control for floor heating systems IMI HEIMEIER / Floor Heating Control / Multibox Multibox K, RTL and K-RTL Multibox K, RTL and K-RTL is used for

More information

R557R EN January 2012

R557R EN January 2012 R7R- 077EN January 0 07U 00 00 00 WITH HIGH TEMPERATURE MANIFOLDS Example: R7RY0 + RAY00 R7R- WITH THERMAL ENERGY METERING Description R7R- group is used for the regulation of the fixed point heating for

More information

Technical Product Guide

Technical Product Guide FMU - Floor Mixing Unit Boxed set pre-assembled for immediate installation: The FMU Floor Mixing Unit integrates both temperature and flow management, making the single piece unit very easy to install,

More information

Installation and Operation Instructions K36E Modular Heating Circuit - DN 25 Boiler charging set

Installation and Operation Instructions K36E Modular Heating Circuit - DN 25 Boiler charging set PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 Email: info@paw.eu, Web: www.paw.eu Installation and Operation Instructions K36E Modular Heating

More information

Thermostatic valves with radiator connection systems

Thermostatic valves with radiator connection systems Multilux Eclipse Thermostatic valves with radiator connection systems with two-point connection for two-pipe heating systems, with automatic flow limitation IMI HEIMEIER / Thermostatic heads and Radiator

More information

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

SD2. Differential Controller. Operating and Installation Instructions F2 72.3 SD2 Differential Controller Operating and Installation Instructions F2 72.3 i Please follow the safety information and read these Instructions carefully before putting the system into operation. Safety

More information

Multibox 4. Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off

Multibox 4. Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off Multibox 4 Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off IMI HEIMEIER / Floor Heating Control / Multibox 4 Multibox 4 RTL and K-RTL and K-RTL is

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

SDU A. SDU A Loops. (available in 3, 4, 5 loops) Water Based Systems. Standard Distribution Unit assembled with: A Blank Port (capped)

SDU A. SDU A Loops. (available in 3, 4, 5 loops) Water Based Systems. Standard Distribution Unit assembled with: A Blank Port (capped) 3102 SDU A Standard Distribution Unit assembled with: A Blank Port (capped) SDU A - 3-5 Loops (available in 3, 4, 5 loops) Made of 1 stainless steel Suitable for 16/2mm Pro-Pipe 4 x 8mm holes for mounting

More information

Convertible radiator valve for one-pipe systems, centre distance 35 mm

Convertible radiator valve for one-pipe systems, centre distance 35 mm Convertible radiator valve for one-pipe systems, centre distance 35 mm 56 series ACCREDITED ISO 900 FM 65 033/6 GB Function 56 series convertible radiator valves are used on one-pipe radiator systems.

More information

Underfloor Heating Installation Guide

Underfloor Heating Installation Guide Underfloor Heating Installation Guide Beneath Heat Ltd Unit 3, Dunne s Farm, Laindon Road, Horndon On The Hill, Essex. SS17 8QB. Tel: 01268 543475 Fax: 01233 221616 Email: info@beneathheat.co.uk www.beneathheat.co.uk

More information

Mounting and Operating Instructions EB 2231 EN

Mounting and Operating Instructions EB 2231 EN Self-operated Regulators Thermostats Type 223 and Type 2232 Bulb Sensors Type 2233, Type 2234, and Type 2235 Air Sensors Type 223 with bulb sensor Type 2232 with bulb sensor (separate) Type 2233 with air

More information

LCF Touch Modbus Datasheet Application Security Advice Caution

LCF Touch Modbus Datasheet Application Security Advice Caution LCF Touch Modbus Electronic Fan Coil Thermostat with Touch Display (Flush mounting) Datasheet Subject to technical alteration Issue date: 3.11.214 Application Modern design flush mounting fan coil room

More information

Trade Product List 2013 BIOMASS ACCESSORIES

Trade Product List 2013 BIOMASS ACCESSORIES Trade Product List 2013 BIOMASS ACCESSORIES BIOMASS SYSTEM COMPONENTS Constant Temperature Control Accessories CONSTANT TEMPERATURE CONTROL PRODUCTS Order Code Description of Package and Contents Pictures

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

Control solutions Biofloor

Control solutions Biofloor TEF234 Electronic room thermostat with display 230V & 24V COMAP proposes a new control system for heating and cooling underfloor. Consisting of a 6 or 10- channels controller (MCF234), analogic (TAF234)

More information

1. Product description

1. Product description 1. Product description Technical data sheet clima DL-110 Available inputs and outputs The clima DL-110 is a universal room controller. It is suitable for controlling static heating/cooling systems (like

More information

HERZ-DR-T-90. Radiator Control Valves with Pre-Setting Function by Means of Double Cone, Suitable for Conversion to Thermostatic Operation. H max.

HERZ-DR-T-90. Radiator Control Valves with Pre-Setting Function by Means of Double Cone, Suitable for Conversion to Thermostatic Operation. H max. Radiator Control Valves with Pre-Setting Function by Means of Double Cone, Suitable for Conversion to Thermostatic Operation Standard Sheet for 6823/ 6824 Edition 1000 (0999) 6823 6824 Special Models 1

More information

WOLF GAS CONDENSING BOILERS COMFORTLINE

WOLF GAS CONDENSING BOILERS COMFORTLINE WOLF GAS CONDENSING BOILERS COMFORTLINE CGB-35/50 / CGB-75/100 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build

More information

Protection and Control of Solid Fuel Boilers

Protection and Control of Solid Fuel Boilers Protection and Control of Solid Fuel Boilers thermal relief valves thermostatic valves and pump stations draft regulators www.regulus.eu BOILER PROTECTION AGAINST OVERHEATING Solid fuel boilers may get

More information

Manual Wöhler Rotary Viper Vent M 10

Manual Wöhler Rotary Viper Vent M 10 Manual Wöhler Rotary Viper Vent M 10 Best.-Nr. 21884 20 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Contents Contents 1 General

More information

Temperature Sensor TRG Original Installation Instructions English

Temperature Sensor TRG Original Installation Instructions English Temperature Sensor TRG 5-6.. EN English Original Installation Instructions 818597-05 1 Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety note...4 Directives and standards

More information

EN Z Subject to change due to technical improvements! Operating instructions

EN Z Subject to change due to technical improvements! Operating instructions SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE Operating instructions Temperature differential controller 3 inputs, 1 output These operating instructions are part of the product. Read

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

INSTALLATION AND OPERATING INSTRUCTIONS General operating instructions for sample gas conditioner Model: MAK 6

INSTALLATION AND OPERATING INSTRUCTIONS General operating instructions for sample gas conditioner Model: MAK 6 List of contents 1.0 Uses 2.0 Technical data 2.1 Operating data 2.2 Construction and installation 2.3 Climatic load 2.4 Power supply 3.0 Function and design 3.1 General comments 3.2 Design 3.3 Performance

More information

CALEFFI. Modulating temperature regulating unit for heating and cooling with high temperature distribution kit. series /04 GB.

CALEFFI. Modulating temperature regulating unit for heating and cooling with high temperature distribution kit. series /04 GB. Modulating temperature regulating unit for heating and cooling with high temperature distribution kit series cert. n ISO / GB Function The modulating temperature regulating unit with high temperature distribution

More information

Storage tank size Rated volume [l] Actual volume [l]

Storage tank size Rated volume [l] Actual volume [l] 10 Technical Data Volumes and heat loss Storage tank size 356 456 656 756 956 Rated volume [l] 350 450 650 750 950 Actual volume [l] 365 448 623 695 886 Hot water standby volume [l] Economy Standard Comfort

More information

Alpha CombiMax 350 and 600

Alpha CombiMax 350 and 600 Installation and Servicing Instructions Alpha CombiMax 350 and 600 Unvented Hot Water Store for use with the Alpha 240/280 Range of Gas Fired Combination Boilers For Technical help or for Service call...

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

Line Smoke Detector LRMX

Line Smoke Detector LRMX Line Smoke Detector LRMX Motorized detector head User-friendly commissioning via automatic selfadjustment Disturbance-protected operation via automatic electromechanical tracking of the detector head during

More information

Installation and instruction manual SOLAR STATION

Installation and instruction manual SOLAR STATION INSTALLATION AND INSTRUCTION MANUAL SOLAR STATION Installation and instruction manual SOLAR STATION SST 25-1E / SST25-2E EN April 2015 1 Table of contents Usage 3 Warranty 3 Safety instructions and symbol

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50 Differential Pressure and Flow Meter Media 5 Indicator 160 Ø PN 50 Application Transmitter for measuring and indicating the differential pressure or measured variables derived from it Suitable for gases

More information

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen Hydronic Mixing Block Version 1.104 The Hydronic Mixing Block is a mixing device and boiler control, with a built in circulator and system controller. The block can provide either a fixed or reset water

More information

EVAPORATIVE COOLER PUMPS

EVAPORATIVE COOLER PUMPS EVAPORATIVE COOLER PUMPS ebmpapst Evaporative Cooler Pump EBMALPHA $144.65 @ 1. metre Head @ 2. metre Head Power Supply 32 litres/min 25 litres/min 24V/1/5Hz Nominal Watts 5 watts Outlet Connection 2mm

More information

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans Installation and Maintenance IPX4* The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU 1.0 SAFETY INFORMATION

More information

51AKB / 51 AKC OWNER S MANUAL

51AKB / 51 AKC OWNER S MANUAL 51AKB / 51 AKC OWNER S MANUAL This manual applies to the following models 51AKB 009 51AKB 012 51AKC 009 51AKC 012 Read this instruction manual thoroughly before using the air conditioner. Control panel

More information

Pump assembly Instruction manual

Pump assembly Instruction manual Instruction manual EN Version 2.0 /Release 06/2012 Table of content 1 Key background information...3 1.1 Limitation of liability...3 1.2 Responsibilities of the operator...3 1.3 Documentation...3 1.3.1

More information

Closomat Lima Vita installation & user guide

Closomat Lima Vita installation & user guide Closomat Lima Vita installation & user guide design manufacture supply install service recycle Technical data The Closomat toilet MUST be installed by a competent or qualified person. Explanation of symbols

More information

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21 Electronic Standard Devices Annunciator Relay MR and MRE MR 2 and MRE 2 The products described in this brochure are intended for industrial use and meet the requirements laid down by the EU directive 7

More information

breeze easytm model # F100-1W

breeze easytm model # F100-1W DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain

More information

INSTALLATION INSTRUCTIONS ONE LARGE ZONE

INSTALLATION INSTRUCTIONS ONE LARGE ZONE INSTALLATION INSTRUCTIONS ONE LARGE ZONE Unit 1 79 Friar Street Worcester WR1 2NT Tel: 01905 354 791 Fax: 01905 352 100 E-mail: info@underfloorheatingsystems.co.uk Website: www.underfloorheatingsystems.co.uk

More information

Function series Thermo-electric actuator electric supply 230 V (ac) or 24 V (ac/dc)

Function series Thermo-electric actuator electric supply 230 V (ac) or 24 V (ac/dc) onvertible radiator valve for one-pipe and two-pipe systems series ARIT 0/ G ISO 0 M ISO 0 No. 000 unction The series convertible radiator valve can be used both on one-pipe and two-pipe radiator systems.

More information

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems Akva Vita TDP-F Table of contents Akva Vita TDP-F...1 Table of contents...1 Safety notes...2 Delivery...2

More information

Maincor Air Temperature Controls AIR TEMPERATURE CONTROL

Maincor Air Temperature Controls AIR TEMPERATURE CONTROL AIR TEMPERATURE CONTROL Overview In multi-zone systems, a thermostat is positioned in the room which is being heated and is set to the required temperature. Once the room gets up to the pre-set temperature,

More information

Assembly- and Usermanual. Rainmaker. Code No GB. Edition: 09/2007

Assembly- and Usermanual. Rainmaker. Code No GB. Edition: 09/2007 Assembly- and Usermanual Rainmaker Code No. 99-97-1729 GB Edition: 09/2007 Table of contents Page I 1 Overview and system specifications.................................. 1 1.1 Purpose of Evaporative

More information

HD Kompakt Service Manual

HD Kompakt Service Manual HD Kompakt Service Manual English 5.906-583.0 Rev. 00 (08/13) 1 1 Contents 1 Contents.................................................... 2 2 Preface.....................................................

More information

Thermostatic valve bodies

Thermostatic valve bodies Thermostatic valve bodies for single pipe heating systems Thermostatic valves with radiator connection systems IMI HEIMEIER / Thermostatic heads and Radiator valves / Thermostatic valve bodies for single

More information

Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function

Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function HERZ-3000 Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function Standard Sheet for 3791 3792 Edition 1000 (0999) Dimensions in mm 1 3001 01 Cone sleeve 1 3002 01 Connection

More information