1 5.18 Voice and Data Distribution General Introduction 1. This standards document is to be used for any projects on the University of Calgary campus that involves the voice and data distribution system or the facilities that house them. It is designed not only to provide the standard implementation system to be used on campus but also provides guidance regarding engagement of Network Services for projects. 2. This section of the standards document provides information on University of Calgary cabling practices, standards, and components. All cabling projects are required to follow these standards and practices to insure that the University structured cabling system can support new applications that require higher speeds and increased reliability. History has shown that the building structured cabling systems often require replacement at considerable cost before the effective life span of the building or project area. This fact significantly increases the carbon footprint and long term costs of campus projects. With this fact in mind the University of Calgary has now standardized on Cat 6A cabling for all new buildings as well as for capital and major projects that can form the basis for a building cable system renewal. Client requirements will be examined and Network Services in consultation with Campus Infrastructure will determine the best solution for each project. 3. Standards outlined here follow the EIA, TIA, and CSA standards for commercial buildings and BiCSi best practice recommendations. Relevant national electrical codes are always to be followed Network Services Project Involvement 1. Network Services project involvement. While University standards will be followed in all cases, the unique nature of every project requires Network Services input on all projects that involve voice, data, or wireless. Network Services is to be consulted for the following: a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations. c. Demolition d. Construction e. Commissioning Project Management 1. Project Managers will engage Network Services at appropriate points in the project as indicated below. a. Initial project design and preliminary budgeting. b. Participate in site meetings. c. Network Services will examine how individual projects interact with existing and future infrastructure & equipment requirements to help specify the best campus solution. Last Updated: Jun 2010 Page 1 of Voice & Data Distribution

2 d. All Network Services costs are to be included in the project budget. e. Project Managers need to provide as-built drawings for risers and cabling systems. f. If project designs are more than a year old they should be re-evaluated by Network Services to insure they meet current standards and components. 2. Project sign off by Network Services will occur at the following project stages. a. Specifications b. 80% design drawings c. Change orders d. Completion Cabling Systems 1. Copper Cabling. The U of C follows the TIA/EIA-568-B cabling standards with T568B pin pair assignments. Each project has to be evaluated to determine the copper station cabling to be used. Standard practice is shown below. a. Once a building has a manufacturer presence the whole building will remain with that manufacturer for that generation of cabling system. b. New buildings will be open for quotes using all approved copper cable manufacturers and our approved Cat 6A copper cabling solutions. Approved copper cable manufacturers include Belden, Panduit, and Commscope. c. Projects in older buildings will have to be evaluated by Network Services individually to see if cable plant renewal is required. Belden is the only manufacturer of Cat 6 cabling to be used if the cable plant is not upgraded to Cat 6A. d. Acceptable Belden Cat 6 cabling and components are specified in section e. Acceptable Cat 6A cabling and components are specified in section Acceptable manufacturers are Belden, Commscope, or Panduit. A given project will only use cable components from one manufacturer. f. 10 ft. patch cables for station connectivity and communication room equipment are to be included in the project scope and left on site in the communications room for deployment. 2. Building Fiber Cabling. The University of Calgary has standardized on Corning fiber solutions for all in building fiber and campus backbone fiber panel products. Cabling will be specified for each project depending on requirements. a. Should provide redundant routes for fiber. b. Typically only Single Mode fiber will be required. 3. Copper phone cables, connectors, and enclosures Last Updated: Jun 2010 Page 2 of Voice & Data Distribution

3 a. Backbone and riser cables are to be NORDX/CDT twenty-four (24) AWG ARMM/ATMM multi-conductor that conforms to CSA Standard T529-M91, Section Or a compatible product approved by Network Services. b. Communications Technology PIC Aerial Closure kits. c. 3M Telecom Systems MS2 Termination modules. d. Typical 200 pair required to building entrance AirUC Wireless 1. The AirUC wireless system must be installed in all new buildings and renovations. AirUC wireless costs will be included in project budgets. a. Network Services will produce required wireless designs for all projects and will consult with the project teams to determine AP locations. 2. Generally for a/b/g/n, one AP is installed for every 1200 square feet. Usage density, floor plans, and obstructions all influence AP placement so Network Services will provide placement recommendations based on blue prints and site surveys if required. 3. Certain types of research or other activities may produce radio interference with a/b/g/n wireless devices. Any anticipated radio interference sources shall be discussed with Network Services before project completion Contractor Requirements 1. Contractors. All contractors working on site must go through the EH&S CASP training as well as a Network Services orientation session. 2. Contractors are required to be manufacturer certified in the cabling solution being installed for a given project Facility Requirements 1. Main Riser a. The primary communications room of the building should be located close to the building service entrance. b. A minimum of three (3) 100 mm ducts or a 300 mm x 100 mm tray is required from the service entrance of the building to the communications room. The duct/tray shall originate to the existing low voltage tray in the service tunnel and terminate at the backboard. Sweep 90 degree bends are to be installed to facilitate pulling of PIC-S backbone cable, home run data cables, and fiber-optic cable. c. The building communications room shall be planned exclusively for telecommunications support. Avoid any building power or water distribution equipment for facilities in the same room. Last Updated: Jun 2010 Page 3 of Voice & Data Distribution

4 d. The floor of the communications rooms shall, at minimum, be sealed to reduce dust. Door seals or sweeps are preferred to reduce the collection of dust and debris in the communications room. e. While sizing will have to be adjusted to suit individual requirements, we recommend that the main communications room be a minimum of 3 m x 6 m unobstructed by door swing. See the next section for typical room layout and sizing information. f. Communications riser rooms shall be vertically aligned with the primary communications room, riser facilities. In some cases more than one riser stack might be required, cabletray shall be provided from the communications rooms to each remote riser system. g. All cable-trays shall be brought to the vicinity of one of the 6m walls without a door. Risers and all other cable-trays shall be located in the vicinity of the same wall. h. Three (3) 1,200 mm x 2,400 mm sheets of 20 mm G1S plywood shall be mounted, with their longest edge vertical, on the 3m wall noted above. The sheets shall be mounted directly to the wall and painted with fire retardant paint to match the surrounding area. i. A minimum of four (4) dedicated 120 VAC single-phase (15) ampere circuits shall be placed evenly in the cabinets with quad-outlet boxes. Emergency power and UPS shall be included for these and any communications riser room circuits on the system. Other outlets may be required depending on the actual equipment to be located in the room. j. Adequate light to allow technicians to work on communications support equipment shall be provided. k. There shall be a minimum of 2,400 mm of clearance between the working floor and the lowest ceiling-mounted fixtures (lights, cable-trays, etc.). l. The equipment located in the room will be generating heat. While precise environmental control requirements, if any cannot be generalized without specific knowledge of equipment requirements, air circulation through the room is required at minimum. The target room temperature shall be 18 C to 24 C (64 F to 75 F). Designers shall keep in mind the fact that many building air handling systems deliver heat during the cold months, and special treatment of the communications room may be required. m. Communications room doors must, at least, be provided with locks that are keyed to Maintenance and Operations Standards. Depending on the importance of the communications facilities to the occupants, security alarms should be seriously considered. n. Fire extinguishing water sprinklers may be provided in the ceiling of the communications room, but high temperature (100 C) fusible links shall be used and the system will be a dry pipe system. In some circumstances, a complete fire suppression system may be required. In any case, a fire extinguisher shall be located inside the door of the room. o. Smoke detectors and heat detectors shall be installed in the communications room and wired to the building fire alarm system. p. The communications room must have its own earth ground brought to the backboard noted. This ground must not be in common with building electrical grounds and shall join Last Updated: Jun 2010 Page 4 of Voice & Data Distribution

5 all communications riser grounds only at the building ground point. The ground is used for sensitive equipment, not for bonding conduit and tray systems. A minimum of #6 copper wire shall be used unless codes call for larger wire. The ground is to terminate on a solid copper ground bar (50 mm x 260 mm x 5.6 mm bent to have a 20 mm standoff. q. All communication racks to be grounded to the main grounding bar individually. r. Typical 24 Single Mode fiber to each floor. s. Panduit four post racks with 15 cable managers for station cables and 6 for fiber. t. Bonding - In all cases where pairs enter or leave the cable sheath, the cable shield must be bonded to the ground bus bar using #6 AWG copper wire. u. Any plywood mounted with in the room shall be painted with fire retardant paint Communications Riser Rooms And Riser Systems 1. Design considerations for communications riser rooms and riser systems are the same as those noted above for main riser room. a. The room size is dictated by the number of cabinets required in the room and the unobstructed clearance required around the cabinets and back wall. Room size requirements shall be based on the square footage of the area being serviced so that future growth can be accommodated without substantial redesign. The table and diagrams below can be used to determine required sizes. Risers servicing multiple floors may need to be larger. b. Under normal circumstances, three (3) 100 mm conduit sleeves per riser room shall be provided for passage between floors. In general, one sleeve will be used primarily for voice cabling, one sleeve will be used primarily for data cabling, and the third sleeve will allow for quick and inexpensive growth and change. Note that the recommendation is for short sleeves between floors and not for continuous conduit and that these sleeves must be equipped with removable fire stops. In general, we have found sleeves to be much easier to work with than slots or other facilities. All sleeves must be bonded to the building ground system. All sleeves shall have conduit extending 5cm above the floor slab to prevent water damage in the event of a flood. c. For buildings with certain types of communications requirements, the rule of three (3) conduit sleeves per riser room per floor would possibly change. d. For buildings with more than one (1) riser system, facilities shall be provided to support cable runs between the riser rooms on each floor, as will be detailed in the section on horizontal distribution systems below. e. These facilities must be separate from the horizontal distribution systems specified for the voice/data outlet wiring; i.e., riser cables must be kept separate from all other cables. f. The size of the communication riser room will vary depending on the floor space being covered. The following tables and diagrams indicate the required space requirements for various sized installations. It should be noted that typical requirements will be based Last Updated: Jun 2010 Page 5 of Voice & Data Distribution

6 on floor space and not initial space utilization due to the very high costs of adding additional capacity at a later date. g. Any plywood mounted with in the room shall be painted with fire retardant paint. h. All communication racks to be grounded to the main grounding bar individually. Table: Square feet to cabinet requirements for 24 port patch panels m * 3m m * 4m m * 5m m * 6m m *7m Last Updated: Jun 2010 Page 6 of Voice & Data Distribution

7 Diagram: One cabinet telecommunications room Diagram: Two cabinet telecommunications room Last Updated: Jun 2010 Page 7 of Voice & Data Distribution

8 Diagram: Three cabinet telecommunications room Diagram: Four cabinet telecommunication room Last Updated: Jun 2010 Page 8 of Voice & Data Distribution

9 Station Cable Distribution 1. Above Floor a. Centralized tray system. b. Consolidation point every 1200 square feet 2. Manufacture approved J hooks a. Conduits stubbed at location at least 5 cm above partition walls 3. Raised Floor a. Centralized tray system. b. Consolidation point every 1200 square feet c. Consolidation point locations shall be labeled d. If movable walls ties into furniture 4. Typically 2 cables per workstation location a. If conduit is to be installed each outlet requires its own run of conduit (no daisy-chaining) either to the main cabling pathway, or directly back to the main Comm. room 5. Terminated on 24 port patch panels 6. End to end solution provided through the project including all required patch cables. 7. Labeling (as per EIA/TIA 606A standards). Labeling processes are reviewed in the Network Services orientation for contractors but include the following. a. Building /Floor/Riser/Patch Panel/Port Jack location. b. Patch Panel to identify panel id/port/room 8. Some areas on campus that deal with medical information have additional security requirements that impact distribution systems. These requirements are in place to allow compliance with medical record information security standards. Network Services will provide advice on these standards as required Testing 1. Copper cable plant: a. Backbone and riser cable: Perform the following tests on the backbone and riser cables: b. Continuity and polarity test for each pair c. db loss of white blue pair of each binder group d. Length of white blue pair of each binder group Last Updated: Jun 2010 Page 9 of Voice & Data Distribution

10 e. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 2. Station wiring: a. Each drop shall be channel tested to meet the transmission performance specifications for the category of cable system being installed. b. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 3. Data tie cables: a. Testing is to meet the transmission performance specifications for the category of cable being installed. b. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 4. Testing procedures for fiber optic cables: a. After cable delivery (still on reel), for a fiber installation, the contractor or manufacturer shall test each fiber for attenuation at 1300 nm for Multi-Mode fiber and 1550 nm for Single-Mode fiber using an Optical Time domain Reflectometer (O.T.D.R.). The contractor shall provide a written report (with soft copy) of the test results to The University of Calgary. The University of Calgary must approve format of soft copy. The report must identify which fiber corresponds with the respective test measurement data supplied, so The University of Calgary; Network Services technical personnel can verify the results before installation begins. b. During and upon completion of a fiber cable installation, The University of Calgary, Network Services technical personnel reserves the right to inspect and test the cables at any time to ensure proper installation and testing procedures are being adhered to. c. O.T.D.R. tests are to be conducted upon completion of a fiber installation and are to be conducted from both directions. d. Attenuation is to be measured end to end. Nominal operating wavelengths of 850 nm and 1300 nm for Multi-mode fibers and 1550 nm for Single-Mode fibers are to be verified and specified in decibels (db) on acceptance documents approved by The University of Calgary, Network Services Department. e. Visual hard copy records (print of O.T.D.R. Data trace, signed off) of fiber, splice, and/or connectors are required. These records are also to be provided in soft format approved by The University of Calgary, Network Services Department f. Distances to localized attenuation, splices, connectors and fiber ends are to be measured on the O.T.D.R. documented on acceptance documents providing information for system maintenance and trouble shooting. Last Updated: Jun 2010 Page 10 of Voice & Data Distribution

11 g. O.T.D.R. graphs are to be submitted to The University of Calgary, Network Services Department. One signed off set of these graphs is required. Records are also to be submitted electronically, on USB drive, or on CD. The file format shall be in TIFF format. h. The cable shall meet or exceed the requirements of the specifications for fiber dimensions, attenuation, band width, numerical aperture, fire proof test, cable bending, tensile load, impact resistance, crush resistance, and attenuation versus temperature Services 1. Voice Services. All new projects will use VoIP and must carry the cost of upgrading building network hardware to support voice traffic requirements if required. Emergency and help phones will be specified on a project by project basis depending on project floor space and user requirements. a. VoIP and supporting network infrastructure will be deployed for all major renovation and new projects b. Dual power required for VoIP Head End equipment (refer to Data Network Standards section 5.4.1) c. Emergency TDM phones mounted in designated locations 2. For Classroom phones a. Mounted in the front of the room adjacent to the white (black) boards, on the side nearest the door. In cases of fixed commedia installations mount the phone on the side nearest the commedia installation. b. The Standard mounting height for the classroom phones shall be +1170mm (46") AFF to center of the box (single gang plaster ring). c. There shall be at least 200mm (8 ) clearance on each side from vertical center, at least 600mm (24 ) from a chalk board, and at least 600mm (24 ) clearance from horizontal center above and below. d. Install a single Cat 6A cable, leaving 3m from the edge of the backboard in the communications room and 0.3m at the jack. e. Label each end as, class phone and with room number. f. Install an RJ12 modular female insert at the end of the cable, leave loose in outlet box. Wire out the wh/blu, blu/wh only. 3. For wall phones a. The Standard mounting height for Wall phones shall be +1400mm (55") AFF to center of box (single gang plaster ring), with a minimum of 350 mm (14 ) radius of clear wall space. b. Install a single Cat 6A cable, leaving 3m from the edge of the backboard in the communications room and.3m at the jack. Last Updated: Jun 2010 Page 11 of Voice & Data Distribution

12 c. Label each end as the next jack in the room-labeling scheme. d. Install a single gang walljack, (with protruding wall-mounting studs). 4. Help phones inside locations a. Supply and install Guardian HDE-11 (flush mounted) b. The Standard mounting height for the Emergency Phones shall be +1170mm (46 ) AFF to center of mounting box (8.3 x10 x2.45 ). (This refers to the Guardian HDE-11 units with the stainless fronts). Note only original manufacturers back boxes are to be used. A cut out of 8.75 x10 is required for this box and it must be mounted in the centre of the hole. c. Blue light shall be mounted as high as practical but need not exceed + 3m (10 ) to the bottom of the light. d. Install a single Cat 6A cable, leaving 3m from the edge of the backboard and 0.3m at the jack. e. For outdoor installations (required at all building main entrances): Install a weather proof surface mount emergency phone yellow Guardian HDE-12. All conduit entries for help phones and blue lights shall be into the bottom of back boxes. Special assembly help phones subject to approval. 5. Help phones Mounted in dedicated use unisex accessible washrooms a. Supply and install Guardian HDE-11 back box for future use with Allen Bradley remote push button box. (refer to Appendix A) b. The Standard mounting height for the Emergency Phones shall be +1370mm (54 ) AFF to center of mounting box (8.3 x10 x2.45 ). (This refers to the Guardian HDE-11 recessed units with the stainless fronts). Note only original manufacturers back boxes are to be used. A cut out of 8.75 x10 is required for this box and it must be mounted in the centre of the hole. c. Mount a remote Push Button (below the Help Phone back box) at mm (18 ) AFF, in a 4 x 4 x 2 1/8 deep box c/w a 2 gang plaster ring. Install a ¾ EMT conduit between the remote PB and the Help Phone back box. Mount this box at 600 mm diagonally from the center of the W/C (seating position). Require a 4x4 stainless steel cover plate with knockout for the push button. d. Shall be mounted in a clear space to allow a fallen user to use any body part to activate the phone. Install a single cat 6a cable, leaving 3m from the edge of the backboard and 0.3m at the jack. e. Remote push button Allen Bradley. Contact Voice Services for part numbers. 6. Elevator telephones and equipment rooms a. Supply and install Adams Survivor Plus in each Car telephone with survivor panel or equivalent mounted in main elevator lobby. Last Updated: Jun 2010 Page 12 of Voice & Data Distribution

13 b. Provide three dedicated telephone lines (one for emergency service, one for elevator maintenance, and one for modem) terminated in a junction box in elevator machine room. c. Provide conduit with pull wire between nearest telephone closet and junction box in elevator machine room for elevator telephone. d. Provide conduit with cat6 wire from junction box in elevator machine room to elevator controllers for car telephone. e. Elevator car telephone phone specified: Adams Survivor Plus part # A930P3-01 Model 2400 or approved equivalent. f. The phone is to be mounted in COP (Car Operating Panel) behind a speaker vent. g. Install an ADA (American Disability Approved) illuminated pushbutton in Car Operating Panel to activate the above phone. h. Provide one additional in car telephone per car as part of spare parts list for elevator maintenance i. Wall outlet for elevator maintenance (Safety Phone) j. Provide dedicated wall telephone lines to main fire annunciator panel location Network Services Equipment 1. Every project deployment will use the University of Calgary s current standards for network equipment and device configuration. Project budgets carry the burden for the services they will use. This will insure proper system operation and quality support. Budgetary figures for the required equipment will be provided by Network Services during the project cycle. This equipment is documented in the document Data Network Standards: In Buildings. 2. Based on budgetary figures provided to the project Network Services will purchase, deploy, and configure all active components that are specifically required for voice and data services Other UCIT Services 1. When possible all server requirements should be housed in a UCIT data center. This will reduce the significant overhead costs associated with small data center construction and operation and reduce the environmental footprint of these systems. Due to the scale and level of support available through UCIT system reliability is usually higher in this scenario as well. UCIT can provide further information as required. 2. Panduit cabinets and parts are the standardized network racks and modular solution for the data centers. Last Updated: Jun 2010 Page 13 of Voice & Data Distribution

14 Parts and Components 1. Network Services uses a standard list of parts and components to decrease deployment time and improve long term serviceability of the systems. Occasional specialized applications may require components that are not listed below but in any case Network Services will approve the components that are to be used on specific projects. Part Number Color Systimax 10GX Cable AWH R1000 White MDVO MGS White Face Plates Dual M12LE-262 White Face Plates Quad M14LE-262 White Furniture Plates M14CE-262 White 7ft Patch Cords CPC F007 white 10ft Patch Cord CPC F010 White 15ft Patch Cord CPC F015 White 25ft Patch Cord CPC F025 White 24 port Patch Panel 1100GS5-24 Belden 10GX Cable White MDVO AX White Face Plates Dual AX White Face Plates Quad AX White Furniture Plates AX White 7ft Patch Cord AX White 10ft Patch Cord AX White 15ft Patch Cord AX White 25ft Patch Cord AX White 24 port Patch Panel AX Panduit 10GX Cable PUP6X04WH-UG White MDVO CJ6X88TGIW White Face Plates Dual CFPL2WHY White Face Plates Quad CFPL4WHY White Furniture Plates CFFP4WH White 7ft Patch Cord UTP6X7WHY White 10ft Patch Cord UTP6X10WHY White 15ft Patch Cord UTP6X15WHY White 25ft Patch Cord UTP6X25WHY White 24 port Patch Panel DP246X88TGY Belden Cat6 Cable (cat6) NOR MDVO PS5e (Blue) AX Blue MDVO USOC(Almond) AX Almond 106 Housing (Almond) AX Almond 10ft Patch Cord AX Yellow Last Updated: Jun 2010 Page 14 of Voice & Data Distribution

15 Part Number Color 15ft Patch Cord AX Yellow 25ft Patch Cord AX Yellow GigaBIX Mount AX GigaBIX connector AX GigaBIX Wire Guard AX GigaBIX Desi strip AX GigaBIX Management Ring AX Corning Fiber Components Rack Mount Enclosure PCH-04U Splice Tray Bracket PC4-SPLC-12SR 12 Fiber Splice Tray M RH 6 Port LC Panel CCH-CP-12-A9 12 Port ST MM Panel CCH-CP-12-15T Racks Panduit 4 Post Rack Panduit 6" Wire Manager Panduit 12" Wire Manager Panduit 15 Wire Manager VoIP and TDM Telephone Components Adams Survivor Plus Model 2400 Guardian HDE-11 Guardian HDE-12 Allen Bradley Remote Push Button Allen Bradley Contact Block Allen Bradley Latch Blue Lights CMR4P84 PRVF6 PRVF12 PRVF15 A930P FP-MM64 800FX10 800FALM Carmanah Signs 2. Data Center parts & Components: Parts Cabinets Copper Patch Cables Components Panduit CN1 Net-Access cabinet 45U (32 W X 41 D x 84 H with top, doors, sides Panduit CN2 Net-Access cabinet 45U (32 W X 41 D x 84 H with top and doors Panduit QAPP48HDBL Quicknet Patch Panel empty UTP 48- Port Angled for Preterm cassette Panduit QPP24BL Quicknet Patch Panel empty UTP 24- Port Angled for Preterm cassette Panduit QARWCHCHXX??N Quicknet UTP Cat 6A White riser cassette/cassette jacks?? Feet Panduit UTP6X_??? Cat6A patch cord??? colour _feet need to be supplied by Network services Last Updated: Jun 2010 Page 15 of Voice & Data Distribution

16 Appendix A Help phones Mounted in dedicated use unisex accessible washrooms drawing Last Updated: Jun 2010 Page 16 of Voice & Data Distribution

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing.

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing. 3.4 TESTING OF FIBER OPTICS CABLING A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing. B. General: In the event

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Design Guideline Element includes design standards and requirements for telecommunications service and distribution. This is a design standard and is not intended

More information

Special Provision No. 683S28 December 2017

Special Provision No. 683S28 December 2017 FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE - Item No. FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE (TEMPORARY) - Item No. Special Provision No. 683S28 December 2017 1. SCOPE

More information

ECP OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS

ECP OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0009 OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS EPN, LPN, SPN This standard details the requirements for the splicing,

More information

Telecommunications Survey

Telecommunications Survey Victor Valley College Telecommunications Survey Victor Valley College 18422 Bear Valley Road Victorville, CA 92395 November 30, 2010 Submitted by P2S Engineering, Inc. Executive Summary Background and

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

SECTION COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE

SECTION COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE SECTION 27 16 19 COMMUNICATIONS PATCH CORDS, STATION CORDS AND CROSS CONNECT WIRE PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary

More information

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE N.J. Specification No. Effective Date: July 1, 2001 New

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00.19 COMMUNICATIONS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Category 6 and Category 5e horizontal UTP cabling. 2. Cable connecting hardware, patch panels, patch

More information

Compact Module. Category 6A FTP Cabling System 1.1

Compact Module. Category 6A FTP Cabling System 1.1 Updated 24/09/12 Compact Module Cat 6A performance Suitable for 10-Gigabit Ethernet Ultra-slimline design Euro style module Interchangeable with other Euro Modules and blanks Individually QA tested Easy

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 16 Communications Cabinets, Racks, Frames and Enclosures A. Provide all labor, materials, and equipment

More information

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work.

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work. PART 1 GNRAL 1.1. APPLICABL PROVISIONS A. The General, Supplementary and other Conditions of the Contract, modifications to the General Conditions, the Drawings, and the applicable provisions of the other

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER PART 1 - GENERAL 1.1 SUMMARY A. Section Includes the following: 1. 50/125-micrometer, optical fiber cabling. 2. Cable connecting hardware, termination panels,

More information

UBC Technical Guidelines Section Edition Access Control Page 1 of 5

UBC Technical Guidelines Section Edition Access Control Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 28 05 00 Access Services: General Standards.2 Section 08 71 00 Door Hardware 1.2 Coordination Requirements.1 UBC Access Services 1.3 Description.1

More information

SECTION TESTING OF FIBER OPTIC CABLES

SECTION TESTING OF FIBER OPTIC CABLES SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Hands-On Fiber Optic ISP / OSP Combo-Tech Splicing, Termination & Testing

Hands-On Fiber Optic ISP / OSP Combo-Tech Splicing, Termination & Testing Hands-On Splicing, Termination & Testing BICSI CECs This course has been approved for CEC credits by BICSI. Please read below for a breakdown of the credits that we offer for this course. For more information

More information

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed* Simplex ES Network UL, ULC Listed* ES Net features ES Network (ES Net) is a high bandwidth (100 Mbps) IP based fire alarm network that supports up to 99 nodes and uses industry standard network technology

More information

SECTION COMMUNICATIONS FIBER CABINETS, ADAPTERS AND CONNECTORS

SECTION COMMUNICATIONS FIBER CABINETS, ADAPTERS AND CONNECTORS SECTION 27 11 20 COMMUNICATIONS FIBER CABINETS, ADAPTERS AND CONNECTORS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform

More information

HELKAMA. Optical Fibre Cables

HELKAMA. Optical Fibre Cables 1 Contents Optical fibres and their characteristics Cable constructions Cable tests Installation, jointing and terminating Manufacturing (pictures) 2 Multimode Fibre (GK) Attenuation and Bandwidth Fibre

More information

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling Hands-On Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling Certification Course Description This Hands-On course is customized to give Technicians the confidence and skills to maintain Fiber

More information

4120 Fire Alarm Network Reference

4120 Fire Alarm Network Reference 4120 Fire Alarm Network Reference Features Autocall 4120 Fire Alarm Network communications are available for wired or fiber optic connections Wired communications are available on Network Interface Cards

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

Universal Connectivity Platform A Modular Approach to Infrastructure Design

Universal Connectivity Platform A Modular Approach to Infrastructure Design A Modular Approach to Infrastructure Design TE Connectivity s Universal Connectivity Platform (UCP) provides a fully modular approach to designing data centers and telecommunications rooms. This patch

More information

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No.

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No. Special Provision No. 683S01 December 2017 1. SCOPE This Special Provision covers

More information

350 Pine Street, Suite 720 Edison Plaza Beaumont, TX Fax

350 Pine Street, Suite 720 Edison Plaza Beaumont, TX Fax 350 Pine Street, Suite 720 Edison Plaza Beaumont, TX 77701 409.866.7196 409.866.1745 Fax Project: Addendum No. 1 FIRE STATION #2 NORTH END CITY OF BEAUMONT 4990 HELBIG ROAD, BEAUMONT, TEXAS BID PROPOSAL:

More information

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech Course Description This Hands-On 3-day course has been customized to provide technicians with a practical understanding of fiber optic theory and fiber

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

CONSTRUCTION MANUAL PART 4

CONSTRUCTION MANUAL PART 4 CONSTRUCTION MANUAL PART 4 Technical Specifications and Standards Revised June 21, 2016 Original Issue Date: February 9, 1990 Revisions January 16, 2019 November 8, 2018 August 10, 2017 August 4, 2016

More information

PRODUCT BROCHURE. Steel City 5 SQUARE boxes It s time for an upgrade

PRODUCT BROCHURE. Steel City 5 SQUARE boxes It s time for an upgrade PRODUCT BROCHURE Steel City 5 SQUARE boxes It s time for an upgrade STEEL CITY 5 SQUARE BOXES 5 SQUARE boxes Install peace of mind. When hospitals, universities and government agencies require outlet boxes

More information

Hands-On CAT 5/6 & Fiber Optic Installer

Hands-On CAT 5/6 & Fiber Optic Installer Hands-On BICSI CECs This course has been approved for CEC credits by BICSI. Please read below for a breakdown of the credits that we offer for this course. For more information regarding BICSI please visit

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Fiber Optics for Todays Industry Applications

Fiber Optics for Todays Industry Applications Hands-On Fiber Optics for Todays Industry Applications (A Non-Telephone Company Course) Course Description This Hands-On course is designed to provide technicians with a practical understanding and Hands-On

More information

Undercarpet Cabling Products Undercarpet Power, Voice and Data Distribution

Undercarpet Cabling Products Undercarpet Power, Voice and Data Distribution Undercarpet Cabling Products TE Connectivity Enterprise Networks Warranty Power Distribution Product Coverage* TE Connectivity warrants that all Undercarpet cabling system products within this catalog

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY DIVISION 28 ELECTRONIC SAFETY AND SECURITY CENTRALLY MANAGED ELECTRONIC ACCESS CONTROL, VIDEO SURVEILLANCE, AND INTRUSION ALARM SYSTEMS 1. All questions on equipment approvals in this section shall be

More information

Fiber Optic Products Catalog

Fiber Optic Products Catalog Fiber Optic Products Catalog No epoxy, no polish, no crimp Two fibers in one ferrule MT-RJ Patch Panel Jack packages include: 6 MT-RJ Jacks 2 Actuator Tools 1 Fiber Guide 1 Icon Wheel Bend Limiting Boots

More information

Design Requirements Provide work area copper cable (CAT-5 or CAT-6) in accordance with TIA-568-2, with a thermoplastic jacket colored as follows:

Design Requirements Provide work area copper cable (CAT-5 or CAT-6) in accordance with TIA-568-2, with a thermoplastic jacket colored as follows: JBLM Design Standards Design Requirements Provide work area copper cable (CAT-5 or CAT-6) in accordance with TIA-568-2, with a thermoplastic jacket colored as follows: a. RED - SIPR b. BLUE - NIPR (STANDARD

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 27 12 23 FIBER OPTIC DATA NETWORK A. Furnish, install, terminate, and test all fiber optic equipment and cabling necessary for a complete and functional data highway

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS SECTION 275116 - PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Preamplifiers. 2. Power amplifiers. 3. Microphones. 4. Control console. 5. Loudspeakers.

More information

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation. UL, ULC Approved* Fire Control Panels Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting Features Converts multiple fire alarm communications signals into a single fiber optic

More information

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5

More information

CATEGORY 6A FTP RJ45 SOLUTION

CATEGORY 6A FTP RJ45 SOLUTION CATEGORY 6A FTP RJ45 SOLUTION Clipsal titanium Patch Cord Clipsal titanium LSZH Patch Cord Clipsal titanium Keystone Jacks Clipsal titanium Modular Jacks Clipsal titanium Patch Panels Clipsal titanium

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Telecommunications Standards Document February

Telecommunications Standards Document February Telecommunications Standards Document February - 2014 Introduction & Overview Introduction California Polytechnic State University, San Luis Obispo relies heavily on its technology infrastructure to support

More information

PART 1 CHANGES TO SPECIFICATIONS

PART 1 CHANGES TO SPECIFICATIONS ADDENDUM NO. ONE Date: 4 November 2014 Project: From: To: League City Council Chamber Renovation City of League City 200 West Walker St. 77573 PGAL 3131 Briarpark Suite 200 Houston, Texas 77042 Prospective

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

ACCESS CONTROL ENTERPRISE SYSTEM (ACES) CARD ACCESS DIVISION , ISSUE # 6, JANUARY,

ACCESS CONTROL ENTERPRISE SYSTEM (ACES) CARD ACCESS DIVISION , ISSUE # 6, JANUARY, Page 1 of 31 ACCESS CONTROL ENTERPRISE SYSTEM (ACES) CARD ACCESS DIVISION 28 13 00, ISSUE # 6, JANUARY, 2018 http://maps.stanford.edu/fdg_available ISSUE AUTHOR, DATE APPROVED BY, DATE EFFECTIVE DATE 1

More information

. SECTION CONTROL-VOLTAGE ELECTRICAL POWER CABLES

. SECTION CONTROL-VOLTAGE ELECTRICAL POWER CABLES . SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a. Flash / Flare Architectural and Engineering Specification for a Flash / Flare June 27, 2014 Page 1 of 12 T1DA0115-001 Rev D This document is intended to provide performance specifications and operational requirements

More information

Mar11 Rev B

Mar11 Rev B Product Specification 108-1576-2 11Mar11 Rev B NETCONNECT*, CHAMP* System 5 Modular Jack Patch Panel 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for NETCONNECT*

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Zone Cabling & Wireless Enclosures

Zone Cabling & Wireless Enclosures Zone Cabling & Wireless Enclosures Helping you Organize. Store. Secure. SM technology equipment... Solution Overview Solution Overview Today s mobile workforce needs a flexible workspace where it is easy

More information

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes.

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes. DIVISION 14 - CONVEYING SYSTEMS Section 14000 - General Discussion Introduction The size, number, and location of elevators must be addressed at the earliest stages of the design, to ensure that neither

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150 Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1150 April 2018 Page 1 of 14 AE-FP-005-IN-R1-E-04/18 This document is intended to provide

More information

OFS IV Optical Fibre System

OFS IV Optical Fibre System OFS IV Optical Fibre System FOR ALL FIBRE OPTIC USERS Fibre optic training has assumed great importance in today s world of widespread fibre optic usage whether in telecommunications or railways, industrial

More information

Universal Connectivity Platform

Universal Connectivity Platform Enabling Business Transformation through Agility Availability Efficiency UCP provides a fully modular approach to accommodate both copper and fiber into one common footprint, simplifying network architecture

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

PROJECT DATE FLANGE FINISH

PROJECT DATE FLANGE FINISH PROJECT INFORMATION PROJECT DATE TYPE 1" 2-1/2" BeveLED Recessed Downlight - Illuminate your space with any color available in the spectrum with BeveLED Infinite Color+. Tune the light from saturated blue,

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY Guide Specifications HyperPod System THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED

More information

Town of Cicero Local Code Amendments

Town of Cicero Local Code Amendments Town of Cicero Local Code Amendments 2009 International Residential Code Local Amendments: DELETE Table R302.1 (Exterior Walls), see Attachment A. DELETE Exception for Subsection R313.2 (One and Two-Family

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features Fire Control Panels UL, ULC, CSFM Listed; FM Approved* Features Compatible with Simplex 4120 Network Converts multiple 4120 network communications signals into a single fiber optic link to: Multiplex audio

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

EcoAisle Thermal Containment System

EcoAisle Thermal Containment System Guide Specifications EcoAisle Thermal Containment System THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

Technology Design Guidelines. Version 8.0. February 2, 2015

Technology Design Guidelines. Version 8.0. February 2, 2015 TECHNOLOGY SERVICES Version 8.0 February 2, 2015 425 Prescott Street Greensboro, NC 27401 P 336.335.3000 SECTION 01 Project Scope Part 1 Project Scope 1.1. The shall be used for all construction and renovation

More information

TECHNICAL - *All Pricing are Exclusive of VAT. Introduction to Fibre Optics for non-fibre Technicians (can also be done on-site) TARGET AUDIENCE:

TECHNICAL - *All Pricing are Exclusive of VAT. Introduction to Fibre Optics for non-fibre Technicians (can also be done on-site) TARGET AUDIENCE: TECHNICAL - *All Pricing are Exclusive of VAT Introduction to Fibre Optics for non-fibre Technicians (can also be done on-site) Admin personnel, Health and Safety, Project Managers, Sales People, Planners,

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 0715 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: Furnish, install, and test communications horizontal cabling as described in Contract Documents

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

AMP NETCONNECT Category 5E SL Shielded Cabling System. 1. General Description

AMP NETCONNECT Category 5E SL Shielded Cabling System. 1. General Description Category 5E SL Shielded Cabling System Table of Content: 1. General System 7.1. DIN Style Faceplates & Outlets 2. System Cables 7.2. 45x45 MOSAIC Style Faceplates & Outlets 3. Category 5E Shielded SL (SlimLine)

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

The Rise of Tier 2 Testing

The Rise of Tier 2 Testing The Rise of Tier 2 Testing Why enterprises today demand better visibility into their fiber infrastructure Unprecedented demand for more bandwidth, faster network speeds, lower latency, and improved data

More information

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 0513 -CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications Ensuring Cabling Performance in the Customer-Owned Outside Plant Keith Foord Product Manager Greenlee Communications Introduction: Outside plant fiber networks require low reflectance terminations for

More information

commercial-type cabling and connectivity products into the industrial landscape.

commercial-type cabling and connectivity products into the industrial landscape. Product Bulletin PB 315 Belden DataTuff Industrial Ethernet Connectivity, Tools & Accessories Belden DataTuff Cat 6 and 5e IP67/IP20 Cord Sets, IP67 Modular Jacks, IP67 Plug Kits, Cabling Accessories and

More information

SECTION TESTING OF FIBER OPTIC CABLES

SECTION TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Optical Return Loss Measurement by Gregory Lietaert, Product Manager

Optical Return Loss Measurement by Gregory Lietaert, Product Manager White Paper Optical Return Loss Measurement by Gregory Lietaert, Product Manager Introduction With the increasing frequency of high-speed transmission systems and DWDM deployment, optical return loss (ORL)

More information

Telephone and Data Structured Wiring

Telephone and Data Structured Wiring Data Specification Category 6A General Telephone and Data Structured Wiring The Electrical Sub-Contractor shall employ a specialist sub-contractor to provide the following systems:- Manufacturer System

More information

GE LightSweep Lighting Control System Guideform Specification

GE LightSweep Lighting Control System Guideform Specification GE Lighting Control GE LightSweep Lighting Control System Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative,

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

Fire Sprinkler Plan Submittal Form

Fire Sprinkler Plan Submittal Form Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10

More information

DSCR Communications Room Standards

DSCR Communications Room Standards Document number: 0203 Status: Classifications: Published Project Restricted New Builds Deep Refurbishments Design Performance Standard Date: April 2010 Version: 1.3 Issue number Date Description 0.1 July

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information